TQSIOH835 DAYTON VA MODERNIZE REPORT Rev4.pdf
PDF 13 MB Posted
- Attached to
- H959--5 Year Arc Flash Survey
- Solicitation number
- 36C25021Q0996
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25021Q0996 0005.docx | DOCX document | |
| 36C25021Q0996 0004.docx | DOCX document | |
| 36C25021Q0996 0003.docx | DOCX document | |
| 36C25021Q0996 0002.docx | DOCX document | |
| 15-0608FinalRev-S Dayton VAMC Study Report.pdf | ||
| VA Dayton building list-Arf Flsah Study 2021.pdf | ||
| 2018-08-07 FH Dayton Electrical As-Built E-1.pdf | ||
| 36C25021Q0996 0001.docx | DOCX document | |
| 36C25021Q0996.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Dayton VA Correct Arc Flash Deficiencies i
REVISION HISTORY
Rev # Issued Revision / Modification Description
- 04/2019 Initial Study Report Issue
1 05/2019 Misc document corrections, added One Lines
2 5/2019 Misc document corrections, added building 126, corrected bldg 305
3 7/2019 Building 410 corrections
4 9/2019 Added additional One Lines and corrected changes per As Built 3-22-19
Dayton VA Correct Arc Flash Deficiencies ii
TABLE OF CONTENTS
EXECUTIVE SUMMARY ....................................................................................... 1-1
SHORT-CIRCUIT ANALYSIS................................................................................ 2-1
PROTECTIVE DEVICE COORDINATION STUDY ................................................ 3-1
RECOMMENDED PROTECTIVE DEVICE SETTINGS ......................................... 4-1
ARC FLASH INCIDENT ENERGY ANALYSIS ..................................................... 5-1
SYSTEM DATA ..................................................................................................... 6-1
SHORT-CIRCUIT INPUT REPORT ....................................................................... 7-1
SHORT-CIRCUIT RESULTS ................................................................................. 8-1
UTILITY DATA ...................................................................................................... 9-1
APPLICABLE CODES AND STANDARDS ........................................................ 10-1
ONE-LINE DIAGRAM INDEX .............................................................................. 11-1
Dayton VA Correct Arc Flash Deficiencies 1-1
EXECUTIVE SUMMARY
This summary report contains the results of analyses performed on the electrical distribution system for Dayton VA Corrections of Arc Flash Deficiencies. The purpose of this study is to evaluate new electrical equipment provided for this facility.
System data and necessary modeling assumptions are provided under Section 6.0.
1. Short-Circuit Analysis
Perform a short-circuit study on the electrical distribution system shown in order to determine the available fault current at pertinent locations throughout the distribution system. The scope of the study includes:
• Analysis beginning at the incoming 69 kV utility service, continuing through the medium and low voltage substations, and ending at the low voltage panelboards as shown in the contract drawings.
The available fault currents determined by the short-circuit study will be used in the electrical distribution analyses.
2. Equipment Evaluation
Evaluate the short-circuit ratings of new protective devices and other distribution equipment supplied by Eaton under this contract.
3. Coordination Study
Develop time-current coordination plots to derive coordinated settings for new protective devices.
4. Arc Flash Analysis
Perform an arc flash incident energy analysis per NFPA 70E on the electrical distribution system as per Eaton’s scope of work.
An incident energy analysis is defined by NFPA 70E to be a component of an arc flash risk assessment used to predict the incident energy of an arc flash for a specified set of conditions.
5. Recommendations
Provide specific recommendations for improving the electrical distribution system performance and correcting any deficiencies found by the studies.
1. Short-Circuit Study
The system was modeled for worst-case fault currents. Short-circuit currents were calculated for a three-phase bolted fault and single-line-to-ground fault at each bus shown on the one-line diagrams found in Section 11.0.
See Section 2.0, Section 7.0, and Section 8.0 for more information.
Dayton VA Correct Arc Flash Deficiencies 1-2
2. Equipment Evaluation
The Equipment Evaluation is based on the power system worst-case short-circuit current configuration. The short-circuit ratings of protective devices and other distribution equipment are evaluated in Section 2.0, Table 2.1.
In summary of Table 2.1, specific equipment has failed the equipment evaluation and are considered overdutied. It is recommended that the overdutied panelboards be reviewed for breaker and/or panelboard replacement to comply with the short-circuit current ratings required.
See Section 2.0 for detailed analysis and evaluation results.
3. Coordination Study
The time-current coordination plots of the protective overcurrent devices are shown in Section 3.0. In developing the device settings, consideration was given to the isolation of faults, protection of cables, and protection of transformers.
Efforts were made to provide the best coordination possible with the protective devices supplied under this contract and existing protective devices. It should be understood that coordination between two instantaneous trip units cannot be achieved for fault levels above the instantaneous pickup of the upstream device.
There is some overlapping of curves that cannot be avoided.
In summary of the coordination study, the following recommended changes would maximize coordination while maintaining adequate protection:
• Cables CBL-126-1-10, CBL-126-1-10C and CBL-126-1-09 DISC are undersized per NEC Article 310.15. Recommend upgrading to #1/0 CU AWG.
• Cable CBL-1726 is undersized per NEC Article 240.4(D). Recommend upgrading to #8 CU AWG or using a 30A fuse.
• Cable CBL-412-1-04B is undersized per NEC 310.15. Recommend upgrading cable to #3 CU AWG.
All of the adjustable low voltage electronic trip and thermal magnetic circuit breakers should be tested and adjusted according to the recommended settings given in Section 4.0.
4. Protective Device Settings
Settings for the protective devices supplied by Eaton should be set as shown and recommended in Section 4.0.
5. Arc Flash Incident Energy Analysis
Details of the arc flash incident energy analysis are shown in Section 5.0. Please note for this study, the arc flash hazard has been calculated by performing an incident energy analysis. The results of this study can be used by qualified workers to determine the arc flash boundary and select appropriate arc flash PPE as part of an overall arc flash risk assessment. NFPA 70E Table 130.5(g) provides guidance on the selection of arc rated clothing and other PPE based on the results of an incident energy analysis. It is the responsibility of the employer and qualified person(s) to conduct an overall arc flash risk assessment as detailed in NFPA 70E- 2018 Article 130.5 before the commencement of work on electrical equipment. The
Dayton VA Correct Arc Flash Deficiencies 1-3 risk associated with performing energized electrical work will vary based on the work being performed as well as the condition of the equipment and other factors that can be best determined by a qualified person in the field.
The PPE requirements outlined in NFPA 70E only address the thermal hazards associated with arc flash events and do not provide protection against other possible physical trauma resulting from an arc flash event. See NFPA 70E Article 120 for details on establishing an electrically safe work condition.
6. Testing and Preventative Maintenance
The 2018 edition of NFPA 70E Section 205.3 and 205.4 requires that regularly scheduled testing and preventative maintenance be performed to ensure that the electrical distribution equipment continues to perform at an optimum level. Testing should entail primary injection testing of all circuit breakers to verify proper tripping ranges, contact resistance testing, insulation resistance testing and complete switchgear and transformer cleaning and inspection. Refer to NFPA-70B for specific types of testing and interval recommendations. The industry generally performs breaker testing every 3-5 years.
