Att 3.pdf
PDF 3 MB Posted
- Attached to
- 4210--Fire Suppression Service, Testing, Maintenance, Certification Amendment 2 Federal contract opportunity
- Solicitation number
- 36C25625Q1231
About this file
This document is an NFPA 25 inspection report for the fire protection systems at Overton Brooks VA Medical Center in Shreveport, Louisiana, conducted by Johnson Controls on August 12-17, 2024. The comprehensive inspection covered multiple fire protection components across the hospital, including 71 tamper switches, 60 water flow switches, control valves, easy riser systems, hose valve outlets, hydrants, antifreeze systems, and fire pumps. The inspection revealed mostly compliant systems with a few notable deficiencies: a tamper switch on the 9th floor with a supervisory signal issue, painted fusible link sprinklers in the Annex's 2nd floor mechanical room, and missing control valve handles on hose valves on the 7th floor and 10th floor.
The inspection was performed by two primary inspectors, William "Andy" Rolen and Ethan Williamson, who systematically examined fire protection infrastructure across the building's basement, first through twelfth floors, stairwells, and campus fire loop. The report documents detailed testing of each system component, including water pressure measurements, valve positions, visual inspections, and functional tests. Most systems passed inspection, with only 4 out of 518 total devices failing, resulting in a 99.23% compliance rate. The report includes specific recommendations for addressing the identified deficiencies and provides comprehensive documentation of the fire protection systems' condition as of August 2024.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25625Q1231 0002_1.docx | DOCX document | |
| Att 1 - Antifreeze.pdf | ||
| Att 2 Water Storage Reservoir.pdf | ||
| Att 4.pdf | ||
| SF-30 Amendment 2.pdf | ||
| SF-30 Amendment.pdf | ||
| 36C25625Q1231 0001.docx | DOCX document | |
| 36C25625Q1231_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Johnson Controls is committed to serving our customers with the best-in-class services and technologies. Xaap is an advanced inspection reporting application that has been used by Johnson Controls on your inspections.
Xaap is a software-as-a-service (SaaS) solution that provides a streamlined and digitized approach for performing fire and life safety inspections and managing compliance reports in a single, centralized platform.
The application allows inspectors to capture data for fire and life safety systems and devices while generating the required compliance reports directly from their phones. It also provides facility managers, building managers and key stakeholders with a centralized view of all building systems and deficiency data. Users can easily access, download and share historical inspection reports through Xaap.
See how your organization can leverage this smart technology for your internal inspections Visit info.jci.com/xaap-tjc To Learn More
This report is powered by Xaap, the Building Compliance Reporting Platform used by Johnson Controls.
This page is informational only and not part of The Joint Commission Report
This report is powered by https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc
[This Page Intentionally Left Blank]
Inspection Summary
Customer Information
Name Overton Brooks
Building Information
Name Overton Brooks - Main Hospital
Address 510 E Stoner Ave, Shreveport, LA, 71101
Contact Information
Name Paul Celli
Role Supervisor
E-Mail paul.celli@va.gov
Phone 3189905568
Account Information
Service Provider
Johnson Controls North America
Office Address
3691 Old Shed Road, Bossier City, LA 71111
Office Phone 318-655-9114
Office License
F186
Inspector Name
William “Andy” Rolen
Inspector License
LA - E25457 / Backflow - 20240991
Inspection Information
Start Date 08/12/2024
Date 08/17/2024
Inspection Type
Joint Commission
Work Order# 57425096, 57425098, 57425100, 57425102, 57425104, 57425106
Timezone GMT-05:00
Inspection Summary
The following Tests and Inspections have been covered in this inspection
EP 2 - Tamper Switches and Water Flow Devices
EP 9 - Sprinkler Systems Main Drain
EP 10 - Fire Department Water Supply Connections
EP 11 - Fire Pump Tested Under Full Flow (Annual) and/or Pump Supervisory Signals
NFPA 25
www.xaapbuildings.com
General Inspection Notes
1. Annual Fire Sprinkler, Fire Pump, & Fire Hydrant Inspection - Green & Yellow Tagged
GENERAL DEFICIENCIES
DESCRIPTION IMAGES
Annex, 2nd floor mechanical room 2AE101 has painted, fusible link uprights and pendents (see report for pics). —
Hose Valve Outlet 10W5 has missing Control Valve handle (see reports for pics). —
Hose Valve Outlet 7W50 has missing Control Valve handle (see reports for pics). —
9W18 Control Valve Tamper did not indicate supervisory trouble during testing. —
DEVICE DEFICIENCIES
TEST TO
PERFORM
LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE
INSPECTOR /
DATE
IMAGES
EP2 9th floor 9W18 control valve tamper
— Tamper Switch Tamper switch Built in 287006257 Andy Rolen 08/13/2024
DEFICIENCY
IMAGES
APPENDIX 1.1
FAILURE TYPE: Functional Failure,Visual Failure FAILURE REASON: Supervisory signal did not indicate supervisory trouble during testing/inspection.
