H342--FY20: Fire Suppression Testing Federal contract opportunity
Solicitation number
36C24820Q0471
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

36C24820Q0471 Fire Suppression Testing Nov 2018 SKJ.xlsx

View the file

Other files for this federal contract opportunity

Other files attached to H342--FY20: Fire Suppression Testing, newest first.
File Type Posted
36C24820Q0471-022.pdf PDF
36C24820Q0471-014.pdf PDF
36C24820Q0471-015.pdf PDF
36C24820Q0471-019.pdf PDF
36C24820Q0471-017.pdf PDF
36C24820Q0471-013.docx DOCX document
36C24820Q0471-016.pdf PDF
36C24820Q0471-021.pdf PDF
36C24820Q0471-023.pdf PDF
36C24820Q0471-018.pdf PDF
36C24820Q0471-000.docx DOCX document
36C24820Q0471-001.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Main Bldg

LocationDeficiencyWork Order #Date CorrectedComments
6TH FLOOR, OUTSIDE OF STAIRWELL 5, MECH ROOM, TOP LANDING2" BALL VALVE W/ BUILT IN TAMPER SWITCH, NOT WIRED UP
5TH FLOOR, E WING, STAIRWELL 6WATER FLOW SWITCH L7M33 DOES NOT REPORT TO FIRE ALARM PANEL DURING WATER FLOW
5TH FLOOR, A WING, STAIRWELL 4TAMPER SWITCH #103 COMES IN AS AN ALARM
4TH FLOOR, E WING, STAIRWELL 5TAMPER SWITCH ZONE 4-F REPORTS TO FIRE ALARM PANEL AS WATER FLOW ALARM
4TH FLOOR, E WING, STAIRWELL 5WATER FLOW SWITCH ZONE 4-F REPORTS TO FIRE ALARM PANEL AS TAMPER SUPERVISORY
2ND FLOOR, E WING, STAIRWELL 5ZONE 2-F TAMPER AND WATER FLOW SWITCHES DID NOT REPORT
2ND FLOOR, E WING, STAIRWELL 5ZONE 2-E TAMPER SWITCH #73 AND WATER FLOW SWITCH #74 DID NOT REPORT TO FIRE ALARM PANEL(door stop)
2ND FLOOR, A WING, STAIRWELL 1FIRE SPRINKLER SYSTEM IS OFF DUE TO AREA BEING UNDER CONSTRUCTION AT THE TIME OF INSPECTION
1ST FLOOR, E WING, STAIRWELL 5ZONE 1-H TAMPER SWITCH #97 AND WATER FLOW SWITCH #96 DO NOT REPORT TO FIRE ALARM PANEL
1ST FLOOR, E WING, STAIRWELL 5ZONE 1-I TAMPER SWITCH #91 AND WATER FLOW SWITCH #90 DO NOT REPORT TO FIRE ALARM PANEL
1ST FLOOR, F WING, STAIRWELL 7TAMPER SWITCH #59 AND WATER FLOW SWITCH #60 DO NOT REPORT TO FIRE ALARM PANEL
1ST FLOOR, G WING, STAIRWELL 8TAMPER SWITCH #20 AND WATER FLOW SWITCH #19 DO NOT REPORT TO FIRE ALARM PANEL
1ST FLOOR, A WING, STAIRWELL 1TAMPER SWITCH #68 REPORTS TO FIRE ALARM PANEL AS ALARM
BASEMENT FLOOR, E WING, ROOM EB 60-1TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL
BASEMENT FLOOR, B WING, IN CORRIDOR ABOVE CEILING AT B041-1 OUTSIDE RETAIL STORETAMPER SWITCH IS NOT WIRED UP
BASEMENT FLOOR, B WING, IN CORRIDOR ABOVE CEILING AT B041-1 OUTSIDE RETAIL STORESYSTEM GAUGE IS OVER 5 YEARS OLD
BASEMENT FLOOR, E WING, STAIRWELL 6 AT LOADING DOCKANTIFREEZE SYSTEM IS NOT INSTALLED CORRECTLY
BASEMENT FLOOR, E WING, STAIRWELL 6 AT LOADING DOCKCANNOT TEST FLOW SWITCH WITHOUT DISCHARGING ANTI-FREEZE SOLUTION. TESTED FLOW SWITCH MANUALLY.
BASEMENT FLOOR, E WING, FIRE PUMP ROOMGAUGE ON SUCTION SIDE OF FIRE PUMP IS NOT A SUCTION GAUGE 0-30
BASEMENT FLOOR, E WING, FIRE PUMP ROOMBACKFLOW PREVENTER IS NOT A RP
BASEMENT FLOOR, E WING, FIRE PUMP ROOMNO GAUGE BEFORE THE #1 CHECK VALVE ON FIRE PROTECTION BACKFLOW
BASEMENT FLOOR, E WING, MECHANICAL ROOM/BOILER ROOM6" BUTTERFLY CONTROL VALVE UP HIGH AT ROLL-UP-DOOR IS BROKEN IN THE OPEN POSITION
BASEMENT FLOOR, E WING, MECHANICAL ROOM/BOILER ROOMANTI-FREEZE SYSTEM IN THE CORNER UP HIGH - CONTROL VALVE NEEDS TO BE CHAINED AND LOCKED
BASEMENT FLOOR, E WING, MECHANICAL ROOM/BOILER ROOMSYSTEM ON THE BACK WALL OF THE FIRE PUMP ROOM AT EXIT DOOR - ONE SYSTEM GAUGE IS 5 YEARS OLD AND TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL
BASEMENT FLOOR, E WING, STAIRWELL 7, CRAWL SPACE, COLUMN H174" OS&Y VALVE NEEDS TO BE CHAINED AND LOCKED IN THE OPEN POSITION
BASEMENT FLOOR, E WING, STAIRWELL 7, CRAWL SPACE, COLUMN H144" OS&Y VALVE NEEDS TO BE CHAINED AND LOCKED IN THE OPEN POSITION
BASEMENT FLOOR, E WING, NORTH OF STAIRWELL 4 AND NORTH OF COLUMN B-13ONE 6" BUTTERFLY CONTROL VALVE TAMPER SWITCH NOT WIRED UP
BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN J22 1/2" OS&Y TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL AND VALVE IS LEAKING AT FLANGE
BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN J24" OS&Y VALVE TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL
BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN F52" OS&Y TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL
BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN F5WATER FLOW SWITCH DOES NOT REPORT TO FIRE ALARM PANEL
BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN F56" OS&Y VALVE IS CLOSED AT TIME OF INSPECTION
BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN K54" OS&Y VALVE DOES NOT REPORT TO FIRE ALARM PANEL
BASEMENT FLOOR, E WING, CRAWL SPACE AT STAIRWELL 1 AT COLUMN F4BOTH 4" OS&Y VALVE TAMPER SWITCHES DO NOT REPORT TO FIRE ALARM PANEL
BASEMENT FLOOR, E WING, CRAWL SPACE EAST OF GRAPHIC CONTROL ROOM AT COLUMN P116" OS&Y VALVE AND 4" OS&Y VALVE TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL
BASEMENT FLOOR, E WING, CRAWL SPACE AT COLUMN K11TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL
BASEMENT FLOOR, E WING, CRAWL SPACE WEST OF COLUMN K11TAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL
November 2018Malcolm Randall VAMC
Semi Annual Fire Suppression TestingMain Building

