36C25019B0055-007.xlsx

XLSX spreadsheet Posted

Attached to
Upgrade Building Management System, Marion (VA-19-00074140)
Solicitation number
36C25019B0055
Issued by

About this file

36C25019B0055 Marion_Issues Log_EEI_11-6-15 10232017.xlsx

View the file

Other files

File Type Posted
36C25019C0295-000.docx DOCX document
36C25019B0055-0001000.docx DOCX document
36C25019B0055-0001001.docx DOCX document
36C25019B0055-0001001.docx DOCX document
36C25019B0055-0001000.docx DOCX document
36C25019B0055-001.docx DOCX document
36C25019B0055-008.doc DOC document
36C25019B0055-004.pdf PDF
36C25019B0055-005.pdf PDF
36C25019B0055-002.pdf PDF
36C25019B0055-006.docx DOCX document
36C25019B0055-003.pdf PDF
36C25019B0055-008.doc DOC document
36C25019B0055-007.xlsx XLSX spreadsheet
36C25019B0055-004.pdf PDF
36C25019B0055-001.docx DOCX document
36C25019B0055-006.docx DOCX document
36C25019B0055-003.pdf PDF
36C25019B0055-002.pdf PDF
36C25019B0055-005.pdf PDF
36C25019B0055-000.docx DOCX document
36C25019B0055-000.docx DOCX document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Issues Log

Location Name:Marion VA, Marion IndianaUpdated On:7/24/15
Prepared By:Engineering Economics, Inc.Updated By:KK
Issue
NumberBuilding
NumberEquipment
LocationEquipment
TagIssue
TypeIssue
DescriptionDate
EnteredRecommended
Corrective ActionRepair
ResponsibilitySimple Repair
(Y/N)Repair
ByDate Repair
CompletedCalculation
RequiredHow is item planned for completion? (in-House, Credit Card, NRM, Other to be identified)Assigned to (shop or Person)Initials of M&O staff that performed workMonth Planned for completionYear Planned for CompletionActual Date CompletedComments
152BasementHP-01Sequence of OperationCompressor cycles even though room temperature is below room setpoint.7/17/15Verify the compressor staging control setpoints and the changeover valve programming is correct.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
165Conference RoomHP-01Humidity ControlHigh humidity levels in space and the discharge air temperature is not cold during cooling 50-55 degf.7/17/151) Verify the unit is charged with the correct amount of refrigerant.

2) Lower the fan speed to run the unit longer.

3) Remove the air from the water loop.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
265Catholic ChapelHP-02Humidity ControlHigh humidity levels in space and the discharge air temperature is not cold during cooling 50-55 degf.7/17/151) Verify the unit is charged with the correct amount of refrigerant.

2) Lower the fan speed to run the unit longer.

3) Remove the air from the water loop.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
365Protestant ChapelHP-03Humidity ControlHigh humidity levels in space and the discharge air temperature is not cold during cooling 50-55 degf.7/17/151) Verify the unit is charged with the correct amount of refrigerant.

2) Lower the fan speed to run the unit longer.