NFPA 25 10th Floor 10W5 hose valve — Hose Valve
Outlet Hose valve 2.5 287006241
Ethan Williamson 08/14/2024
FAILURE TYPE: Functional Failure,Visual Failure FAILURE REASON: House outlet handle missing. A new one needs to be installed.
NFPA 25 2nd floor, Annex 2AE101 wet system, between
2AE65 & 2AE67
Easy Riser or
Shotgun System
— Easy riser 287005971
Andy Rolen 08/15/2024
FAILURE TYPE: Visual Failure FAILURE REASON: Painted, fusible link uprights and pendents
NFPA 25 7th floor 7W50 hose valve — Hose Valve
Outlet Hose valve 2.5 287006310
Andy Rolen 08/13/2024
FAILURE TYPE: Functional Failure FAILURE REASON: Control valve handle missing
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
TEST PERFORMED DEVICE TYPE TOTAL PASSED FAILED CANNOT INSPECT % INSPECTED TOTAL
EP2 Tamper Switch 71 70 1 0 100 71
EP2 Water Flow Switch 60 60 0 0 100 60
EP9 Main Drain - Standpipe Valve 1 1 0 0 100 1
EP10 Fire Dept. Connection 3 3 0 0 100 3
EP11 Diesel Fire Pumps 1 1 0 0 100 1
NFPA 25 Antifreeze System 4 4 0 0 100 4
NFPA 25 Check Valve 6 6 0 0 100 6
NFPA 25 Control Valve 83 83 0 0 100 83
NFPA 25 Drain 4 4 0 0 100 4
NFPA 25 Easy Riser or Shotgun System 55 54 1 0 100 55
NFPA 25 Gauge 68 68 0 0 100 68
NFPA 25 Hose Valve Outlet 80 78 2 0 100 80
NFPA 25 Hydrants - dry barrel and wall 12 12 0 0 100 12
NFPA 25 Hydrants - wet barrel 1 1 0 0 100 1
NFPA 25 Inspectors Test Valve 57 57 0 0 100 57
NFPA 25 Low Point Drain 1 1 0 0 100 1
NFPA 25 Post Indicator Valve 10 10 0 0 100 10
NFPA 25 Sectional Control Valve 1 1 0 0 100 1
TOTAL 518 514 4 0 100 518
TAMPER SWITCHES AND WATER FLOW DEVICES
CUSTOMER NAME: Overton Brooks
BUILDING NAME: Overton Brooks - Main Hospital
BUILDING ADDRESS: 510 E Stoner Ave, Shreveport, LA, 71101
CONTACT NAME: Paul Celli
CONTACT E-MAIL: paul.celli@va.gov
CONTACT ROLE: Supervisor
CONTACT PHONE: 3189905568
SERVICE PROVIDER: Johnson Controls North America
OFFICE ADDRESS: 3691 Old Shed Road, Bossier City, LA 71111
OFFICE PHONE: 318-655-9114
OFFICE LICENSE: F186
INSPECTOR: William “Andy” Rolen
INSPECTOR LICENSE: LA - E25457 / Backflow - 20240991
INSPECTION START DATE: 08/12/2024
INSPECTION END DATE: 08/17/2024
WORK ORDER: 57425096, 57425098, 57425100, 57425102, 57425104, 57425106
TIMEZONE: GMT-05:00
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT
Water Flow Switch 60 60 0 0 100 60
Tamper Switch 71 70 1 0 100 71
DEVICE DEFICIENCIES
LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE DATE OF TEST TYPE IMAGES
9th floor 9W18 control valve tamper
— Tamper Switch Tamper switch Built in 287006257 08/13/2024
FUNCTIONAL
FAILURE,VISUAL
FAILURE
DEFICIENCY
IMAGES
APPENDIX 1.1
FAILURE REASON: Supervisory signal did not indicate supervisory trouble during testing/inspection.
