Dayton VA Correct Arc Flash Deficiencies i

REVISION HISTORY

Rev # Issued Revision / Modification Description

- 04/2019 Initial Study Report Issue

1 05/2019 Misc document corrections, added One Lines

2 5/2019 Misc document corrections, added building 126, corrected bldg 305

3 7/2019 Building 410 corrections

4 9/2019 Added additional One Lines and corrected changes per As Built 3-22-19

Dayton VA Correct Arc Flash Deficiencies ii

TABLE OF CONTENTS

EXECUTIVE SUMMARY ....................................................................................... 1-1

SHORT-CIRCUIT ANALYSIS................................................................................ 2-1

PROTECTIVE DEVICE COORDINATION STUDY ................................................ 3-1

RECOMMENDED PROTECTIVE DEVICE SETTINGS ......................................... 4-1

ARC FLASH INCIDENT ENERGY ANALYSIS ..................................................... 5-1

SYSTEM DATA ..................................................................................................... 6-1

SHORT-CIRCUIT INPUT REPORT ....................................................................... 7-1

SHORT-CIRCUIT RESULTS ................................................................................. 8-1

UTILITY DATA ...................................................................................................... 9-1

APPLICABLE CODES AND STANDARDS ........................................................ 10-1

ONE-LINE DIAGRAM INDEX .............................................................................. 11-1

Dayton VA Correct Arc Flash Deficiencies 1-1

EXECUTIVE SUMMARY

This summary report contains the results of analyses performed on the electrical distribution system for Dayton VA Corrections of Arc Flash Deficiencies. The purpose of this study is to evaluate new electrical equipment provided for this facility.

System data and necessary modeling assumptions are provided under Section 6.0.

1. Short-Circuit Analysis

Perform a short-circuit study on the electrical distribution system shown in order to determine the available fault current at pertinent locations throughout the distribution system. The scope of the study includes:

• Analysis beginning at the incoming 69 kV utility service, continuing through the medium and low voltage substations, and ending at the low voltage panelboards as shown in the contract drawings.

The available fault currents determined by the short-circuit study will be used in the electrical distribution analyses.

2. Equipment Evaluation

Evaluate the short-circuit ratings of new protective devices and other distribution equipment supplied by Eaton under this contract.

3. Coordination Study

Develop time-current coordination plots to derive coordinated settings for new protective devices.

4. Arc Flash Analysis

Perform an arc flash incident energy analysis per NFPA 70E on the electrical distribution system as per Eaton’s scope of work.

An incident energy analysis is defined by NFPA 70E to be a component of an arc flash risk assessment used to predict the incident energy of an arc flash for a specified set of conditions.

5. Recommendations

Provide specific recommendations for improving the electrical distribution system performance and correcting any deficiencies found by the studies.

1. Short-Circuit Study

The system was modeled for worst-case fault currents. Short-circuit currents were calculated for a three-phase bolted fault and single-line-to-ground fault at each bus shown on the one-line diagrams found in Section 11.0.

See Section 2.0, Section 7.0, and Section 8.0 for more information.

Dayton VA Correct Arc Flash Deficiencies 1-2

2. Equipment Evaluation

The Equipment Evaluation is based on the power system worst-case short-circuit current configuration. The short-circuit ratings of protective devices and other distribution equipment are evaluated in Section 2.0, Table 2.1.

In summary of Table 2.1, specific equipment has failed the equipment evaluation and are considered overdutied. It is recommended that the overdutied panelboards be reviewed for breaker and/or panelboard replacement to comply with the short-circuit current ratings required.

See Section 2.0 for detailed analysis and evaluation results.

3. Coordination Study

The time-current coordination plots of the protective overcurrent devices are shown in Section 3.0. In developing the device settings, consideration was given to the isolation of faults, protection of cables, and protection of transformers.

Efforts were made to provide the best coordination possible with the protective devices supplied under this contract and existing protective devices. It should be understood that coordination between two instantaneous trip units cannot be achieved for fault levels above the instantaneous pickup of the upstream device.

There is some overlapping of curves that cannot be avoided.

In summary of the coordination study, the following recommended changes would maximize coordination while maintaining adequate protection:

• Cables CBL-126-1-10, CBL-126-1-10C and CBL-126-1-09 DISC are undersized per NEC Article 310.15. Recommend upgrading to #1/0 CU AWG.

• Cable CBL-1726 is undersized per NEC Article 240.4(D). Recommend upgrading to #8 CU AWG or using a 30A fuse.

• Cable CBL-412-1-04B is undersized per NEC 310.15. Recommend upgrading cable to #3 CU AWG.

All of the adjustable low voltage electronic trip and thermal magnetic circuit breakers should be tested and adjusted according to the recommended settings given in Section 4.0.

4. Protective Device Settings

Settings for the protective devices supplied by Eaton should be set as shown and recommended in Section 4.0.

5. Arc Flash Incident Energy Analysis

Details of the arc flash incident energy analysis are shown in Section 5.0. Please note for this study, the arc flash hazard has been calculated by performing an incident energy analysis. The results of this study can be used by qualified workers to determine the arc flash boundary and select appropriate arc flash PPE as part of an overall arc flash risk assessment. NFPA 70E Table 130.5(g) provides guidance on the selection of arc rated clothing and other PPE based on the results of an incident energy analysis. It is the responsibility of the employer and qualified person(s) to conduct an overall arc flash risk assessment as detailed in NFPA 70E- 2018 Article 130.5 before the commencement of work on electrical equipment. The

Dayton VA Correct Arc Flash Deficiencies 1-3 risk associated with performing energized electrical work will vary based on the work being performed as well as the condition of the equipment and other factors that can be best determined by a qualified person in the field.

The PPE requirements outlined in NFPA 70E only address the thermal hazards associated with arc flash events and do not provide protection against other possible physical trauma resulting from an arc flash event. See NFPA 70E Article 120 for details on establishing an electrically safe work condition.

6. Testing and Preventative Maintenance

The 2018 edition of NFPA 70E Section 205.3 and 205.4 requires that regularly scheduled testing and preventative maintenance be performed to ensure that the electrical distribution equipment continues to perform at an optimum level. Testing should entail primary injection testing of all circuit breakers to verify proper tripping ranges, contact resistance testing, insulation resistance testing and complete switchgear and transformer cleaning and inspection. Refer to NFPA-70B for specific types of testing and interval recommendations. The industry generally performs breaker testing every 3-5 years.

Dayton VA Correct Arc Flash Deficiencies 2-1

SHORT-CIRCUIT ANALYSIS

The short-circuit study determines the fault currents that flow in the system during various fault conditions. A system model was created using SKM Systems Analysis software. The calculated fault currents are used in the device evaluation and coordination studies. See Section 7.0 and Section 8.0 for the computer generated input data and output data. NEC-2017, Article 110.24(A) requires that service entrance equipment is labeled with the following pieces of information:

• Maximum available fault current

• Date on which the fault current was calculated

Article 110.24(B) adds that if there is a modification that may change this fault current value, it must be recalculated. The field marking must be updated to reflect the new value of maximum fault current.

Separate “Z” (complex), “X” (reactive), and "R" (resistive) networks are used for the short-circuit analysis. Complex network reduction and the relationship E/Z are used to calculate the fault current magnitude and angle at each faulted bus. The complex equivalent circuit impedance, Z, is calculated by the reduction of the “Z” (complex) network. The X/R ratios calculated for each fault condition are based on the separate reduction of the X and R networks. These X/R ratios are used for the calculation of fault duty multipliers, to evaluate the short-circuit ratings of system components.