3) Remove the air from the water loop.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
465BasementGSP 1,2,3Sequence of OperationAll of the ground source pumps operate when the heat pumps are not running.8/27/15Modify the pump programming to disable the ground source pumps when the heat pumps are off.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
565BasementGSP 1,2,3Sequence of OperationAll of the ground source pumps operate when one heat pump is running.8/27/15Modify the programming to stage the source pumps to maintain the ground supply water temperature and the required flow for the number of heat pumps running.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
665BasementGSP 1,2,3Air In The SystemThere is air in the ground source condenser water loop.8/27/15Add air vents to the top of the piping to bleed air from the system and then add glycol/water to fill the system.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
765BasementGSP 1,2,3GaugesThe pump gauges are not reading correctly.8/27/15Replace the gauges.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
NRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1138B 001AHU-1Sensor CalibrationSupply air temperature reading 7˚ F. from actual7/10/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
2138B 001AHU-1Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/10/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
3138B 001AHU-2Sensor CalibrationReturn Air RH Sensor reading 40% from actual7/10/15Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
4138B 001AHU-2VFDThe supply fan is operator overridden from the graphics to 90% due to fan oscillation.7/10/15Tune the control loop to minimize the cycling of the fan VFD.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
5138B 001AHU-2VFDThe return fan is operator overridden from the graphics to 70%.7/10/15Tune the control loop to minimize the cycling of the fan VFD.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
6138B 001AHU-2Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/10/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
7138B 001AHU-3Sensor CalibrationCold deck air temperature reading 8˚ F. from actual7/10/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
8138B 001AHU-3Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/10/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
9138B 001AHU-3Static PressureStatic pressure below setpoint, 0.03 iwc and supply fan and 100% speed. When the OAD is open, the static pressure increases to 1.3 iwc.7/8/16Verify the outside air minimum damper position is correct. This may be corrected when the new airflow stations are operational.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
10138B 001AHU-4Sensor CalibrationCold deck air temperature reading 7˚ F. from actual7/10/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
11138B 001AHU-4Sensor CalibrationReturn Air RH Sensor reading 43% from actual7/10/15Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
12138B 001AHU-4Binary CommandReturn fan shows on when it is off7/8/16Investigate and repair the status input.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
13138B 001AHU-4Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/10/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
14138B 001AHU-4VFDThe supply fan is operator overridden from the graphics to 80%.7/10/15Investigate static pressure control and return to the automatic mode of operation.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
15138B 001AHU-4VFDThe return fan is operator overridden from the graphics to 60%.7/10/15Investigate static pressure control and return to the automatic mode of operation.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
16138B 001AHU-4Static PressureStatic pressure below setpoint and supply fan and 80% speed7/11/16Investigate and return to the automatic mode of operation.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
18138B 001AHU-1DAT SetpointCannot maintain DAT SP of 50 to 54 F, CHW at 100%.7/16/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
19138B 001AHU-2DAT SetpointCannot maintain DAT SP of 50 to 54 F, CHW at 100%.7/16/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
20138B 001AHU-3DAT SetpointDAT close to DA SP of 50 F, CHW valve at 100%.7/16/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
21138B 001AHU-4DAT SetpointCannot maintain DAT SP of 50 F, DAT averages 56 F and CHW at 100%.7/16/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
22138B 001AHU-2DA Static PressureSupply fan at 90% not meeting DAP SP.7/17/15Tune the control loop to minimize the cycling of the fan VFD.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
23138B 001AHU-4DA Static PressureSupply Fan at 100% and SP between 0.4 and 1.4 in WG.7/17/15Verify the belts are tight and the CFM is correct.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
24138Mechanical RoomBAS ControllersSystem Communication IssuesSusceptible to IT communications issues.7/17/15Consider migrating to a local network instead of the campus network.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
25138All VAV Terminal UnitsAllTerminal Box Control SetpointNo space temperature setpoint reset.7/17/15The controllers are being reprogrammed under a separate project. This should be included in that project.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
26138Rm 106NVAV 1-06Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 74 F. with 100% reheat valve and peak DAT of 82 Deg. F.7/17/15The heating hot water system is being reset too low to heat the AHU discharge air.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
27138BasementVAV B-01Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 52 Deg. F. Suspect reheat problem.7/17/15Investigate the reheat valve operation and the heating hot water temperature and repair or make setpoint changes are required..OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
28138BasementVAV B-02Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 52 Deg. F. Suspect reheat problem.7/17/15Investigate the reheat valve operation and the heating hot water temperature and repair or make setpoint changes are required..OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
29138BasementVAV B-03Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 74 F. with 100% reheat valve and peak DAT of 82 Deg. F.7/17/15The heating hot water system is being reset too low to heat the AHU discharge air.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
30138BasementVAV B-04Terminal Box Valve and Actuator MaintenanceRoom temp maintaining setpoint of 73 F, but hot water reheat cycling between 30% and 100% to do so. Suspect tuning issue.7/17/15Tune the control loop as required.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
31138Room 104SVAV-1-03Terminal Box Valve and Actuator MaintenanceAt max air flow the room temperature is above setpoint by up to 3 DegF.7/17/15Increase the maximum CFM flow setpoint if the VAV is large enough. Consider installing a large VAV.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
32138Room 104NVAV-1-04Terminal Box Valve and Actuator MaintenanceAt max air flow and room temp above setpoint by up to 4 DegF.7/17/15Increase the maximum CFM flow setpoint if the VAV is large enough. Consider installing a large VAV.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
33138B 001AHU-2VFDThe supply fan VFD minimum frequency is set in the drive to 6 Hz.8/26/15Verify the VFD is setup correctly for minimum frequency.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
34138B 001AHU-2VFDThe return fan VFD maximum frequency at 100% output is 35 Hz.8/26/15Verify the VFD is setup correctly for maximum frequency.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
35138B 001AHU-2ValveThe cooling valve is a 3 way valves and the system is controlling to a differential pressure setpoint. The differential pressure will not vary much with a three way valve and therefore the pump speed will not be reduced to save energy.8/26/15Install a balancing valve in the bypass line to reduce the water flow through the bypass line.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
36138B 001AHU-2DA Static PressureThe fan VFD is cycling frequently from 100% to 0% to try to maintain the duct static pressure.8/26/15Tune the control loop to minimize the cycling of the fan VFD.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
37138B 001AHU-4Analog CommandThe face and bypass damper did not respond to override commands.8/26/15Verify the correct points are displayed on the graphic.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
38138B 001AHU-4Analog CommandThe supply and return fan VFD's run at 15 Hz @ 0%, 22.7 Hz @ 50% and 60 Hz @ 100%. The VFD does not ramp linearly with the control output.8/26/15Verify the VFD is programmed to ramp linearly with the control output.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
39138B 001AHU-4Sensor CalibrationThe down duct static pressure indicates -0.14 IWC when the fan is turned off.8/26/15Verify the sensor calibration or replaced the sensor if defective.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
40138B 001AHU-3VFDThe supply fan VFD minimum frequency is set in the drive to 6 Hz.8/27/15Verify the minimum frequency setting is correct.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
41138B 001AHU-3VFDThe return fan VFD is overridden at the graphics and when placed in the auto mode the output ramps up and down rapidly.8/27/15Verify the control inputs are operating correctly and tune the control loop.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
42138B 001AHU-3Static PressureThe first floor static pressure sensor is indicating a negative pressure and is controlling the supply fan to 100% speed.8/27/15Repair or replace the sensor or wiring.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
43138B 001AHU-3Static PressureWhen the fan is off, the second floor static pressure sensor is indicating +0.99 iwc.8/27/15Calibrated the pressure sensor or replace if defective.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
44138B 001AHU-1ValveThe cooling valve is a 3 way valves and the system is controlling to a differential pressure setpoint. The differential pressure will not vary much with a three way valve and therefore the pump speed will not be reduced to save energy.8/26/15Install a balancing valve in the bypass line to reduce the water flow through the bypass line.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