Bed Tower

LocationDeficiencyWork Order #Date CorrectedComments
4TH FLOOR, STAIRWELL 10WATER FLOW SWITCH HAS BAD DIAPHRAM
2ND FLOOR, STAIRWELL 10WATER FLOW SWITCH HAS BAD DIAPHRAM
OUTSIDE PIV, NORTH SIDE OF BUILDINGTAMPER SWITCH IS BROKEN
November 2018Malcolm Randall VAMC
Semi Annual Fire Suppression TestingBed Tower

T11 TRAILER

LocationDeficiencyWork Order #Date CorrectedComments
RISER ROOMBOTH TAMPER SWITCHES DO NOT REPORT TO MAIN FIRE ALARM PANEL
RISER ROOMPIV - WHEN CLOSED CANNOT READ TARGET
RISER ROOMPIV - TAMPER DOES NOT REPORT TO MAIN FIRE ALARM PANEL

November 2018 Semi Annual Fire Suppression Testing T11

T6 TRAILER

LocationDeficiencyWork Order #Date CorrectedComments
114 HOUSINGNO GAUGE BEFORE #1 CHECK VALVE ON BACKFLOW PREVENTER
114 HOUSINGNO SYSTEM GAUGE
114 HOUSINGTAMPER SWITCH DOES NOT REPORT TO FIRE ALARM PANEL
114 HOUSINGWATER FLOW SWITCH HAS BROKEN RESISTOR, WILL NOT CLEAR AT PANEL
114 HOUSINGINSPECTOR TEST HAS NO ORIFICE
114 HOUSINGTHE ISPECTOR'S TEST PIPING IS PVC, NEEDS TO BE FIRE CRVC OR STEEL PIPE