The software is capable of generating three types of short-circuit reports for both balanced (three-phase bolted) and unbalanced (line-to-ground) faults. The reports that are generated depend on the system that is being evaluated.

The three types of short-circuit reports are:

• Fault Report (for low voltage)

• Momentary Duty Report (for medium voltage) – Not Applicable

• Interrupting Duty Report (for medium voltage) – Not Applicable

1. Fault Report

The fault currents reported in the “Fault Report” are applicable to low voltage devices and components. The fault currents calculated in this report are based on the contribution data derived from IEEE Std C37.13™. The fault currents are calculated as follows:

• Motor and generator subtransient reactance values (Xd”) are adjusted per the first cycle duty multipliers described in IEEE Std 141™.

• The complex equivalent circuit impedance, Z, is calculated by network reduction of the “Z” (complex) network.

• The momentary symmetrical current = E/Z.

• The X/R ratio is equal to the equivalent circuit reactance, X, divided by the equivalent circuit resistance, R. As discussed above, X is calculated by the reduction of the “X” (reactive) network and R is calculated by the reduction of the “R” (resistive) network.

Dayton VA Correct Arc Flash Deficiencies 2-2

Multiplying factors are determined, and used to adjust the calculated symmetrical fault current. The adjusted current is used to evaluate low voltage protective devices. Low voltage output algorithms and output reports reflect NEMA AB-1 molded case breaker de-rating multipliers. Breakers are de-rated for circuits where the power factor is lower than the NEMA test circuit (higher X/R ratio). The multipliers adjust the symmetrical fault current to the value associated with the systems fault point X/R ratio. The adjusted value listed on the report may then be compared directly with the manufacturer's published interrupting rating.

The objective of the short-circuit analysis is to calculate the maximum short-circuit currents produced by balanced three-phase and unbalanced faults at each bus shown on the one-line diagrams.

1. Short-Circuit System Model

The system was modeled for worst-case fault currents. Short-circuit currents were calculated for a three-phase bolted fault and single-line-to-ground fault at each bus shown on the study one-line diagrams.

a) Evaluated Short-Circuit Cases:

The following short-circuit study cases were evaluated:

• Study Case No. 1 – System supplied from Crown source.

• Study Case No. 2 – System supplied from Tait source.

The purpose of the equipment evaluation is to compare the maximum calculated short-circuit currents to the short-circuit ratings of protective devices. The comparison is made in order to determine if the device can interrupt or withstand the available fault currents of the electrical system to which the device is applied, as required by NEC Articles 110.9 and 110.10. The device evaluation follows the evaluation procedures outlined in IEEE Std C37.13, IEEE Std C37.010, IEEE Std C37.5, IEEE Std C37.41™, IEEE Std 1015™, and applicable ANSI, NEMA, and UL standards.

The results of the short-circuit equipment evaluation are summarized in Table 2.1.

The tables indicates “Bus I.D.” (corresponds to bus designations used in the one-line diagrams, “Manufacturer”, “Status” (Pass, fail, unknown, or marginal), “Type” (equipment category), “Equip Volts”, calculated short-circuit duty, the equipment short-circuit rating, the series rating (if applicable), and the maximum duty rating.

The maximum duty rating is calculated by:

RatingCDeviceS dutyCS

If the short-circuit rating of a device is not known, and/or short-circuit rating information is not available, a Minimum Required short-circuit rating is listed. All short-circuit current values are reported in units of kA.

Dayton VA Correct Arc Flash Deficiencies 2-3

1. For low voltage devices:

The calculated short-circuit duty is reported under “Calc Isc (kA)" and the device short-circuit rating is reported under "Equip Isc (kA)". The calculated duty has been adjusted accordingly per the system X/R and device test X/R.

Information used in modeling the power system to provide conservative, worst-case results is listed in Section 6.0. The results of the short-circuit analysis, including calculated branch contributions, are provided under Section 8.0. The one-line diagrams with referenced bus identification are included in Section 11.0.

Dayton VA Correct Arc Flash Deficiencies 2-4

Table 2.1 – Low-Voltage Equipment Evaluation

Bus I.D. Manufacturer Status Type Bus Voltage (V) Calc

Isc (kA) Equip

Isc (kA) Rating %

115-1-03A-2B EATON Pass LV Panelboard 208 12.53 22.00 56.96

115-1-03A-2D EATON Pass LV Panelboard 208 12.12 22.00 55.09

115-1-03A-2E EATON Pass LV Panelboard 208 13.80 22.00 62.73

115 CH-1 CP UL 67 Pass LV Panelboard 208 18.10 65.00 27.85

118 PNL LP-1 UL 67 Pass LV Panelboard 240 2.42 10.00 24.20

PNLBD 120-1 UL 67 Pass LV Panelboard 208 7.93 10.00 79.3

126-1-08A-05 UL 67 Pass LV Panelboard 208 4.67 18.00 25.95

126-1-09 DISC UL 67 Pass LV Disconnect 208 4.25 65.00 6.54

126-1-11 UL 67 Pass LV Panelboard 208 7.87 65.00 12.11

305CH-2 UL 67 Pass LV Panelboard 208 10.22 65.00 15.73

305-1-02B EATON Pass LV Panelboard 208 6.47 10.00 64.69

305-1-04-34A EATON Pass LV Panelboard 208 0.82 22.00 3.71

305-1-04-34B EATON Pass LV Panelboard 208 1.29 22.00 5.86

305-1-05 EATON Pass LV Panelboard 208 7.83 10.00 78.32

305-1-05-02 UL 67 Pass LV Panelboard 208 6.37 10.00 63.69

305-1-05-03 UL 67 Pass LV Panelboard 208 3.61 10.00 36.1

305-1-05-04 EATON Pass LV Panelboard 208 2.03 10.00 20.29

305-1-05-05 UL 67 Pass LV Panelboard 208 6.56 10.00 65.57

305-1-05-06 UL 67 Pass LV Panelboard 208 2.11 10.00 21.09

305-1-05-08 UL 67 Pass LV Panelboard 208 7.51 (*N1) 10.00 75.13

305-1-05-09A UL 67 Pass LV Panelboard 208 2.82 5.00 56.4

305-1-05-09B UL 67 Pass LV Panelboard 208 2.03 5.00 40.69

305-1-05-10 EATON Pass LV Panelboard 208 3.27 10.00 32.68

305-1-05-11 UL 67 Pass LV Panelboard 208 4.32 10.00 43.23

Dayton VA Correct Arc Flash Deficiencies 2-5

Bus I.D. Manufacturer Status Type Bus Voltage (V) Calc

Isc (kA) Equip

Isc (kA) Rating %

305-1-06 EATON Pass LV Panelboard 208 11.13 22.00 50.58

LSD BLDG 315 EATON Pass LV Panelboard 480 13.77 18.00 76.5

PANEL 315 MD UL 891 Pass LV Switchboard 480 17.20 (*N1) 22.00 78.17

315 CH-1 CP UL 67 Pass LV Panelboard 480 14.72 65.00 22.64

320E-1 UL 67 Pass LV Panelboard 480 15.47 22.00 70.34

321 PNL DP UL 67 Pass LV Panelboard 208 7.90 (*N1) 10.00 79.01

PNL LN-1B-PET UL 67 Pass LV Panelboard 208 0.66 22.00 3

PNL HNBC UL 67 Pass LV Panelboard 480 8.99 14.00 64.18

PNL LN4C EATON Pass LV Panelboard 208 1.68 (*N1) 10.00 16.77

PNL LNBC EATON Pass LV Panelboard 208 2.22 (*N1) 10.00 22.16

PNL EL1 UL 67 Pass LV Panelboard 480 13.41 65.00 20.63

PNL EL2 UL 67 Pass LV Panelboard 480 13.26 65.00 20.4

400-1-10 EATON Pass LV Panelboard 208 8.52 10.00 85.2

BLDG 402 MDP-1 UL 891 Pass LV Switchboard 208 19.89 42.00 47.37

409E-1 UL 891 Pass LV Switchboard 208 23.55 65.00 36.23

410-1-03 UL 67 Pass LV Panelboard 208 22.76 25.00 91.02

410-1-04 EATON Pass LV Panelboard 208 21.52 42.00 51.24

410-1-04-01 UL 67 Pass LV Panelboard 208 7.49 10.00 74.93

410-1-04-21 EATON Pass LV Panelboard 208 8.91 22.00 40.52

410-1-04-34 EATON Pass LV Panelboard 208 4.33 22.00 19.66

410-1-06-01A-01 UL 67 Pass LV Panelboard 208 12.11 25.00 48.45

410E-1-02A-01A-01 UL 67 Pass LV Panelboard 208 4.22 10.00 42.19

410E-1-5 EATON Pass LV Panelboard 208 14.65 22.00 66.58

412-1-03 EATON Pass LV Panelboard 208 6.49 10.00 64.91

412-1-04A EATON Pass LV Panelboard 208 7.91 10.00 79.07

412-1-04B EATON Pass LV Panelboard 208 2.6 10.00 26.01

Dayton VA Correct Arc Flash Deficiencies 2-6

Bus I.D. Manufacturer Status Type Bus Voltage (V) Calc

Isc (kA) Equip

Isc (kA) Rating %

412-AC LOBBY UL 67 Pass LV Panelboard 208 6.16 22.00 28.01

(*N1) System X/R higher than Test X/R, Calc Isc (kA) modified based on low voltage factor.

Dayton VA Correct Arc Flash Deficiencies 3-1

PROTECTIVE DEVICE COORDINATION STUDY

The protective device coordination study determines overcurrent protective relay and circuit breaker settings in order to provide an optimal compromise between protection and selectivity.

Using the appropriate maximum fault currents, the time-current coordination curves were plotted as operating time versus current magnitudes to show protective device tripping and/or clearing characteristics and coordination among these devices.

Consideration was given to provide both selective isolation of faults and maximum protection of equipment such as cables, transformers, motors, etc.

To achieve the optimum protection and selectivity, the following guidelines were followed throughout the study:

1. Ideally, the settings of any overcurrent device should be high enough to permit the continuous full-load operating capacity of the cables and the equipment they supply, and to ride through system temporary disturbances such as in-rush current. On the other hand, the settings should be low enough to provide overload and short-circuit protection under minimum fault conditions.

2. Considering any two protective devices in series:

• The maximum available fault current at the downstream device determines the upper limit of the coordination range between these two devices.

• The minimum available fault current at the downstream device or the pick-up setting of the upstream device determines the lower limit of the coordination range.

• Series instantaneous devices do not coordinate unless there is sufficient impedance between the two devices.

• When plotting coordination curves, certain time intervals must be maintained between the curves in order to ensure correct selectivity. These time intervals vary, depending on the device types. In general, however, the following must be taken into consideration when determining the appropriate time separation interval: Breaker clearing time, relay tolerances, induction disk over-travel, and a reasonable safety margin for error.

Protective device coordination was performed in accordance with IEEE Std 242™.

Minimum guidelines for equipment protection, as outlined in the National Electrical Code (NEC) and applicable standards of the American National Standards Institute (ANSI), were followed.

Applicable requirements are summarized below.

1. Cables

Power cables require overload and short-circuit protection in order to meet the requirements stated in NEC Article 240, and IEEE Std 242. The NEC further

Dayton VA Correct Arc Flash Deficiencies 3-2 requires that the ampacity of low voltage cable (0-2000 Volts) be determined by NEC Article 310.15. Cable de-rating based upon ambient temperature and the number of current carrying conductors in a raceway must also be applied. Medium voltage cable (2001-35,000 Volts) ampacity is defined by NEC Articles 240.100(A) and 310.60.

2. Transformers

A transformer is recommended to have protective devices on both primary and secondary side in order to meet the basic protection requirements for overloads and short-circuit withstand values. However, a transformer is permitted to be protected by only a primary side device if it meets the exceptions listed in NEC Article 240.4(F).

In addition, the transformer protective devices must be able to withstand magnetizing inrush currents without tripping.

NEC protection requirements for transformers: Overcurrent devices should be selected, and settings should be recommended to provide overcurrent protection in accordance with NEC Article 450.3. Paragraph (A) specifies that transformers over 600 V comply with Table 450.3(A). Paragraph (B) specifies that transformers less than 600 V comply with Table 450.3(B).

Short-circuit thermal limits for transformers: The primary devices should be set on the basis that the transformers have short-circuit withstand capabilities as defined by IEEE Std C57.109™.

3. Motors

The motors should have appropriate protective devices to meet the basic protection requirements for overloads and fault current withstand values. In addition, the motor short-circuit and ground fault protective devices should be set to ride through motor starting current.

Please see Section 6.0 for a complete list of data and assumptions that were used in modeling the power system to provide conservative, worst-case results. Please note that complete information regarding the system model used for the computer simulation is included in Section 7.0.

As shown on the time-current plots, each device curve is tagged with an arrow and label referencing its location on the plot's individual representative one-line diagram.

This label also references the device to its specific manufacturer information, including ratings and settings, as indicated in the text box on each plot. The device time-current characteristics are truncated at maximum through-fault current for a downstream fault.

Efforts were made to provide the best coordination possible with the protective devices supplied under this contract. Areas where breaker trip curves overlap indicate areas of possible non-selective breaker operation. Where possible, efforts were made to reduce non-selective breaker operation while maintaining adequate system protection. In some cases, because of device limitations, little can be done to improve device selectivity. Such device limitations include the fixed operating characteristic of a fuse, the built-in instantaneous or instantaneous “over-ride”

Dayton VA Correct Arc Flash Deficiencies 3-3 elements of molded case circuit breakers, and the limited instantaneous trip range of trip units with an instantaneous trip function.

In cases involving redundant protective devices, non-selective breaker operation is of little or no concern. Protective devices are redundant if, regardless of which device opens, the same system outage occurs. Often, in order to improve overall system protection and coordination, redundant devices are intentionally set to overlap (i.e.

non-selectively coordinate with) one another.

Adequate coordination is achieved using the recommended protective devices, with settings and ratings as listed in Section 4.0. The recommended adjustments would maximize coordination in an attempt to allow the various downstream devices to isolate faults without operation of the upstream devices. Although instantaneous trip devices provide the highest degree of protection, when applied in series they compromise selectivity at high-magnitude fault currents.

Refer to the following pages for the plotted coordination curves, which graphically indicate the degree of selectivity and protection obtained.

In some cases, a single time-current curve may be applicable to several locations in the system, where each location utilizes substantially similar devices, and serves similar loads.

The following list references the attached time-current curves for this report.

Table 3.1 – TCC Plots Index

Title Page Number

01 NEW CB-BLDG 118 MAIN Page 3-4

02 NEW PNLBD 120-1 FDR Page 3-5

03 SWBD 115-1-03A to 115-1-03A-2B Page 3-6

04 305-1-02B Page 3-7

05 LSD BLDG 315 Page 3-8

06 PNL LNBC Page 3-9

07 PNL LN4C Page 3-10

08 PNL 410-1-04 Page 3-11

09 PNL 412-1-04A Page 3-12

10 BLD 315 MAIN Page 3-13

11 CB 410-1-03 to CB 410-1-06-01A-01 Page 3-14

12 CB 410E-1-4 MAIN TO CB-410E-1-02A-01A-01 MAIN Page 3-15

13 CB 305-1A TO CB-305-1-06 MAIN Page 3-16

Dayton VA Correct Arc Flash Deficiencies 3-4

Title Page Number

14 CB-305-1-05 MAIN TO CB-305-1-05-02 Page 3-17

15 CB-305-1-05 MAIN TO CB-305-1-04-34B Page 3-18

16 F-115-1-03A-T2 TO CB-115-1-03A-2E MAIN Page 3-19

17 CB-BLDG 120 MAIN TO F 120-1-01A-01-01F Page 3-20

18 CB-126-1-08A TO CB-126-1-08A-05 Page 3-21

19 F-LSD ATS E TO LSD BLDG 315 Page 3-22

20 CB320 ELEV 2 N & E FEED Page 3-23

21 F-TX-T-17-1 TO CB 402-1-5MAIN Page 3-24

22 CB-412-1-03 TO CB-412-AC LOBBY Page 3-25

23 CB-412-1-04 TO CB-412-1-04B MAIN Page 3-26

24 BLD 315 MAIN (GND) Page 3-27

TX Inrush

0.5 1 10 10

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

F-TX T-4-1

COOPER

1.5C-200C TYPE: NX (C-Rated), 15.5kV Sensor/Trip: 12A, Phase

12.0 Amps

CB-BLDG 118 MAIN

CUTLER-HAMMER

300-600A

TYPE: LD

Sensor/Trip: 300A, Plug: 300 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (3000A)

CB-118LP2

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 175A, Plug: 175 AT Phase Fixed TX-T-4-1

50 kVA 12470 / 240 V

F-TX T-4-1

COOPER

1.5C-200C TYPE: NX (C-Rated), 15.5kV Sensor/Trip: 12A, Phase

12.0 Amps

CB-BLDG 118 MAIN

CUTLER-HAMMER

300-600A

TYPE: LD

Sensor/Trip: 300A, Plug: 300 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (3000A)

CB-118LP2

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 175A, Plug: 175 AT Phase Fixed TX-T-4-1

50 kVA 12470 / 240 V

Plot name: 01 NEW CB-BLDG 118 MAIN Ref. Voltage: 240V Current Scale: x 1

F-TX T-4-1

COOPER

NX (C-Rated), 15.5kV 12A

S

P TX-T-4-1

50 kVA 12470 / 240V 4.50% Z

CB-BLDG 118 MAIN

CUTLER-HAMMER

LD

300A/300A

CB-118LP2

CUTLER-HAMMER

EDB, 2-3 Poles 175A/175A

CBL-118 LP1

2 - #350 200 ft Copper

118 PNL LP-1

240V

Eaton Electrical Services and Systems September 4, 2019

VAMC DAYTON 3-4

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-BLDG 120 MAIN

CUTLER-HAMMER

100-400A

TYPE: KD

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (2000A)

CB-ATS-120 N

CUTLER-HAMMER

15-100A TYPE: QBHW, 3-Pole Sensor/Trip: 90A, Plug: 90 AT Phase Fixed

CB-BLDG 120 MAIN

CUTLER-HAMMER

100-400A

TYPE: KD

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (2000A)

CB-ATS-120 N

CUTLER-HAMMER

15-100A TYPE: QBHW, 3-Pole Sensor/Trip: 90A, Plug: 90 AT Phase Fixed

Plot name: 02 NEW PNLBD 120-1 FDR Ref. Voltage: 208V Current Scale: x 1

CB-BLDG 120 MAIN

CUTLER-HAMMER

KD

400A/400A

CB-ATS-120 N

CUTLER-HAMMER

QBHW, 3-Pole 90A/90A

PNLBD 120-1

208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-5

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

F-115-1-03A-2B

BUSSMANN

1-600A TYPE: LPN-RK, 250V Class RK1 Sensor/Trip: 200A, CB-115-1-03A-2B MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

CB 115AHU2

CUTLER-HAMMER

15-100A TYPE: QBHW, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed

F-115-1-03A-2B

BUSSMANN

1-600A TYPE: LPN-RK, 250V Class RK1 Sensor/Trip: 200A, CB-115-1-03A-2B MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

CB 115AHU2

CUTLER-HAMMER

15-100A TYPE: QBHW, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed

Plot name: 03 SWBD 115-1-03A to 115-1-03A-2B Ref. Voltage: 208V Current Scale: x 1

F-115-1-03A-2B

BUSSMANN

LPN-RK, 250V Class RK1 200A

CB-115-1-03A-2B MAIN

CUTLER-HAMMER

EDB, 2-3 Poles 200A/200A

CBL-115-1-03A-2B

1 - #3/0 60 ft Copper

115-1-03A-2B 208V

CB 115AHU2

CUTLER-HAMMER

QBHW, 3-Pole 50A/50A

CBL-115AHU2

1 - #6 25 ft Copper

115 AHU2 VFD

208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-6

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-305-1-02A MAIN

SQUARE D

125-400A

TYPE: LA

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve

INST 4 (3504A)

CB-305-1-02B MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 225A, Plug: 225 AT Phase Fixed

CB-305-1-02A MAIN

SQUARE D

125-400A

TYPE: LA

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve

INST 4 (3504A)

CB-305-1-02B MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 225A, Plug: 225 AT Phase Fixed

Plot name: 04 305-1-02B Ref. Voltage: 208V Current Scale: x 1

CB-305-1-02A MAIN

SQUARE D

LA

400A/400A

CB-305-1-02B MAIN

CUTLER-HAMMER

EDB, 2-3 Poles 225A/225A

CBL-305-1-02B

1 - #4/0 6 ft Copper

305-1-02A 208V

305-1-02B 208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-7

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-LSD MAIN

CUTLER-HAMMER

100-400A

TYPE: KD

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CB-MD#2 ATS-LSD N

CUTLER-HAMMER

70-400A

TYPE: LB

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CB-315EDPA

CUTLER-HAMMER

15-225A

TYPE: FD

Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

CB-LSD MAIN

CUTLER-HAMMER

100-400A

TYPE: KD

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CB-MD#2 ATS-LSD N

CUTLER-HAMMER

70-400A

TYPE: LB

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CB-315EDPA

CUTLER-HAMMER

15-225A

TYPE: FD

Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

Plot name: 05 LSD BLDG 315 Ref. Voltage: 480V Current Scale: x 1

LSD BLDG 315

480V

CB-LSD MAIN

CUTLER-HAMMER

KD

400A/400A

CB-MD#2 ATS-LSD N

CUTLER-HAMMER

LB

400A/400A

CB-315EDPA

CUTLER-HAMMER

FD

200A/200A

CBL-315LSD

1 - #500 45 ft Copper

ATS-LSD

480V

EN

ATS#LSD

CBL-ATS-LSD N

1 - #500 40 ft Copper

Eaton Electrical Services and Systems

VAMC DAYTON 3-8

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-TX LNBC

CUTLER-HAMMER

15-100A

TYPE: GHB

Sensor/Trip: 60A, Plug: 60 AT Phase Fixed

CB-LNBC MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 150A, Plug: 150 AT Phase Fixed