Dayton VA Correct Arc Flash Deficiencies 2-1
SHORT-CIRCUIT ANALYSIS
The short-circuit study determines the fault currents that flow in the system during various fault conditions. A system model was created using SKM Systems Analysis software. The calculated fault currents are used in the device evaluation and coordination studies. See Section 7.0 and Section 8.0 for the computer generated input data and output data. NEC-2017, Article 110.24(A) requires that service entrance equipment is labeled with the following pieces of information:
• Maximum available fault current
• Date on which the fault current was calculated
Article 110.24(B) adds that if there is a modification that may change this fault current value, it must be recalculated. The field marking must be updated to reflect the new value of maximum fault current.
Separate “Z” (complex), “X” (reactive), and "R" (resistive) networks are used for the short-circuit analysis. Complex network reduction and the relationship E/Z are used to calculate the fault current magnitude and angle at each faulted bus. The complex equivalent circuit impedance, Z, is calculated by the reduction of the “Z” (complex) network. The X/R ratios calculated for each fault condition are based on the separate reduction of the X and R networks. These X/R ratios are used for the calculation of fault duty multipliers, to evaluate the short-circuit ratings of system components.
The software is capable of generating three types of short-circuit reports for both balanced (three-phase bolted) and unbalanced (line-to-ground) faults. The reports that are generated depend on the system that is being evaluated.
The three types of short-circuit reports are:
• Fault Report (for low voltage)
• Momentary Duty Report (for medium voltage) – Not Applicable
• Interrupting Duty Report (for medium voltage) – Not Applicable
1. Fault Report
The fault currents reported in the “Fault Report” are applicable to low voltage devices and components. The fault currents calculated in this report are based on the contribution data derived from IEEE Std C37.13™. The fault currents are calculated as follows:
• Motor and generator subtransient reactance values (Xd”) are adjusted per the first cycle duty multipliers described in IEEE Std 141™.
• The complex equivalent circuit impedance, Z, is calculated by network reduction of the “Z” (complex) network.
• The momentary symmetrical current = E/Z.
• The X/R ratio is equal to the equivalent circuit reactance, X, divided by the equivalent circuit resistance, R. As discussed above, X is calculated by the reduction of the “X” (reactive) network and R is calculated by the reduction of the “R” (resistive) network.
Dayton VA Correct Arc Flash Deficiencies 2-2
Multiplying factors are determined, and used to adjust the calculated symmetrical fault current. The adjusted current is used to evaluate low voltage protective devices. Low voltage output algorithms and output reports reflect NEMA AB-1 molded case breaker de-rating multipliers. Breakers are de-rated for circuits where the power factor is lower than the NEMA test circuit (higher X/R ratio). The multipliers adjust the symmetrical fault current to the value associated with the systems fault point X/R ratio. The adjusted value listed on the report may then be compared directly with the manufacturer's published interrupting rating.
The objective of the short-circuit analysis is to calculate the maximum short-circuit currents produced by balanced three-phase and unbalanced faults at each bus shown on the one-line diagrams.
1. Short-Circuit System Model
The system was modeled for worst-case fault currents. Short-circuit currents were calculated for a three-phase bolted fault and single-line-to-ground fault at each bus shown on the study one-line diagrams.
a) Evaluated Short-Circuit Cases:
The following short-circuit study cases were evaluated:
• Study Case No. 1 – System supplied from Crown source.
• Study Case No. 2 – System supplied from Tait source.
The purpose of the equipment evaluation is to compare the maximum calculated short-circuit currents to the short-circuit ratings of protective devices. The comparison is made in order to determine if the device can interrupt or withstand the available fault currents of the electrical system to which the device is applied, as required by NEC Articles 110.9 and 110.10. The device evaluation follows the evaluation procedures outlined in IEEE Std C37.13, IEEE Std C37.010, IEEE Std C37.5, IEEE Std C37.41™, IEEE Std 1015™, and applicable ANSI, NEMA, and UL standards.
The results of the short-circuit equipment evaluation are summarized in Table 2.1.
The tables indicates “Bus I.D.” (corresponds to bus designations used in the one-line diagrams, “Manufacturer”, “Status” (Pass, fail, unknown, or marginal), “Type” (equipment category), “Equip Volts”, calculated short-circuit duty, the equipment short-circuit rating, the series rating (if applicable), and the maximum duty rating.
The maximum duty rating is calculated by:
RatingCDeviceS dutyCS
If the short-circuit rating of a device is not known, and/or short-circuit rating information is not available, a Minimum Required short-circuit rating is listed. All short-circuit current values are reported in units of kA.
Dayton VA Correct Arc Flash Deficiencies 2-3
1. For low voltage devices:
The calculated short-circuit duty is reported under “Calc Isc (kA)" and the device short-circuit rating is reported under "Equip Isc (kA)". The calculated duty has been adjusted accordingly per the system X/R and device test X/R.
Information used in modeling the power system to provide conservative, worst-case results is listed in Section 6.0. The results of the short-circuit analysis, including calculated branch contributions, are provided under Section 8.0. The one-line diagrams with referenced bus identification are included in Section 11.0.
Dayton VA Correct Arc Flash Deficiencies 2-4
Table 2.1 – Low-Voltage Equipment Evaluation
Bus I.D. Manufacturer Status Type Bus Voltage (V) Calc
Isc (kA) Equip
Isc (kA) Rating %
115-1-03A-2B EATON Pass LV Panelboard 208 12.53 22.00 56.96
115-1-03A-2D EATON Pass LV Panelboard 208 12.12 22.00 55.09
115-1-03A-2E EATON Pass LV Panelboard 208 13.80 22.00 62.73
115 CH-1 CP UL 67 Pass LV Panelboard 208 18.10 65.00 27.85
118 PNL LP-1 UL 67 Pass LV Panelboard 240 2.42 10.00 24.20
PNLBD 120-1 UL 67 Pass LV Panelboard 208 7.93 10.00 79.3
126-1-08A-05 UL 67 Pass LV Panelboard 208 4.67 18.00 25.95
126-1-09 DISC UL 67 Pass LV Disconnect 208 4.25 65.00 6.54
126-1-11 UL 67 Pass LV Panelboard 208 7.87 65.00 12.11
305CH-2 UL 67 Pass LV Panelboard 208 10.22 65.00 15.73
305-1-02B EATON Pass LV Panelboard 208 6.47 10.00 64.69
305-1-04-34A EATON Pass LV Panelboard 208 0.82 22.00 3.71
305-1-04-34B EATON Pass LV Panelboard 208 1.29 22.00 5.86
305-1-05 EATON Pass LV Panelboard 208 7.83 10.00 78.32
305-1-05-02 UL 67 Pass LV Panelboard 208 6.37 10.00 63.69
305-1-05-03 UL 67 Pass LV Panelboard 208 3.61 10.00 36.1
305-1-05-04 EATON Pass LV Panelboard 208 2.03 10.00 20.29
305-1-05-05 UL 67 Pass LV Panelboard 208 6.56 10.00 65.57
305-1-05-06 UL 67 Pass LV Panelboard 208 2.11 10.00 21.09
305-1-05-08 UL 67 Pass LV Panelboard 208 7.51 (*N1) 10.00 75.13
305-1-05-09A UL 67 Pass LV Panelboard 208 2.82 5.00 56.4
305-1-05-09B UL 67 Pass LV Panelboard 208 2.03 5.00 40.69
305-1-05-10 EATON Pass LV Panelboard 208 3.27 10.00 32.68
305-1-05-11 UL 67 Pass LV Panelboard 208 4.32 10.00 43.23
Dayton VA Correct Arc Flash Deficiencies 2-5
Bus I.D. Manufacturer Status Type Bus Voltage (V) Calc
Isc (kA) Equip
Isc (kA) Rating %
305-1-06 EATON Pass LV Panelboard 208 11.13 22.00 50.58
LSD BLDG 315 EATON Pass LV Panelboard 480 13.77 18.00 76.5
