Text version
01-01-16
SECTION 08 71 00
DOOR HARDWARE
SPEC WRITER NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs.
PART 1 - GENERAL
1.1 DESCRIPTION
A. Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
| A. | Caulking: Section 07 92 00 JOINT SEALANTS. |
| B. | Application of Hardware: // Section 08 14 00, WOOD DOORS // Section 08 11 13, HOLLOW METAL DOORS AND FRAMES // Section 08 17 10, INTEGRATED DOOR ASSEMBLIES // Section 08 41 13, ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS // Section 08 42 33, REVOLVING DOOR ENTRANCES // Section 08 33 00, COILING DOORS AND GRILLES // Section 08 33 13, COILING ENTRANCES // Section 08 42 29, AUTOMATIC ENTRANCES // Section 08 71 13, AUTOMATIC DOOR OPERATORS //Section 08 71 13.11, LOW ENERGY DOOR OPERATORS // |
| C. | Finishes: Section 09 06 00, SCHEDULE FOR FINISHES. |
| D. | Painting: Section 09 91 00, PAINTING. |
| E. | Card Readers: Section 28 13 11, PHYSICAL ACCESS CONTROL SYSTEMS. |
| F. | Electrical: Division 26, ELECTRICAL. |
| G. | Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM. |
1.3 GENERAL
| A. | All hardware shall comply with UFAS, (Uniform Federal Accessible Standards) unless specified otherwise. |
| B. | Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC). |
| C. | Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements. The word "FIRE" must be included as part of the certification on the Underwriters Laboratories label on exit devices to be used on fire doors. |
| D. | Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction. |
| E. | The following items shall be of the same manufacturer, except as otherwise specified: |
| 1. | Mortise locksets. |
| 2. | Hinges for hollow metal and wood doors. |
| 3. | Surface applied overhead door closers. |
| 4. | Exit devices. |
| 5. | Floor closers. |
1.4 WARRANTY
| A. | Automatic door operators shall be subject to the terms of FAR Clause 52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below: |
| 1. | Locks, latchsets, and panic hardware: 5 years. |
| 2. | Door closers and continuous hinges: 10 years. |
1.5 MAINTENANCE MANUALS
A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
| A. | Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the schedule per Section 01 33 23. Submit 2 final copies of the final approved schedules to VAMC Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith). |
| B. | Hardware Schedule: Prepare and submit hardware schedule in the following form: |
| Hardware Item | |
| Quantity | |
| Size | |
| Reference Publication Type No. | |
| Finish | |
| Mfr. Name and Catalog No. | |
| Key Control Symbols | |
| UL Mark (if fire rated and listed) | |
| ANSI/BHMA Finish Designation |
| C. | Samples and Manufacturers' Literature: |
| 1. | Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number. |
| 2. | Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified. |
| D. | Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval. |
1.7 DELIVERY AND MARKING
A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to Resident Engineer for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number. These items shall remain on file in Resident Engineer's office until all other similar items have been installed in project, at which time the Resident Engineer will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 preinstallation meeting
| A. | Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and Hardware Manufacturer’s Representative. Review the following: |
| 1. | Inspection of door hardware. |
| 2. | Job and surface readiness. |
| 3. | Coordination with other work. |
| 4. | Protection of hardware surfaces. |
| 5. | Substrate surface protection. |
| 6. | Installation. |
| 7. | Adjusting. |
| 8. | Repair. |
| 9. | Field quality control. |
10. Cleaning.
1.9 INSTRUCTIONS
A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.
SPEC WRITER NOTE: Delete following paragraph if new hospital station, or where existing station is to be rekeyed.
