REQUEST FOR INFORMATION (RFI)
36C25018B0461
PROJECT NUMBER: 610-16-105 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Upgrade Primary Loop
PROJECT LOCATION:
Department of Veterans Affairs VA Northern Indiana HCS 1700 E. 38th St.
Marion, IN 46953
TO:
Felecia Beamen, Contracting Officer Department of Veterans Affairs NCO10 West Contracting Office 8888 Keystone Crossing, Suite 1100 Indianapolis, IN 46240 Felecia.beamen@va.gov
RFI NO.: 4 DATE: 07 June 2018 SPEC/DWG. REFERENCE(s):
ED-100, Notes 7 - 11
REPLY NEEDED BY:
INFORMATION NEEDED:
1. ED100 - Notes 7-11 detail the breakers needed to fit existing. 138.ED100 - Notes 3-6 detail the breakers to fit existing, but they don't say who is the manufacturer for panel EEDP (Note 3). What is the IAC rating for the replacement breakers?
REPLY:
RFIs will be answered by amendment(s).
REPLY FROM:
DATE:
ATTACHMENTS:
COPY TO:
SUBMITTED BY: Proven Techniques Applied, LLC CITY/STATE: Cantonment, Fl
PHONE: 850-791-1853
Note 3 on sheet 138.ED100 indicates that panel EEDP is manufactured by FPE.
The IAC rating for replacement breakers 10kA for 120/208V or 120/240V and 14kA for 277/480V breakers.
RFI 15