November 2018 Semi Annual Fire Suppression Testing T6

T3 TRAILER

LocationDeficiencyWork Order #Date CorrectedComments
OUTSIDE RISER ROOMNIPPLE ON CITY SIDE CONTROL VALVE IS LEAKING AND CORRODED
OUTSIDE RISER ROOMRISER ROOM HAS NO HEAT
OUTSIDE RISER ROOMINSPECTOR TEST HAS NO PIPET OUTSIDE OF RISER ROOM

November 2018 Semi Annual Fire Suppression Testing T3

T7 TRAILER

LocationDeficiencyWork Order #Date CorrectedComments
OUTSIDE RISER CLOSETNO HEAT
OUTSIDE RISER CLOSETTAMPER SWITCH REPORTS TO FIRE ALARM PANEL AS AN ALARM

November 2018` Semi Annual Fire Suppression Testintg T7

T8 TRAILER

LocationDeficiencyWork Order #Date CorrectedComments
OUTSIDE RISER CLOSETNO HEAT
OUTSIDE RISER CLOSETTAMPER SWITCH COMES IN AS A FIRE ALARM

November 2018 Semi Annual Fire Suppression Testing T8

T9 TRAILER

LocationDeficiencyWork Order #Date CorrectedComments
RISER ROOM IN HOUSEKEEPINGNO GAUGE BEFORE #1 CHECK VALVE ON BACKFLOW PREVENTER
RISER ROOM IN HOUSEKEEPINGNO SIGN ON INSPECTION TEST OR MAIN DRAIN
RISER ROOM IN HOUSEKEEPINGINSPECTOR'S TEST HAS NO SIGN GLASS
RISER ROOM IN HOUSEKEEPINGLOW RESIDUAL DURING MAIN DRAIN TEST

November 2018 Semi Annual Fire Suppression Testing T9

BUILDING 14 GENERATOR ROOM

LocationDeficiencyWork Order #Date CorrectedComments
PIVCANNOT READ THE OPEN TARGET
FDCMISSING BOTH CAPS
RISERNO GUAGE BEFORE #1 CHECK VALVE ON FIRE BACKFLOW PREVENTER
RISER(2) SYSTEM GAUGES OUT OF DATE
RISERBOTH TAMPER SWITCHES COME IN AS AN ALARM
RISERONE FLOW SWITCH COMES IN AS A SUPERVISORY

November 2018 Semi Annaul Fire Suppression Testing Bldg 14

FREEDOM PARKING GARAGE MIDDLE

LocationDeficiencyWork Order #Date CorrectedComments
STAIRWELL 1, NORTH SIDEHAS NO GAUGE AT TOP OF STANDPIPE
STAIRWELL 1, NORTH SIDEMISSING ONE 2 1/2" CAP ON FHV1
STAIRWELL 1, 4TH FLOORMISSING ONE 2 1/2" CAP ON FHV1
TOP PARKING LEVEL, C STANDPIPEFHV HAS BEEN HIT, CANNOT OPERATE VALVE
TOP PARKING LEVEL, C STANDPIPESTANDPIPE GAUGE OVER 5 YEARS OLD
STAIRWELL 2, 4TH FLOORMISSING ONE 2 1/2" CAP ON FHV1
5TH LANDINGHAS NO GAUGE AT TOP OF STANDPIPE
5TH LANDINGMISSING ONE 2 1/2" CAP ON FHV1
FDC NORTH END OF BUIOLDINGLABELED INCORRECTLY
FDC SOUTH END OF BUIOLDINGLABELED INCORRECTLY
STAIRWELL 1, 5TH FLOORMISSING ONE 2 1/2" CAP ON FHV1
ALL (3) STANDPIPESFULL OF WATER, NEED TO BE DRAINED
5

November 2018 Semi Annual Fire Suppression Testing Freedom Garage

INDEPENDENCE WEST PKG GARAGE

LocationDeficiencyWork Order #Date CorrectedComments
3RD FLOOR, TOP PARKING LEVEL, CENTER STANDPIPENO GAUGE AT TOP OF STANDPIPE
FDC NORTH END OF BUILDINGLABELED INCORRECTLY, READS AUTO SPRINKLER
FDC SOUTH END OF BUILDINGLABELED INCORRECTLY, READS AUTO SPRINKLER
3RD FLOOR, STAIRWELL 4STANDPIPE MISSING ONE 2 1/2" CAP ON FHV1
2ND FLOOR, STAIRWELL 4STANDPIPE MISSING ONE 2 1/2" CAP ON FHV1
2