PANEL 315 MD UL 891 Pass LV Switchboard 480 17.20 (*N1) 22.00 78.17
315 CH-1 CP UL 67 Pass LV Panelboard 480 14.72 65.00 22.64
320E-1 UL 67 Pass LV Panelboard 480 15.47 22.00 70.34
321 PNL DP UL 67 Pass LV Panelboard 208 7.90 (*N1) 10.00 79.01
PNL LN-1B-PET UL 67 Pass LV Panelboard 208 0.66 22.00 3
PNL HNBC UL 67 Pass LV Panelboard 480 8.99 14.00 64.18
PNL LN4C EATON Pass LV Panelboard 208 1.68 (*N1) 10.00 16.77
PNL LNBC EATON Pass LV Panelboard 208 2.22 (*N1) 10.00 22.16
PNL EL1 UL 67 Pass LV Panelboard 480 13.41 65.00 20.63
PNL EL2 UL 67 Pass LV Panelboard 480 13.26 65.00 20.4
400-1-10 EATON Pass LV Panelboard 208 8.52 10.00 85.2
BLDG 402 MDP-1 UL 891 Pass LV Switchboard 208 19.89 42.00 47.37
409E-1 UL 891 Pass LV Switchboard 208 23.55 65.00 36.23
410-1-03 UL 67 Pass LV Panelboard 208 22.76 25.00 91.02
410-1-04 EATON Pass LV Panelboard 208 21.52 42.00 51.24
410-1-04-01 UL 67 Pass LV Panelboard 208 7.49 10.00 74.93
410-1-04-21 EATON Pass LV Panelboard 208 8.91 22.00 40.52
410-1-04-34 EATON Pass LV Panelboard 208 4.33 22.00 19.66
410-1-06-01A-01 UL 67 Pass LV Panelboard 208 12.11 25.00 48.45
410E-1-02A-01A-01 UL 67 Pass LV Panelboard 208 4.22 10.00 42.19
410E-1-5 EATON Pass LV Panelboard 208 14.65 22.00 66.58
412-1-03 EATON Pass LV Panelboard 208 6.49 10.00 64.91
412-1-04A EATON Pass LV Panelboard 208 7.91 10.00 79.07
412-1-04B EATON Pass LV Panelboard 208 2.6 10.00 26.01
Dayton VA Correct Arc Flash Deficiencies 2-6
Bus I.D. Manufacturer Status Type Bus Voltage (V) Calc
Isc (kA) Equip
Isc (kA) Rating %
412-AC LOBBY UL 67 Pass LV Panelboard 208 6.16 22.00 28.01
(*N1) System X/R higher than Test X/R, Calc Isc (kA) modified based on low voltage factor.
Dayton VA Correct Arc Flash Deficiencies 3-1
PROTECTIVE DEVICE COORDINATION STUDY
The protective device coordination study determines overcurrent protective relay and circuit breaker settings in order to provide an optimal compromise between protection and selectivity.
Using the appropriate maximum fault currents, the time-current coordination curves were plotted as operating time versus current magnitudes to show protective device tripping and/or clearing characteristics and coordination among these devices.
Consideration was given to provide both selective isolation of faults and maximum protection of equipment such as cables, transformers, motors, etc.
To achieve the optimum protection and selectivity, the following guidelines were followed throughout the study:
1. Ideally, the settings of any overcurrent device should be high enough to permit the continuous full-load operating capacity of the cables and the equipment they supply, and to ride through system temporary disturbances such as in-rush current. On the other hand, the settings should be low enough to provide overload and short-circuit protection under minimum fault conditions.
2. Considering any two protective devices in series:
• The maximum available fault current at the downstream device determines the upper limit of the coordination range between these two devices.
• The minimum available fault current at the downstream device or the pick-up setting of the upstream device determines the lower limit of the coordination range.
• Series instantaneous devices do not coordinate unless there is sufficient impedance between the two devices.
• When plotting coordination curves, certain time intervals must be maintained between the curves in order to ensure correct selectivity. These time intervals vary, depending on the device types. In general, however, the following must be taken into consideration when determining the appropriate time separation interval: Breaker clearing time, relay tolerances, induction disk over-travel, and a reasonable safety margin for error.
Protective device coordination was performed in accordance with IEEE Std 242™.
Minimum guidelines for equipment protection, as outlined in the National Electrical Code (NEC) and applicable standards of the American National Standards Institute (ANSI), were followed.
Applicable requirements are summarized below.
1. Cables
Power cables require overload and short-circuit protection in order to meet the requirements stated in NEC Article 240, and IEEE Std 242. The NEC further
Dayton VA Correct Arc Flash Deficiencies 3-2 requires that the ampacity of low voltage cable (0-2000 Volts) be determined by NEC Article 310.15. Cable de-rating based upon ambient temperature and the number of current carrying conductors in a raceway must also be applied. Medium voltage cable (2001-35,000 Volts) ampacity is defined by NEC Articles 240.100(A) and 310.60.
2. Transformers
A transformer is recommended to have protective devices on both primary and secondary side in order to meet the basic protection requirements for overloads and short-circuit withstand values. However, a transformer is permitted to be protected by only a primary side device if it meets the exceptions listed in NEC Article 240.4(F).
In addition, the transformer protective devices must be able to withstand magnetizing inrush currents without tripping.
NEC protection requirements for transformers: Overcurrent devices should be selected, and settings should be recommended to provide overcurrent protection in accordance with NEC Article 450.3. Paragraph (A) specifies that transformers over 600 V comply with Table 450.3(A). Paragraph (B) specifies that transformers less than 600 V comply with Table 450.3(B).
Short-circuit thermal limits for transformers: The primary devices should be set on the basis that the transformers have short-circuit withstand capabilities as defined by IEEE Std C57.109™.
3. Motors
The motors should have appropriate protective devices to meet the basic protection requirements for overloads and fault current withstand values. In addition, the motor short-circuit and ground fault protective devices should be set to ride through motor starting current.
Please see Section 6.0 for a complete list of data and assumptions that were used in modeling the power system to provide conservative, worst-case results. Please note that complete information regarding the system model used for the computer simulation is included in Section 7.0.
As shown on the time-current plots, each device curve is tagged with an arrow and label referencing its location on the plot's individual representative one-line diagram.
This label also references the device to its specific manufacturer information, including ratings and settings, as indicated in the text box on each plot. The device time-current characteristics are truncated at maximum through-fault current for a downstream fault.
Efforts were made to provide the best coordination possible with the protective devices supplied under this contract. Areas where breaker trip curves overlap indicate areas of possible non-selective breaker operation. Where possible, efforts were made to reduce non-selective breaker operation while maintaining adequate system protection. In some cases, because of device limitations, little can be done to improve device selectivity. Such device limitations include the fixed operating characteristic of a fuse, the built-in instantaneous or instantaneous “over-ride”
Dayton VA Correct Arc Flash Deficiencies 3-3 elements of molded case circuit breakers, and the limited instantaneous trip range of trip units with an instantaneous trip function.
In cases involving redundant protective devices, non-selective breaker operation is of little or no concern. Protective devices are redundant if, regardless of which device opens, the same system outage occurs. Often, in order to improve overall system protection and coordination, redundant devices are intentionally set to overlap (i.e.
non-selectively coordinate with) one another.