RETIRED DEVICES
No retired devices in this inspection.
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
Customer: Overton Brooks | Building: Overton Brooks - Main Hospital
Elements of Performance #2
At least semi-annually, the facility tests water-flow devices and at least semi-annually the facility tests supervisory valve tamper switches. The completion date of the tests is documented.
Valve Tamper Switches and Water Flow devices
For additional guidance on performing tests, see NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Device Test Method
Control Valve Tamper Switch:
14.4.2.2-14.(i).(1)
Valve shall be operated and signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacture's specifications
Mechanical, Electro-sonic, or Pressure-Type Water flow Device:
14.4.2.2-14.(j)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25.
A.1.1.1.2 There are times when a single inspection or test can meet the requirements of both NFPA 25 and NFPA 72 (e.g., operation of a tamper switch). This standard does not necessarily require that two separate inspections or tests be conducted on the same component, provided the inspection or test meets the requirements of both standards and the individual performing the inspection or test is qualified to perform the inspection or test required by both standards.
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
TAMPER SWITCH
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 1st floor 1E35 above ceiling control valve tamper Tamper Switch Tamper Switch 287005956 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
2 1st floor 1E89 above ceiling control valve tamper.
Tamper Switch Tamper Switch 287005954 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
3 1st floor 1E99 control valve tamper Tamper switch Tamper Switch 287006094 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
4 1st floor 1N7 above ceiling control valve tamper Tamper Switch Tamper Switch 287005958 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
5 1st floor 1N7 control valve tamper Tamper switch Tamper Switch 287006087 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
6 1st floor 1W24a control valve tamper Tamper switch Tamper Switch 287006079 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
7 1st floor 1W26 control valve tamper Tamper switch Tamper Switch 287006072 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
8 2nd floor, Annex 2AE101 control valve tamper, between
2AE65 & 2AE67
Tamper switch Tamper Switch 287005972 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
9 2nd floor 2E28 control valve tamper Tamper switch Tamper Switch 287006064 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
10 2nd floor 2N16 control valve tamper Tamper switch Tamper Switch 287006057 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
11 2nd floor 2W29A control valve tamper Tamper switch Tamper Switch 287006041 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
12 2nd floor 2W29 control valve tamper Tamper switch Tamper Switch 287006049 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
13 3rd floor 3E31 control valve tamper Tamper switch Tamper Switch 287006013 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
14 3rd floor 3N11 control valve tamper Tamper switch Tamper Switch 287006006 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
15 3rd floor 3W66 control valve tamper Tamper switch Tamper Switch 287006021 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
16 3rd floor 3W70 control valve tamper Tamper switch Tamper Switch 287006028 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
17 4th floor 4E1 control valve tamper Tamper switch Tamper Switch 287006035 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
18 4th floor 4N13 control valve tamper Tamper switch Tamper Switch 287006376 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
19 4th floor 4W49 control valve tamper Tamper switch Tamper Switch 287006367 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
20 4th floor 4W55 control valve tamper Tamper switch Tamper Switch 287006360 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
21 4th floor
4W-rt control valve tamper, through
4W34 out opposite door, across roof to double doors
Tamper switch Tamper Switch 287005086 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
22 5th floor 5E1 control valve tamper Tamper switch Tamper Switch 287006390 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
23 5th floor 5N25 control valve tamper (must ring bell for entrance)
Tamper switch Tamper Switch 287006383 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
24 5th floor 5W45 control valve tamper Tamper switch Tamper Switch 287006397 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
25 5th floor 5W52 control valve tamper Tamper switch Tamper Switch 287006351 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
26 6th floor 6E1 control valve tamper Tamper switch Tamper Switch 287005007 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
27 6th floor 6W36 control valve tamper Tamper switch Tamper Switch 287006197 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
28 6th floor 6W52 control valve tamper Tamper switch Tamper Switch 287006344 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
29 7th floor 7E1 control valve tamper Tamper switch Tamper Switch 287006326 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
30 7th floor 7N4 control valve tamper Tamper switch Tamper Switch 287006265 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
31 7th floor 7W36 control valve tamper Tamper switch Tamper Switch 287006319 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
32 7th floor 7W50 control valve tamper Tamper switch Tamper Switch 287006312 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
33 8th floor 8E1 control valve tamper Tamper switch Tamper Switch 287006303 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
34 8th floor 8N5 control valve tamper Tamper switch Tamper Switch 287006288 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
35 8th floor 8W37 control valve tamper Tamper switch Tamper Switch 287006296 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
36 8th floor 8W57 control valve tamper Tamper switch Tamper Switch 287005977 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
37 9th floor
9E20 control valve tamper (will need star bit screwdriver to get in cabinet)
Tamper switch Tamper Switch 287005099 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
38 9th floor 9N6 control valve tamper Tamper switch Tamper Switch 287006281 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
39 9th floor 9W18 control valve tamper Tamper switch Tamper Switch 287006257 Andy Rolen 08/13/2024 Failed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? No
Reason for failure: (Functional Failure,Visual Failure) Supervisory signal did not indicate supervisory trouble during testing/inspection.
