36C25618B0555-00001000.docx
DOCX document 31 KB Posted
- Attached to
- 580-18-116 Replace AHU in B100 and B110 Federal contract opportunity
- Solicitation number
- 36C25618B0555
About this file
36C25618B0555 00001 36C25618B0555 00001.docx
View the file
Other files for this federal contract opportunity
Show all 38
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2.
AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE
OF PAGES
10A. MODIFICATION OF
CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV.
11/2016) is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO:
Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITE M 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR
43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes r eference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS
ENTERED INTO
PURSUANT TO AUTHORITY OF:
D. OTHER
BY
Contractor
16C. DATE SIGNED
14.
DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME
AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS
OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 00001 06-01-2018 580-18-116 Department of Veterans Affairs
NCO 16
Michael E. DeBakey VA Medical Center 2002 Holcombe Boulevard Houston TX 77030 4298 Department of Veterans Affairs
NCO 16
Michael E. DeBakey VA Medical Center 2002 Holcombe Boulevard Houston TX 77030 To all Offerors/Bidders
36C25618B0555 06-01-2018
X X X X RE: Replace AHU in B100 and B110
See clarifications attached.
580-18-116 Replace AHU in B100 and B110 Clarifications
1. What size are the existing valves that are to be replaced?
See attached file existing AHU Submittal, for existing AHU information including pipe size.
2. Are the valves gate valves, butterfly valve, or ball valves?
Gate valves and ball valves.
3. What type of pipe are we to tie onto IE. Steel or copper?
Black iron and copper.
4. Please provide a unit casing specification.
See attached file 580 18 116 Spec Book
5. What are the dimensions of the existing units?
See attached file existing AHU Submittal, for existing AHU information including pipe size.
6. What is the smallest opening that the units in each room will have to fit through?
Interested bidders were permitted to measure opening during the organized site visit. Contractors are welcome to return and measure and plan a rigging route.
7. What is the haul route for the new unit to each mechanical room as well as haul route for debris?
SOW calls for all major debris to be removed through the louvers, and new AHU module be rigged in through the louvers as well. For the case of the small AHU that will fit thru the elevator, COR may authorize rigging through the area using service elevators. Contractor shall take extra precautions when rigging in and out material to ensure infection control requirements are met. In case the contractor causes any spill or dust spreading during rigging, contractor shall be required to only use louvers.
8. Will the contractor be provided a key to access all areas?
Yes, there is a deposit of $100 per key, which is refunded after successfully completion of project.
9. Can the period of performance be extended to 450 days?
We can extend to 365 days. AHU shall be replaced during the winter months. Exhaust fans can be replaced at any time during the year.
10. Can work on the units begin in November instead of December?
Yes, only if the average temperature during the weekend is 55°F or less.
11. Is the intent to change out one unit per weekend?
Contractor may install more than one unit per weekend if there are enough contract workers to complete the tasks.
12. Can more time be given on some of the larger units than just Friday at 6:00 P.M. till Sunday at Midnight?
No, unless they are scheduled during a federal holiday weekend.
13. Can the new insulation on the chilled water piping and hot water piping be fiberglass to match the existing? We assume 2” fiberglass on chilled water and 1 ½” on hot water.
See Spec 23 07 11 of the attached file 580 18 116 Spec Book.
14. Are there liquidated damages on the project?
No.
15. In order to bid this we need plans of the existing mechanical rooms. Please provide these plans.
See attached file Mechanical Bay Drawings
16. What existing power feed goes to each unit as well as breaker brands and sizes?
See file attached Pictures.
17. Since there is no sole source justification on Johnson Controls, can we utilize other brands to DDC controls?
Yes, as long it is compatible with existing BAS which is MetaSys by Johnson Controls
18. Please provide an AHU casing specification.
See answer to question 4.
19. What is being done to prevent shell companies that do not self-perform mechanical work from turning in a price as we noticed almost all of them at the walk through didn’t self-perform 25% of the work?
VAAR clause 852.219-10 is included in the solicitation and the resulting contract. Awardee is required to adhere to these terms. The limitations on subcontracting – monitoring and compliance is also included and provides the government the right to inspect at any time.
20. Since it will be winter during the replacement, shouldn’t the heating water be hooked up instead of the chilled water?
Chilled water shall be hooked up during the weekend. Hot water shall be connected shortly after. The AHU will be ran manually or with minor control system until all systems install is complete.
21. Please provide a roof plan for crane purposes of each exhaust fan.
See attached file Roof Plan
22. Please provide a duct connection size and plan for each exhaust fan.
See attached file Pictures for more details.
23. Please provide a photo of each exhaust fan.
See attached file Pictures for details.
24. Please provide the existing electrical information on the exhaust fan.
See attached schedule on SOW and attached file Pictures.
25. How many units can be stored on site at one time?
Units may not be stored onsite. Contractor shall deliver units when ready to install.
26. Will a location and power be provided for an office trailer?
Contractor may be provided with some exterior location for trailers, but they are responsible for installing electrical connections to the trailer. Installation shall include a power meter to measure consumption and contractor shall reimburse the government for power use.
27. Will a location for a piping laydown yard be provided?
A piping lay down area may be provided on the exterior, away from B100.
28. What days can crane picks be conducted?
Crane operations shall be conducted during the weekend.
29. Will onsite parking be provided?
Contractors are authorized to park in Lot W.
30. Is there asbestos or lead paint that will be encounter in the work areas, if so who is to abate and what amounts are there?
There is no asbestos in B100. B110 has some areas of asbestos containing materials, but SOW of this project does not disturb any of those materials.
31. What is the contact name and number of the current building automation vendor?
BAS system is MetaSys by Johnson Controls. Currently Lange mechanical has control technicians to support the system and maintenance.
32. Will a location for a dumpster be provided?
Yes, upon request, location may be away from Building 100.
33. Can propress be used on the copper and steel pipe from 4” to ½”?
No.
34. Can grooved fittings and couplings be used on copper and steel pipe from 8” to 2”?
Yes, from 2-1/2 NPS and up. They should not be used on steam pipe.
35. What power is available in each mechanical room for a welder?
480 V 3 ph or 277 V 3 phase
36. What is the sizing for existing and new control valves for hot water and steam?
Size shall match existing or match new coil size.
37. What control valves are 3 way and what are 2 way?
This is information is contained in the SOW. AHU 87, 89, 91, 95 and 97 heating and cooling coil control valves are 3-way valves.
38. Are the control valves flanged, screwed, or grooved?
Most of them are screwed.
39. Is this project funded?
Yes.
40. What is the size of the plenums to be painted?
Contractor shall field verify this during a site visit. See also existing AHU Submittals for dimensions.
41. Is test and balance of only the units required and not the rest of the items downstream?
Yes only the units, during this process energy control will place all TU boxes on full open position for TAB purposes.
42. Item cc: TAB and Commissioning: Please confirm we are only performing TAB services on the AHU’s and exhaust fans and no VAV Boxes or supply air grills outside the mechanical room.
See answer to question 41.
43. General: Is there asbestos in any of the areas in the scope of work?
See answer to question 30.
44. Can we assume for the purposes of this bid that the isolation valves will hold? If any are found deficient, they will be handled outside the contract?
SOW is specific that the contractor shall plan to freeze all pipe lines to allow C/O valves replacements. Previous experience shows around 60% of valves did not hold flow.
45. Scope of work states that the AHU to be removed thru existing intake louvers. Since these are smaller AHU’s, can we transport the material up the elevators and thru the doorways?
See answer to question 7.
See attached document: Roof Plan.
See attached document: Mechanical Bay Drawings.
See attached document: Existing AHU's Specs.
See attached document: Existing AHU Mechanical Info.
See attached document: Pictures.
See attached document: Existing RF Specs.
See attached document: Existing AHU Submittals.
See attached document: BLDG7AC.