45138B 001AHU-2ValveThe cooling valve is a 3 way valves and the system is controlling to a differential pressure setpoint. The differential pressure will not vary much with a three way valve and therefore the pump speed will not be reduced to save energy.8/26/15Install a balancing valve in the bypass line to reduce the water flow through the bypass line.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
NRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1172B 129AHU-B1Sensor CalibrationReturn Air RH Sensor reading 18% from actual7/8/15Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
2172B 129AHU-B1GraphicsHot water valve display is 100% open and is closed7/8/15Correct graphicOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
3172C 122AHU-C1VFDReturn fan does not turn off when commanded off7/8/16The VFD is operating in the bypass mode. Repair the VFD and retest.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
4172C 122AHU-C1VFDSupply fan stays running when commanded off7/8/16The VFD is operating in the bypass mode. Repair the VFD and retest.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
5172C 122AHU-C1Sensor CalibrationReturn Air RH Sensor reading 24% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
6172C 122AHU-C1Sensor CalibrationPreheat Temp reading 0 Deg. F.7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
8172D 122AHU-D1VFDReturn fan does not turn off when commanded off7/8/16Investigate the VFD and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
9172D 122AHU-D1Sensor CalibrationReturn Air RH Sensor reading 17% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
10172E 129AHU-E1Sensor CalibrationReturn Air RH Sensor reading 31% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
11172E 129AHU-E1Sensor CalibrationMixed air temperature reading 4.5˚ F. from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
12172E 129AHU-E1VFDReturn fan does not turn off when commanded off7/8/16Investigate the VFD and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
13172E 129AHU-E1Sensor CalibrationReturn air temperature reading 2.4˚ F. from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
14172E 129AHU-E1Sensor CalibrationCooling coil air temperature reading 4.1˚ F. from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
15172E 129AHU-E1Sensor CalibrationSupply Air RH Sensor reading 13% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
16172E 129AHU-E1Sensor CalibrationNo access to measure the preheat temperature for calibration.7/8/16Provide access and verify the calibration of the sensor.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
17172E 129AHU-E1Analog CommandHot water & chilled water commands from graphic do not work.7/8/16Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
18172E 129AHU-E1Analog CommandExhaust air damper command from graphic does not work.7/8/16Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
19172E 129AHU-E1DamperExhaust air damper is closed with unit running and does not operate in manual or automatic.7/8/16Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
201722A 207AHU-A1DamperNo access to damper actuator.7/8/16Provide access panelOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
211722A 207AHU-A1Sensor CalibrationSupply Air RH Sensor reading 9% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
221722A 206AHU-A2Sensor CalibrationReturn Air RH Sensor reading 5% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
231722A 206AHU-A2Sensor CalibrationMixed air temperature reading 4˚ F. from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
241722A 206AHU-A2Sensor CalibrationSupply Air RH Sensor reading 51% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
251722A 206AHU-A2Sensor CalibrationCooling coil air temperature reading 3˚ F. from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
261722A 206AHU-A2Analog CommandChilled water commands from graphic does not work.7/8/16Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
271722A 206AHU-A2DamperNo access to EA damper actuator.7/8/16Provide access panel and verify the damper operates.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
28172AHU-A3AHU-A3VFDReturn fan does not turn off when commanded off7/8/16Investigate the VFD and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
29172AHU-A3AHU-A3Sensor CalibrationReturn Air RH Sensor reading 12% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
30172AHU-A3AHU-A3Sensor CalibrationSupply Air RH Sensor reading 14% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
31172AHU-A3AHU-A3Analog CommandExhaust air damper command from graphic does not work.7/8/16Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
32172AHU-A4AHU-A4VFDReturn fan does not turn off when commanded off7/8/16Investigate the VFD and control relay then repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
33172AHU-A4AHU-A4Sensor CalibrationReturn Air RH Sensor reading 12% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
34172AHU-A4AHU-A4Sensor CalibrationMixed air temperature reading 4˚ F. from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
35172AHU-A4AHU-A4Sensor CalibrationSupply Air RH Sensor reading 30% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
36172AHU-A4AHU-A4Analog CommandOutside air damper does not operate correctly.7/8/16Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
37172AHU-A4AHU-A4Analog CommandExhaust air damper command from graphic does not work.7/8/16Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
38172AHU-B3AHU-B3Sensor CalibrationReturn Air RH Sensor reading 6% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
39172AHU-B3AHU-B3Sensor CalibrationSupply Air RH Sensor reading 14% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
40172AHU-B3AHU-B3DamperExhaust damper does not operate proportionally to command.7/8/16Adjust the linkage and verify the damper strokes fully.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
41172AHU-B3AHU-B3Static PressureStatic pressure below setpoint and supply fan and 100% speed7/8/16The fans sheaves are worn and need to be replaced.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
42172AHU-C2AHU-C2Binary CommandReturn fan shows on when it is off7/8/16Investigate the status input point and repair.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
43172AHU-C2AHU-C2Incorrect GraphicSupply fan start/stop not shown on graphic7/8/16Correct graphicOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
44172AHU-C2AHU-C2Static PressureStatic pressure below setpoint and supply fan and 100% speed7/8/16The fans sheaves are worn and need to be replaced.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
45172AHU-C2AHU-C2Sensor CalibrationReturn Air RH Sensor reading 9% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
46172AHU-C2AHU-C2Sensor CalibrationSupply Air RH Sensor reading 14% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
47172AHU-D2AHU-D2Binary CommandReturn fan shows on when it is off7/8/16Investigate the status input point and repair.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
48172AHU-D2AHU-D2Sensor CalibrationReturn Air RH Sensor reading 20% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
49172AHU-D2AHU-D2Sensor CalibrationSupply Air RH Sensor reading 7% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
50172AHU-D2AHU-D2Sensor FailedReturn air temperature sensor reads failed7/8/16Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
51172AHU-D2AHU-D2VFDSupply fan minimum speed set to 0%7/8/16Set the drive minimum speed to the motor manufactures minimum speed recommendations.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
52172AHU-D2AHU-D2DamperMixed air dampers go to 10% open and not closed during shutdown.7/8/16Verify the control programming closes the damper when the unit status is off.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
53172AHU-E3AHU-E3Sensor CalibrationReturn Air RH Sensor reading 21% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
54172AHU-E3AHU-E3Sensor CalibrationSupply Air RH Sensor reading 13% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
55172AHU-E3AHU-E3Sensor CalibrationReturn air temperature reading 3.8˚ F. from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
56172AHU-E4AHU-E4Sensor CalibrationReturn Air RH Sensor reading 37% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
57172AHU-E4AHU-E4Sensor CalibrationSupply Air RH Sensor reading 18% from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
58172AHU-E4AHU-E4Binary CommandSupply fan shows on when it is off7/8/16Investigate the status input point and repair.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
59172AHU-E4AHU-E4Sensor CalibrationCooling coil air temperature reading 4˚ F. from actual7/8/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
60172B 129AHU-B1Binary StatusThe return fan displays on when commanded off.7/11/15Investigate the status input point and repair.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
61172B 129AHU-B1ValveThe HW valve does not close off 100%. Leaking through.7/11/15Adjust the valve linkage, replace the valve seats or replace the valve.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
62172B 129AHU-B1ValveThe CHW valve does not stroke open 100%.7/11/15Adjust the valve linkage to stroke 100% with the control output.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
63172B 129AHU-B1ValveThe CHW valve does not close off 100%. Leaking through.7/11/15Adjust the valve linkage to stroke 100% with the control output.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
64172B 129AHU-B1Sequence of OperationThe OSA/EA/RA dampers do not position closed/closed/open when the fan is off.7/11/15Verify the control programming positions the dampers correctly when the unit status is off.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
65172B 129AHU-B1Sensor CalibrationMixed Air Sensor reading 6.1degf. from actual7/11/15Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
66172B 129AHU-B1Sequence of OperationThe HW valve does not lock out when economizer is disabled and cooling enabled.7/11/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
67172B 129AHU-B1Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/11/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