//B. Keying: All cylinders shall be keyed into existing ___________ // Great // Grand Master Key System //. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset //. Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the Resident Engineer.//
1.10 APPLICABLE PUBLICATIONS
| A. | The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified. |
| B. | American Society for Testing and Materials (ASTM): |
| F883-04 | Padlocks |
E2180-07................Standard Test Method for Determining the Activity of Incorporated Antimicrobial Agent(s) In Polymeric or Hydrophobic Materials
| C. | American National Standards Institute/Builders Hardware Manufacturers Association (ANSI/BHMA): |
| A156.1-06 | Butts and Hinges |
| A156.2-03 | Bored and Pre-assembled Locks and Latches |
| A156.3-08 | Exit Devices, Coordinators, and Auto Flush Bolts |
| A156.4-08 | Door Controls (Closers) |
| A156.5-14 | Cylinders and Input Devices for Locks. |
| A156.6-05 | Architectural Door Trim |
| A156.8-05 | Door Controls-Overhead Stops and Holders |
| A156.15-06 | Release Devices-Closer Holder, Electromagnetic and Electromechanical |
| A156.16-08 | Auxiliary Hardware |
| A156.18-06 | Materials and Finishes |
| A156.21-09 | Thresholds |
| A156.22-05 | Door Gasketing and Edge Seal Systems |
| A156.23-04 | Electromagnetic Locks |
| A156.24-03 | Delayed Egress Locking Systems |
A156.25-07 .............Electrified Locking Devices A156.26-06 Continuous Hinges A156.29-07 .............Exit Locks and Alarms
| A156.31-07 | Electric Strikes and Frame Mounted Actuators |
| A156.36-10 | Auxiliary Locks |
| A250.8-03 | Standard Steel Doors and Frames |
| D. | National Fire Protection Association (NFPA): |
| 80-10 | Fire Doors and Other Opening Protectives |
| 101-09 | Life Safety Code |
| E. | Underwriters Laboratories, Inc. (UL): |
| Building Materials Directory (2008) |
PART 2 - PRODUCTS
2.2 CONTINUOUS HINGES
| A. | ANSI/BHMA A156.26, Grade 1-600. |
| 1. | Listed under Category N in BHMA's "Certified Product Directory." |
| B. | General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete |
| C. | Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge. |
| 1. | Base Metal for Exterior Hinges: Stainless steel. |
| 2. | Base Metal for Interior Hinges: Aluminum. |
| 3. | Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel. |
| 4. | Provide with non-removable pin (hospital tip option) at lockable outswing doors. |
| 5. | Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required. |
| 6. | Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur. |
| 7. | Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections. |
| 8. | Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard. |
2.3 DOOR CLOSING DEVICES
A. Closing devices shall be products of one manufacturer.
2.4 OVERHEAD CLOSERS
| A. | Conform to ANSI A156.4, Grade 1. |
| B. | Closers shall conform to the following: |
| 1. | The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening. |
| 2. | Where specified, closer shall have hold-open feature. |
| 3. | Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application. |
| 4. | Material of closer body shall be forged or cast. |
| 5. | Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron. |
| 6. | Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material. |
| 7. | Closers shall have full size metal cover; plastic covers will not be accepted. |
| 8. | Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve. |
| 9. | Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders. |
10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
11. Provide parallel arm closers with heavy duty rigid arm.
12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1 ½” (38mm) minimum piston diameter.
2.6 DOOR STOPS
| A. | Conform to ANSI A156.16. |
| B. | Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use lead expansion shields for mounting door stops. |
| C. | Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button. |
| D. | Provide floor stops (Type L02141 or L02161 in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width. |
| E. | Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere. |
| F. | Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement. |
| G. | Omit stops where floor mounted door holders are required and where automatic operated doors occur. |
| H. | Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging. |
| I. | Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used. |
| J. | Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door. |
| K. | Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall. |
| L. | Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used). |
2.7 OVERHEAD DOOR STOPS and HOLDERS
A. Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
Specify pushbutton locks, card-reader-controlled electric locks, or keyed locks per site-specific requirements and the requirements of the VA Physical Security Manual.