November 2018 Semi Annual Fire Suppression Testing Independence Garage

LIBERTY PARKING GARAGE EAST

LocationDeficiencyWork Order #Date CorrectedComments
3 FDC'SNO BALL DRIPS
1ST FLOOR PARKING AREA, CENTER STANDPIPEMISSING ONE 2 1/2" CAP ON FHV1
2ND FLOOR, STAIRWELL 1MISSING ONE 2 1/2" CAP ON FHV1
2ND FLOOR, PARKING AREA, SW CORNERMISSING ONE 2 1/2" CAP ON FHV1
2ND FLOOR, PARKING AREA, CENTER STANDPIPEMISSING ONE 2 1/2" CAP ON FHV1
2ND FLOOR, STAIRWELL 2MISSING ONE 2 1/2" CAP ON FHV1
2ND FLOOR, STAIRWELL 2, CENTER STANDPIPEMISSING ONE 2 1/2" CAP ON FHV1
3RD FLOOR, STAIRWELL 1MISSING ONE 2 1/2" CAP ON FHV1
3RD FLOOR, PARKING AREA, SW CORNERMISSING ONE 2 1/2" CAP ON FHV1
3RD FLOOR, PARKING AREA, CENTER STANDPIPEMISSING ONE 2 1/2" CAP ON FHV1
3RD FLOOR, STAIRWELL 2MISSING ONE 2 1/2" CAP ON FHV1
4TH FLOOR, STAIRWELL 1MISSING ONE 2 1/2" CAP ON FHV1
4TH FLOOR, PARKING AREA, SW CORNERMISSING ONE 2 1/2" CAP ON FHV1
4TH FLOOR, PARKING AREA, CENTER STANDPIPEMISSING ONE 2 1/2" CAP ON FHV1
4TH FLOOR, STAIRWELL 2MISSING ONE 2 1/2" CAP ON FHV1
4TH FLOOR, CENTER STANDPIPE OUTSIDE STAIRWELL 2MISSING ONE 2 1/2" CAP ON FHV1
5TH FLOOR, STAIRWELL 1MISSING ONE 2 1/2" CAP ON FHV1
5TH FLOOR, PARKING AREA, SW CORNERMISSING ONE 2 1/2" CAP ON FHV1
5TH FLOOR, PARKING AREA, CENTER STANDPIPEMISSING ONE 2 1/2" CAP ON FHV1
5TH FLOOR, STAIRWELL 2MISSING ONE 2 1/2" CAP ON FHV1
5TH FLOOR, CENTER STANDPIPE OUTSIDE STAIRWELL 2MISSING ONE 2 1/2" CAP ON FHV1
6TH FLOOR, STAIRWELL 1MISSING ONE 2 1/2" CAP ON FHV1
6TH FLOOR, PARKING AREA, SW CORNERMISSING ONE 2 1/2" CAP ON FHV1
6TH FLOOR, PARKING AREA, CENTER STANDPIPEMISSING ONE 2 1/2" CAP ON FHV1
6TH FLOOR, STAIRWELL 2MISSING ONE 2 1/2" CAP ON FHV1
6TH FLOOR, CENTER STANDPIPE OUTSIDE STAIRWELL 2MISSING ONE 2 1/2" CAP ON FHV1
7TH FLOOR, PARKING AREA, SW CORNERMISSING ONE 2 1/2" CAP ON FHV1
7TH FLOOR, PARKING AREA, CENTER STANDPIPEMISSING ONE 2 1/2" CAP ON FHV1
7TH FLOOR, STAIRWELL 2MISSING ONE 2 1/2" CAP ON FHV1
28

November 2018 Semi Annual Fire Suppression Testing Liberty Garage

ACA

Location Deficiency Work Order # Date Corrected Comments

December 2018Malcolm Randall VAMC
Semi Annual Fire Suppression TestingACA

Bldg 12-CLC Location Deficiency Work Order # Date Corrected Comments

December 2018Malcolm Randall VAMC
Semi Annual Fire Suppression InspectionBldg 12 - CLC

T5 TRAILER

LocationDeficiencyWork Order #Date CorrectedComments
RISER ROOM 76-102LOW RESIDUAL PRESSURE
RISER ROOM 76-102INSPECTOR'S TEST HAS NO ORIFICE

November 2018 Semi Annual Fire Suppression Testing T5