68172B 129AHU-B1GraphicsThe graphic does not show the SA/RA CFM differential setpoint.7/11/15Add the setpoint during the associated project.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
69172B 129AHU-B1VFDThe minimum speed of the SF/RF VFD is set to 6 hz.7/11/15Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
70172C 122AHU-C1VFDThe minimum speed of the SF/RF VFD is set to 6 hz.7/11/15Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
71172C 122AHU-C1ValveThe HW valve does not stroke closed 100%.7/11/15Adjust the valve linkage to stroke 100% with the control output.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
72172C 122AHU-C1ValveThe CHW valve does not stroke open 100%.7/11/15Adjust the valve linkage to stroke 100% with the control output.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
73172C 122AHU-C1ValveThe CHW valve does not close off 100%. Leaking through.7/11/15Adjust the valve linkage to stroke 100% with the control output.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
74172C 122AHU-C1Sensor FailedThe preheat sensor reads 0 degf. on the graphics.Recalibrate or ReplaceOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
75172C 122AHU-C1Sequence of OperationThe OSA/EA/RA dampers do not position closed/closed/open when the fan is off.7/11/15Verify the control programming positions the dampers correctly when the unit status is off.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
76172C 122AHU-C1Sequence of OperationThe HW valve does not lock out when economizer is disabled and cooling enabled.7/11/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
77172C 122AHU-C1Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/11/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
78172C 122AHU-C1GraphicsThe graphic does not show the SA/RA CFM differential setpoint.7/11/15Add the setpoint during the associated project.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
79172C 122AHU-C1Static PressureStatic pressure below setpoint and supply fan and 100% speed7/11/16Verify the fan belts are tight and the fan is operating at 100% CFM.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
80172C 122AHU-C1Sensor CalibrationThe return air temperature displayed is 3.8 degf. from measured.7/11/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
81172C 122AHU-C1Sensor CalibrationThe return air humidity displayed is 24.4% RH from measured.7/11/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
82172D 122AHU-D1VFDThe minimum speed of the SF VFD is set to 15 hz and the RF VFD is set to 6 hz.7/11/15Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
83172D 122AHU-D1Sequence of OperationThe OSA/EA/RA dampers do not position closed/closed/open when the fan is off.7/11/15Verify the control programming positions the dampers correctly when the unit status is off.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
84172D 122AHU-D1Sensor CalibrationNo access to measure the preheat temperature for calibration.7/11/15Provide access and verify the calibration of the sensor.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
85172D 122AHU-D1Sensor CalibrationThe cooling coil air temperature displayed is 2.2 degf. from measured.7/11/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
86172D 122AHU-D1Sensor CalibrationThe return air temperature displayed is 3.9 degf. from measured.7/11/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
87172D 122AHU-D1Sensor CalibrationThe return air humidity displayed is 17.2% RH from measured.7/11/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
88172D 122AHU-D1Sequence of OperationThe HW valve does not lock out when economizer is disabled and cooling enabled.7/11/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
89172D 122AHU-D1Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/11/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
90172D 122AHU-D1GraphicsThe graphic does not show the SA/RA CFM differential setpoint.7/11/15Add the setpoint during the associated project.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
91172D 122AHU-D1Static PressureStatic pressure below setpoint and supply fan and 100% speed7/11/16Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
92172E 129AHU-E1VFDThe minimum speed of the SF/RF VFD is set to 15 hz.7/11/15Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
93172E 129AHU-E1Sequence of OperationThe OSA/EA/RA dampers do not position closed/closed/open when the fan is off.7/11/15Verify the control programming positions the dampers correctly when the unit status is off.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
94172E 129AHU-E1Sequence of OperationThe HW valve does not lock out when economizer is disabled and cooling enabled.7/11/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
95172E 129AHU-E1Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/11/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
96172E 129AHU-E1Static PressureStatic pressure below setpoint and the supply fan is operating at 100% speed7/11/16The air flow is low, tighten the fan belts and resheeve if the amperage allowsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