40 9th floor 9W23 control valve tamper Tamper switch Tamper Switch 287006274 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
41 10th Floor 10E32 control valve tamper Tamper switch Tamper Switch 287006250 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
42 10th Floor 10N8 Control valve tamper Tamper switch Tamper Switch 287006236 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
43 10th Floor 10W5 control valve tamper Tamper switch Tamper Switch 287006243 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
44 11th floor 11-1 AF Loop control valve tamper Tamper switch Tamper Switch 287006177 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
45 11th floor 11-1 control valve tamper Tamper switch Tamper Switch 287006159 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
46 11th floor 11-2 AF Loop control valve tamper Tamper switch Tamper Switch 287006184 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
47 11th floor 11-3 AF Loop control valve tamper Tamper switch Tamper Switch 287006192 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
48 12th floor 12-1 control valve tamper Tamper switch Tamper Switch 287006168 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
49 Basement BE18 control valve tamper Tamper switch Tamper Switch 287006140 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
50 Basement BE21 control valve tamper Tamper switch Tamper Switch 287006132 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
51 Basement BE24 control valve tamper Tamper switch Tamper Switch 287006100 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
52 Basement BE34 control valve tamper Tamper switch Tamper Switch 287006124 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
53 Basement BN8 control valve tamper Tamper switch Tamper Switch 287006117 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
54 Basement BW1 standpipe control valve tamper Tamper switch Tamper Switch 287005995 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
55 Basement BW8 control valve tamper Tamper switch Tamper Switch 287006109 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
56 Basement
BW12A Control valve tamper (inside closet in Audiology Waiting
Room)
Tamper Switch Tamper Switch 287005953 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
57 Fire Pump Room Fire pump valve 1 tamper Tamper switch Tamper Switch 287005115 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
58 Fire Pump Room Fire pump valve 2 tamper Tamper switch Tamper Switch 287005116 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
59 Fire Pump Room Fire pump valve 3 tamper Tamper switch Tamper Switch 287005117 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
60 Fire Pump Room Fire pump valve 4 tamper Tamper switch Tamper Switch 287005118 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
61 Fire Pump Room Fire pump valve 5 tamper Tamper switch Tamper Switch 287005119 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
62 Fire Pump Room Fire pump valve 6 tamper Tamper switch Tamper Switch 287005120 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
63 Fire Pump Room Fire pump valve 7 tamper Tamper switch Tamper Switch 287005121 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
64 Sub-Basement SB1 control valve tamper Tamper switch Tamper Switch 287006147 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
65 Sub-Basement SB4 AF Loop control valve tamper Tamper switch Tamper Switch 287006156 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
66 Sub-Basement
SB4 control valve tamper (facing Fire Pump Room door, go right to fenced in area, look up)
Tamper Switch Tamper Switch 287005959 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
67 1st floor, Stairwell 11 Stairwell 11 control valve tamper Tamper switch Tamper Switch 287005030 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
3rd floor , Stairwell
Stairwell 11 control valve tamper (ladder needed) Tamper switch Tamper Switch 287005014 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
2nd floor, Stairwell
Stairwell 11 control valve tamper (ladder needed) Tamper switch Tamper Switch 287005023 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
70 Basement Stairwell @ BE94 (ladder needed)
Stem & Yoke Tamper Switch 287005080 Andy Rolen 08/14/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Stairwell 8 storage area
SW8A control valve tamper (thru dbl doors @ 1W15, walkway to small door)
Tamper switch Tamper Switch 287005061 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
WATER FLOW SWITCH
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 1st floor 1E35 above ceiling water flow switch
Water flow switch Water Flow Switch 287005957 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
2 1st floor 1E89 above ceiling water flow switch
Water flow switch Water Flow Switch 287005955 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
3 1st floor 1E99 water flow switch Water flow switch Water Flow Switch 287006095 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
4 1st floor 1N7 water flow switch Water flow switch Water Flow Switch 287006088 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
WATER FLOW SWITCH