CB PNL LNBC1

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 60A, Plug: 60 AT Phase Fixed

TX-LNBC

45 kVA 480 / 208 V

CB-TX LNBC

CUTLER-HAMMER

15-100A

TYPE: GHB

Sensor/Trip: 60A, Plug: 60 AT Phase Fixed

CB-LNBC MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 150A, Plug: 150 AT Phase Fixed

CB PNL LNBC1

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 60A, Plug: 60 AT Phase Fixed

TX-LNBC

45 kVA 480 / 208 V

Plot name: 06 PNL LNBC Ref. Voltage: 208V Current Scale: x 1

CB-TX LNBC

CUTLER-HAMMER

GHB

60A/60A

S

P TX-LNBC

45 kVA 480 / 208V 5.80% Z

CB-LNBC MAIN

CUTLER-HAMMER

EDB, 2-3 Poles 150A/150A

CB PNL LNBC1

CUTLER-HAMMER

BAB, 3-Pole 60A/60A

CBL-PNL LNBC

1 - #1/0 6 ft Copper

PNL LNBC

208V

CBL-TX LNBC

1 - #6 6 ft Copper

Eaton Electrical Services and Systems

VAMC DAYTON 3-9

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-TX LN4C

WESTINGHOUSE

15-100A

TYPE: GHB

Sensor/Trip: 40A, Plug: 40 AT Phase Fixed

CB LN4C MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CB-HN4C MAIN

WESTINGHOUSE

70-250A

TYPE: JDB, JD

Sensor/Trip: 150A, Plug: 150 AT Phase

LTD

INST 10.0 (1500A)

TX-LN4C

30 kVA 480 / 208 V

CB-TX LN4C

WESTINGHOUSE

15-100A

TYPE: GHB

Sensor/Trip: 40A, Plug: 40 AT Phase Fixed

CB LN4C MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CB-HN4C MAIN

WESTINGHOUSE

70-250A

TYPE: JDB, JD

Sensor/Trip: 150A, Plug: 150 AT Phase

LTD

INST 10.0 (1500A)

TX-LN4C

30 kVA 480 / 208 V

Plot name: 07 PNL LN4C Ref. Voltage: 208V Current Scale: x 1

CB-TX LN4C

WESTINGHOUSE

GHB

40A/40A

S

P TX-LN4C

30 kVA 480 / 208V 5.00% Z

CB LN4C MAIN

CUTLER-HAMMER

EDB, 2-3 Poles 100A/100A

CBL-TX LN4C

1 - #8 8 ft Copper

CBL-PNL LN4C

1 - #1 9 ft Copper

PNL HN4C

480V

CB-HN4C MAIN

WESTINGHOUSE

JDB, JD

150A/150A

Eaton Electrical Services and Systems

VAMC DAYTON 3-10

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB 410-1-04

SQUARE D

125-400A, Inst 5-10

TYPE: LH

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10.0 (4000A)

CB-410-1-04-01

CUTLER-HAMMER

100-225A

TYPE: ED

Sensor/Trip: 175A, Plug: 175 AT Phase Fixed

CB 410-1-04

SQUARE D

125-400A, Inst 5-10

TYPE: LH

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10.0 (4000A)

CB-410-1-04-01

CUTLER-HAMMER

100-225A

TYPE: ED

Sensor/Trip: 175A, Plug: 175 AT Phase Fixed

Plot name: 08 PNL 410-1-04 Ref. Voltage: 208V Current Scale: x 1

CB-410-1-04-01

CUTLER-HAMMER

ED

175A/175A

410-1-04 208V

CBL-410-1-4

1 - #500 30 ft Copper

CB 410-1-04

SQUARE D

LH

400A/400A

Eaton Electrical Services and Systems

VAMC DAYTON 3-11

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-412-1-04

GE

15-150A

TYPE: THED

Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CB-412-1-04B MAIN

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CBL-412-1-04

Size: 2 AWG Qty/Ph: 1

CBL-412-1-04B

Size: 4 AWG Qty/Ph: 1

CB-412-1-04

GE

15-150A

TYPE: THED

Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CB-412-1-04B MAIN

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CBL-412-1-04

Size: 2 AWG Qty/Ph: 1

CBL-412-1-04B

Size: 4 AWG Qty/Ph: 1

Plot name: 09 PNL 412-1-04A Ref. Voltage: 208V Current Scale: x 1

CB-412-1-04

GE

THED

100A/100A

CBL-412-1-04

1 - #2 60 ft Copper

CBL-412-1-04B

1 - #4 100 ft Copper

CB-412-1-04B MAIN

CUTLER-HAMMER

BAB, 3-Pole 100A/100A

412-1-04A 208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-12

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-BLDG 315 MAIN

EATON

LSI, 320-1200A, UL/CSA

TYPE: NG, 310+

Sensor/Trip: 1200A, Plug: 1200 AT Phase Ir for In = 1200A H (1200) (1200A) LTD (2-24 Sec. 1200A) 10 STPU (2-9 x Ir) 5 (6000A) STD (Inst-300ms) Inst.

INST OR (14.4 kA) Fixed (14400A)

CB-MD#2 ATS-LSD N

CUTLER-HAMMER

70-400A

TYPE: LB

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

F-TX-T-33

COOPER

3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 50A, Phase

50.0 Amps

TX-T-33

750 kVA 12470 / 480 V

CBL-0122

Size: 500 kcmil Qty/Ph: 3

CB-BLDG 315 MAIN

EATON

LSI, 320-1200A, UL/CSA

TYPE: NG, 310+

Sensor/Trip: 1200A, Plug: 1200 AT Phase Ir for In = 1200A H (1200) (1200A) LTD (2-24 Sec. 1200A) 10 STPU (2-9 x Ir) 5 (6000A) STD (Inst-300ms) Inst.