2.9 LOCKS AND LATCHES
| A. | Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than seven pins. Cylinders for all locksets shall be removable core type. Cylinder shall be removable by special key or tool. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Great Grand Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores. |
| B. | In addition to above requirements, locks and latches shall comply with following requirements: |
| 1. | Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets, except on designated doors in Psychiatric (Mental Health) areas, shall have lever handles fabricated from cast stainless steel. No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case. |
| 2. | Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Provide lever design to match design selected by Architect or to match existing lever design. Where two turn pieces are specified for lock F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position. (This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.) |
| 3. | Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36. |
| 5. | Privacy locks in non-mental-health patient rooms shall have an inside thumbturn for privacy and an outside thumbturn for emergency entrance. Single occupancy patient privacy doors shall typically swing out; where such doors cannot swing out, provide center-pivoted doors with rescue hardware (see HW-2B). |
2.10 PUSH-BUTTON COMBINATION LOCKS
| A. | ANSI/BHMA A156.5, Grade 1. Battery operated pushbutton entry. |
| B. | Construction: Heavy duty mortise lock housing conforming to ANSI/BHMA A156.13, Grade 1. Lever handles and operating components in compliance with the UFAS and the ADA Accessibility Guidelines. Match lever handles of locks and latchsets on adjacent doors. |
| C. | Special Features: Key override to permit a master keyed security system and a pushbutton security code activated passage feature to allow access without using the entry code. |
2.11 ELECTROMAGNETIC LOCKS
| A. | ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product Directory." |
| 1. | Type: Full exterior or full interior, as required by application indicated. |
| 2. | Strength Ranking: //1500 lbf (6672 N) |
| 3. | Inductive Kickback Peak Voltage: Not more than //53// //0// V. |
| 4. | Residual Magnetism: Not more than //4 lbf (18 N) to separate door from magnet. |
| B. | Delayed-Egress Locks: BHMA A156.24.// Listed under Category G in BHMA's "Certified Product Directory". // |
| 1. | Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than 15 lbf (67 N) for not more than 3 seconds, as required by NFPA 101. |
| 2. | Security Grade: Activated from secure side of door by initiating device. |
| 3. | Movement Grade: Activated by door movement as initiating device. |
| 4. | The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop. |
2.12 ELECTRIC STRIKES
| A. | ANSI/ BHMA A156.31 Grade 1. |
| B. | General: Use fail-secure electric strikes at fire-rated doors. |
SPEC WRITER NOTE: Check height of existing kick-mop plates. Use 200 mm (8 inch) high plates on alteration work to match existing and 125 mm (5 inch) high plates on new work.
2.15 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
| A. | Conform to ANSI Standard A156.6. |
| B. | Provide protective plates // and door edging // as specified below: |
| 1. | Kick plates, mop plates and armor plates of metal, Type J100 series. |
| 2. | Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames. |
| 3. | Kick plates and/or mop plates are not required on following door sides: |
| a. | Armor plate side of doors; |
| b. | Exterior side of exterior doors; |
| c. | Closet side of closet doors; |
| d. | Both sides of aluminum entrance doors. |
| 4. | Armor plates for doors are listed under Article "Hardware Sets". Armor plates shall be thickness as noted in the hardware set, 875 mm (35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all 4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar. |
| 5. | Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high. |
| 6. | Provide stainless steel edge guards where so specified at wood doors. Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors. |
2.16 EXIT DEVICES
| A. | Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging. |
| B. | Surface vertical rod panics shall only be provided less bottom rod; provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors. |
| D. | Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature. |
| E. | At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature. |
| F. | Exit devices for fire doors shall comply with Underwriters Laboratories, Inc., requirements for Fire Exit Hardware. Submit proof of compliance. |
2.17 FLUSH BOLTS (LEVER EXTENSION)
| A. | Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to ANSI A156.16, for flush bolts required on lower part of doors. |
| B. | Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel. |
| C. | Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches). |
| D. | Frictionfit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur. |
| E. | Provide extension rods for top bolt where door height exceeds 2184 mm (7 feet 2 inches). |
2.18 FLUSH BOLTS (AUTOMATIC)
A. Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).
SPEC WRITER NOTE: Review less bottom bolt option for security doors with campus locksmith. Specify auto flush bolts with bottom bolts and dust proof strikes if so requested by campus locksmith.
B. At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than 20 minutes; provide fire pins as required by auto flush bolt and door fire labels.
2.22 COORDINATORS
A. Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.
2.23 THRESHOLDS
| A. | Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in a bed of sealant with ¼-20 stainless steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings. |
| B. | For thresholds at elevators entrances see other sections of specifications. |
| C. | At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish. |
| D. | Provide with miter returns where threshold extends more than 12 mm (0.5 inch) beyond face of frame. |
2.25 WEATHERSTRIPS (For Exterior Doors)
A. Conform to ANSI A156.22. Air leakage shall not to exceed 0.50 CFM per foot of crack length (0.000774m3/s/m).
2.26 MISCELLANEOUS HARDWARE
| A. | Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types): Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer. |
| C. | Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors. Provide 4 mutes or silencers for frames for each Dutch type door. Provide 2 mutes for each edge of sliding door which would contact door frame. |
2.29 HINGED WIRE GUARDS (For Windows, Doors and Transoms) AND WIRE PARTITION DOORS
2. Key locks for partitions enclosing mechanical and electrical equipment in Engineer's Set. (See detailed drawings for number of locks and butt hinges required for each guard).
