36C25019B0055-007.xlsx
XLSX spreadsheet Posted
- Solicitation number
- 36C25019B0055
About this file
36C25019B0055 Marion_Issues Log_EEI_11-6-15 10232017.xlsx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25019C0295-000.docx | DOCX document | |
| 36C25019B0055-0001000.docx | DOCX document | |
| 36C25019B0055-0001001.docx | DOCX document | |
| 36C25019B0055-0001001.docx | DOCX document | |
| 36C25019B0055-0001000.docx | DOCX document | |
| 36C25019B0055-001.docx | DOCX document | |
| 36C25019B0055-008.doc | DOC document | |
| 36C25019B0055-004.pdf | ||
| 36C25019B0055-005.pdf | ||
| 36C25019B0055-002.pdf | ||
| 36C25019B0055-006.docx | DOCX document | |
| 36C25019B0055-003.pdf | ||
| 36C25019B0055-008.doc | DOC document | |
| 36C25019B0055-007.xlsx | XLSX spreadsheet | |
| 36C25019B0055-004.pdf | ||
| 36C25019B0055-001.docx | DOCX document | |
| 36C25019B0055-006.docx | DOCX document | |
| 36C25019B0055-003.pdf | ||
| 36C25019B0055-002.pdf | ||
| 36C25019B0055-005.pdf | ||
| 36C25019B0055-000.docx | DOCX document | |
| 36C25019B0055-000.docx | DOCX document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Issues Log
| Location Name: | Marion VA, Marion Indiana | Updated On: | 7/24/15 | ||||||||||||||
| Prepared By: | Engineering Economics, Inc. | Updated By: | KK | ||||||||||||||
| Issue | |||||||||||||||||
| Number | Building | ||||||||||||||||
| Number | Equipment | ||||||||||||||||
| Location | Equipment | ||||||||||||||||
| Tag | Issue | ||||||||||||||||
| Type | Issue | ||||||||||||||||
| Description | Date | ||||||||||||||||
| Entered | Recommended | ||||||||||||||||
| Corrective Action | Repair | ||||||||||||||||
| Responsibility | Simple Repair | ||||||||||||||||
| (Y/N) | Repair | ||||||||||||||||
| By | Date Repair | ||||||||||||||||
| Completed | Calculation | ||||||||||||||||
| Required | How is item planned for completion? (in-House, Credit Card, NRM, Other to be identified) | Assigned to (shop or Person) | Initials of M&O staff that performed work | Month Planned for completion | Year Planned for Completion | Actual Date Completed | Comments | ||||||||||
| 1 | 52 | Basement | HP-01 | Sequence of Operation | Compressor cycles even though room temperature is below room setpoint. | 7/17/15 | Verify the compressor staging control setpoints and the changeover valve programming is correct. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | |||
| 1 | 65 | Conference Room | HP-01 | Humidity Control | High humidity levels in space and the discharge air temperature is not cold during cooling 50-55 degf. | 7/17/15 | 1) Verify the unit is charged with the correct amount of refrigerant. |
2) Lower the fan speed to run the unit longer.
| 3) Remove the air from the water loop. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||||
| 2 | 65 | Catholic Chapel | HP-02 | Humidity Control | High humidity levels in space and the discharge air temperature is not cold during cooling 50-55 degf. | 7/17/15 | 1) Verify the unit is charged with the correct amount of refrigerant. |
2) Lower the fan speed to run the unit longer.
| 3) Remove the air from the water loop. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||||
| 3 | 65 | Protestant Chapel | HP-03 | Humidity Control | High humidity levels in space and the discharge air temperature is not cold during cooling 50-55 degf. | 7/17/15 | 1) Verify the unit is charged with the correct amount of refrigerant. |
2) Lower the fan speed to run the unit longer.