5 1st floor 1W24a water flow switch Water flow switch Water Flow Switch 287006080 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
6 1st floor 1W26 water flow switch Water flow switch Water Flow Switch 287006073 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
7 2nd floor, Annex 2AE101 water flow switch, between
2AE65 & 2AE67
Water flow switch Water Flow Switch 287005949 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 17
Open test connection/bypass. Did water flow activate the alarm? Yes
8 2nd floor 2E28 water flow switch Water flow switch Water Flow Switch 287006065 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 9
Open test connection/bypass. Did water flow activate the alarm? Yes
9 2nd floor 2N16 water flow switch Water flow switch Water Flow Switch 287006058 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 16
Open test connection/bypass. Did water flow activate the alarm? Yes
10 2nd floor 2W29A water flow switch Water flow switch Water Flow Switch 287006043 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 25
Open test connection/bypass. Did water flow activate the alarm? Yes
11 2nd floor 2W29 water flow switch Water flow switch Water Flow Switch 287006050 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
12 3rd floor 3E31 water flow switch Water flow switch Water Flow Switch 287006012 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
13 3rd floor 3N11 water flow switch Water flow switch Water Flow Switch 287006005 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 8
Open test connection/bypass. Did water flow activate the alarm? Yes
14 3rd floor 3W66 water flow switch Water flow switch Water Flow Switch 287006020 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
15 3rd floor 3W70 water flow switch Water flow switch Water Flow Switch 287006027 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
16 4th floor 4E1 water flow switch Water flow switch Water Flow Switch 287006034 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 3
Open test connection/bypass. Did water flow activate the alarm? Yes
17 4th floor 4N13 water flow switch Water flow switch Water Flow Switch 287006375 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 3
Open test connection/bypass. Did water flow activate the alarm? Yes
18 4th floor 4W49 water flow switch Water flow switch Water Flow Switch 287006368 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 3
Open test connection/bypass. Did water flow activate the alarm? Yes
19 4th floor 4W55 water flow switch Water flow switch Water Flow Switch 287006361 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
20 4th floor
4W-rt water flow switch, through
4W34 out opposite door, across roof to double doors
Water flow switch Water Flow Switch 287005085 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20
Open test connection/bypass. Did water flow activate the alarm? Yes
21 5th floor 5E1 water flow switch Water flow switch Water Flow Switch 287006388 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
22 5th floor 5N25 water flow switch (must ring bell for entrance)
Water flow switch Water Flow Switch 287006382 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
23 5th floor 5W45 water flow switch Water flow switch Water Flow Switch 287006396 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
24 5th floor 5W52 water flow switch Water flow switch Water Flow Switch 287006352 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
25 6th floor 6E1 water flow switch Water flow switch Water Flow Switch 287005009 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 3
Open test connection/bypass. Did water flow activate the alarm? Yes
26 6th floor 6W36 water flow switch Water flow switch Water Flow Switch 287006199 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 3
Open test connection/bypass. Did water flow activate the alarm? Yes
27 6th floor 6W52 water flow switch Water flow switch Water Flow Switch 287006345 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
28 7th floor 7E1 water flow switch Water flow switch Water Flow Switch 287006327 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30
Open test connection/bypass. Did water flow activate the alarm? Yes
29 7th floor 7N4 water flow switch Water flow switch Water Flow Switch 287006264 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
30 7th floor 7W36 water flow switch Water flow switch Water Flow Switch 287006320 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
31 7th floor 7W50 water flow switch Water flow switch Water Flow Switch 287006313 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
32 8th floor 8E1 water flow switch Water flow switch Water Flow Switch 287006304 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
33 8th floor 8N5 water flow switch Water flow switch Water Flow Switch 287006289 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
34 8th floor 8W37 water flow switch Water flow switch Water Flow Switch 287006297 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
35 8th floor 8W57 water flow switch Water flow switch Water Flow Switch 287005978 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20
Open test connection/bypass. Did water flow activate the alarm? Yes
36 9th floor
9E20 water flow switch (will need star bit screwdriver to get in cabinet)