Adequate coordination is achieved using the recommended protective devices, with settings and ratings as listed in Section 4.0. The recommended adjustments would maximize coordination in an attempt to allow the various downstream devices to isolate faults without operation of the upstream devices. Although instantaneous trip devices provide the highest degree of protection, when applied in series they compromise selectivity at high-magnitude fault currents.
Refer to the following pages for the plotted coordination curves, which graphically indicate the degree of selectivity and protection obtained.
In some cases, a single time-current curve may be applicable to several locations in the system, where each location utilizes substantially similar devices, and serves similar loads.
The following list references the attached time-current curves for this report.
Table 3.1 – TCC Plots Index
Title Page Number
01 NEW CB-BLDG 118 MAIN Page 3-4
02 NEW PNLBD 120-1 FDR Page 3-5
03 SWBD 115-1-03A to 115-1-03A-2B Page 3-6
04 305-1-02B Page 3-7
05 LSD BLDG 315 Page 3-8
06 PNL LNBC Page 3-9
07 PNL LN4C Page 3-10
08 PNL 410-1-04 Page 3-11
09 PNL 412-1-04A Page 3-12
10 BLD 315 MAIN Page 3-13
11 CB 410-1-03 to CB 410-1-06-01A-01 Page 3-14
12 CB 410E-1-4 MAIN TO CB-410E-1-02A-01A-01 MAIN Page 3-15
13 CB 305-1A TO CB-305-1-06 MAIN Page 3-16
Dayton VA Correct Arc Flash Deficiencies 3-4
Title Page Number
14 CB-305-1-05 MAIN TO CB-305-1-05-02 Page 3-17
15 CB-305-1-05 MAIN TO CB-305-1-04-34B Page 3-18
16 F-115-1-03A-T2 TO CB-115-1-03A-2E MAIN Page 3-19
17 CB-BLDG 120 MAIN TO F 120-1-01A-01-01F Page 3-20
18 CB-126-1-08A TO CB-126-1-08A-05 Page 3-21
19 F-LSD ATS E TO LSD BLDG 315 Page 3-22
20 CB320 ELEV 2 N & E FEED Page 3-23
21 F-TX-T-17-1 TO CB 402-1-5MAIN Page 3-24
22 CB-412-1-03 TO CB-412-AC LOBBY Page 3-25
23 CB-412-1-04 TO CB-412-1-04B MAIN Page 3-26
24 BLD 315 MAIN (GND) Page 3-27
TX Inrush
0.5 1 10 10
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
F-TX T-4-1
COOPER
1.5C-200C TYPE: NX (C-Rated), 15.5kV Sensor/Trip: 12A, Phase
12.0 Amps
CB-BLDG 118 MAIN
CUTLER-HAMMER
300-600A
TYPE: LD
Sensor/Trip: 300A, Plug: 300 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (3000A)
CB-118LP2
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 175A, Plug: 175 AT Phase Fixed TX-T-4-1
50 kVA 12470 / 240 V
F-TX T-4-1
COOPER
1.5C-200C TYPE: NX (C-Rated), 15.5kV Sensor/Trip: 12A, Phase
12.0 Amps
CB-BLDG 118 MAIN
CUTLER-HAMMER
300-600A
TYPE: LD
Sensor/Trip: 300A, Plug: 300 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (3000A)
CB-118LP2
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 175A, Plug: 175 AT Phase Fixed TX-T-4-1
50 kVA 12470 / 240 V
Plot name: 01 NEW CB-BLDG 118 MAIN Ref. Voltage: 240V Current Scale: x 1
F-TX T-4-1
COOPER
NX (C-Rated), 15.5kV 12A
S
P TX-T-4-1
50 kVA 12470 / 240V 4.50% Z
CB-BLDG 118 MAIN
CUTLER-HAMMER
LD
300A/300A
CB-118LP2
CUTLER-HAMMER
EDB, 2-3 Poles 175A/175A
CBL-118 LP1
2 - #350 200 ft Copper
118 PNL LP-1
240V
Eaton Electrical Services and Systems September 4, 2019
VAMC DAYTON 3-4
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-BLDG 120 MAIN
CUTLER-HAMMER
100-400A
TYPE: KD
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (2000A)
CB-ATS-120 N
CUTLER-HAMMER
15-100A TYPE: QBHW, 3-Pole Sensor/Trip: 90A, Plug: 90 AT Phase Fixed
CB-BLDG 120 MAIN
CUTLER-HAMMER
100-400A
TYPE: KD
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (2000A)
CB-ATS-120 N
CUTLER-HAMMER
15-100A TYPE: QBHW, 3-Pole Sensor/Trip: 90A, Plug: 90 AT Phase Fixed
Plot name: 02 NEW PNLBD 120-1 FDR Ref. Voltage: 208V Current Scale: x 1
CB-BLDG 120 MAIN
CUTLER-HAMMER
KD
400A/400A
CB-ATS-120 N
CUTLER-HAMMER
QBHW, 3-Pole 90A/90A
PNLBD 120-1
208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-5
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
F-115-1-03A-2B
BUSSMANN
1-600A TYPE: LPN-RK, 250V Class RK1 Sensor/Trip: 200A, CB-115-1-03A-2B MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
CB 115AHU2
CUTLER-HAMMER
15-100A TYPE: QBHW, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed
F-115-1-03A-2B
BUSSMANN
1-600A TYPE: LPN-RK, 250V Class RK1 Sensor/Trip: 200A, CB-115-1-03A-2B MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
CB 115AHU2
CUTLER-HAMMER
15-100A TYPE: QBHW, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed
Plot name: 03 SWBD 115-1-03A to 115-1-03A-2B Ref. Voltage: 208V Current Scale: x 1
F-115-1-03A-2B
BUSSMANN
LPN-RK, 250V Class RK1 200A
CB-115-1-03A-2B MAIN
CUTLER-HAMMER
EDB, 2-3 Poles 200A/200A
CBL-115-1-03A-2B
1 - #3/0 60 ft Copper
115-1-03A-2B 208V
CB 115AHU2
CUTLER-HAMMER
QBHW, 3-Pole 50A/50A
CBL-115AHU2
1 - #6 25 ft Copper
115 AHU2 VFD
208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-6
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-305-1-02A MAIN
SQUARE D
125-400A
TYPE: LA
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve
INST 4 (3504A)
CB-305-1-02B MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 225A, Plug: 225 AT Phase Fixed
CB-305-1-02A MAIN
SQUARE D
125-400A
TYPE: LA
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve
INST 4 (3504A)
CB-305-1-02B MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 225A, Plug: 225 AT Phase Fixed
Plot name: 04 305-1-02B Ref. Voltage: 208V Current Scale: x 1
CB-305-1-02A MAIN
SQUARE D
LA
400A/400A
CB-305-1-02B MAIN
CUTLER-HAMMER
EDB, 2-3 Poles 225A/225A
CBL-305-1-02B