97172E 129AHU-E1GraphicsThe graphic does not show the SA/RA CFM differential setpoint.7/11/15Add the setpoint during the associated project.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
98172E 129AHU-E2Sensor CalibrationThe return air temperature displayed is 4.5 degf. from measured.7/11/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
99172E 129AHU-E2Sensor CalibrationThe return air humidity displayed is 12.9% RH from measured.7/11/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
100172E 129AHU-E2Sensor CalibrationThe mixed air temperature displayed is 23.3 degf. from measured.7/11/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
101172E 129AHU-E2Sequence of OperationThe HW valve does not lock out when economizer is disabled and cooling enabled.7/11/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
102172E 129AHU-E2Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/11/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1031722A 207AHU-A1Sensor CalibrationThe return air temperature displayed is 8.6 degf. from measured.7/11/16Recalibrate or ReplaceOwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1041722A 207AHU-A1Sensor CalibrationNo access to measure the preheat temperature for calibration.Provide access and verify the calibration of the sensor.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1051722A 207AHU-A1Sequence of OperationThe OSA/EA/RA dampers do not position closed/closed/open when the fan is off.7/11/15Verify the control programming positions the dampers correctly when the unit status is off.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1061722A 207AHU-A1Sequence of OperationThe HW valve is commanded open during cooling.7/11/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1071722A 207AHU-A1Sequence of OperationThe HW valve does not lock out when economizer is disabled and cooling enabled.7/11/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1081722A 207AHU-A1Sequence of OperationThe chilled water valve is commanded to 100% open with the discharge air below setpoint.7/11/15Verify the control loop is operating correctly and tune the control loop.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1091722A 207AHU-A1Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/11/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1101722A 207AHU-A1GraphicsThe VAV's for AHU-A2 are under AHU-A1 Page 2 on the menu tree.7/11/15Modify the graphic menu tree for ease of navigation.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1111722A 206AHU-A2Sensor CalibrationNo access to measure the preheat temperature for calibration.7/11/16Provide access and verify the calibration of the sensor.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1121722A 206AHU-A2VFDThe minimum speed of the SF/RF VFD is set to 15 hz.7/11/15Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly.OwnerYesNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1131722A 206AHU-A2Sequence of OperationThe HW valve does not lock out when economizer is disabled and cooling enabled.7/11/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1141722A 206AHU-A2Sequence of OperationThe discharge air temperature reset is not limited at the high and low setpoints.7/11/15Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpointsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1151722A 206AHU-A2Sequence of OperationThe HW and CHW valves are both operating at 100% open with the DAT setpoint set at 50 degf. during testing.7/11/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1161722A 206AHU-A2Sequence of OperationThe CHW valve is 100% open and does not respond to DAT setpoint changes.7/11/15Verify the control sequence of operation is working properly.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
1171722A 206AHU-A2Sequence of OperationThe graphic displays the system in WINTER mode during cooling season.7/11/15Verify the control sequence of operation is working properly.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
118172E 129AHU-E1DAT SetpointDAT unable to maintain DAT SP with CHW valve at 100% open.7/16/15Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
119172E 129AHU-E2DAT SetpointDAT unable to maintain DAT SP with CHW valve at 100% open.7/16/15Investigate and repairOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
120172B 129AHU-B1Hot Water Valve OperationHot water valve is modulated to maintain discharge air setpoint, suspect MA damper or tuning issue.7/16/15Modify the control sequence to not allow heating and cooling at the same time.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
121172A PenthouseAHU-A3DA Static PressureSupply fan speed at 100% speed and cannot maintain the static pressure setpoint of 1.2 in WG.7/17/15The air flow is low, tighten the fan belts and resheeve if the amperage allowsOwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
122172All VAV Terminal UnitsAllTerminal Box Control SetpointNo space temperature setpoint reset.7/17/15There is a program modification associated with another project. The program modifications should be reviewed after the project is completed.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