Water flow switch Water Flow Switch 287005100 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 17
Open test connection/bypass. Did water flow activate the alarm? Yes
37 9th floor 9N6 water flow switch Water flow switch Water Flow Switch 287006283 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
38 9th floor 9W18 water flow switch Water flow switch Water Flow Switch 287006259 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
39 9th floor 9W23 water flow switch Water flow Water Flow Switch 287006276 Andy Rolen 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
40 10th Floor 10E32 water flow switch Water flow switch Water Flow Switch 287006251 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
41 10th Floor 10N8 water flow switch Water flow switch Water Flow Switch 287006237 Ethan Williamson 08/13/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
42 10th Floor 10W5 water flow switch Water flow switch Water Flow Switch 287006244 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 11
Open test connection/bypass. Did water flow activate the alarm? Yes
43 11th floor 11-1 AF Loop water flow switch Water flow switch Water Flow Switch 287006179 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30
Open test connection/bypass. Did water flow activate the alarm? Yes
44 11th floor 11-1 water flow switch Water flow switch Water Flow Switch 287006160 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30
Open test connection/bypass. Did water flow activate the alarm? Yes
45 11th floor 11-2 AF Loop water flow switch Water flow switch Water Flow Switch 287006182 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30
Open test connection/bypass. Did water flow activate the alarm? Yes
46 11th floor 11-3 AF Loop water flow switch Water flow switch Water Flow Switch 287006190 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30
Open test connection/bypass. Did water flow activate the alarm? Yes
47 12th floor 12-1 water flow switch Water flow switch Water Flow Switch 287006169 Andy Rolen 08/12/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30
Open test connection/bypass. Did water flow activate the alarm? Yes
48 Basement BE18 water flow switch Water flow switch Water Flow Switch 287006141 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 3
Open test connection/bypass. Did water flow activate the alarm? Yes
49 Basement BE21 water flow switch Water flow switch Water Flow Switch 287006135 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 11
Open test connection/bypass. Did water flow activate the alarm? Yes
50 Basement BE24 water flow switch Water flow switch Water Flow Switch 287006101 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
51 Basement BE34 water flow switch Water flow switch Water Flow Switch 287006129 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 5
Open test connection/bypass. Did water flow activate the alarm? Yes
52 Basement BN8 water flow switch Water flow switch Water Flow Switch 287006118 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 8
Open test connection/bypass. Did water flow activate the alarm? Yes
53 Basement BW8 water flow switch Water flow switch Water Flow Switch 287006110 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 10
Open test connection/bypass. Did water flow activate the alarm? Yes
54 Basement
BW12A water flow switch (inside closet in Audiology Waiting
Room)
Water flow switch Water Flow Switch 287005952 Ethan Williamson 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
55 Sub-Basement SB1 water flow switch Water flow switch Water Flow Switch 287006148 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
56 Sub-Basement
SB4 water flow switch (facing Fire Pump Room door, go right to fenced in area, look up)
Water flow switch Water Flow Switch 287005960 Ethan Williamson 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 3
Open test connection/bypass. Did water flow activate the alarm? Yes
57 1st floor, Stairwell 11 Stairwell 11 water flow switch Water flow switch Water Flow Switch 287005032 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20
Open test connection/bypass. Did water flow activate the alarm? Yes
3rd floor , Stairwell
Stairwell 11 water flow switch (ladder needed) Water flow switch Water Flow Switch 287005015 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20
Open test connection/bypass. Did water flow activate the alarm? Yes
2nd floor, Stairwell
Stairwell 11 water flow switch (ladder needed) Water flow switch Water Flow Switch 287005026 Andy Rolen 08/15/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed I5
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
60 Basement Stairwell @ BE94 (ladder needed)
Notifier Water Flow Switch 287005078 Andy Rolen 08/14/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20
Open test connection/bypass. Did water flow activate the alarm? Yes
Inspector Signature
Inspector Name William “Andy” Rolen Date 08/17/2024
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2 a3ae3ef9-e3ee-48f6-80f2-8dc027bdcb9c | Tamper Switches and Water Flow Devices | 08/17/2024
SPRINKLER SYSTEMS MAIN DRAIN
BUILDING NAME: Overton Brooks - Main Hospital
BUILDING ADDRESS: 510 E Stoner Ave, Shreveport, LA, 71101
CONTACT NAME: Paul Celli
CONTACT…