REQUEST FOR INFORMATION (RFI)
36C25018B0461
PROJECT NUMBER: 610-16-105 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Upgrade Primary Loop
PROJECT LOCATION:
Department of Veterans Affairs VA Northern Indiana HCS 1700 E. 38th St.
Marion, IN 46953
TO:
Felecia Beamen, Contracting Officer Department of Veterans Affairs NCO10 West Contracting Office 8888 Keystone Crossing, Suite 1100 Indianapolis, IN 46240 Felecia.beamen@va.gov
RFI NO.: 3 DATE: 07 June 2018 SPEC/DWG. REFERENCE(s):
Sheet ED001, Note 7,8,9,10 and 11 Sheet 138.ED100, Notes 3,4,5,6
REPLY NEEDED BY:
INFORMATION NEEDED:
1. The information provided on the plans does not give all of the information needed to provide accurate pricing for the breakers. The plans state to provide electronic trip breakers with adjustable settings to replace existing breakers in FPE, SQ D and GE panels and they state only the type of panel existing. In some cases we know there is not an electronic trip breaker available to go into the panels listed. For example Federal Pacific no longer makes a panelboard or breaker and never made an electronic trip breaker. We need to know the manufacturer and catalog number of the existing breakers to properly determine if an electronic trip breaker is available to replace the existing and also what AIC rating is required per breaker.
SUBMITTED BY: Proven Techniques Applied, LLC CITY/STATE: Cantonment, Fl
PHONE: 850-791-1853
Manufacturers and panel types have been provided for all panels with breakers to be replaced.
The AIC ratings for breakers to be replaced shall be as follows:
120/208V or 120/240V AIC = 10kA 277/480V AIC = 14kA.
RFI 14
REPLY:
RFIs will be answered by amendment(s).
REPLY FROM:
DATE:
ATTACHMENTS:
COPY TO: