Attachment A Questions and Answers.pdf
PDF 124 KB Posted
- Attached to
- 4410--6-Month Deaerator Tank Rental
- Solicitation number
- 36C24824Q1454
About this file
This document contains the Questions and Answers (Q&A) for Request for Quote (RFQ) 36C24824Q1454 0001 for a 6-Month Deaerator Tank Rental at the Bay Pines VA Medical Center. The key details are:
The solicitation is for the rental of a 72,000 PPH Deaerator tank, including delivery, installation, start-up, and maintenance. The contractor must provide all necessary materials, labor, and equipment. The deaerator must be compatible with the existing Supervisory Controls and Data Acquisition (SCADA) system. Delivery is required within 90 days of order receipt, and the contract term is 6 months. The solicitation is set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB), with a NAICS code of 532490 and a $40 million size standard. Quotes must be submitted by August 12, 2024 at 12:00 PM EST to the Contracting Officer, Lakiesha Anderson. The Q&A addresses technical details such as the location, pipe sizes, and fittings for the temporary bypass tank.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment B Boiler Room Pictures.pdf | ||
| 36C24824Q1454 0001.docx | DOCX document | |
| RFQ 36C24824Q1454 6 Month Deaerator Tank Rental.pdf | ||
| Statement of Work 6 Month Deaerator Tank Rental.pdf | ||
| 36C24824Q1454.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment A
RFQ 36C24824Q1454 0001
Questions and Answers
1. How far from the current system will the temporary bypass tank be installed?
Answer: There is space for the temporary to be in the plant within 5-10ft of the current DA tank.
The connections for water and steam are within about 15-20 ft of that location as they are on the back side of the current DA Tank.
2. What types of pipe connections/size are currently on the preexisting deaerator tank on the inflow and outflow side? for example victaulic, bauer, flanged, or camlock connections.
Answer: All connections are 8 hole flanged. 3in pipe for the water and 2 in for the steam. This answers questions 2 and 3.
3. What are the current sizes/diameter of pipes currently connected to the deaerator tank? for example 2" or 3" pipes
Answer: SEE ABOVE
4. What type of fitting/pipe connection will we have access to for the bypass for the inflow and outflow (if they are different from above)?
Answer: No special fittings other than listed above should be needed. However, for the LP side, the secondary flange is 4”