1 - #4/0 6 ft Copper
305-1-02A 208V
305-1-02B 208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-7
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-LSD MAIN
CUTLER-HAMMER
100-400A
TYPE: KD
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CB-MD#2 ATS-LSD N
CUTLER-HAMMER
70-400A
TYPE: LB
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CB-315EDPA
CUTLER-HAMMER
15-225A
TYPE: FD
Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
CB-LSD MAIN
CUTLER-HAMMER
100-400A
TYPE: KD
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CB-MD#2 ATS-LSD N
CUTLER-HAMMER
70-400A
TYPE: LB
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CB-315EDPA
CUTLER-HAMMER
15-225A
TYPE: FD
Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
Plot name: 05 LSD BLDG 315 Ref. Voltage: 480V Current Scale: x 1
LSD BLDG 315
480V
CB-LSD MAIN
CUTLER-HAMMER
KD
400A/400A
CB-MD#2 ATS-LSD N
CUTLER-HAMMER
LB
400A/400A
CB-315EDPA
CUTLER-HAMMER
FD
200A/200A
CBL-315LSD
1 - #500 45 ft Copper
ATS-LSD
480V
EN
ATS#LSD
CBL-ATS-LSD N
1 - #500 40 ft Copper
Eaton Electrical Services and Systems
VAMC DAYTON 3-8
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-TX LNBC
CUTLER-HAMMER
15-100A
TYPE: GHB
Sensor/Trip: 60A, Plug: 60 AT Phase Fixed
CB-LNBC MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 150A, Plug: 150 AT Phase Fixed
CB PNL LNBC1
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 60A, Plug: 60 AT Phase Fixed
TX-LNBC
45 kVA 480 / 208 V
CB-TX LNBC
CUTLER-HAMMER
15-100A
TYPE: GHB
Sensor/Trip: 60A, Plug: 60 AT Phase Fixed
CB-LNBC MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 150A, Plug: 150 AT Phase Fixed
CB PNL LNBC1
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 60A, Plug: 60 AT Phase Fixed
TX-LNBC
45 kVA 480 / 208 V
Plot name: 06 PNL LNBC Ref. Voltage: 208V Current Scale: x 1
CB-TX LNBC
CUTLER-HAMMER
GHB
60A/60A
S
P TX-LNBC
45 kVA 480 / 208V 5.80% Z
CB-LNBC MAIN
CUTLER-HAMMER
EDB, 2-3 Poles 150A/150A
CB PNL LNBC1
CUTLER-HAMMER
BAB, 3-Pole 60A/60A
CBL-PNL LNBC
1 - #1/0 6 ft Copper
PNL LNBC
208V
CBL-TX LNBC
1 - #6 6 ft Copper
Eaton Electrical Services and Systems
VAMC DAYTON 3-9
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-TX LN4C
WESTINGHOUSE
15-100A
TYPE: GHB
Sensor/Trip: 40A, Plug: 40 AT Phase Fixed
CB LN4C MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CB-HN4C MAIN
WESTINGHOUSE
70-250A
TYPE: JDB, JD
Sensor/Trip: 150A, Plug: 150 AT Phase
LTD
INST 10.0 (1500A)
TX-LN4C
30 kVA 480 / 208 V
CB-TX LN4C
WESTINGHOUSE
15-100A
TYPE: GHB
Sensor/Trip: 40A, Plug: 40 AT Phase Fixed
CB LN4C MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CB-HN4C MAIN
WESTINGHOUSE
70-250A
TYPE: JDB, JD
Sensor/Trip: 150A, Plug: 150 AT Phase
LTD
INST 10.0 (1500A)
TX-LN4C
30 kVA 480 / 208 V
Plot name: 07 PNL LN4C Ref. Voltage: 208V Current Scale: x 1
CB-TX LN4C
WESTINGHOUSE
GHB
40A/40A
S
P TX-LN4C
30 kVA 480 / 208V 5.00% Z
CB LN4C MAIN
CUTLER-HAMMER
EDB, 2-3 Poles 100A/100A
CBL-TX LN4C
1 - #8 8 ft Copper
CBL-PNL LN4C
1 - #1 9 ft Copper
PNL HN4C
480V
CB-HN4C MAIN
WESTINGHOUSE
JDB, JD
150A/150A
Eaton Electrical Services and Systems
VAMC DAYTON 3-10
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB 410-1-04
SQUARE D
125-400A, Inst 5-10
TYPE: LH
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10.0 (4000A)
CB-410-1-04-01
CUTLER-HAMMER
100-225A
TYPE: ED
Sensor/Trip: 175A, Plug: 175 AT Phase Fixed
CB 410-1-04
SQUARE D
125-400A, Inst 5-10
TYPE: LH
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10.0 (4000A)
CB-410-1-04-01
CUTLER-HAMMER
100-225A
TYPE: ED
Sensor/Trip: 175A, Plug: 175 AT Phase Fixed
Plot name: 08 PNL 410-1-04 Ref. Voltage: 208V Current Scale: x 1
CB-410-1-04-01
CUTLER-HAMMER
ED
175A/175A
410-1-04 208V
CBL-410-1-4
1 - #500 30 ft Copper
CB 410-1-04
SQUARE D
LH
400A/400A
Eaton Electrical Services and Systems
VAMC DAYTON 3-11
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-412-1-04
GE
15-150A
TYPE: THED
Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CB-412-1-04B MAIN
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CBL-412-1-04
Size: 2 AWG Qty/Ph: 1
CBL-412-1-04B
Size: 4 AWG Qty/Ph: 1
CB-412-1-04
GE
15-150A
TYPE: THED
Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CB-412-1-04B MAIN
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CBL-412-1-04
Size: 2 AWG Qty/Ph: 1
CBL-412-1-04B
Size: 4 AWG Qty/Ph: 1
Plot name: 09 PNL 412-1-04A Ref. Voltage: 208V Current Scale: x 1
CB-412-1-04
GE
THED
100A/100A
CBL-412-1-04
1 - #2 60 ft Copper
CBL-412-1-04B
1 - #4 100 ft Copper
CB-412-1-04B MAIN
CUTLER-HAMMER
BAB, 3-Pole 100A/100A
412-1-04A 208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-12
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-BLDG 315 MAIN
EATON
LSI, 320-1200A, UL/CSA
TYPE: NG, 310+
Sensor/Trip: 1200A, Plug: 1200 AT Phase Ir for In = 1200A H (1200) (1200A) LTD (2-24 Sec. 1200A) 10 STPU (2-9 x Ir) 5 (6000A) STD (Inst-300ms) Inst.
INST OR (14.4 kA) Fixed (14400A)
CB-MD#2 ATS-LSD N
CUTLER-HAMMER
70-400A
TYPE: LB
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
F-TX-T-33
COOPER
3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 50A, Phase
50.0 Amps
TX-T-33
750 kVA 12470 / 480 V
CBL-0122
Size: 500 kcmil Qty/Ph: 3
CB-BLDG 315 MAIN
EATON
LSI, 320-1200A, UL/CSA
TYPE: NG, 310+
Sensor/Trip: 1200A, Plug: 1200 AT Phase Ir for In = 1200A H (1200) (1200A) LTD (2-24 Sec. 1200A) 10 STPU (2-9 x Ir) 5 (6000A) STD (Inst-300ms) Inst.
