36C24820Q0471-020.xlsx
XLSX spreadsheet Posted
- Attached to
- H342--FY20: Fire Suppression Testing Federal contract opportunity
- Solicitation number
- 36C24820Q0471
About this file
36C24820Q0471 Fire Suppression Testing Nov 2018 SKJ.xlsx
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24820Q0471-022.pdf | ||
| 36C24820Q0471-014.pdf | ||
| 36C24820Q0471-015.pdf | ||
| 36C24820Q0471-019.pdf | ||
| 36C24820Q0471-017.pdf | ||
| 36C24820Q0471-013.docx | DOCX document | |
| 36C24820Q0471-016.pdf | ||
| 36C24820Q0471-021.pdf | ||
| 36C24820Q0471-023.pdf | ||
| 36C24820Q0471-018.pdf | ||
| 36C24820Q0471-000.docx | DOCX document | |
| 36C24820Q0471-001.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Main Bldg
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| 6TH FLOOR, OUTSIDE OF STAIRWELL 5, MECH ROOM, TOP LANDING | 2" BALL VALVE W/ BUILT IN TAMPER SWITCH, NOT WIRED UP | |||
| 5TH FLOOR, E WING, STAIRWELL 6 | WATER FLOW SWITCH L7M33 DOES NOT REPORT TO FIRE ALARM PANEL DURING WATER FLOW | |||
| 5TH FLOOR, A WING, STAIRWELL 4 | TAMPER SWITCH #103 COMES IN AS AN ALARM | |||
| 4TH FLOOR, E WING, STAIRWELL 5 | TAMPER SWITCH ZONE 4-F REPORTS TO FIRE ALARM PANEL AS WATER FLOW ALARM | |||
| 4TH FLOOR, E WING, STAIRWELL 5 | WATER FLOW SWITCH ZONE 4-F REPORTS TO FIRE ALARM PANEL AS TAMPER SUPERVISORY | |||
| 2ND FLOOR, E WING, STAIRWELL 5 | ZONE 2-F TAMPER AND WATER FLOW SWITCHES DID NOT REPORT | |||
| 2ND FLOOR, E WING, STAIRWELL 5 | ZONE 2-E TAMPER SWITCH #73 AND WATER FLOW SWITCH #74 DID NOT REPORT TO FIRE ALARM PANEL | (door stop) | ||
| 2ND FLOOR, A WING, STAIRWELL 1 | FIRE SPRINKLER SYSTEM IS OFF DUE TO AREA BEING UNDER CONSTRUCTION AT THE TIME OF INSPECTION | |||
| 1ST FLOOR, E WING, STAIRWELL 5 | ZONE 1-H TAMPER SWITCH #97 AND WATER FLOW SWITCH #96 DO NOT REPORT TO FIRE ALARM PANEL | |||
| 1ST FLOOR, E WING, STAIRWELL 5 | ZONE 1-I TAMPER SWITCH #91 AND WATER FLOW SWITCH #90 DO NOT REPORT TO FIRE ALARM PANEL | |||
| 1ST FLOOR, F WING, STAIRWELL 7 | TAMPER SWITCH #59 AND WATER FLOW SWITCH #60 DO NOT REPORT TO FIRE ALARM PANEL | |||
| 1ST FLOOR, G WING, STAIRWELL 8 | TAMPER SWITCH #20 AND WATER FLOW SWITCH #19 DO NOT REPORT TO FIRE ALARM PANEL | |||
| 1ST FLOOR, A WING, STAIRWELL 1 | TAMPER SWITCH #68 REPORTS TO FIRE ALARM PANEL AS ALARM | |||
| BASEMENT FLOOR, E WING, ROOM EB 60-1 | TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL | |||
| BASEMENT FLOOR, B WING, IN CORRIDOR ABOVE CEILING AT B041-1 OUTSIDE RETAIL STORE | TAMPER SWITCH IS NOT WIRED UP | |||
| BASEMENT FLOOR, B WING, IN CORRIDOR ABOVE CEILING AT B041-1 OUTSIDE RETAIL STORE | SYSTEM GAUGE IS OVER 5 YEARS OLD | |||
| BASEMENT FLOOR, E WING, STAIRWELL 6 AT LOADING DOCK | ANTIFREEZE SYSTEM IS NOT INSTALLED CORRECTLY | |||
| BASEMENT FLOOR, E WING, STAIRWELL 6 AT LOADING DOCK | CANNOT TEST FLOW SWITCH WITHOUT DISCHARGING ANTI-FREEZE SOLUTION. TESTED FLOW SWITCH MANUALLY. | |||
| BASEMENT FLOOR, E WING, FIRE PUMP ROOM | GAUGE ON SUCTION SIDE OF FIRE PUMP IS NOT A SUCTION GAUGE 0-30 | |||
| BASEMENT FLOOR, E WING, FIRE PUMP ROOM | BACKFLOW PREVENTER IS NOT A RP | |||
| BASEMENT FLOOR, E WING, FIRE PUMP ROOM | NO GAUGE BEFORE THE #1 CHECK VALVE ON FIRE PROTECTION BACKFLOW | |||
| BASEMENT FLOOR, E WING, MECHANICAL ROOM/BOILER ROOM | 6" BUTTERFLY CONTROL VALVE UP HIGH AT ROLL-UP-DOOR IS BROKEN IN THE OPEN POSITION | |||