123172Room 1C 101VAV-1-C2Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 72 Deg. F. Suspect reheat problem.7/17/15This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
124172Room 1D 103VAV-1-D1Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 56 Deg. F. Suspect reheat problem.7/17/15Verify the reheat valve is operational and repair as required.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
125172Room 1D 139VAV-1-D2Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 60 Deg. F. Suspect reheat problem.7/17/15Verify the reheat valve is operational and repair as required.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
126172Room C1 30VAV-1-E30Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 75 F. with 100% reheat valve and peak DAT of 62 Deg. F. Suspect reheat problem.7/17/15Verify the reheat valve is operational and repair as required.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
127172Room C1 36VAV-1-A 3Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 71 F. with 100% reheat valve and peak DAT of 60 Deg. F. Suspect reheat problem.7/17/15Verify the reheat valve is operational and repair as required.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
128172Room 1A 107VAV-1-A4Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 75 F. with 100% reheat valve and peak DAT of 62 Deg. F. Suspect reheat problem.7/17/15Verify the reheat valve is operational and repair as required.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
129172Room C1 4VAV-1-A5Terminal Box Valve and Actuator MaintenanceRoom temp above setpoint with HWV open and VAV box damper opening with no increase in air flow.7/17/15Investigate the VAV operation and repair.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
130172Room 1A 106VAV-1-A6Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 70 F. with 100% reheat valve and peak DAT of 55 Deg. F. VAV box damper at 100% open with no indication of air flow.7/17/15Investigate the VAV operation and repair.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
131172Room 1B 146VAV-1-B2Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 75 Deg. F. Suspect reheat problem.7/17/15This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
132172Room C1 13VAV-1-B4Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 75 F. with 100% reheat valve Suspect reheat problem.7/17/15Investigate the VAV operation and repair.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
133172Room C1 10AVAV-1-B7Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 71 F. with 100% reheat valve and peak DAT of 70 Deg. F. Suspect reheat problem.7/17/15This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
134172Room 1D 120VAV-1-D10Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 68 F. with 100% reheat valve and peak DAT of 78 Deg. F. Suspect reheat problem.7/17/15This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
135172Room 2A 230CVAV-2-A4Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 68 F. with 100% reheat valve and peak DAT of 70 Deg. F. Suspect reheat problem.7/17/15This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
136172Room 2C 11AVAV-2-B7Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 68 F. with 100% reheat valve and peak DAT of 73 Deg. F. Suspect reheat problem.7/17/15This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
137172Room C2 18AVAV-2-C7Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 76 F. with 100% reheat valve and peak DAT of 55 Deg. F. Suspect reheat problem.7/17/15Verify the reheat valve is operational and repair as required.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
138172Room C2 25VAV-2-D4Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 73F. with 100% reheat valve and peak DAT of 60 Deg. F. Suspect reheat problem.7/17/15This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
139172Room C1-9VAV-1-B30Terminal Box Valve and Actuator MaintenanceVAV box unable to maintain max air flow7/17/15Verify the VAV damper is opening 100%. Verify the supply fan is delivering the correct CFM. Verify the maximum VAV CFM setpoint is set to design conditions.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
140172Room C14VAV-1-A5Terminal Box Valve and Actuator MaintenanceRoom temp above setpoint with HWV open and VAV box damper opening with no increase in air flow.7/17/15Verify the VAV damper is opening 100%. Verify the supply fan is delivering the correct CFM. Verify the maximum VAV CFM setpoint is set to design conditions.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
141172Room 1A 106VAV-1-A6Terminal Box Valve and Actuator MaintenanceRoom temp below setpoint of 70 F. with 100% reheat valve and peak DAT of 55 Deg. F. VAV box damper at 100% open with no indication of air flow.7/17/15Verify the reheat valve is operational and repair as required.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.
142172Room 1C 109VAV-1-C5Terminal Box Valve and Actuator MaintenanceRoom temp above setpoint with VAV box damper at 100% with no air flow.7/17/15Verify the VAV damper is opening 100%. Verify the supply fan is delivering the correct CFM. Verify the maximum VAV CFM setpoint is set to design conditions.OwnerNoNRMA. Mercker122018Upgrade BMS, M Project 610-18-105.