INST OR (14.4 kA) Fixed (14400A)

CB-MD#2 ATS-LSD N

CUTLER-HAMMER

70-400A

TYPE: LB

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

F-TX-T-33

COOPER

3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 50A, Phase

50.0 Amps

TX-T-33

750 kVA 12470 / 480 V

CBL-0122

Size: 500 kcmil Qty/Ph: 3

Plot name: 10 BLD 315 MAIN Ref. Voltage: 480V Current Scale: x 10

CB-BLDG 315 MAIN

EATON

NG, 310+

1200A/1200A

CB-MD#2 ATS-LSD N

CUTLER-HAMMER

LB

400A/400A

F-TX-T-33

COOPER

ELX, 8.3-23kV 50A

S

P TX-T-33

750 kVA 12470 / 480V 5.66% Z

CBL-0122

3 - #500 45 ft Copper

PANEL 315 MD

480V

Eaton Electrical Services and Systems

VAMC DAYTON 3-13

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB 410-1-06-01A-01

SQUARE D

70-250A

TYPE: QD

Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

CB 410-1-03MAIN

SQUARE D

125-400A, Inst 5-10

TYPE: LA

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10.0 (4000A)

CB 410-1-03

SQUARE D

125-400A, Inst 5-10

TYPE: LH

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5.0 (2000A)

CB 410-1-06-01A-01

SQUARE D

70-250A

TYPE: QD

Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

CB 410-1-03MAIN

SQUARE D

125-400A, Inst 5-10

TYPE: LA

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10.0 (4000A)

CB 410-1-03

SQUARE D

125-400A, Inst 5-10

TYPE: LH

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5.0 (2000A)

Plot name: 11 CB 410-1-03 to CB 410-1-06-01A-01 Ref. Voltage: 208V Current Scale: x 1

CB 410-1-06-01A-01

SQUARE D

QD

200A/200A

CB 410-1-03MAIN

SQUARE D

LA

400A/400A

CB 410-1-03

SQUARE D

LH

400A/400A

CBL-410-1-03

1 - #600 25 ft Copper

410-1-03 208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-14

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB 410E-1-4 MAIN

SQUARE D

125-400A

TYPE: LA

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve

INST LO (2000A)

CB 410E-MAIN E&W EM

SQUARE D

70-250A

TYPE: QD

Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

FS 410E-1-02A-01A

BUSSMANN

1-600A TYPE: LPN-RK, 250V Class RK1 Sensor/Trip: 200A, CB-410E-1-02A-01A-01 MAIN

GE

70-225A

TYPE: TFK

Sensor/Trip: 175A, Plug: 175 AT Phase Thermal Curve (Fixed) INST (4.5-10 x Trip) LO (787.5A)

CBL-410E-1-02A-01A

Size: 4/0 AWG Qty/Ph: 1

CB 410E-1-4 MAIN

SQUARE D

125-400A

TYPE: LA

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve

INST LO (2000A)

CB 410E-MAIN E&W EM

SQUARE D

70-250A

TYPE: QD

Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

FS 410E-1-02A-01A

BUSSMANN

1-600A TYPE: LPN-RK, 250V Class RK1 Sensor/Trip: 200A, CB-410E-1-02A-01A-01 MAIN

GE

70-225A

TYPE: TFK

Sensor/Trip: 175A, Plug: 175 AT Phase Thermal Curve (Fixed) INST (4.5-10 x Trip) LO (787.5A)

CBL-410E-1-02A-01A

Size: 4/0 AWG Qty/Ph: 1

Plot name: 12 CB 410E-1-4 MAIN TO CB-410E-1-02A-01A-01 MAIN Ref. Voltage: 208V Current Scale: x 1

CB 410E-1-4 MAIN

SQUARE D

LA

400A/400A

CB 410E-MAIN E&W EM

SQUARE D

QD

200A/200A

FS 410E-1-02A-01A

BUSSMANN

LPN-RK, 250V Class RK1 200A

CBL-410E-MAIN E&W EM

1 - #4/0 25 ft Copper

CBL-410E-1-02A-01A

1 - #4/0 130 ft Copper

CB-410E-1-02A-01A-01 MAIN

GE

TFK

175A/175A

410E-1-4 208V

410E-1-02A-01A SWT

208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-15

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB 305-1A

GE

300-1200A TYPE: SKHA, Spectra RMS Sensor/Trip: 600A, Plug: 600 AT Phase

MAX

CB 305-1-06

SQUARE D

150-250A, UL

TYPE: J-Frame, Powerpact Sensor/Trip: 225A, Plug: 225 AT Phase Thermal Curve INST (5-10 x Trip) Low (1125A)

CBL-305-1-06

Size: 4/0 AWG Qty/Ph: 1

CB 305-1A

GE

300-1200A TYPE: SKHA, Spectra RMS Sensor/Trip: 600A, Plug: 600 AT Phase

MAX

CB 305-1-06

SQUARE D

150-250A, UL

TYPE: J-Frame, Powerpact Sensor/Trip: 225A, Plug: 225 AT Phase Thermal Curve INST (5-10 x Trip) Low (1125A)

CBL-305-1-06

Size: 4/0 AWG Qty/Ph: 1

Plot name: 13 CB 305-1A TO CB-305-1-06 MAIN Ref. Voltage: 208V Current Scale: x 1

CB 305-1A

GE

SKHA, Spectra RMS 600A/600A

CB 305-1-06

SQUARE D

J-Frame, Powerpact 225A/225A

CBL-305-1-06

1 - #4/0 80 ft Copper

CB-305-1-06 MAIN

EATON

EDB, 2-3 Poles 225A/225A

CBL-305-1A

4 - #350 25 ft Copper

305-1A 208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-16

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-305-1-05-05

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

CB-305-1-05 MAIN

CUTLER-HAMMER

250-400A

TYPE: DK

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CB-305-1-05-05 MAIN

CUTLER-HAMMER

150-200A

TYPE: CC & CCH

Sensor/Trip: 225A, Plug: 225 AT Phase Thermal-Magnetic Curve

CB-305-1-05-02

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CBL-305-1-05-05

Size: 3/0 AWG Qty/Ph: 1

CB-305-1-05-05

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

CB-305-1-05 MAIN

CUTLER-HAMMER

250-400A

TYPE: DK

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CB-305-1-05-05 MAIN

CUTLER-HAMMER

150-200A

TYPE: CC & CCH

Sensor/Trip: 225A, Plug: 225 AT Phase Thermal-Magnetic Curve

CB-305-1-05-02

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CBL-305-1-05-05

Size: 3/0 AWG Qty/Ph: 1

Plot name: 14 CB-305-1-05 MAIN TO CB-305-1-05-02 Ref. Voltage: 208V Current Scale: x 1

CB-305-1-05-05

CUTLER-HAMMER

EDB, 2-3 Poles 200A/200A

CB-305-1-05 MAIN

CUTLER-HAMMER

DK

400A/400A

CBL-305-1-05-05

1 - #3/0 35 ft Copper

CB-305-1-05-05 MAIN

CUTLER-HAMMER

CC & CCH

225A/225A

CB-305-1-05-02

CUTLER-HAMMER

BAB, 3-Pole 100A/100A

305-1-05 208V

305-1-05-05 208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-17

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-305-1-05 4

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 90A, Plug: 90 AT Phase Fixed

CB-305-1-04-34B

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed

CB-305-1-05 MAIN

CUTLER-HAMMER

250-400A

TYPE: DK

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CBL-305-1-05-04

Size: 4 AWG Qty/Ph: 1

CB-305-1-05 4

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 90A, Plug: 90 AT Phase Fixed

CB-305-1-04-34B

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed

CB-305-1-05 MAIN

CUTLER-HAMMER

250-400A

TYPE: DK

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CBL-305-1-05-04

Size: 4 AWG Qty/Ph: 1

Plot name: 15 CB-305-1-05 MAIN TO CB-305-1-04-34B Ref. Voltage: 208V Current Scale: x 1

CB-305-1-05 4

CUTLER-HAMMER

BAB, 3-Pole 90A/90A

CBL-305-1-05-04

1 - #4 148 ft Copper

CB-305-1-04-34B

CUTLER-HAMMER

BAB, 3-Pole 50A/50A

CB-305-1-05 MAIN

CUTLER-HAMMER

DK

400A/400A

305-1-05 208V

305-1-05-04 208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-18

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

F-115-1-03A-2E

GOULD SHAWMUT

30-600A TYPE: AT-DE, 250V Class RK5 Sensor/Trip: 200A, CB-115-1-03A-2E MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