INST OR (14.4 kA) Fixed (14400A)
CB-MD#2 ATS-LSD N
CUTLER-HAMMER
70-400A
TYPE: LB
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
F-TX-T-33
COOPER
3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 50A, Phase
50.0 Amps
TX-T-33
750 kVA 12470 / 480 V
CBL-0122
Size: 500 kcmil Qty/Ph: 3
Plot name: 10 BLD 315 MAIN Ref. Voltage: 480V Current Scale: x 10
CB-BLDG 315 MAIN
EATON
NG, 310+
1200A/1200A
CB-MD#2 ATS-LSD N
CUTLER-HAMMER
LB
400A/400A
F-TX-T-33
COOPER
ELX, 8.3-23kV 50A
S
P TX-T-33
750 kVA 12470 / 480V 5.66% Z
CBL-0122
3 - #500 45 ft Copper
PANEL 315 MD
480V
Eaton Electrical Services and Systems
VAMC DAYTON 3-13
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB 410-1-06-01A-01
SQUARE D
70-250A
TYPE: QD
Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
CB 410-1-03MAIN
SQUARE D
125-400A, Inst 5-10
TYPE: LA
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10.0 (4000A)
CB 410-1-03
SQUARE D
125-400A, Inst 5-10
TYPE: LH
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5.0 (2000A)
CB 410-1-06-01A-01
SQUARE D
70-250A
TYPE: QD
Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
CB 410-1-03MAIN
SQUARE D
125-400A, Inst 5-10
TYPE: LA
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10.0 (4000A)
CB 410-1-03
SQUARE D
125-400A, Inst 5-10
TYPE: LH
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5.0 (2000A)
Plot name: 11 CB 410-1-03 to CB 410-1-06-01A-01 Ref. Voltage: 208V Current Scale: x 1
CB 410-1-06-01A-01
SQUARE D
QD
200A/200A
CB 410-1-03MAIN
SQUARE D
LA
400A/400A
CB 410-1-03
SQUARE D
LH
400A/400A
CBL-410-1-03
1 - #600 25 ft Copper
410-1-03 208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-14
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB 410E-1-4 MAIN
SQUARE D
125-400A
TYPE: LA
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve
INST LO (2000A)
CB 410E-MAIN E&W EM
SQUARE D
70-250A
TYPE: QD
Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
FS 410E-1-02A-01A
BUSSMANN
1-600A TYPE: LPN-RK, 250V Class RK1 Sensor/Trip: 200A, CB-410E-1-02A-01A-01 MAIN
GE
70-225A
TYPE: TFK
Sensor/Trip: 175A, Plug: 175 AT Phase Thermal Curve (Fixed) INST (4.5-10 x Trip) LO (787.5A)
CBL-410E-1-02A-01A
Size: 4/0 AWG Qty/Ph: 1
CB 410E-1-4 MAIN
SQUARE D
125-400A
TYPE: LA
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve
INST LO (2000A)
CB 410E-MAIN E&W EM
SQUARE D
70-250A
TYPE: QD
Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
FS 410E-1-02A-01A
BUSSMANN
1-600A TYPE: LPN-RK, 250V Class RK1 Sensor/Trip: 200A, CB-410E-1-02A-01A-01 MAIN
GE
70-225A
TYPE: TFK
Sensor/Trip: 175A, Plug: 175 AT Phase Thermal Curve (Fixed) INST (4.5-10 x Trip) LO (787.5A)
CBL-410E-1-02A-01A
Size: 4/0 AWG Qty/Ph: 1
Plot name: 12 CB 410E-1-4 MAIN TO CB-410E-1-02A-01A-01 MAIN Ref. Voltage: 208V Current Scale: x 1
CB 410E-1-4 MAIN
SQUARE D
LA
400A/400A
CB 410E-MAIN E&W EM
SQUARE D
QD
200A/200A
FS 410E-1-02A-01A
BUSSMANN
LPN-RK, 250V Class RK1 200A
CBL-410E-MAIN E&W EM
1 - #4/0 25 ft Copper
CBL-410E-1-02A-01A
1 - #4/0 130 ft Copper
CB-410E-1-02A-01A-01 MAIN
GE
TFK
175A/175A
410E-1-4 208V
410E-1-02A-01A SWT
208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-15
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB 305-1A
GE
300-1200A TYPE: SKHA, Spectra RMS Sensor/Trip: 600A, Plug: 600 AT Phase
MAX
CB 305-1-06
SQUARE D
150-250A, UL
TYPE: J-Frame, Powerpact Sensor/Trip: 225A, Plug: 225 AT Phase Thermal Curve INST (5-10 x Trip) Low (1125A)
CBL-305-1-06
Size: 4/0 AWG Qty/Ph: 1
CB 305-1A
GE
300-1200A TYPE: SKHA, Spectra RMS Sensor/Trip: 600A, Plug: 600 AT Phase
MAX
CB 305-1-06
SQUARE D
150-250A, UL
TYPE: J-Frame, Powerpact Sensor/Trip: 225A, Plug: 225 AT Phase Thermal Curve INST (5-10 x Trip) Low (1125A)
CBL-305-1-06
Size: 4/0 AWG Qty/Ph: 1
Plot name: 13 CB 305-1A TO CB-305-1-06 MAIN Ref. Voltage: 208V Current Scale: x 1
CB 305-1A
GE
SKHA, Spectra RMS 600A/600A
CB 305-1-06
SQUARE D
J-Frame, Powerpact 225A/225A
CBL-305-1-06
1 - #4/0 80 ft Copper
CB-305-1-06 MAIN
EATON
EDB, 2-3 Poles 225A/225A
CBL-305-1A
4 - #350 25 ft Copper
305-1A 208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-16
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-305-1-05-05
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
CB-305-1-05 MAIN
CUTLER-HAMMER
250-400A
TYPE: DK
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CB-305-1-05-05 MAIN
CUTLER-HAMMER
150-200A
TYPE: CC & CCH
Sensor/Trip: 225A, Plug: 225 AT Phase Thermal-Magnetic Curve
CB-305-1-05-02
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CBL-305-1-05-05
Size: 3/0 AWG Qty/Ph: 1
CB-305-1-05-05
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
CB-305-1-05 MAIN
CUTLER-HAMMER
250-400A
TYPE: DK
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CB-305-1-05-05 MAIN
CUTLER-HAMMER
150-200A
TYPE: CC & CCH
Sensor/Trip: 225A, Plug: 225 AT Phase Thermal-Magnetic Curve
CB-305-1-05-02
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CBL-305-1-05-05
Size: 3/0 AWG Qty/Ph: 1
Plot name: 14 CB-305-1-05 MAIN TO CB-305-1-05-02 Ref. Voltage: 208V Current Scale: x 1
CB-305-1-05-05
CUTLER-HAMMER
EDB, 2-3 Poles 200A/200A
CB-305-1-05 MAIN
CUTLER-HAMMER
DK
400A/400A
CBL-305-1-05-05
1 - #3/0 35 ft Copper
CB-305-1-05-05 MAIN
CUTLER-HAMMER
CC & CCH
225A/225A
CB-305-1-05-02
CUTLER-HAMMER
BAB, 3-Pole 100A/100A
305-1-05 208V
305-1-05-05 208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-17
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-305-1-05 4
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 90A, Plug: 90 AT Phase Fixed
CB-305-1-04-34B