| 3) Remove the air from the water loop. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | |||||||||
| 4 | 65 | Basement | GSP 1,2,3 | Sequence of Operation | All of the ground source pumps operate when the heat pumps are not running. | 8/27/15 | Modify the pump programming to disable the ground source pumps when the heat pumps are off. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 5 | 65 | Basement | GSP 1,2,3 | Sequence of Operation | All of the ground source pumps operate when one heat pump is running. | 8/27/15 | Modify the programming to stage the source pumps to maintain the ground supply water temperature and the required flow for the number of heat pumps running. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 6 | 65 | Basement | GSP 1,2,3 | Air In The System | There is air in the ground source condenser water loop. | 8/27/15 | Add air vents to the top of the piping to bleed air from the system and then add glycol/water to fill the system. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 7 | 65 | Basement | GSP 1,2,3 | Gauges | The pump gauges are not reading correctly. | 8/27/15 | Replace the gauges. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||||||||||||
| 1 | 138 | B 001 | AHU-1 | Sensor Calibration | Supply air temperature reading 7˚ F. from actual | 7/10/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 2 | 138 | B 001 | AHU-1 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/10/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 3 | 138 | B 001 | AHU-2 | Sensor Calibration | Return Air RH Sensor reading 40% from actual | 7/10/15 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 4 | 138 | B 001 | AHU-2 | VFD | The supply fan is operator overridden from the graphics to 90% due to fan oscillation. | 7/10/15 | Tune the control loop to minimize the cycling of the fan VFD. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 5 | 138 | B 001 | AHU-2 | VFD | The return fan is operator overridden from the graphics to 70%. | 7/10/15 | Tune the control loop to minimize the cycling of the fan VFD. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 6 | 138 | B 001 | AHU-2 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/10/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 7 | 138 | B 001 | AHU-3 | Sensor Calibration | Cold deck air temperature reading 8˚ F. from actual | 7/10/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 8 | 138 | B 001 | AHU-3 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/10/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 9 | 138 | B 001 | AHU-3 | Static Pressure | Static pressure below setpoint, 0.03 iwc and supply fan and 100% speed. When the OAD is open, the static pressure increases to 1.3 iwc. | 7/8/16 | Verify the outside air minimum damper position is correct. This may be corrected when the new airflow stations are operational. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 10 | 138 | B 001 | AHU-4 | Sensor Calibration | Cold deck air temperature reading 7˚ F. from actual | 7/10/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 11 | 138 | B 001 | AHU-4 | Sensor Calibration | Return Air RH Sensor reading 43% from actual | 7/10/15 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 12 | 138 | B 001 | AHU-4 | Binary Command | Return fan shows on when it is off | 7/8/16 | Investigate and repair the status input. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 13 | 138 | B 001 | AHU-4 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/10/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 14 | 138 | B 001 | AHU-4 | VFD | The supply fan is operator overridden from the graphics to 80%. | 7/10/15 | Investigate static pressure control and return to the automatic mode of operation. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 15 | 138 | B 001 | AHU-4 | VFD | The return fan is operator overridden from the graphics to 60%. | 7/10/15 | Investigate static pressure control and return to the automatic mode of operation. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 16 | 138 | B 001 | AHU-4 | Static Pressure | Static pressure below setpoint and supply fan and 80% speed | 7/11/16 | Investigate and return to the automatic mode of operation. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 18 | 138 | B 001 | AHU-1 | DAT Setpoint | Cannot maintain DAT SP of 50 to 54 F, CHW at 100%. | 7/16/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 19 | 138 | B 001 | AHU-2 | DAT Setpoint | Cannot maintain DAT SP of 50 to 54 F, CHW at 100%. | 7/16/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 20 | 138 | B 001 | AHU-3 | DAT Setpoint | DAT close to DA SP of 50 F, CHW valve at 100%. | 7/16/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 21 | 138 | B 001 | AHU-4 | DAT Setpoint | Cannot maintain DAT SP of 50 F, DAT averages 56 F and CHW at 100%. | 7/16/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 22 | 138 | B 001 | AHU-2 | DA Static Pressure | Supply fan at 90% not meeting DAP SP. | 7/17/15 | Tune the control loop to minimize the cycling of the fan VFD. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 23 | 138 | B 001 | AHU-4 | DA Static Pressure | Supply Fan at 100% and SP between 0.4 and 1.4 in WG. | 7/17/15 | Verify the belts are tight and the CFM is correct. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 24 | 138 | Mechanical Room | BAS Controllers | System Communication Issues | Susceptible to IT communications issues. | 7/17/15 | Consider migrating to a local network instead of the campus network. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 25 | 138 | All VAV Terminal Units | All | Terminal Box Control Setpoint | No space temperature setpoint reset. | 7/17/15 | The controllers are being reprogrammed under a separate project. This should be included in that project. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 26 | 138 | Rm 106N | VAV 1-06 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 74 F. with 100% reheat valve and peak DAT of 82 Deg. F. | 7/17/15 | The heating hot water system is being reset too low to heat the AHU discharge air. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 27 | 138 | Basement | VAV B-01 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 52 Deg. F. Suspect reheat problem. | 7/17/15 | Investigate the reheat valve operation and the heating hot water temperature and repair or make setpoint changes are required.. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 28 | 138 | Basement | VAV B-02 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 52 Deg. F. Suspect reheat problem. | 7/17/15 | Investigate the reheat valve operation and the heating hot water temperature and repair or make setpoint changes are required.. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 29 | 138 | Basement | VAV B-03 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 74 F. with 100% reheat valve and peak DAT of 82 Deg. F. | 7/17/15 | The heating hot water system is being reset too low to heat the AHU discharge air. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 30 | 138 | Basement | VAV B-04 | Terminal Box Valve and Actuator Maintenance | Room temp maintaining setpoint of 73 F, but hot water reheat cycling between 30% and 100% to do so. Suspect tuning issue. | 7/17/15 | Tune the control loop as required. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 31 | 138 | Room 104S | VAV-1-03 | Terminal Box Valve and Actuator Maintenance | At max air flow the room temperature is above setpoint by up to 3 DegF. | 7/17/15 | Increase the maximum CFM flow setpoint if the VAV is large enough. Consider installing a large VAV. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 32 | 138 | Room 104N | VAV-1-04 | Terminal Box Valve and Actuator Maintenance | At max air flow and room temp above setpoint by up to 4 DegF. | 7/17/15 | Increase the maximum CFM flow setpoint if the VAV is large enough. Consider installing a large VAV. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 33 | 138 | B 001 | AHU-2 | VFD | The supply fan VFD minimum frequency is set in the drive to 6 Hz. | 8/26/15 | Verify the VFD is setup correctly for minimum frequency. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 34 | 138 | B 001 | AHU-2 | VFD | The return fan VFD maximum frequency at 100% output is 35 Hz. | 8/26/15 | Verify the VFD is setup correctly for maximum frequency. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 35 | 138 | B 001 | AHU-2 | Valve | The cooling valve is a 3 way valves and the system is controlling to a differential pressure setpoint. The differential pressure will not vary much with a three way valve and therefore the pump speed will not be reduced to save energy. | 8/26/15 | Install a balancing valve in the bypass line to reduce the water flow through the bypass line. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 36 | 138 | B 001 | AHU-2 | DA Static Pressure | The fan VFD is cycling frequently from 100% to 0% to try to maintain the duct static pressure. | 8/26/15 | Tune the control loop to minimize the cycling of the fan VFD. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 37 | 138 | B 001 | AHU-4 | Analog Command | The face and bypass damper did not respond to override commands. | 8/26/15 | Verify the correct points are displayed on the graphic. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 38 | 138 | B 001 | AHU-4 | Analog Command | The supply and return fan VFD's run at 15 Hz @ 0%, 22.7 Hz @ 50% and 60 Hz @ 100%. The VFD does not ramp linearly with the control output. | 8/26/15 | Verify the VFD is programmed to ramp linearly with the control output. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 39 | 138 | B 001 | AHU-4 | Sensor Calibration | The down duct static pressure indicates -0.14 IWC when the fan is turned off. | 8/26/15 | Verify the sensor calibration or replaced the sensor if defective. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 40 | 138 | B 001 | AHU-3 | VFD | The supply fan VFD minimum frequency is set in the drive to 6 Hz. | 8/27/15 | Verify the minimum frequency setting is correct. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 41 | 138 | B 001 | AHU-3 | VFD | The return fan VFD is overridden at the graphics and when placed in the auto mode the output ramps up and down rapidly. | 8/27/15 | Verify the control inputs are operating correctly and tune the control loop. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 42 | 138 | B 001 | AHU-3 | Static Pressure | The first floor static pressure sensor is indicating a negative pressure and is controlling the supply fan to 100% speed. | 8/27/15 | Repair or replace the sensor or wiring. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 43 | 138 | B 001 | AHU-3 | Static Pressure | When the fan is off, the second floor static pressure sensor is indicating +0.99 iwc. | 8/27/15 | Calibrated the pressure sensor or replace if defective. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 44 | 138 | B 001 | AHU-1 | Valve | The cooling valve is a 3 way valves and the system is controlling to a differential pressure setpoint. The differential pressure will not vary much with a three way valve and therefore the pump speed will not be reduced to save energy. | 8/26/15 | Install a balancing valve in the bypass line to reduce the water flow through the bypass line. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 45 | 138 | B 001 | AHU-2 | Valve | The cooling valve is a 3 way valves and the system is controlling to a differential pressure setpoint. The differential pressure will not vary much with a three way valve and therefore the pump speed will not be reduced to save energy. | 8/26/15 | Install a balancing valve in the bypass line to reduce the water flow through the bypass line. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||||||||||||
