36C24820Q0471-015.pdf
PDF Posted
- Attached to
- H342--FY20: Fire Suppression Testing Federal contract opportunity
- Solicitation number
- 36C24820Q0471
About this file
36C24820Q0471 VAMC ELECTRIC Annual 4-1-19.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24820Q0471-022.pdf | ||
| 36C24820Q0471-020.xlsx | XLSX spreadsheet | |
| 36C24820Q0471-023.pdf | ||
| 36C24820Q0471-018.pdf | ||
| 36C24820Q0471-014.pdf | ||
| 36C24820Q0471-019.pdf | ||
| 36C24820Q0471-017.pdf | ||
| 36C24820Q0471-013.docx | DOCX document | |
| 36C24820Q0471-016.pdf | ||
| 36C24820Q0471-021.pdf | ||
| 36C24820Q0471-000.docx | DOCX document | |
| 36C24820Q0471-001.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REPORT TO: VA Hospital BUILDING: Fire Pump Room
ADDRESS: 1601 SW Archer Rd INSPECTOR: Mark Mosley
CITY/STATE/ZIP: Gainesville, FL 32608 DATE: 4-1-2019
NOTE: This pump test shall be conducted without flowing water and allowing automatic starting of the pump to occur. Mark all answers below with: Yes, No, or N/A.
Heat in pump room YES Operate the fire pump YES
Operating louvers in pump room appear Check packing gland tightness
(slight leak at no flow)
Record suction pressure from gauge (PSI) 72
Record discharge pressure from gauge (PSI) 133
No leaks in piping or hoses YES Adjust gland nuts if necessary YES
Suction line pressure is normal YES Check for unusual noise or vibration YES
System line pressure is normal YES Check packing boxes, bearings, or pump
Suction reservoir is full YES casing for overheating
Controller pilot light (power on) is illuminated YES Record pump starting pressure 88
Transfer switch is normal; power light is Observe time for motor to accelerate to full speed
Isolating switch for standby power is closed YES For reduced voltage or reduced current N/A
Reverse phase alarm light is not illuminated YES For pumps equipped with automatic stop
Normal phase rotation light is illuminated N/A feature, record running time
Oil level in vertical motor sight glass is normal N/A
Controller selector switch is in auto position YES
DISCREPANCIES OR COMMENTS:
Jockey Start: 100 Stop: 116
See Annual Report for all Discrepancies.
Pump suction, discharge & bypass valves open operational illuminated
ANNUAL TEST AND INSPECTION REPORT FOR ELECTRICAL PUMP
N/A
YES
10 MIN
W. W. Gay Fire & Integrated Systems, Inc.
Phone: (904) 387-7973 Fax: (904) 394-7261
Jacksonville, Florida 32204
522 Stockton Street
YES
YES
YESYES