CBL-115-1-03A-2E

Size: 3/0 AWG Qty/Ph: 1

F-115-1-03A-2E

GOULD SHAWMUT

30-600A TYPE: AT-DE, 250V Class RK5 Sensor/Trip: 200A, CB-115-1-03A-2E MAIN

CUTLER-HAMMER

100-225A, UL

TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

CBL-115-1-03A-2E

Size: 3/0 AWG Qty/Ph: 1

Plot name: 16 F-115-1-03A-T2 TO CB-115-1-03A-2E MAIN Ref. Voltage: 208V Current Scale: x 1

F-115-1-03A-2E

GOULD SHAWMUT

AT-DE, 250V Class RK5 200A

CB-115-1-03A-2E MAIN

CUTLER-HAMMER

EDB, 2-3 Poles 200A/200A

CBL-115-1-03A-2E

1 - #3/0 49 ft Copper

Eaton Electrical Services and Systems

VAMC DAYTON 3-19

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-BLDG 120 MAIN

CUTLER-HAMMER

100-400A

TYPE: KD

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (2000A)

CB-120-1 1

EATON

15-100A TYPE: BAB-H, 3-Pole Sensor/Trip: 70A, Plug: 70 AT Phase Fixed

F 120-1-01A-01-01F

BUSSMANN

1-600A

TYPE: FRN-R

Sensor/Trip: 25A, CB-BLDG 120 MAIN

CUTLER-HAMMER

100-400A

TYPE: KD

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (2000A)

CB-120-1 1

EATON

15-100A TYPE: BAB-H, 3-Pole Sensor/Trip: 70A, Plug: 70 AT Phase Fixed

F 120-1-01A-01-01F

BUSSMANN

1-600A

TYPE: FRN-R

Sensor/Trip: 25A, Plot name: 17 CB-BLDG 120 MAIN TO F 120-1-01A-01-01F Ref. Voltage: 208V Current Scale: x 1

CB-BLDG 120 MAIN

CUTLER-HAMMER

KD

400A/400A

CB-120-1 1

EATON

BAB-H, 3-Pole 70A/70A

F 120-1-01A-01-01F

BUSSMANN

FRN-R

25A

PNLBD 120-1

208V

CBL-120-1-01

1 - #2 4 ft Copper

Eaton Electrical Services and Systems

VAMC DAYTON 3-20

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-126-1-08A-05

SQUARE D

15-100A

TYPE: FA

Sensor/Trip: 90A, Plug: 90 AT Phase Fixed

CB-126-1-08A

CUTLER-HAMMER

250-400A

TYPE: DK

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 6 (2400A)

CBL-126-1-08A

Size: 500 kcmil Qty/Ph: 1

CB-126-1-08A-05

SQUARE D

15-100A

TYPE: FA

Sensor/Trip: 90A, Plug: 90 AT Phase Fixed

CB-126-1-08A

CUTLER-HAMMER

250-400A

TYPE: DK

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 6 (2400A)

CBL-126-1-08A

Size: 500 kcmil Qty/Ph: 1

Plot name: 18 CB-126-1-08A TO CB-126-1-08A-05 Ref. Voltage: 208V Current Scale: x 1

CB-126-1-08A-05

SQUARE D

FA

90A/90A

CB-126-1-08A

CUTLER-HAMMER

DK

400A/400A

CBL-126-1-08A

1 - #500 56 ft Copper

126-1-08A 208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-21

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-LSD MAIN

CUTLER-HAMMER

100-400A

TYPE: KD

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CB-315EDPA

CUTLER-HAMMER

15-225A

TYPE: FD

Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

F-LSD ATS E

BUSSMANN

15-600A TYPE: LPS-RK, 600V Class RK1 Sensor/Trip: 400A, CB-LSD MAIN

CUTLER-HAMMER

100-400A

TYPE: KD

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

CB-315EDPA

CUTLER-HAMMER

15-225A

TYPE: FD

Sensor/Trip: 200A, Plug: 200 AT Phase Fixed

F-LSD ATS E

BUSSMANN

15-600A TYPE: LPS-RK, 600V Class RK1 Sensor/Trip: 400A, Plot name: 19 F-LSD ATS E TO LSD BLDG 315 Ref. Voltage: 480V Current Scale: x 1

CB-LSD MAIN

CUTLER-HAMMER

KD

400A/400A

CB-315EDPA

CUTLER-HAMMER

FD

200A/200A

F-LSD ATS E

BUSSMANN

LPS-RK, 600V Class RK1 400A

CBL-315LSD

1 - #500 45 ft Copper

ATS-LSD

480V

LSD BLDG 315

480V

ATS#LSD

Eaton Electrical Services and Systems

VAMC DAYTON 3-22

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB320ELEV2

SIEMENS

15-125A TYPE: ED6 Sentron, 2 & 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Thermal Curve (Fixed) INST Fixed (800A)

CB-320ATS-CR N

WESTINGHOUSE

400-800A

TYPE: MC SELTRNC

Sensor/Trip: 800A, Plug: 800 AT Phase

LTPU 1.0 (800A)

LTD LTD

STPU 10.0 (8000A)

STD-I2T STD (I^s T On) CB-320ATS-CR E

SQUARE D

LI, 100-1200A, UL

TYPE: Powerpact P-Frame, 3.0 & 3.0A Sensor/Trip: 800A, Plug: 800 AT Phase LTPU/LTD (A 0.4-1.0 x S) 1 (800A); 0.5 INST (1.5-12 x S) 1.5 (1200A)

CB320ELEV2

SIEMENS

15-125A TYPE: ED6 Sentron, 2 & 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Thermal Curve (Fixed) INST Fixed (800A)

CB-320ATS-CR N

WESTINGHOUSE

400-800A

TYPE: MC SELTRNC

Sensor/Trip: 800A, Plug: 800 AT Phase

LTPU 1.0 (800A)

LTD LTD

STPU 10.0 (8000A)

STD-I2T STD (I^s T On) CB-320ATS-CR E

SQUARE D

LI, 100-1200A, UL

TYPE: Powerpact P-Frame, 3.0 & 3.0A Sensor/Trip: 800A, Plug: 800 AT Phase LTPU/LTD (A 0.4-1.0 x S) 1 (800A); 0.5 INST (1.5-12 x S) 1.5 (1200A)

Plot name: 20 CB320 ELEV 2 N & E FEED Ref. Voltage: 480V Current Scale: x 1

CB320ELEV2

SIEMENS

ED6 Sentron, 2 & 3-Pole 100A/100A

CB-320ATS-CR N

WESTINGHOUSE

MC SELTRNC

800A/800A

CB-320ATS-CR E

SQUARE D

Powerpact P-Frame, 3.0 & 3.0A 800A/800A

320E-1 480V

CBL-320ATS-CR N

2 - #500 37 ft Copper

CBL-320ATS-CR E

2 - #500 50 ft Copper

E N

320ATS-CR

ATS-320 CR

480V

CBL-320E-1

2 - #500 25 ft Copper

Eaton Electrical Services and Systems

VAMC DAYTON 3-23

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

F-TX-T-17-1

COOPER

3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 40A, Phase

40.0 Amps

CB-PNL402-1-5

SQUARE D

15-100A

TYPE: FH

Sensor/Trip: 60A, Plug: 60 AT Phase Fixed

CB 402-1-5MAIN

SQUARE D

15-100A TYPE: QO, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed (730-6, 50A)