| BASEMENT FLOOR, E WING, MECHANICAL ROOM/BOILER ROOM | ANTI-FREEZE SYSTEM IN THE CORNER UP HIGH - CONTROL VALVE NEEDS TO BE CHAINED AND LOCKED | |||
| BASEMENT FLOOR, E WING, MECHANICAL ROOM/BOILER ROOM | SYSTEM ON THE BACK WALL OF THE FIRE PUMP ROOM AT EXIT DOOR - ONE SYSTEM GAUGE IS 5 YEARS OLD AND TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL | |||
| BASEMENT FLOOR, E WING, STAIRWELL 7, CRAWL SPACE, COLUMN H17 | 4" OS&Y VALVE NEEDS TO BE CHAINED AND LOCKED IN THE OPEN POSITION | |||
| BASEMENT FLOOR, E WING, STAIRWELL 7, CRAWL SPACE, COLUMN H14 | 4" OS&Y VALVE NEEDS TO BE CHAINED AND LOCKED IN THE OPEN POSITION | |||
| BASEMENT FLOOR, E WING, NORTH OF STAIRWELL 4 AND NORTH OF COLUMN B-13 | ONE 6" BUTTERFLY CONTROL VALVE TAMPER SWITCH NOT WIRED UP | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN J2 | 2 1/2" OS&Y TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL AND VALVE IS LEAKING AT FLANGE | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN J2 | 4" OS&Y VALVE TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN F5 | 2" OS&Y TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN F5 | WATER FLOW SWITCH DOES NOT REPORT TO FIRE ALARM PANEL | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN F5 | 6" OS&Y VALVE IS CLOSED AT TIME OF INSPECTION | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN K5 | 4" OS&Y VALVE DOES NOT REPORT TO FIRE ALARM PANEL | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE AT STAIRWELL 1 AT COLUMN F4 | BOTH 4" OS&Y VALVE TAMPER SWITCHES DO NOT REPORT TO FIRE ALARM PANEL | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE EAST OF GRAPHIC CONTROL ROOM AT COLUMN P11 | 6" OS&Y VALVE AND 4" OS&Y VALVE TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN K11 | TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL | |||
| BASEMENT FLOOR, E WING, CRAWL SPACE WEST OF COLUMN K11 | TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL |
| November 2018 | Malcolm Randall VAMC |
| Semi Annual Fire Suppression Testing | Main Building |
Bed Tower
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| 4TH FLOOR, STAIRWELL 10 | WATER FLOW SWITCH HAS BAD DIAPHRAM | |||
| 2ND FLOOR, STAIRWELL 10 | WATER FLOW SWITCH HAS BAD DIAPHRAM | |||
| OUTSIDE PIV, NORTH SIDE OF BUILDING | TAMPER SWITCH IS BROKEN |
| November 2018 | Malcolm Randall VAMC |
| Semi Annual Fire Suppression Testing | Bed Tower |
T11 TRAILER
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| RISER ROOM | BOTH TAMPER SWITCHES DO NOT REPORT TO MAIN FIRE ALARM PANEL | |||
| RISER ROOM | PIV - WHEN CLOSED CANNOT READ TARGET | |||
| RISER ROOM | PIV - TAMPER DOES NOT REPORT TO MAIN FIRE ALARM PANEL |
November 2018 Semi Annual Fire Suppression Testing T11
T6 TRAILER
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| 114 HOUSING | NO GAUGE BEFORE #1 CHECK VALVE ON BACKFLOW PREVENTER | |||
| 114 HOUSING | NO SYSTEM GAUGE | |||
| 114 HOUSING | TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL | |||
| 114 HOUSING | WATER FLOW SWITCH HAS BROKEN RESISTOR, WILL NOT CLEAR AT PANEL | |||
| 114 HOUSING | INSPECTOR TEST HAS NO ORIFICE | |||
| 114 HOUSING | THE ISPECTOR'S TEST PIPING IS PVC, NEEDS TO BE FIRE CRVC OR STEEL PIPE |
November 2018 Semi Annual Fire Suppression Testing T6
T3 TRAILER
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| OUTSIDE RISER ROOM | NIPPLE ON CITY SIDE CONTROL VALVE IS LEAKING AND CORRODED | |||
| OUTSIDE RISER ROOM | RISER ROOM HAS NO HEAT | |||
| OUTSIDE RISER ROOM | INSPECTOR TEST HAS NO PIPET OUTSIDE OF RISER ROOM |
November 2018 Semi Annual Fire Suppression Testing T3
T7 TRAILER
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| OUTSIDE RISER CLOSET | NO HEAT | |||
| OUTSIDE RISER CLOSET | TAMPER SWITCH REPORTS TO FIRE ALARM PANEL AS AN ALARM |
November 2018` Semi Annual Fire Suppression Testintg T7
T8 TRAILER
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| OUTSIDE RISER CLOSET | NO HEAT | |||
| OUTSIDE RISER CLOSET | TAMPER SWITCH COMES IN AS A FIRE ALARM |
November 2018 Semi Annual Fire Suppression Testing T8
T9 TRAILER
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| RISER ROOM IN HOUSEKEEPING | NO GAUGE BEFORE #1 CHECK VALVE ON BACKFLOW PREVENTER | |||
| RISER ROOM IN HOUSEKEEPING | NO SIGN ON INSPECTION TEST OR MAIN DRAIN | |||
| RISER ROOM IN HOUSEKEEPING | INSPECTOR'S TEST HAS NO SIGN GLASS | |||
| RISER ROOM IN HOUSEKEEPING | LOW RESIDUAL DURING MAIN DRAIN TEST |
November 2018 Semi Annual Fire Suppression Testing T9
BUILDING 14 GENERATOR ROOM
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| PIV | CANNOT READ THE OPEN TARGET | |||
| FDC | MISSING BOTH CAPS | |||
| RISER | NO GUAGE BEFORE #1 CHECK VALVE ON FIRE BACKFLOW PREVENTER | |||
| RISER | (2) SYSTEM GAUGES OUT OF DATE | |||
| RISER | BOTH TAMPER SWITCHES COME IN AS AN ALARM | |||
| RISER | ONE FLOW SWITCH COMES IN AS A SUPERVISORY |
November 2018 Semi Annaul Fire Suppression Testing Bldg 14
FREEDOM PARKING GARAGE MIDDLE
| Location | Deficiency | Work Order # | Date Corrected | Comments | |
| STAIRWELL 1, NORTH SIDE | HAS NO GAUGE AT TOP OF STANDPIPE | ||||
| STAIRWELL 1, NORTH SIDE | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| STAIRWELL 1, 4TH FLOOR | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| TOP PARKING LEVEL, C STANDPIPE | FHV HAS BEEN HIT, CANNOT OPERATE VALVE | ||||
| TOP PARKING LEVEL, C STANDPIPE | STANDPIPE GAUGE OVER 5 YEARS OLD | ||||
| STAIRWELL 2, 4TH FLOOR | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 5TH LANDING | HAS NO GAUGE AT TOP OF STANDPIPE | ||||
| 5TH LANDING | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| FDC NORTH END OF BUIOLDING | LABELED INCORRECTLY | ||||
| FDC SOUTH END OF BUIOLDING | LABELED INCORRECTLY | ||||
| STAIRWELL 1, 5TH FLOOR | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| ALL (3) STANDPIPES | FULL OF WATER, NEED TO BE DRAINED | ||||
| 5 |
November 2018 Semi Annual Fire Suppression Testing Freedom Garage
INDEPENDENCE WEST PKG GARAGE
| Location | Deficiency | Work Order # | Date Corrected | Comments | |
| 3RD FLOOR, TOP PARKING LEVEL, CENTER STANDPIPE | NO GAUGE AT TOP OF STANDPIPE | ||||
| FDC NORTH END OF BUILDING | LABELED INCORRECTLY, READS AUTO SPRINKLER | ||||
| FDC SOUTH END OF BUILDING | LABELED INCORRECTLY, READS AUTO SPRINKLER | ||||
| 3RD FLOOR, STAIRWELL 4 | STANDPIPE MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 2ND FLOOR, STAIRWELL 4 | STANDPIPE MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 2 |