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed
CB-305-1-05 MAIN
CUTLER-HAMMER
250-400A
TYPE: DK
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CBL-305-1-05-04
Size: 4 AWG Qty/Ph: 1
CB-305-1-05 4
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 90A, Plug: 90 AT Phase Fixed
CB-305-1-04-34B
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed
CB-305-1-05 MAIN
CUTLER-HAMMER
250-400A
TYPE: DK
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CBL-305-1-05-04
Size: 4 AWG Qty/Ph: 1
Plot name: 15 CB-305-1-05 MAIN TO CB-305-1-04-34B Ref. Voltage: 208V Current Scale: x 1
CB-305-1-05 4
CUTLER-HAMMER
BAB, 3-Pole 90A/90A
CBL-305-1-05-04
1 - #4 148 ft Copper
CB-305-1-04-34B
CUTLER-HAMMER
BAB, 3-Pole 50A/50A
CB-305-1-05 MAIN
CUTLER-HAMMER
DK
400A/400A
305-1-05 208V
305-1-05-04 208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-18
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
F-115-1-03A-2E
GOULD SHAWMUT
30-600A TYPE: AT-DE, 250V Class RK5 Sensor/Trip: 200A, CB-115-1-03A-2E MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
CBL-115-1-03A-2E
Size: 3/0 AWG Qty/Ph: 1
F-115-1-03A-2E
GOULD SHAWMUT
30-600A TYPE: AT-DE, 250V Class RK5 Sensor/Trip: 200A, CB-115-1-03A-2E MAIN
CUTLER-HAMMER
100-225A, UL
TYPE: EDB, 2-3 Poles Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
CBL-115-1-03A-2E
Size: 3/0 AWG Qty/Ph: 1
Plot name: 16 F-115-1-03A-T2 TO CB-115-1-03A-2E MAIN Ref. Voltage: 208V Current Scale: x 1
F-115-1-03A-2E
GOULD SHAWMUT
AT-DE, 250V Class RK5 200A
CB-115-1-03A-2E MAIN
CUTLER-HAMMER
EDB, 2-3 Poles 200A/200A
CBL-115-1-03A-2E
1 - #3/0 49 ft Copper
Eaton Electrical Services and Systems
VAMC DAYTON 3-19
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-BLDG 120 MAIN
CUTLER-HAMMER
100-400A
TYPE: KD
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (2000A)
CB-120-1 1
EATON
15-100A TYPE: BAB-H, 3-Pole Sensor/Trip: 70A, Plug: 70 AT Phase Fixed
F 120-1-01A-01-01F
BUSSMANN
1-600A
TYPE: FRN-R
Sensor/Trip: 25A, CB-BLDG 120 MAIN
CUTLER-HAMMER
100-400A
TYPE: KD
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 5 (2000A)
CB-120-1 1
EATON
15-100A TYPE: BAB-H, 3-Pole Sensor/Trip: 70A, Plug: 70 AT Phase Fixed
F 120-1-01A-01-01F
BUSSMANN
1-600A
TYPE: FRN-R
Sensor/Trip: 25A, Plot name: 17 CB-BLDG 120 MAIN TO F 120-1-01A-01-01F Ref. Voltage: 208V Current Scale: x 1
CB-BLDG 120 MAIN
CUTLER-HAMMER
KD
400A/400A
CB-120-1 1
EATON
BAB-H, 3-Pole 70A/70A
F 120-1-01A-01-01F
BUSSMANN
FRN-R
25A
PNLBD 120-1
208V
CBL-120-1-01
1 - #2 4 ft Copper
Eaton Electrical Services and Systems
VAMC DAYTON 3-20
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-126-1-08A-05
SQUARE D
15-100A
TYPE: FA
Sensor/Trip: 90A, Plug: 90 AT Phase Fixed
CB-126-1-08A
CUTLER-HAMMER
250-400A
TYPE: DK
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 6 (2400A)
CBL-126-1-08A
Size: 500 kcmil Qty/Ph: 1
CB-126-1-08A-05
SQUARE D
15-100A
TYPE: FA
Sensor/Trip: 90A, Plug: 90 AT Phase Fixed
CB-126-1-08A
CUTLER-HAMMER
250-400A
TYPE: DK
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 6 (2400A)
CBL-126-1-08A
Size: 500 kcmil Qty/Ph: 1
Plot name: 18 CB-126-1-08A TO CB-126-1-08A-05 Ref. Voltage: 208V Current Scale: x 1
CB-126-1-08A-05
SQUARE D
FA
90A/90A
CB-126-1-08A
CUTLER-HAMMER
DK
400A/400A
CBL-126-1-08A
1 - #500 56 ft Copper
126-1-08A 208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-21
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-LSD MAIN
CUTLER-HAMMER
100-400A
TYPE: KD
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CB-315EDPA
CUTLER-HAMMER
15-225A
TYPE: FD
Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
F-LSD ATS E
BUSSMANN
15-600A TYPE: LPS-RK, 600V Class RK1 Sensor/Trip: 400A, CB-LSD MAIN
CUTLER-HAMMER
100-400A
TYPE: KD
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
CB-315EDPA
CUTLER-HAMMER
15-225A
TYPE: FD
Sensor/Trip: 200A, Plug: 200 AT Phase Fixed
F-LSD ATS E
BUSSMANN
15-600A TYPE: LPS-RK, 600V Class RK1 Sensor/Trip: 400A, Plot name: 19 F-LSD ATS E TO LSD BLDG 315 Ref. Voltage: 480V Current Scale: x 1
CB-LSD MAIN
CUTLER-HAMMER
KD
400A/400A
CB-315EDPA
CUTLER-HAMMER
FD
200A/200A
F-LSD ATS E
BUSSMANN
LPS-RK, 600V Class RK1 400A
CBL-315LSD
1 - #500 45 ft Copper
ATS-LSD
480V
LSD BLDG 315
480V
ATS#LSD
Eaton Electrical Services and Systems
VAMC DAYTON 3-22
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB320ELEV2
SIEMENS
15-125A TYPE: ED6 Sentron, 2 & 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Thermal Curve (Fixed) INST Fixed (800A)
CB-320ATS-CR N
WESTINGHOUSE
400-800A
TYPE: MC SELTRNC
Sensor/Trip: 800A, Plug: 800 AT Phase
LTPU 1.0 (800A)
LTD LTD
STPU 10.0 (8000A)
STD-I2T STD (I^s T On) CB-320ATS-CR E
SQUARE D
LI, 100-1200A, UL
TYPE: Powerpact P-Frame, 3.0 & 3.0A Sensor/Trip: 800A, Plug: 800 AT Phase LTPU/LTD (A 0.4-1.0 x S) 1 (800A); 0.5 INST (1.5-12 x S) 1.5 (1200A)
CB320ELEV2
SIEMENS
15-125A TYPE: ED6 Sentron, 2 & 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Thermal Curve (Fixed) INST Fixed (800A)
CB-320ATS-CR N
WESTINGHOUSE
400-800A
TYPE: MC SELTRNC
Sensor/Trip: 800A, Plug: 800 AT Phase
LTPU 1.0 (800A)
LTD LTD
STPU 10.0 (8000A)
STD-I2T STD (I^s T On) CB-320ATS-CR E
SQUARE D
LI, 100-1200A, UL
TYPE: Powerpact P-Frame, 3.0 & 3.0A Sensor/Trip: 800A, Plug: 800 AT Phase LTPU/LTD (A 0.4-1.0 x S) 1 (800A); 0.5 INST (1.5-12 x S) 1.5 (1200A)
Plot name: 20 CB320 ELEV 2 N & E FEED Ref. Voltage: 480V Current Scale: x 1
CB320ELEV2
SIEMENS
ED6 Sentron, 2 & 3-Pole 100A/100A
CB-320ATS-CR N
WESTINGHOUSE
MC SELTRNC
800A/800A
CB-320ATS-CR E
SQUARE D
Powerpact P-Frame, 3.0 & 3.0A 800A/800A
320E-1 480V
CBL-320ATS-CR N
2 - #500 37 ft Copper
CBL-320ATS-CR E
2 - #500 50 ft Copper
E N
320ATS-CR
ATS-320 CR
480V
CBL-320E-1
2 - #500 25 ft Copper
Eaton Electrical Services and Systems
VAMC DAYTON 3-23
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
F-TX-T-17-1
COOPER
3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 40A, Phase
40.0 Amps
CB-PNL402-1-5
SQUARE D
15-100A
TYPE: FH
Sensor/Trip: 60A, Plug: 60 AT Phase Fixed
CB 402-1-5MAIN
SQUARE D
15-100A TYPE: QO, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed (730-6, 50A)
TX-T-17-1
500 kVA 12470 / 208 V
CBL-0148
Size: 600 kcmil Qty/Ph: 4
CBL-PNL402-1-5
Size: 6 AWG Qty/Ph: 1
F-TX-T-17-1
COOPER
3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 40A, Phase
40.0 Amps
CB-PNL402-1-5
SQUARE D
15-100A
TYPE: FH
Sensor/Trip: 60A, Plug: 60 AT Phase Fixed
CB 402-1-5MAIN
SQUARE D
15-100A TYPE: QO, 3-Pole Sensor/Trip: 50A, Plug: 50 AT Phase Fixed (730-6, 50A)
TX-T-17-1
500 kVA 12470 / 208 V
CBL-0148
Size: 600 kcmil Qty/Ph: 4
CBL-PNL402-1-5
Size: 6 AWG Qty/Ph: 1
Plot name: 21 F-TX-T-17-1 TO CB 402-1-5MAIN Ref. Voltage: 12470V Current Scale: x 1
F-TX-T-17-1
COOPER
ELX, 8.3-23kV 40A
S
P TX-T-17-1
500 kVA 12470 / 208V 5.50% Z
CBL-0148
4 - #600 81 ft Copper
CB-PNL402-1-5
SQUARE D
FH
60A/60A
CBL-PNL402-1-5
1 - #6 150 ft Copper
CB 402-1-5MAIN
SQUARE D
QO, 3-Pole 50A/50A
BLDG 402 MDP-1
208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-24
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-412-1-03
GE
15-150A
TYPE: THED
Sensor/Trip: 70A, Plug: 70 AT Phase Fixed
CB-412-AC LOBBY
EATON
10-70A TYPE: BAB, 1-Pole Sensor/Trip: 20A, Plug: 20 AT Phase Fixed
CBL-412-1-03
Size: 4 AWG Qty/Ph: 1
CB-412-1-03
GE
15-150A
TYPE: THED
Sensor/Trip: 70A, Plug: 70 AT Phase Fixed
CB-412-AC LOBBY
EATON
10-70A TYPE: BAB, 1-Pole Sensor/Trip: 20A, Plug: 20 AT Phase Fixed
CBL-412-1-03
Size: 4 AWG Qty/Ph: 1
Plot name: 22 CB-412-1-03 TO CB-412-AC LOBBY Ref. Voltage: 208V Current Scale: x 1
CB-412-1-03
GE
THED
70A/70A
CBL-412-1-03
1 - #4 51 ft Copper
CB-412-AC LOBBY
EATON
BAB, 1-Pole 20A/20A
412-1-03 208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-25
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-412-1-04
GE
15-150A
TYPE: THED
Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CB-412-1-04B MAIN
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CBL-412-1-04
Size: 2 AWG Qty/Ph: 1
CBL-412-1-04B
Size: 4 AWG Qty/Ph: 1
CB-412-1-04
GE
15-150A
TYPE: THED
Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CB-412-1-04B MAIN
CUTLER-HAMMER
15-100A TYPE: BAB, 3-Pole Sensor/Trip: 100A, Plug: 100 AT Phase Fixed
CBL-412-1-04
Size: 2 AWG Qty/Ph: 1
CBL-412-1-04B
Size: 4 AWG Qty/Ph: 1
Plot name: 23 CB-412-1-04 TO CB-412-1-04B MAIN Ref. Voltage: 208V Current Scale: x 1
CB-412-1-04
GE
THED
100A/100A
CBL-412-1-04
1 - #2 60 ft Copper
CBL-412-1-04B
1 - #4 100 ft Copper
CB-412-1-04B MAIN
CUTLER-HAMMER
BAB, 3-Pole 100A/100A
412-1-04A 208V
Eaton Electrical Services and Systems
VAMC DAYTON 3-26
1K 10 K
0.01
0.10
CURRENT IN AMPERES
TIME IN SECONDS
CB-BLDG 315 MAIN
EATON
GF, 320-1200AS, UL
TYPE: NG, 310+
Sensor/Trip: 1200A, Plug: 1200 AT
GND
GFPU, (0.2 - 1 x In) .8X (960A) GFD LSIG, (Inst-300ms) 300ms
CB-MD#2 ATS-LSD N
CUTLER-HAMMER
70-400A
TYPE: LB
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
F-TX-T-33
COOPER
3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 50A, Phase
50.0 Amps
TX-T-33
750 kVA 12470 / 480 V
CBL-0122
Size: 500 kcmil Qty/Ph: 3
CB-BLDG 315 MAIN
EATON
GF, 320-1200AS, UL
TYPE: NG, 310+
Sensor/Trip: 1200A, Plug: 1200 AT
GND
GFPU, (0.2 - 1 x In) .8X (960A) GFD LSIG, (Inst-300ms) 300ms
CB-MD#2 ATS-LSD N
CUTLER-HAMMER
70-400A
TYPE: LB
Sensor/Trip: 400A, Plug: 400 AT Phase Thermal Curve (Fixed) INST (5-10 x Trip) 10 (4000A)
F-TX-T-33
COOPER
3C-100C TYPE: ELX, 8.3-23kV Sensor/Trip: 50A, Phase
50.0 Amps
TX-T-33
750 kVA 12470 / 480 V
CBL-0122
Size: 500 kcmil Qty/Ph: 3
Plot name: 24 BLD 315 MAIN (GND) Ref. Voltage: 480V Current Scale: x 10
CB-BLDG 315 MAIN
EATON
NG, 310+
1200A/1200A
CB-MD#2 ATS-LSD N
CUTLER-HAMMER
LB
400A/400A
F-TX-T-33
COOPER
ELX, 8.3-23kV 50A
S
P TX-T-33
750 kVA 12470 / 480V 5.66% Z
CBL-0122
3 - #500 45 ft Copper
PANEL 315 MD
480V
Eaton Electrical Services and Systems
VAMC DAYTON 3-27
Dayton VA Correct Arc Flash Deficiencies 4-1
RECOMMENDED PROTECTIVE DEVICE SETTINGS
The following table shows a comprehensive summary of the recommended settings for the adjustable protective devices. The devices are grouped by system bus name/location. Refer to Section 11.0 for the system one-line diagrams.
Table 4.1 – Recommended Low-Voltage Protective Device Settings
Name / Type Description Frame / Sensor / Plug
Recommended Settings
CB-BLDG 315 MAIN EATON 1200A Phase
Static Trip NG, 310+ 1200A Ir for In = 1200A H (1200) (1200A)
LTD (2-24 Sec. 1200A) 10
STPU (2-9 x Ir) 5 (6000A)
STD (Inst-300ms) Inst.
INST OR (14.4 kA) Fixed (14400A)
GND
GFPU, (0.2 – 1 x In) .6X (720A)
GFD LSIG, (Inst – 300ms) 300ms
CB-305-1-05 MAIN CUTLER-HAMMER 400A Thermal Curve (Fixed)
Thermal Magnetic DK 400A INST (5-10 x Trip) 10 (4000A)
400A
CB-LSD MAIN CUTLER-HAMMER 400A Thermal Curve (Fixed)
Thermal Magnetic KD 400A INST (5-10 x Trip) 10 (4000A)
400A
CB-BLDG 118 MAIN CUTLER-HAMMER 600A Thermal Curve (Fixed)
Thermal Magnetic LD 300A INST (5-10 x Trip) 10 (3000A)
300A
Dayton VA Correct Arc Flash Deficiencies 5-1
ARC FLASH INCIDENT ENERGY ANALYSIS
This section of the report contains the interpretation for the arc flash incident energy…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .