This document is a 35% Schematic Design Submission for Asbestos & Lead Paint Summary at Cincinnati and Ft. Thomas VA Medical Centers, focusing on a door repair and replacement project (22.8001.01). The site visit on November 14, 2022, conducted by Castle Hill Associates, revealed asbestos-containing materials in wood fire door cores and lead paint presence in specific locations.
The hazardous materials summary shows varied findings across multiple buildings. At the Cincinnati VAMC, Buildings 1 and 3 have asbestos present in wood fire doors on certain floors, while at Ft. Thomas VAMC, Building 64 shows more extensive contamination, with asbestos in wood fire doors on basement, first, second, and third floors. Notably, a specific door frame (C-B-4-2) in the basement of Building 64 tested positive for lead paint. The XRF lead paint testing data, performed using a Viken Detection Pb200i analyzer, provides detailed readings for doors and door frames across the buildings, with most readings being negative for lead concentration.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25026B0003 0002.docx | DOCX document | |
| 36C25026B0003 0001.docx | DOCX document | |
| Attachment VII - VHA Directive 1192.01, Flu.pdf | ||
| Attachment VI - 852.219-75 LOS.docx | DOCX document | |
| Attachment IV - RFI Form.pdf | ||
| Attachment III - Drawings Rev 8-4-25.pdf | ||
| Attachment II - Specifications Rev 8-4-25.pdf | ||
| Attachment XI - PCRA-ICRA.pdf | ||
| Attachment VIII - Best Sole Source J-A Redacted.pdf | ||
| Attachment V - EMR Form.pdf | ||
| Attachment I - WD OH20250082.pdf | ||
| 36C25026B0003.docx | DOCX document | |
| Attachment XIII - WD KY20250088.pdf | ||
| Attachmennt XII - NEPA Repair and Replace Doors.pdf | ||
| Attachment X - JCI Sole Source J-A - Redacted.pdf | ||
| Attachment IX - Corbin Russwin J-A - Redacted.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
35% SCHEMATIC DESIGN SUBMISSION
ASBESTOS & LEAD PAINT SUMMARY
CINCINNATI & FT. THOMAS VA MEDICAL CENTER
REPAIR AND REPLACE DOORS 22.8001.01
Date: November 15, 2022
Item: Summary Results of HazMat Site Visit (asbestos & lead paint)
Site Visit: November 14, 2022
Inspectors: Brett Brumbaugh & Matt Brumbaugh - Castle Hill Associates
Findings: Asbestos containing materials are assumed present in wood fire doors interiors
Lead paint is present at Ft. Thomas VAMC (C-B-4-2 Door Frame in Basement 2)
BUILDING HAZMAT SUMMARIES
CINCINNATI VAMC
Building Number
Floor Asbestos Present?
(Cores of Wood Fire Doors)
Lead Paint Present?
(Doors & Door
Frames)
1 Basement No No
1 3rd Floor YES No
1 7th Floor YES No
3 Basement No No
3 1st Floor No No
15 1st Floor No No
FT. THOMAS VAMC
Building Number
Floor Asbestos Present?
(Cores of Wood Fire Doors)
Lead Paint Present?
(Doors & Door
Frames)
64 Basement YES
YES
(C-B-4-2 Door Frame)
64 1st Floor YES No
64 2nd Floor YES No
64 3rd Floor YES No
Notes:
• The wood passage and hallway doors are assumed to contain an asbestos core insulation. Sampling was not conducted on the wood cores.
• Metal passage and entry doors are not considered suspect for asbestos interior insulation.
35% SCHEMATIC DESIGN SUBMISSION
ASBESTOS & LEAD PAINT SUMMARY
CINCINNATI & FT. THOMAS VA MEDICAL CENTER
REPAIR AND REPLACE DOORS 22.8001.01
LEAD PAINT TESTING DATA
Project: VA Cincinnati & Ft. Thomas Repair and Replace Doors
Buildings: 1, 3, 15, and 64
Technician: Brett Brumbaugh
Dates: 11/14/2022
XRF Mfg.: Viken Detection
Model: Pb200i
Type: XRF Lead Paint Analyzer
Serial # 2757
Reading # Building Floor Room Component Substrate Pb Conc.
mg/cm2 Result
1 1 Basement C*B*7 Door Metal 0.3 Negative
2 1 Basement C*B*7 Door frame Metal 0.2 Negative
3 1 Basement A023 Door Metal 0.2 Negative
4 1 Basement A023 Door frame Metal 0.1 Negative
5 1 Basement B013 Door Metal 0.0 Negative
6 1 Basement B013 Door frame Metal 0.1 Negative
7 1 3rd Floor C*3*9 Door Metal 0.1 Negative
8 1 3rd Floor C*3*17 Door frame Metal 0.2 Negative
9 1 3rd Floor B303 Door frame Metal 0.2 Negative
10 1 3rd Floor C-3-7 Door frame Metal 0.0 Negative
11 1 3rd Floor C*3*6 Door frame Metal -0.1 Negative
12 1 7th Floor S-7-2 Door frame Metal 0.3 Negative
13 1 7th Floor S-7-2 Door Metal 0.1 Negative
14 1 7th Floor A720 Door frame Metal 0.0 Negative
15 1 7th Floor A717 Door frame Metal -0.1 Negative
16 1 7th Floor A723 Door frame Metal 0.2 Negative
17 1 7th Floor A725 Door frame Metal 0.0 Negative
18 1 7th Floor A710 Door frame Metal -0.1 Negative
19 1 7th Floor A707 Door frame Metal 0.2 Negative
20 1 7th Floor A704 Door frame Metal -0.1 Negative
21 1 7th Floor A-727A Door Metal 0.0 Negative
22 1 7th Floor A-727A Door frame Metal 0.2 Negative
23 3 Basement 13 Door Metal 0.3 Negative
24 3 Basement 13 Door frame Metal 0.2 Negative
25 3 Sub-basement sub4 Door Metal 0.5 Negative
26 3 Sub-basement sub4 Door frame Metal 0.0 Negative
27 15 1st floor 117 Door Metal 0.1 Negative
28 15 1st floor 117 Door frame Metal -0.1 Negative
29 15 1st floor 119 Door Metal 0.2 Negative
30 15 1st floor 119 Door frame Metal -0.1 Negative
31 64 Basement 1 C-B-1 Door Metal 0.1 Negative
32 64 Basement 1 C-B-1 Door frame Metal 0.2 Negative
33 64 Basement 1 4 Door Metal 0.2 Negative
34 64 Basement 1 4 Door frame Metal 0.3 Negative
35 64 Basement 1 2 Door Metal 0.0 Negative
36 64 Basement 1 2 Door frame Metal 0.1 Negative
37 64 Basement 1 28 Door Metal 0.2 Negative
38 64 Basement 1 002A Door frame Metal 0.2 Negative
39 64 Basement 1 C-B-2 Door Metal 0.0 Negative
Project: VA Cincinnati & Ft. Thomas Repair and Replace Doors
Buildings: 1, 3, 15, and 64
Technician: Brett Brumbaugh
Dates: 11/14/2022
XRF Mfg.: Viken Detection
Model: Pb200i
Type: XRF Lead Paint Analyzer
Serial # 2757
Reading # Building Floor Room Component Substrate Pb Conc.
mg/cm2 Result
40 64 Basement 1 C-B-2 Door frame Metal 0.2 Negative
41 64 Basement 2 C-B-4-2 Door Metal -0.1 Negative
42 64 Basement 2 C-B-4-2 Door frame Metal 6.2 POSITIVE
43 64 Basement 2 C-B-4-1 Door Metal 0.0 Negative
44 64 Basement 2 C-B-4-1 Door frame Metal -0.1 Negative
45 64 Basement 2 29 Door Metal -0.1 Negative
46 64 Basement 2 29 Door frame Metal 0.2 Negative
47 64 1st floor 100 Door Metal 0.1 Negative
48 64 1st floor 100 Door frame Metal 0.0 Negative
49 64 1st floor 108 Door frame Metal 0.2 Negative
50 64 1st floor 138 Door frame Metal 0.3 Negative
51 64 1st floor 148a Door frame Metal 0.2 Negative
52 64 1st floor 123 Door frame Metal 0.0 Negative
53 64 1st floor 127 Door frame Metal -0.1 Negative
54 64 1st floor 155 Door frame Metal 0.3 Negative
55 64 1st floor 125 Door frame Metal -0.1 Negative
56 64 2nd floor 264 Door frame Metal 0.3 Negative
57 64 2nd floor c-2-5 Door frame Metal 0.0 Negative
58 64 2nd floor 233 Door frame Metal -0.1 Negative
59 64 3rd Floor S-3-5 Door Metal -0.1 Negative
60 64 3rd Floor S-3-5 Door frame Metal 0.2 Negative
61 64 3rd Floor 360 Door frame Metal 0.0 Negative
62 64 3rd Floor 356 Door frame Metal 0.0 Negative
63 64 3rd Floor 352 Door frame Metal 0.0 Negative
64 64 3rd Floor 305 Door frame Metal 0.2 Negative
65 64 3rd Floor 324 Door frame Metal 0.0 Negative
66 64 3rd Floor S-3-5 Door frame Metal 0.2 Negative