| 1 | 172 | B 129 | AHU-B1 | Sensor Calibration | Return Air RH Sensor reading 18% from actual | 7/8/15 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 2 | 172 | B 129 | AHU-B1 | Graphics | Hot water valve display is 100% open and is closed | 7/8/15 | Correct graphic | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 3 | 172 | C 122 | AHU-C1 | VFD | Return fan does not turn off when commanded off | 7/8/16 | The VFD is operating in the bypass mode. Repair the VFD and retest. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 4 | 172 | C 122 | AHU-C1 | VFD | Supply fan stays running when commanded off | 7/8/16 | The VFD is operating in the bypass mode. Repair the VFD and retest. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 5 | 172 | C 122 | AHU-C1 | Sensor Calibration | Return Air RH Sensor reading 24% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 6 | 172 | C 122 | AHU-C1 | Sensor Calibration | Preheat Temp reading 0 Deg. F. | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 8 | 172 | D 122 | AHU-D1 | VFD | Return fan does not turn off when commanded off | 7/8/16 | Investigate the VFD and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 9 | 172 | D 122 | AHU-D1 | Sensor Calibration | Return Air RH Sensor reading 17% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 10 | 172 | E 129 | AHU-E1 | Sensor Calibration | Return Air RH Sensor reading 31% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 11 | 172 | E 129 | AHU-E1 | Sensor Calibration | Mixed air temperature reading 4.5˚ F. from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 12 | 172 | E 129 | AHU-E1 | VFD | Return fan does not turn off when commanded off | 7/8/16 | Investigate the VFD and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 13 | 172 | E 129 | AHU-E1 | Sensor Calibration | Return air temperature reading 2.4˚ F. from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 14 | 172 | E 129 | AHU-E1 | Sensor Calibration | Cooling coil air temperature reading 4.1˚ F. from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 15 | 172 | E 129 | AHU-E1 | Sensor Calibration | Supply Air RH Sensor reading 13% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 16 | 172 | E 129 | AHU-E1 | Sensor Calibration | No access to measure the preheat temperature for calibration. | 7/8/16 | Provide access and verify the calibration of the sensor. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 17 | 172 | E 129 | AHU-E1 | Analog Command | Hot water & chilled water commands from graphic do not work. | 7/8/16 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 18 | 172 | E 129 | AHU-E1 | Analog Command | Exhaust air damper command from graphic does not work. | 7/8/16 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 19 | 172 | E 129 | AHU-E1 | Damper | Exhaust air damper is closed with unit running and does not operate in manual or automatic. | 7/8/16 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 20 | 172 | 2A 207 | AHU-A1 | Damper | No access to damper actuator. | 7/8/16 | Provide access panel | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 21 | 172 | 2A 207 | AHU-A1 | Sensor Calibration | Supply Air RH Sensor reading 9% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 22 | 172 | 2A 206 | AHU-A2 | Sensor Calibration | Return Air RH Sensor reading 5% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 23 | 172 | 2A 206 | AHU-A2 | Sensor Calibration | Mixed air temperature reading 4˚ F. from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 24 | 172 | 2A 206 | AHU-A2 | Sensor Calibration | Supply Air RH Sensor reading 51% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 25 | 172 | 2A 206 | AHU-A2 | Sensor Calibration | Cooling coil air temperature reading 3˚ F. from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 26 | 172 | 2A 206 | AHU-A2 | Analog Command | Chilled water commands from graphic does not work. | 7/8/16 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 27 | 172 | 2A 206 | AHU-A2 | Damper | No access to EA damper actuator. | 7/8/16 | Provide access panel and verify the damper operates. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 28 | 172 | AHU-A3 | AHU-A3 | VFD | Return fan does not turn off when commanded off | 7/8/16 | Investigate the VFD and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 29 | 172 | AHU-A3 | AHU-A3 | Sensor Calibration | Return Air RH Sensor reading 12% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 30 | 172 | AHU-A3 | AHU-A3 | Sensor Calibration | Supply Air RH Sensor reading 14% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 31 | 172 | AHU-A3 | AHU-A3 | Analog Command | Exhaust air damper command from graphic does not work. | 7/8/16 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 32 | 172 | AHU-A4 | AHU-A4 | VFD | Return fan does not turn off when commanded off | 7/8/16 | Investigate the VFD and control relay then repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 33 | 172 | AHU-A4 | AHU-A4 | Sensor Calibration | Return Air RH Sensor reading 12% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 34 | 172 | AHU-A4 | AHU-A4 | Sensor Calibration | Mixed air temperature reading 4˚ F. from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 35 | 172 | AHU-A4 | AHU-A4 | Sensor Calibration | Supply Air RH Sensor reading 30% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 36 | 172 | AHU-A4 | AHU-A4 | Analog Command | Outside air damper does not operate correctly. | 7/8/16 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 37 | 172 | AHU-A4 | AHU-A4 | Analog Command | Exhaust air damper command from graphic does not work. | 7/8/16 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 38 | 172 | AHU-B3 | AHU-B3 | Sensor Calibration | Return Air RH Sensor reading 6% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 39 | 172 | AHU-B3 | AHU-B3 | Sensor Calibration | Supply Air RH Sensor reading 14% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 40 | 172 | AHU-B3 | AHU-B3 | Damper | Exhaust damper does not operate proportionally to command. | 7/8/16 | Adjust the linkage and verify the damper strokes fully. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 41 | 172 | AHU-B3 | AHU-B3 | Static Pressure | Static pressure below setpoint and supply fan and 100% speed | 7/8/16 | The fans sheaves are worn and need to be replaced. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 42 | 172 | AHU-C2 | AHU-C2 | Binary Command | Return fan shows on when it is off | 7/8/16 | Investigate the status input point and repair. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 43 | 172 | AHU-C2 | AHU-C2 | Incorrect Graphic | Supply fan start/stop not shown on graphic | 7/8/16 | Correct graphic | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 44 | 172 | AHU-C2 | AHU-C2 | Static Pressure | Static pressure below setpoint and supply fan and 100% speed | 7/8/16 | The fans sheaves are worn and need to be replaced. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 45 | 172 | AHU-C2 | AHU-C2 | Sensor Calibration | Return Air RH Sensor reading 9% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 46 | 172 | AHU-C2 | AHU-C2 | Sensor Calibration | Supply Air RH Sensor reading 14% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 47 | 172 | AHU-D2 | AHU-D2 | Binary Command | Return fan shows on when it is off | 7/8/16 | Investigate the status input point and repair. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 48 | 172 | AHU-D2 | AHU-D2 | Sensor Calibration | Return Air RH Sensor reading 20% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 49 | 172 | AHU-D2 | AHU-D2 | Sensor Calibration | Supply Air RH Sensor reading 7% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 50 | 172 | AHU-D2 | AHU-D2 | Sensor Failed | Return air temperature sensor reads failed | 7/8/16 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 51 | 172 | AHU-D2 | AHU-D2 | VFD | Supply fan minimum speed set to 0% | 7/8/16 | Set the drive minimum speed to the motor manufactures minimum speed recommendations. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 52 | 172 | AHU-D2 | AHU-D2 | Damper | Mixed air dampers go to 10% open and not closed during shutdown. | 7/8/16 | Verify the control programming closes the damper when the unit status is off. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 53 | 172 | AHU-E3 | AHU-E3 | Sensor Calibration | Return Air RH Sensor reading 21% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 54 | 172 | AHU-E3 | AHU-E3 | Sensor Calibration | Supply Air RH Sensor reading 13% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 55 | 172 | AHU-E3 | AHU-E3 | Sensor Calibration | Return air temperature reading 3.8˚ F. from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 56 | 172 | AHU-E4 | AHU-E4 | Sensor Calibration | Return Air RH Sensor reading 37% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 57 | 172 | AHU-E4 | AHU-E4 | Sensor Calibration | Supply Air RH Sensor reading 18% from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 58 | 172 | AHU-E4 | AHU-E4 | Binary Command | Supply fan shows on when it is off | 7/8/16 | Investigate the status input point and repair. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 59 | 172 | AHU-E4 | AHU-E4 | Sensor Calibration | Cooling coil air temperature reading 4˚ F. from actual | 7/8/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 60 | 172 | B 129 | AHU-B1 | Binary Status | The return fan displays on when commanded off. | 7/11/15 | Investigate the status input point and repair. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 61 | 172 | B 129 | AHU-B1 | Valve | The HW valve does not close off 100%. Leaking through. | 7/11/15 | Adjust the valve linkage, replace the valve seats or replace the valve. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 62 | 172 | B 129 | AHU-B1 | Valve | The CHW valve does not stroke open 100%. | 7/11/15 | Adjust the valve linkage to stroke 100% with the control output. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 63 | 172 | B 129 | AHU-B1 | Valve | The CHW valve does not close off 100%. Leaking through. | 7/11/15 | Adjust the valve linkage to stroke 100% with the control output. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 64 | 172 | B 129 | AHU-B1 | Sequence of Operation | The OSA/EA/RA dampers do not position closed/closed/open when the fan is off. | 7/11/15 | Verify the control programming positions the dampers correctly when the unit status is off. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 65 | 172 | B 129 | AHU-B1 | Sensor Calibration | Mixed Air Sensor reading 6.1degf. from actual | 7/11/15 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 66 | 172 | B 129 | AHU-B1 | Sequence of Operation | The HW valve does not lock out when economizer is disabled and cooling enabled. | 7/11/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 67 | 172 | B 129 | AHU-B1 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/11/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 68 | 172 | B 129 | AHU-B1 | Graphics | The graphic does not show the SA/RA CFM differential setpoint. | 7/11/15 | Add the setpoint during the associated project. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 69 | 172 | B 129 | AHU-B1 | VFD | The minimum speed of the SF/RF VFD is set to 6 hz. | 7/11/15 | Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 70 | 172 | C 122 | AHU-C1 | VFD | The minimum speed of the SF/RF VFD is set to 6 hz. | 7/11/15 | Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 71 | 172 | C 122 | AHU-C1 | Valve | The HW valve does not stroke closed 100%. | 7/11/15 | Adjust the valve linkage to stroke 100% with the control output. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 72 | 172 | C 122 | AHU-C1 | Valve | The CHW valve does not stroke open 100%. | 7/11/15 | Adjust the valve linkage to stroke 100% with the control output. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 73 | 172 | C 122 | AHU-C1 | Valve | The CHW valve does not close off 100%. Leaking through. | 7/11/15 | Adjust the valve linkage to stroke 100% with the control output. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 74 | 172 | C 122 | AHU-C1 | Sensor Failed | The preheat sensor reads 0 degf. on the graphics. | Recalibrate or Replace | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | |||
| 75 | 172 | C 122 | AHU-C1 | Sequence of Operation | The OSA/EA/RA dampers do not position closed/closed/open when the fan is off. | 7/11/15 | Verify the control programming positions the dampers correctly when the unit status is off. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 76 | 172 | C 122 | AHU-C1 | Sequence of Operation | The HW valve does not lock out when economizer is disabled and cooling enabled. | 7/11/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 77 | 172 | C 122 | AHU-C1 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/11/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 78 | 172 | C 122 | AHU-C1 | Graphics | The graphic does not show the SA/RA CFM differential setpoint. | 7/11/15 | Add the setpoint during the associated project. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 79 | 172 | C 122 | AHU-C1 | Static Pressure | Static pressure below setpoint and supply fan and 100% speed | 7/11/16 | Verify the fan belts are tight and the fan is operating at 100% CFM. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 80 | 172 | C 122 | AHU-C1 | Sensor Calibration | The return air temperature displayed is 3.8 degf. from measured. | 7/11/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 81 | 172 | C 122 | AHU-C1 | Sensor Calibration | The return air humidity displayed is 24.4% RH from measured. | 7/11/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 82 | 172 | D 122 | AHU-D1 | VFD | The minimum speed of the SF VFD is set to 15 hz and the RF VFD is set to 6 hz. | 7/11/15 | Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 83 | 172 | D 122 | AHU-D1 | Sequence of Operation | The OSA/EA/RA dampers do not position closed/closed/open when the fan is off. | 7/11/15 | Verify the control programming positions the dampers correctly when the unit status is off. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 84 | 172 | D 122 | AHU-D1 | Sensor Calibration | No access to measure the preheat temperature for calibration. | 7/11/15 | Provide access and verify the calibration of the sensor. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 85 | 172 | D 122 | AHU-D1 | Sensor Calibration | The cooling coil air temperature displayed is 2.2 degf. from measured. | 7/11/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 86 | 172 | D 122 | AHU-D1 | Sensor Calibration | The return air temperature displayed is 3.9 degf. from measured. | 7/11/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 87 | 172 | D 122 | AHU-D1 | Sensor Calibration | The return air humidity displayed is 17.2% RH from measured. | 7/11/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 88 | 172 | D 122 | AHU-D1 | Sequence of Operation | The HW valve does not lock out when economizer is disabled and cooling enabled. | 7/11/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 89 | 172 | D 122 | AHU-D1 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/11/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 90 | 172 | D 122 | AHU-D1 | Graphics | The graphic does not show the SA/RA CFM differential setpoint. | 7/11/15 | Add the setpoint during the associated project. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 91 | 172 | D 122 | AHU-D1 | Static Pressure | Static pressure below setpoint and supply fan and 100% speed | 7/11/16 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 92 | 172 | E 129 | AHU-E1 | VFD | The minimum speed of the SF/RF VFD is set to 15 hz. | 7/11/15 | Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 93 | 172 | E 129 | AHU-E1 | Sequence of Operation | The OSA/EA/RA dampers do not position closed/closed/open when the fan is off. | 7/11/15 | Verify the control programming positions the dampers correctly when the unit status is off. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 94 | 172 | E 129 | AHU-E1 | Sequence of Operation | The HW valve does not lock out when economizer is disabled and cooling enabled. | 7/11/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 95 | 172 | E 129 | AHU-E1 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/11/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 96 | 172 | E 129 | AHU-E1 | Static Pressure | Static pressure below setpoint and the supply fan is operating at 100% speed | 7/11/16 | The air flow is low, tighten the fan belts and resheeve if the amperage allows | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 97 | 172 | E 129 | AHU-E1 | Graphics | The graphic does not show the SA/RA CFM differential setpoint. | 7/11/15 | Add the setpoint during the associated project. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 98 | 172 | E 129 | AHU-E2 | Sensor Calibration | The return air temperature displayed is 4.5 degf. from measured. | 7/11/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 99 | 172 | E 129 | AHU-E2 | Sensor Calibration | The return air humidity displayed is 12.9% RH from measured. | 7/11/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 100 | 172 | E 129 | AHU-E2 | Sensor Calibration | The mixed air temperature displayed is 23.3 degf. from measured. | 7/11/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 101 | 172 | E 129 | AHU-E2 | Sequence of Operation | The HW valve does not lock out when economizer is disabled and cooling enabled. | 7/11/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 102 | 172 | E 129 | AHU-E2 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/11/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 103 | 172 | 2A 207 | AHU-A1 | Sensor Calibration | The return air temperature displayed is 8.6 degf. from measured. | 7/11/16 | Recalibrate or Replace | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 104 | 172 | 2A 207 | AHU-A1 | Sensor Calibration | No access to measure the preheat temperature for calibration. | Provide access and verify the calibration of the sensor. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | |||
| 105 | 172 | 2A 207 | AHU-A1 | Sequence of Operation | The OSA/EA/RA dampers do not position closed/closed/open when the fan is off. | 7/11/15 | Verify the control programming positions the dampers correctly when the unit status is off. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 106 | 172 | 2A 207 | AHU-A1 | Sequence of Operation | The HW valve is commanded open during cooling. | 7/11/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 107 | 172 | 2A 207 | AHU-A1 | Sequence of Operation | The HW valve does not lock out when economizer is disabled and cooling enabled. | 7/11/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 108 | 172 | 2A 207 | AHU-A1 | Sequence of Operation | The chilled water valve is commanded to 100% open with the discharge air below setpoint. | 7/11/15 | Verify the control loop is operating correctly and tune the control loop. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 109 | 172 | 2A 207 | AHU-A1 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/11/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 110 | 172 | 2A 207 | AHU-A1 | Graphics | The VAV's for AHU-A2 are under AHU-A1 Page 2 on the menu tree. | 7/11/15 | Modify the graphic menu tree for ease of navigation. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 111 | 172 | 2A 206 | AHU-A2 | Sensor Calibration | No access to measure the preheat temperature for calibration. | 7/11/16 | Provide access and verify the calibration of the sensor. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 112 | 172 | 2A 206 | AHU-A2 | VFD | The minimum speed of the SF/RF VFD is set to 15 hz. | 7/11/15 | Verify the minimum speed allowable for the motor with the motor manufacture and set the VFD accordingly. | Owner | Yes | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 113 | 172 | 2A 206 | AHU-A2 | Sequence of Operation | The HW valve does not lock out when economizer is disabled and cooling enabled. | 7/11/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 114 | 172 | 2A 206 | AHU-A2 | Sequence of Operation | The discharge air temperature reset is not limited at the high and low setpoints. | 7/11/15 | Modify the setpoint reset programming to limit the calculated setpoint at the high and low setpoints | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 115 | 172 | 2A 206 | AHU-A2 | Sequence of Operation | The HW and CHW valves are both operating at 100% open with the DAT setpoint set at 50 degf. during testing. | 7/11/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 116 | 172 | 2A 206 | AHU-A2 | Sequence of Operation | The CHW valve is 100% open and does not respond to DAT setpoint changes. | 7/11/15 | Verify the control sequence of operation is working properly. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 117 | 172 | 2A 206 | AHU-A2 | Sequence of Operation | The graphic displays the system in WINTER mode during cooling season. | 7/11/15 | Verify the control sequence of operation is working properly. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 118 | 172 | E 129 | AHU-E1 | DAT Setpoint | DAT unable to maintain DAT SP with CHW valve at 100% open. | 7/16/15 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 119 | 172 | E 129 | AHU-E2 | DAT Setpoint | DAT unable to maintain DAT SP with CHW valve at 100% open. | 7/16/15 | Investigate and repair | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 120 | 172 | B 129 | AHU-B1 | Hot Water Valve Operation | Hot water valve is modulated to maintain discharge air setpoint, suspect MA damper or tuning issue. | 7/16/15 | Modify the control sequence to not allow heating and cooling at the same time. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 121 | 172 | A Penthouse | AHU-A3 | DA Static Pressure | Supply fan speed at 100% speed and cannot maintain the static pressure setpoint of 1.2 in WG. | 7/17/15 | The air flow is low, tighten the fan belts and resheeve if the amperage allows | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 122 | 172 | All VAV Terminal Units | All | Terminal Box Control Setpoint | No space temperature setpoint reset. | 7/17/15 | There is a program modification associated with another project. The program modifications should be reviewed after the project is completed. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 123 | 172 | Room 1C 101 | VAV-1-C2 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 72 Deg. F. Suspect reheat problem. | 7/17/15 | This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 124 | 172 | Room 1D 103 | VAV-1-D1 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 56 Deg. F. Suspect reheat problem. | 7/17/15 | Verify the reheat valve is operational and repair as required. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 125 | 172 | Room 1D 139 | VAV-1-D2 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 60 Deg. F. Suspect reheat problem. | 7/17/15 | Verify the reheat valve is operational and repair as required. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 126 | 172 | Room C1 30 | VAV-1-E30 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 75 F. with 100% reheat valve and peak DAT of 62 Deg. F. Suspect reheat problem. | 7/17/15 | Verify the reheat valve is operational and repair as required. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 127 | 172 | Room C1 36 | VAV-1-A 3 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 71 F. with 100% reheat valve and peak DAT of 60 Deg. F. Suspect reheat problem. | 7/17/15 | Verify the reheat valve is operational and repair as required. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 128 | 172 | Room 1A 107 | VAV-1-A4 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 75 F. with 100% reheat valve and peak DAT of 62 Deg. F. Suspect reheat problem. | 7/17/15 | Verify the reheat valve is operational and repair as required. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 129 | 172 | Room C1 4 | VAV-1-A5 | Terminal Box Valve and Actuator Maintenance | Room temp above setpoint with HWV open and VAV box damper opening with no increase in air flow. | 7/17/15 | Investigate the VAV operation and repair. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 130 | 172 | Room 1A 106 | VAV-1-A6 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 70 F. with 100% reheat valve and peak DAT of 55 Deg. F. VAV box damper at 100% open with no indication of air flow. | 7/17/15 | Investigate the VAV operation and repair. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 131 | 172 | Room 1B 146 | VAV-1-B2 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 72 F. with 100% reheat valve and peak DAT of 75 Deg. F. Suspect reheat problem. | 7/17/15 | This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 132 | 172 | Room C1 13 | VAV-1-B4 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 75 F. with 100% reheat valve Suspect reheat problem. | 7/17/15 | Investigate the VAV operation and repair. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 133 | 172 | Room C1 10A | VAV-1-B7 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 71 F. with 100% reheat valve and peak DAT of 70 Deg. F. Suspect reheat problem. | 7/17/15 | This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 134 | 172 | Room 1D 120 | VAV-1-D10 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 68 F. with 100% reheat valve and peak DAT of 78 Deg. F. Suspect reheat problem. | 7/17/15 | This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 135 | 172 | Room 2A 230C | VAV-2-A4 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 68 F. with 100% reheat valve and peak DAT of 70 Deg. F. Suspect reheat problem. | 7/17/15 | This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 136 | 172 | Room 2C 11A | VAV-2-B7 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 68 F. with 100% reheat valve and peak DAT of 73 Deg. F. Suspect reheat problem. | 7/17/15 | This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 137 | 172 | Room C2 18A | VAV-2-C7 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 76 F. with 100% reheat valve and peak DAT of 55 Deg. F. Suspect reheat problem. | 7/17/15 | Verify the reheat valve is operational and repair as required. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 138 | 172 | Room C2 25 | VAV-2-D4 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 73F. with 100% reheat valve and peak DAT of 60 Deg. F. Suspect reheat problem. | 7/17/15 | This may be caused by the heating hot water reset program lowering the heating hot water setpoint to low. Raise the low limit of the heating hot water setpoint and verify the setpoint program limits the setpoints. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 139 | 172 | Room C1-9 | VAV-1-B30 | Terminal Box Valve and Actuator Maintenance | VAV box unable to maintain max air flow | 7/17/15 | Verify the VAV damper is opening 100%. Verify the supply fan is delivering the correct CFM. Verify the maximum VAV CFM setpoint is set to design conditions. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 140 | 172 | Room C14 | VAV-1-A5 | Terminal Box Valve and Actuator Maintenance | Room temp above setpoint with HWV open and VAV box damper opening with no increase in air flow. | 7/17/15 | Verify the VAV damper is opening 100%. Verify the supply fan is delivering the correct CFM. Verify the maximum VAV CFM setpoint is set to design conditions. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 141 | 172 | Room 1A 106 | VAV-1-A6 | Terminal Box Valve and Actuator Maintenance | Room temp below setpoint of 70 F. with 100% reheat valve and peak DAT of 55 Deg. F. VAV box damper at 100% open with no indication of air flow. | 7/17/15 | Verify the reheat valve is operational and repair as required. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. | ||
| 142 | 172 | Room 1C 109 | VAV-1-C5 | Terminal Box Valve and Actuator Maintenance | Room temp above setpoint with VAV box damper at 100% with no air flow. | 7/17/15 | Verify the VAV damper is opening 100%. Verify the supply fan is delivering the correct CFM. Verify the maximum VAV CFM setpoint is set to design conditions. | Owner | No | NRM | A. Mercker | 12 | 2018 | Upgrade BMS, M Project 610-18-105. |