November 2018 Semi Annual Fire Suppression Testing Independence Garage
LIBERTY PARKING GARAGE EAST
| Location | Deficiency | Work Order # | Date Corrected | Comments | |
| 3 FDC'S | NO BALL DRIPS | ||||
| 1ST FLOOR PARKING AREA, CENTER STANDPIPE | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 2ND FLOOR, STAIRWELL 1 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 2ND FLOOR, PARKING AREA, SW CORNER | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 2ND FLOOR, PARKING AREA, CENTER STANDPIPE | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 2ND FLOOR, STAIRWELL 2 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 2ND FLOOR, STAIRWELL 2, CENTER STANDPIPE | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 3RD FLOOR, STAIRWELL 1 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 3RD FLOOR, PARKING AREA, SW CORNER | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 3RD FLOOR, PARKING AREA, CENTER STANDPIPE | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 3RD FLOOR, STAIRWELL 2 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 4TH FLOOR, STAIRWELL 1 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 4TH FLOOR, PARKING AREA, SW CORNER | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 4TH FLOOR, PARKING AREA, CENTER STANDPIPE | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 4TH FLOOR, STAIRWELL 2 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 4TH FLOOR, CENTER STANDPIPE OUTSIDE STAIRWELL 2 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 5TH FLOOR, STAIRWELL 1 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 5TH FLOOR, PARKING AREA, SW CORNER | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 5TH FLOOR, PARKING AREA, CENTER STANDPIPE | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 5TH FLOOR, STAIRWELL 2 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 5TH FLOOR, CENTER STANDPIPE OUTSIDE STAIRWELL 2 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 6TH FLOOR, STAIRWELL 1 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 6TH FLOOR, PARKING AREA, SW CORNER | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 6TH FLOOR, PARKING AREA, CENTER STANDPIPE | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 6TH FLOOR, STAIRWELL 2 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 6TH FLOOR, CENTER STANDPIPE OUTSIDE STAIRWELL 2 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 7TH FLOOR, PARKING AREA, SW CORNER | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 7TH FLOOR, PARKING AREA, CENTER STANDPIPE | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 7TH FLOOR, STAIRWELL 2 | MISSING ONE 2 1/2" CAP ON FHV | 1 | |||
| 28 |
November 2018 Semi Annual Fire Suppression Testing Liberty Garage
ACA
Location Deficiency Work Order # Date Corrected Comments
| December 2018 | Malcolm Randall VAMC |
| Semi Annual Fire Suppression Testing | ACA |
Bldg 12-CLC Location Deficiency Work Order # Date Corrected Comments
| December 2018 | Malcolm Randall VAMC |
| Semi Annual Fire Suppression Inspection | Bldg 12 - CLC |
T5 TRAILER
| Location | Deficiency | Work Order # | Date Corrected | Comments |
| RISER ROOM 76-102 | LOW RESIDUAL PRESSURE | |||
| RISER ROOM 76-102 | INSPECTOR'S TEST HAS NO ORIFICE |
November 2018 Semi Annual Fire Suppression Testing T5