2.30 FINISHES
| A. | Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING. |
| B. | 626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified. |
| C. | Miscellaneous Finishes: |
| 1. | Hinges --exterior doors: 626 or 630. |
| 2. | Hinges --interior doors: 652 or 630. |
| 3. | Pivots: Match door trim. |
| 4. | Door Closers: Factory applied paint finish. Dull or Satin Aluminum color. |
| 5. | Thresholds: Mill finish aluminum. |
| 6. | Cover plates for floor hinges and pivots: 630. |
| 7. | Other primed steel hardware: 600. |
| D. | Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces E. | Special Finish: Exposed surfaces of hardware for dark bronze anodized aluminum doors shall have oxidized oil rubbed bronze finish (dark bronze) finish on door closers shall closely match doors. |
| F. | Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests. Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies. |
2.31 BASE METALS
| A. | Apply specified U.S. Standard finishes on different base metals as following: |
| Finish | |
| Base Metal |
| 652 |
| Steel |
| 626 |
| Brass or bronze |
| 630 |
| Stainless steel |
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
| //A. | For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA Resident Engineer for approval. // |
| //A. | For new buildings locate hardware on doors at heights specified below, with all hand-operated hardware centered within 864 mm (34 inches) to 1200 mm (48 inches), unless otherwise noted: // |
| B. | Hardware Heights from Finished Floor: |
| 1. | Exit devices centerline of strike (where applicable) 1024 mm (40-5/16 inches). |
| 2. | Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches). |
| 3. | Deadlocks centerline of strike 1219 mm (48 inches). |
| 4. | Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket. |
| 5. | Centerline of door pulls to be 1016 mm (40 inches). |
| 6. | Push plates and push-pull shall be 1270 mm (50 inches) to top of plate. |
| 7. | Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike. |
| 8. | Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware. |
3.2 INSTALLATION
A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors // except security bedroom, bathroom and anteroom doors which shall have closer installed parallel arm on exterior side of doors. //. At exterior doors, closers shall be mounted on interior side. Where closers are mounted on doors they shall be mounted with sex nuts and bolts; foot shall be fastened to frame with machine screws.
| B. | Hinge Size Requirements: |
| Door Thickness | |
| Door Width | |
| Hinge Height |
| 45 mm (1-3/4 inch) |
| 900 mm (3 feet) and less |
| 113 mm (4-1/2 inches) |
| 45 mm (1-3/4 inch) |
| Over 900 mm (3 feet) but |
not more than 1200 mm (4 feet) 125 mm (5 inches)
| 35 mm (13/8 inch) (hollow core wood doors) |
| Not over 1200 mm (4 feet) |
| 113 mm (4-1/2 inches) |
C. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.
Existing hinges shall not be reused on door openings having new doors and new frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.
F. Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted. All fastenings exposed to weather shall be of nonferrous metal.
3.3 FINAL INSPECTION
| A. | Installer to provide letter to VA Resident/Project Engineer that upon completion, installer has visited the Project and has accomplished the following: |
| 1. | Re-adjust hardware. |
| 2. | Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel. |
| 3. | Identify items that have deteriorated or failed. |
| 4. | Submit written report identifying problems. |
3.4 DEMONSTRATION
A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Resident/Project Engineer and VA Locksmith.
ELECTRIC HARDWARE ABBREVIATIONS LEGEND:
ADO = Automatic Door Operator EMCH = Electro-Mechanical Closer-Holder MHO = Magnetic Hold-Open (wall- or floor-mounted)
INTERIOR SINGLE DOORS
HW-1
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | |||
| 1 | Door Pull w/ Plate | J401 x J302 | ||
| 1 | Push Plate | J302 | ||
| 1 | Kick Plate | J102 | ||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||
| 1 | Closer | C02011/C02021 | ||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||
| 3 | Silencers | L03011 |
HW-1A
Each Door to Have: RATED
| X HOSPITAL TIPS @ INSWING DOORS | ||||
| 1 | Latchset | F01 | ||
| 1 | Closer | C02011/C02021 | ||
| x INSTALL OUTSIDE ROOM | ||||
| 1 | Kick Plate | J102 | ||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||
| 1 | Set Seals | R0Y164 |
HW-1B
| Each Door to Have: | NON-RATED/RATED | |||||
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X SWING-CLEAR X ADJUSTA-SCREWS | ||||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Overhead Stop | C01541-ADJUSTABLE | ||||
| 1 | Set Seals | R0Y164 |
NO CLOSER REQUIRED DUE TO EXEMPTION FOR PATIENT ROOM DOORS.
HW-1C
THIS SET NOT USED.
HW-1D
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | |||
| X SWING-CLEAR X ADJUSTA-SCREWS | |||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | |||
| 1 | Mop Plate | J103 | |||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | |||
| 1 | Overhead Stop | C01541-ADJUSTABLE | |||
| 3 | Silencers | L03011 |
HW-1E
Each Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X SWING-CLEAR X ADJUSTA-SCREWS | ||||||
| 1 | Hospital Latch | F01 x PADDLES POINTING DOWN | ||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Wall Stop (@ Inswing Doors) | L02101 CONVEX | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-1F
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | |
| 1 | Latchset | F04 |
| 1 | Kick Plate | J102 |
| 1 | Wall Stop | L02101 CONVEX |
| 3 | Silencers | L03011 |
HW-1G
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | |||
| X ADJUSTA-SCREWS | |||||
| 1 | Latchset | F01 | |||
| 1 | Kick Plate | J102 | |||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | |||
| 1 | Wall Stop | L02101 CONVEX | |||
| 3 | Silencers | L03011 | |||
| 1 | Coat Hook | L03121 |
HW-1J
Each [MHO] Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Latchset | F01 | ||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Heavy-Duty Armor Plate | J101 x 3.175 MM (0.125 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Magnetic Holder | C00011 TRI-VOLTAGE | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
POWER, WIRING, CONDUIT, AND FIRE ALARM CONNECTION BY DIVISION 26.
HW-1K
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | |||
| X ADJUSTA-SCREWS | |||||
| 1 | Hospital Latch | F01 x PADDLES POINTING DOWN | |||
| 1 | Closer | C02011/C02021 | |||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | |||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | |||
| 1 | Overhead Stop | C01541-ADJUSTABLE | |||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | |||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
HW-1Q
Each Door to Have: RATED/NON-RATED
| 1 | Continuous Hinge | |||
| 1 | Latchset | F04 | ||
| 1 | Kick Plate | J102 | ||
| 1 | Closer (@ rated doors) | C02011/C02021 | ||
| 1 | Wall Stop | L02101 CONVEX | ||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
HW-1R
Each Door to Have: RATED/NON-RATED
| 1 | Continuous Hinge | ||
| 1 | Latchset | F04 | |
| 1 | Kick Plate | J102 | |
| 1 | Closer (@ rated doors) | C02011/C02021 | |
| 1 | Wall Stop | L02101 CONVEX | |
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-2
Each Door to Have: RATED/NON-RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | |||
| 1 | Keyed Privacy Indicator Lock | F13 x OCCUPANCY INDICATOR | ||
| 1 | Closer | C02011/C02021 | ||
| 1 | Kick Plate | J102 | ||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-2C
Each Door to Have: NON-RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | |||
| 1 | Privacy Lock | F02-MOD X OCCUPANCY INDICATOR | ||
| 1 | Kick Plate | J102 | ||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||
| 1 | Wall Stop | L02101 CONVEX | ||
| 3 | Silencers | L03011 |
HW-2E
Each Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Hospital Privacy Latch | F02-MOD x TURNPIECE BOTH SIDES | ||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Overhead Stop | C01541-ADJUSTABLE | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
STONE THRESHOLD BY OTHER TRADES.
HW-2H
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Hospital Privacy Latch | F02-MOD x TURNPIECE BOTH SIDES X | ||||
| OCCUPANCY INDICATOR | ||||||
| 1 | Kick Plate | J102 | ||||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Overhead Stop | C01541-ADJUSTABLE | ||||
| 3 | Silencers | L03011 |
HW-2K
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Hospital Privacy Latch | F02-MOD x TURNPIECE BOTH SIDES X | ||||
| OCCUPANCY INDICATOR | ||||||
| 1 | Kick Plate | J102 | ||||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Overhead Stop | C01541-ADJUSTABLE | ||||
| 2 | Set Self-Adhesive Seals | R0Y154 |
HW-3A
Each Door to Have: NON-RATED
THIS SET NOT USED.
HW-3B
Each Door to Have: NON-RATED/RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | ||
| 1 | Office Lock | F04 | |
| 1 | Closer | C02011/C02021 | |
| 1 | Floor Stop | L02121 x 3 FASTENERS | |
| 1 | Set Self-Adhesive Seals | R0Y154 |
OMIT VIEWER IF DOOR PROVIDED WITH VISION LITE.
HW-3C
THIS SET NOT USED.
HW-3E
Each Door to Have: NON-RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | ||
| 1 | Office Lock | F04 | |
| 1 | Floor Stop | L02121 x 3 FASTENERS | |
| 1 | Set Self-Adhesive Seals | R0Y154 | |
| 1 | Coat Hook | L03121 |
OMIT COAT HOOK WHERE GLASS LITE PREVENTS INSTALLATION.
HW-3F
Each Door to Have: RATED/NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Office Lock | F04 | ||||
| 1 | Closer | CO2011/CO2021 | ||||
| @ RATED DOOR | ||||||
| 1 | Kick Plate | J102 | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
HW-3H
Each Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | |||
| X ADJUSTA-SCREWS | |||||
| 1 | Office Lock | F04 | |||
| 1 | Closer | CO2011/CO2021 | |||
| 1 | Kick Plate | J102 | |||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | |||
| 1 | Floor Stop | L02121 x 3 FASTENERS | |||
| 1 | Sets Self-Adhesive Seals | R0Y154 |
HW-3J
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | |||
| X ADJUSTA-SCREWS | |||||
| 1 | Office Lock | F04 | |||
| 1 | Kick Plate | J102 | |||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | |||
| 1 | Floor Stop | L02121 x 3 FASTENERS | |||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) |
HW-4A
Each [ADO] Door to Have: RATED
| 1 | Continuous Transfer Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS x 4-THRUWIRE TRANSFER | ||||||
| X IN-HINGE ACCESS PANEL | ||||||
| 1 | Classroom Lock | F08 | ||||
| 1 | Electric Strike | E09311 (FAIL-SECURE), 12VDC | ||||
| 1 | Power Supply | REGULATED, FILTERED, 12VDC, AMPERAGE | ||||
| AS REQUIRED | ||||||
| 1 | Kick Plate | J102 | ||||
| 1 | Mop Plate (@ Inswing Doors) | J103 @ TOILET ROOMS ONLY | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
AUTOMATIC DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR OPERATORS.
POWER TRANSFER FOR RE-ACTIVATION SENSOR WIRING (RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
HW-4B
Each Door to Have: NON-RATED/RATED
| 1 | Continuous Hinge | |||
| 1 | Public Restroom Lock | F09 | ||
| 1 | Closer | C02011/C02021 | ||
| 1 | Closer | CO2051/CO2061 | ||
| 1 | Kick Plate | J102 | ||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||
| 1 | Floor Stop (@ Outswing Doors) | L02121 x 3 FASTENERS | ||
| 1 | Wall Stop (@ Inswing Doors) | L02101 CONVEX | ||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
HW-4C
Each Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Hospital Utility Lock | F09 x PADDLES POINTING DOWN | ||||
| 1 | Key Cylinder | TYPE AS REQUIRED | ||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Overhead Stop | C01541-ADJUSTABLE | ||||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||||
| 1 | Set Seals | R0Y164 |
HW-4D
Each Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Classroom Lock | F08 | ||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop (@ Outswing Doors) | L02121 x 3 FASTENERS | ||||
| 1 | Wall Stop (@ Inswing Doors) | L02101 CONVEX | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-4E
Each Door to Have: NON-RATED/RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | ||||
| 1 | Utility Lock | F09 | |||
| 1 | Closer (@ rated doors) | C02011/C02021 | |||
| 1 | Closer (@ non-rated doors) | CO2051/CO2061 | |||
| 1 | Kick Plate | J102 | |||
| 1 | Floor Stop | L02121 x 3 FASTENERS | |||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | |||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | |||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
HW-4F
Each Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Utility Lock | F09 | ||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop (@ Outswing Doors) | L02121 x 3 FASTENERS | ||||
| 1 | Wall Stop (@ Inswing Doors) | L02101 CONVEX | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-4G
Each Door to Have: RATED/NON-RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | |||
| 1 | Utility Lock | F09 | ||
| 1 | Closer (@ Rated Doors) | C02011/C02021 | ||
| 1 | Kick Plate | J102 | ||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-4H
Each [MHO] Door to Have: RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | |||
| 1 | Classroom Lock | F08 | ||
| 1 | Closer | C02011/C02021 | ||
| 1 | Kick Plate | J102 | ||
| 1 | Magnetic Holder | C00011 TRI-VOLTAGE | ||
| 1 | Set Self-Adhesive Seals | R0Y154 |
POWER, WIRING, CONDUIT, AND FIRE ALARM CONNECTION BY DIVISION 26.
