36C25018B0461-0002012.pdf

PDF 20 KB Posted

Attached to
Upgrade Primary Loop 610-16-105 Federal contract opportunity
Solicitation number
36C25018B0461
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25018B0461 0002 RFI 14 - VADi.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Upgrade Primary Loop 610-16-105, newest first.
File Type Posted
36C25018B0461-0005000.docx DOCX document
36C25018B0461-0004003.pdf PDF
36C25018B0461-0004005.pdf PDF
36C25018B0461-0004006.pdf PDF
36C25018B0461-0004000.docx DOCX document
36C25018B0461-0004004.pdf PDF
36C25018B0461-0004002.pdf PDF
36C25018B0461-0004001.pdf PDF
36C25018B0461-0004007.doc DOC document
36C25018B0461-0003001.pdf PDF
36C25018B0461-0003000.docx DOCX document
36C25018B0461-0002008.pdf PDF
36C25018B0461-0002007.pdf PDF
36C25018B0461-0002001.pdf PDF
36C25018B0461-0002019.pdf PDF
36C25018B0461-0002011.pdf PDF
36C25018B0461-0002022.pdf PDF
36C25018B0461-0002006.pdf PDF
36C25018B0461-0002003.pdf PDF
36C25018B0461-0002004.pdf PDF
36C25018B0461-0002015.pdf PDF
36C25018B0461-0002020.pdf PDF
36C25018B0461-0002014.pdf PDF
36C25018B0461-0002002.pdf PDF
36C25018B0461-0002010.pdf PDF
36C25018B0461-0002018.pdf PDF
36C25018B0461-0002005.pdf PDF
36C25018B0461-0002016.pdf PDF
36C25018B0461-0002017.pdf PDF
36C25018B0461-0002000.docx DOCX document
36C25018B0461-0002009.pdf PDF
36C25018B0461-0002021.pdf PDF
36C25018B0461-0002013.pdf PDF
36C25018B0461-00001001.pdf PDF
36C25018B0461-00001002.pdf PDF
36C25018B0461-00001000.docx DOCX document
36C25018B0461-007.doc DOC document
36C25018B0461-004.pdf PDF
36C25018B0461-003.pdf PDF
36C25018B0461-005.docx DOCX document
36C25018B0461-009.xlsx XLSX spreadsheet
36C25018B0461-008.docx DOCX document
36C25018B0461-002.pdf PDF
36C25018B0461-006.docx DOCX document
36C25018B0461-000.docx DOCX document
Show all 45

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION (RFI)

36C25018B0461

PROJECT NUMBER: 610-16-105 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Upgrade Primary Loop

PROJECT LOCATION:

Department of Veterans Affairs VA Northern Indiana HCS 1700 E. 38th St.

Marion, IN 46953

TO:

Felecia Beamen, Contracting Officer Department of Veterans Affairs NCO10 West Contracting Office 8888 Keystone Crossing, Suite 1100 Indianapolis, IN 46240 Felecia.beamen@va.gov

RFI NO.: 3 DATE: 07 June 2018 SPEC/DWG. REFERENCE(s):

Sheet ED001, Note 7,8,9,10 and 11 Sheet 138.ED100, Notes 3,4,5,6

REPLY NEEDED BY:

INFORMATION NEEDED:

1. The information provided on the plans does not give all of the information needed to provide accurate pricing for the breakers. The plans state to provide electronic trip breakers with adjustable settings to replace existing breakers in FPE, SQ D and GE panels and they state only the type of panel existing. In some cases we know there is not an electronic trip breaker available to go into the panels listed. For example Federal Pacific no longer makes a panelboard or breaker and never made an electronic trip breaker. We need to know the manufacturer and catalog number of the existing breakers to properly determine if an electronic trip breaker is available to replace the existing and also what AIC rating is required per breaker.

SUBMITTED BY: Proven Techniques Applied, LLC CITY/STATE: Cantonment, Fl

PHONE: 850-791-1853

Manufacturers and panel types have been provided for all panels with breakers to be replaced.

The AIC ratings for breakers to be replaced shall be as follows:

120/208V or 120/240V AIC = 10kA 277/480V AIC = 14kA.

RFI 14

REPLY:

RFIs will be answered by amendment(s).

REPLY FROM:

DATE:

ATTACHMENTS:

COPY TO: