2019_01_03_-_responses.pdf

PDF 51 KB Posted

Attached to
Replace SICU Curtainwall (VA-18-00160141) 541-19-501 Federal contract opportunity
Solicitation number
36C25019B0002
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25019B0002 0003 2019 01 03 - responses.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Replace SICU Curtainwall (VA-18-00160141) 541-19-501, newest first.
File Type Posted
36C25019B0002_0003.docx DOCX document
Photo_2110.jpg JPG image
Attachment_1_-_VA_responses_-_bidding_RFIs.pdf PDF
Photo_2115.jpg JPG image
36C25019B0002_0002.docx DOCX document
Attachment_2_-_Addendum_01.pdf PDF
2nd_Floor_SICU_Stone_Sill_3_IMG_0143.jpg JPG image
Site_Visit_Sign_In_Sheet.pdf PDF
2nd_Floor_SICU_Stone_Sill_2_IMG_0144.jpg JPG image
36C25019B0002_0001.docx DOCX document
2nd_Floor_SICU_Stone_Sill_IMG_0142.jpg JPG image
36C25019B0002-004.pdf PDF
36C25019B0002-005.pdf PDF
36C25019B0002-001.docx DOCX document
36C25019B0002-006.docx DOCX document
36C25019B0002-002.pdf PDF
36C25019B0002-003.pdf PDF
36C25019B0002-000.docx DOCX document
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Replace Surgery Curtainwall Project 541-19-501 Bidding RFI’s

1. Should the contractor be required to remove all existing safing and start with a new UL System Design in order to achieve the specified fire-rating? What is the fire-rating of the existing floor?

VA Response: The fire rating of the existing floor-ceiling assembly is 2 hour, as indicated on Drawing X.1. Contractor shall provide a rated assembly that attains the 2 hour rating. During the submittal process, contractor is to submit a UL Design specific to their curtain wall assembly, for review by the Architect. Contractor shall include in their bid all work necessary to achieve the required 2 hour rating.

2. Is the roof assembly fire rated? If so, should there be a fire-rated UL System installed at the top of the curtainwall at the roof assembly?

VA RESPONSE: The fire rating of the roof assembly is 1 hour, as indicated on Drawing X.1.

Contractor shall provide a rated assembly that attains the 1 hour rating. (see also the response to question 1 above regarding the UL Design.)