HW-4J
| Each Door to Have: | RATED/NON-RATED | |||||
| Hinges | QUANTITY & TYPE AS REQUIRED | |||||
| 1 | Utility Lock | F09 | ||||
| 1 | Closer (@ Rated Doors) | C02011/C02021 | ||||
| 1 | Kick Plate | J102 | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
HW-4K
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Utility Lock | F09 | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-4L
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Classroom Lock | F08 | ||||
| 1 | Kick Plate | J102 | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||||
| 1 | Set Sound/Light Seals | R0Y264/R0Y255 |
HW-4M
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Classroom Hospital Lock | F08 x PADDLES POINTING DOWN | ||||
| 1 | Heavy-Duty Armor Plate | J101 x 3.175 MM (0.125 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-4N
Each Door to Have: RATED/NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Utility Lock | F09 | ||||
| 1 | Closer (@ rated doors) | C02011/C02021 | ||||
| 1 | Kick Plate | J102 | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
HW-4P
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Classroom Hospital Lock | F08 x PADDLES POINTING DOWN | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Overhead Stop | C01541-ADJUSTABLE | ||||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
HW-4Q
Each Door to Have: NON-RATED
| 1 | Pivot Set | C07162 x 454KG (1000 LBS) WEIGHT CAPACITY | |||
| 1 | Intermediate Pivot | CO7311 | |||
| 1 | Utility Hospital Lock | F09 x LEAD-LINED x PADDLES POINTING DOWN | |||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | |||
| 2 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | |||
| 1 | Overhead Stop | C01541-ADJUSTABLE | |||
| 1 | Set Self-Adhesive Seal | R0Y154 |
HW-4R
Each [ADO] Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS x 4-THRUWIRE TRANSFER | ||||||
| X IN-HINGE ACCESS PANEL | ||||||
| 1 | Classroom Lock | F08 | ||||
| 1 | Electric Strike | E09311 (FAIL-SECURE), 24VDC | ||||
| 1 | Power Supply | REGULATED, FILTERED, 24VDC, AMPERAGE | ||||
| AS REQUIRED | ||||||
| 1 | Kick Plate | J102 | ||||
| 1 | Mop Plate (@ Inswing Doors) | J103 @ TOILET ROOMS ONLY | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Threshold | J32300 x 57 MM WIDTH (2-1/4 INCHES) | ||||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||||
| 2 | Set Self-Adhesive Seals | R0Y154 |
AT TOILET ROOMS, OMIT METAL THRESHOLD; STONE THRESHOLD BY OTHER TRADES.
AUTOMATIC DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR OPERATORS.
POWER TRANSFER FOR RE-ACTIVATION SENSOR WIRING (RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
HW-4S
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Classroom Lock | F08 | ||||
| 1 | Heavy-Duty Armor Plate | J101 x 3.175 MM (0.125 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Auto Door Bottom | R0Y346 – HEAVY DUTY | ||||
| 2 | Sets Self-Adhesive Seals | R0Y154 |
HW-4T
Each Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Classroom Hospital Lock | F08 x PADDLES POINTING DOWN | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Overhead Stop | C01541-ADJUSTABLE | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-4U
Each Door to Have: NON-RATED/RATED
| 1 | Continuous Hinge | |||
| 1 | Public Restroom Lock | F09 | ||
| 1 | Closer | C02011/C02021 | ||
| 1 | Closer | CO2051/CO2061 | ||
| 1 | Kick Plate | J102 | ||
| 1 | Mop Plate (@ Inswing Doors) | J103 | ||
| 1 | Floor Stop (@ Outswing Doors) | L02121 x 3 FASTENERS | ||
| 1 | Wall Stop (@ Inswing Doors) | L02101 CONVEX | ||
| 1 | Set Self-Adhesive Seals | R0Y154 |
PROVIDE NON-HOLD-OPEN CLOSER AT TOILET ROOMS.
STONE THRESHOLD BY OTHER TRADES.
HW-4V
Each Lead-Lined Door to Have: NON-RATED
| 1 | Pivot Set | C07162 x 454KG (1000 LBS) WEIGHT CAPACITY | |||
| 1 | Intermediate Pivot | CO7311 | |||
| 1 | Utility Hospital Lock | F09 x LEAD-LINED x PADDLES POINTING DOWN | |||
| 1 | Closer | CO2011/CO2021 x METAL | |||
| LEAD-LINED COVER | |||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | |||
| 2 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | |||
| 1 | Overhead Holder-Stop | C01541-ADJUSTABLE | |||
| 1 | Set Self-Adhesive Seal | R0Y154 |
HW-4X
Each [ADO] Lead-Lined Door to Have: NON-RATED
| 1 | Pivot Set | C07162 x 454KG (1000 LBS) WEIGHT CAPACITY | ||||
| 1 | Intermediate Transfer Pivot | CO7311 x 4 WIRE TRANSFER | ||||
| 1 | Utility Hospital Lock | F09 x LEAD-LINED x PADDLES POINTING DOWN | ||||
| 1 | Electric Unlatch Strike | E09321 | ||||
| 1 | Power Supply | REGULATED, FILTERED, 24VDC, AMPERAGE | ||||
| AS REQUIRED | ||||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 2 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Overhead Stop | C01541-ADJUSTABLE | ||||
| 1 | Set Self-Adhesive Seal | R0Y154 |
POWER TRANSFER PIVOT IS FOR RE-ACTIVATION SENSOR WIRING (RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
AUTO DOOR OPERATORS AND CONTROLS BY SECTION 08 71 13.
HW-4Y
Each [ADO] Door to Have: NON-RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS x 4-THRUWIRE TRANSFER | ||||||
| X IN-HINGE ACCESS PANEL | ||||||
| 1 | Utility Hospital Lock | F09 x PADDLES POINTING DOWN | ||||
| 1 | Electric Unlatch Strike | E09321 | ||||
| 1 | Power Supply | REGULATED, FILTERED, 24VDC, AMPERAGE | ||||
| AS REQUIRED | ||||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Overhead Stop | C01541-ADJUSTABLE | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
POWER TRANSFER PIVOT IS FOR RE-ACTIVATION SENSOR WIRING (RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
AUTOMATIC DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR OPERATORS.
HW-5
Each Door to Have: RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | |||
| 1 | Storeroom Lock | F07 | ||
| 1 | Closer | C02011/C02021 | ||
| 1 | Kick Plate | J102 (@ STORAGE, EVM, & HAC ROOMS ONLY) | ||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-5A
THIS SET NOT USED.
HW-5B
Each Door to Have: RATED
| 1 | Continuous Hinge | x INTEGRAL HINGE GUARD CHANNEL | ||||
| X ADJUSTA-SCREWS | ||||||
| 1 | Storeroom Lock | F07 | ||||
| 1 | Closer | C02011/C02021 | ||||
| 1 | Armor Plate | J101 x 1.275 MM (0.050 INCH) THICKNESS | ||||
| 1 | Edge Guard (@ Wood Doors) | J208M / J211 (VERIFY), CUT: HARDWARE | ||||
| 1 | Floor Stop | L02121 x 3 FASTENERS | ||||
| 1 | Set Self-Adhesive Seals | R0Y154 |
HW-5C
THIS SET NOT USED.
HW-5D
Each Door to Have: NON-RATED
| Hinges | QUANTITY & TYPE AS REQUIRED | |||
| 1 | Storeroom Lock | F07 | ||
| 1 | Kick Plate | J102 (@ STORAGE, EVM, & HAC ROOMS ONLY) | ||
| 1 | Floor Stop (@ Inswing Doors) | L02121 x 3 FASTENERS | ||
| 1 | Wall Stop (@ Outswing Doors) | L02101 CONVEX | ||
| 3 | Silencers | L03011 |
HW-5E
Each Door to Have:…
This is the start of the file's text. The full file is on GovTribe.