TX-T-17-1

500 kVA 12470 / 208 V

CBL-0148

Size: 600 kcmil Qty/Ph: 4

CBL-PNL402-1-5

Size: 6 AWG Qty/Ph: 1

F-TX-T-17-1

COOPER

3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 40A, Phase

40.0 Amps

CB-PNL402-1-5

SQUARE D

15-100A

TYPE: FH

Sensor/Trip: 60A, Plug: 60 AT Phase Fixed

CB 402-1-5MAIN

SQUARE D

15-100A TYPE: QO, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed (730-6, 50A)

TX-T-17-1

500 kVA 12470 / 208 V

CBL-0148

Size: 600 kcmil Qty/Ph: 4

CBL-PNL402-1-5

Size: 6 AWG Qty/Ph: 1

Plot name: 21 F-TX-T-17-1 TO CB 402-1-5MAIN Ref. Voltage: 12470V Current Scale: x 1

F-TX-T-17-1

COOPER

ELX, 8.3-23kV 40A

S

P TX-T-17-1

500 kVA 12470 / 208V 5.50% Z

CBL-0148

4 - #600 81 ft Copper

CB-PNL402-1-5

SQUARE D

FH

60A/60A

CBL-PNL402-1-5

1 - #6 150 ft Copper

CB 402-1-5MAIN

SQUARE D

QO, 3-Pole 50A/50A

BLDG 402 MDP-1

208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-24

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-412-1-03

GE

15-150A

TYPE: THED

Sensor/Trip: 70A, Plug: 70 AT Phase Fixed

CB-412-AC LOBBY

EATON

10-70A TYPE: BAB, 1-Pole Sensor/Trip: 20A, Plug: 20 AT Phase Fixed

CBL-412-1-03

Size: 4 AWG Qty/Ph: 1

CB-412-1-03

GE

15-150A

TYPE: THED

Sensor/Trip: 70A, Plug: 70 AT Phase Fixed

CB-412-AC LOBBY

EATON

10-70A TYPE: BAB, 1-Pole Sensor/Trip: 20A, Plug: 20 AT Phase Fixed

CBL-412-1-03

Size: 4 AWG Qty/Ph: 1

Plot name: 22 CB-412-1-03 TO CB-412-AC LOBBY Ref. Voltage: 208V Current Scale: x 1

CB-412-1-03

GE

THED

70A/70A

CBL-412-1-03

1 - #4 51 ft Copper

CB-412-AC LOBBY

EATON

BAB, 1-Pole 20A/20A

412-1-03 208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-25

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-412-1-04

GE

15-150A

TYPE: THED

Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CB-412-1-04B MAIN

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CBL-412-1-04

Size: 2 AWG Qty/Ph: 1

CBL-412-1-04B

Size: 4 AWG Qty/Ph: 1

CB-412-1-04

GE

15-150A

TYPE: THED

Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CB-412-1-04B MAIN

CUTLER-HAMMER

15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed

CBL-412-1-04

Size: 2 AWG Qty/Ph: 1

CBL-412-1-04B

Size: 4 AWG Qty/Ph: 1

Plot name: 23 CB-412-1-04 TO CB-412-1-04B MAIN Ref. Voltage: 208V Current Scale: x 1

CB-412-1-04

GE

THED

100A/100A

CBL-412-1-04

1 - #2 60 ft Copper

CBL-412-1-04B

1 - #4 100 ft Copper

CB-412-1-04B MAIN

CUTLER-HAMMER

BAB, 3-Pole 100A/100A

412-1-04A 208V

Eaton Electrical Services and Systems

VAMC DAYTON 3-26

1K 10 K

0.01

0.10

CURRENT IN AMPERES

TIME IN SECONDS

CB-BLDG 315 MAIN

EATON

GF, 320-1200AS, UL

TYPE: NG, 310+

Sensor/Trip: 1200A, Plug: 1200 AT

GND

GFPU, (0.2 - 1 x In) .8X (960A) GFD LSIG, (Inst-300ms) 300ms

CB-MD#2 ATS-LSD N

CUTLER-HAMMER

70-400A

TYPE: LB

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

F-TX-T-33

COOPER

3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 50A, Phase

50.0 Amps

TX-T-33

750 kVA 12470 / 480 V

CBL-0122

Size: 500 kcmil Qty/Ph: 3

CB-BLDG 315 MAIN

EATON

GF, 320-1200AS, UL

TYPE: NG, 310+

Sensor/Trip: 1200A, Plug: 1200 AT

GND

GFPU, (0.2 - 1 x In) .8X (960A) GFD LSIG, (Inst-300ms) 300ms

CB-MD#2 ATS-LSD N

CUTLER-HAMMER

70-400A

TYPE: LB

Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)

F-TX-T-33

COOPER

3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 50A, Phase

50.0 Amps

TX-T-33

750 kVA 12470 / 480 V

CBL-0122

Size: 500 kcmil Qty/Ph: 3

Plot name: 24 BLD 315 MAIN (GND) Ref. Voltage: 480V Current Scale: x 10

CB-BLDG 315 MAIN

EATON

NG, 310+

1200A/1200A

CB-MD#2 ATS-LSD N

CUTLER-HAMMER

LB

400A/400A

F-TX-T-33

COOPER

ELX, 8.3-23kV 50A

S

P TX-T-33

750 kVA 12470 / 480V 5.66% Z

CBL-0122

3 - #500 45 ft Copper

PANEL 315 MD

480V

Eaton Electrical Services and Systems

VAMC DAYTON 3-27

Dayton VA Correct Arc Flash Deficiencies 4-1

RECOMMENDED PROTECTIVE DEVICE SETTINGS

The following table shows a comprehensive summary of the recommended settings for the adjustable protective devices. The devices are grouped by system bus name/location. Refer to Section 11.0 for the system one-line diagrams.

Table 4.1 – Recommended Low-Voltage Protective Device Settings

Name / Type Description Frame / Sensor / Plug

Recommended Settings

CB-BLDG 315 MAIN EATON 1200A Phase

Static Trip NG, 310+ 1200A Ir for In = 1200A H (1200) (1200A)

LTD (2-24 Sec. 1200A) 10

STPU (2-9 x Ir) 5 (6000A)

STD (Inst-300ms) Inst.

INST OR (14.4 kA) Fixed (14400A)

GND

GFPU, (0.2 – 1 x In) .6X (720A)

GFD LSIG, (Inst – 300ms) 300ms

CB-305-1-05 MAIN CUTLER-HAMMER 400A Thermal Curve (Fixed)

Thermal Magnetic DK 400A INST (5-10 x Trip) 10 (4000A)

400A

CB-LSD MAIN CUTLER-HAMMER 400A Thermal Curve (Fixed)

Thermal Magnetic KD 400A INST (5-10 x Trip) 10 (4000A)

400A

CB-BLDG 118 MAIN CUTLER-HAMMER 600A Thermal Curve (Fixed)

Thermal Magnetic LD 300A INST (5-10 x Trip) 10 (3000A)

300A

Dayton VA Correct Arc Flash Deficiencies 5-1

ARC FLASH INCIDENT ENERGY ANALYSIS

This section of the report contains the interpretation for the arc flash incident energy…