D4 23RD-VA-GCVetPharmacy-B-0412.pdf
PDF 174 KB Posted
- Attached to
- Pharmacy Mixing Room Fixtures
- Solicitation number
- 36C25623Q1515
About this file
This document contains construction drawings and lighting calculations for a pharmacy mixing room renovation project at a VA medical center in Pensacola, Florida. The drawings specify new lighting fixtures, a luminaire schedule, area summaries, and illumination calculations. Related to this is a federal contract opportunity posted by the Department of Veterans Affairs for pharmacy mixing room fixtures at the Pensacola VA medical center. The solicitation seeks bids for supply and installation of new lighting fixtures matching the specifications in the construction drawings. The response deadline and anticipated award date are not provided. The scope involves replacing existing fixtures with new LED fixtures to provide cleaner illumination and meet illumination targets throughout the mixing room and anteroom areas as calculated in the document.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D ra w n
By
C he ck ed
B y:
Sc al e:
Page M of 1
D at e:
4/
/2
R D
−V A−
G C
V et
P ha rm ac y− B
−0
.A
G I
R ob er t D eW ee se , L
C
IE
S R ob er t D eW ee se
, L C
IE
S
Robert DeWeese, LC, IES
VA
-C
LI
N
IC
P en sa co la
, F l
N
M1.0
ENLARGED RCP - CLEAN ROOM
SCALE: 14" = 1'-0"
Sequence Of Operation:
Occupied Mode is Auto on to White Light with Indigo Mixed Occupied Mode is 0% White Light 100% Indigo System Is Continious Clean Note: Episodic Cleaning should be continued along with the Indigo Continuos Clean.
= Part Of IC150 4-8-L6020-DV(L6020-IR SENSOR)
ICF ICF
ICF
ICF
ICF
ICF
ICL
ICF
ICF 128.6 145.3 126.5 90.1 62.2
188.4 214.8 180.1 122.3 78.5
219.8 251.8 208.6 135.8 85.6
192.1 218.1 183.5 123.3 78.5
139.0 147.9 129.1 93.0 62.6
89.6 105.8 112.1 108.4 93.9
129.2 155.4 164.5 159.4 136.8
157.8 191.7 202.8 196.7 168.2
146.0 176.7 186.8 181.1 155.2
107.8 128.6 136.2 131.7 113.3
160.0 161.5 125.1 84.6 59.0
205.4 208.9 156.1 101.3 68.7
223.2 227.0 168.8 108.1 72.5
207.2 211.7 158.5 102.7 68.4
162.5 167.6 129.8 89.3
129.1 145.5 126.9 90.9 62.8
188.9 214.7 180.0 121.1 78.4
220.0 251.7 208.2 136.5 86.0
192.6 217.5 183.1 122.0 77.7
139.0 147.4 129.5 92.9 62.6
162.6 183.1 160.4
178.0 199.5 175.3
177.6 198.0 174.9
175.7 196.9 173.0
154.8 173.9 152.3
Luminaire Schedule Symbol Qty Label Arrangement Description LLF Luminaire
Lumens Luminaire Watts
Total Watts
1 ICL Single Kenall # IC150-4-8-L6020-DV 0.010 565 4.2 4.2 8 ICF Single Kenall # CSEDOIC-24-150I/100L-43K8-DCC-DV-2F-2H-SYM 0.890 14674 138 1104
LPD Area Summary Label Area Total
Watts
LPD
1B120 ONCOL Prep 93.26 276 2.959
1B120A ANTE ROOM 116.48 276 2.370
1B121 ANTE ROOM 74.03 276 3.728
Calculation Summary Label CalcType Units Avg Max Min Avg/Min Max/Min 1B120 ONCOL PREP_Workplane Illuminance Fc 142.83 227.0 59.0 2.42 3.85 1B120A ANTE ROOM_Workplane Illuminance Fc 145.43 202.8 89.6 1.62 2.26 1B121 ANTE ROOM_Workplane Illuminance Fc 175.73 199.5 152.3 1.15 1.31 1B122 ADMIXTURE_Workplane Illuminance Fc 144.20 251.7 62.6 2.30 4.02 1B122 ADMIXTURE_Workplane_1 Illuminance Fc 144.22 251.8 62.2 2.32 4.05
File details come from the government source that posted it. Updated .