Wm. Jennings Bryan Dorn VA Medical Center
4 SOUTH
"A"
4 NORTH
"A"
4 WEST
"B"
4 WEST
"C"
BUILDING 100
544-16-100
6439 GARNERS FERRY ROAD COLUMBIA, SC
100% BID SET
RENOVATE OR SUITE
COVER SHEET
MSDLPB312/21/2017DATE-1DESCRIPTION-1
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Office of Construction and Facilities Management
DESCRIPTION-2
DESCRIPTION-3
DESCRIPTION-4
DESCRIPTION-5
DESCRIPTION-6
DESCRIPTION-7
DESCRIPTION-8
DESCRIPTION-9
DATE-2
DATE-3
DATE-4
DATE-5
DATE-6
DATE-7
DATE-8
DATE-9
(706) 774-1020
ING CONSULTING INC
550 11th Street Augusta, GA 30901
(706) 556-0197
VETERANS 1ST ARCHITECTURE
110-A North Louisville Street Harlem, GA 30814 WM. JENNINGS BRYAN DORN
Project Location
VA MEDICAL CENTER
6439 GARNERS FERRY ROAD COLUMBIA, SC
WM. JENNINGS BRYAN DORN
VA MEDICAL CENTER
RENOVATE OR SUITE
LOCATION MAP:
CAMPUS MAP: INDEX OF DRAWINGS:
SCHEDULE OF BID ITEMS:
RISK ASSESSMENT / AFTER HOURS WORK:
SUBMITTAL EXCHANGE REQUIREMENTS:
STATEMENT OF WORK:
1. DEMOLITION OF CURRENT FOURTH FLOOR SOUTH "A" WING
2. CONTRACTOR WILL CONDUCT NEW HAZMAT SURVEY AND ABATE
WHERE NEEDED.
3. CONTRACTOR TO PROVIDE DUST AND INFECTION CONTROL
PROTECTION IN ALL AREAS OF PROJECT THROUGH PROJECT
DURATION.
4. MAINTAIN PATH OF EGRESS THROUGH DURATION OF PROJECT.
5. CONSTRUCT 4 NEW OPERATING ROOMS WITH NECESSARY
ANCILLARY SPACES ALONG WITH 12 PRE-OP/PACU PATIENT ROOMS
AND ALL NECESSARY MECHANICAL, ELECTRICAL, PLUMBING, FIRE
PROTECTION INFRASTRUCTURE ACCORDING TO CONTRACT
DOCUMENTS.
GENERAL CONTRACTOR SHALL USE THE ONLINE DOCUMENT
EXCHANGE, SUBMITTAL EXCHANGE, FOR ALL SUBMITTALS
REQUIRED FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE TO
INCUR ALL COST REQUIRED TO ALLOW FULL ACCESS AND USER
CAPABILITIES FOR ALL SUB CONTRACTORS. REFER TO
SPECIFICATION 01 00 00.
WEBSITE FOR PROGRAM: WWW.SUBMITTALEXCHANGE.COM
WEBSITE REPRESENTATIVE CAN BE REACHED BY
PHONE 800-714-0024
RISK ASSESSMENT SHALL BE COORDINATED BETWEEN A/E AND VA
SUPERVISORS REPRESENTING INFECTION CONTROL, SAFETY
OFFICE, AND VA CAMPUS POLICE.
REFERENCE SPECIFICATION SECTIONS 01 00 00 - 01 74 19
NOTE: CONTRACTOR TO POST COPY OF INFECTION CONTROL
PERMITS AT ALL JOBSITE ENTRY POINTS TO INCLUDE T-CART
AREAS OF WORK.
KEY PLAN:
CODE SUMMARY:
1. CONTRACTOR TO ADD $500,000 (FIVE HUNDRED THOUSAND DOLLARS) OWNER DIRECTED
CONTINGENCY TO INCUR CHANGES IN EQUIPMENT SELECTIONS AND CHANGES IN SPECIFIED
EQUIPMENT. WRITTEN APPROVAL IS REQUIRED BY ARCHITECT AND COR BEFORE USE AND ALL
UNUSED FUNDS WILL BE DIRECTED BACK TO THE VETERANS AFFAIRS ADMINISTRATION.
1201 Broad Street, Suite 1-A Augusta, GA 30901
(706) 724-3551 Office (706) 724-8507 Fax
ELECTRICAL DESIGN CONSULTANTS
Project Number: V16-01
Project Number: 16110
ARCHITECTURAL
GI100
GC200
GC300
GC400
AD401
A400 A201 A301 A401 A402 A403 A404 A405 A406
AC401
AI401
AI402
AF401
HAZMAT
HA100
MECHANICAL
M-001 M-002 M-003
MD001
MD002
MH101
MH102
MH103
MH104
MH105
MH106
FIRE PROTECTION
FP101
FP102
PLUMBING
PL000
PL001
PL002
PL003
PD101
PD102
SANITARY
PP101
PP102
PP103
PP104
PP105
PP106
ELECTRICAL
EJ100
ED101
EL200
EP300
EP301
EP302
FA400
ET500
EP600
EP601
STRUCTURAL
S-100 S-101
EQUIPMENT
EQ-4
PT-1.01.0
PT-2.04.1
GENERAL INFORMATION AND NOTES
GROUND & FIRST FLOOR ICRA PLAN AND NOTES
FIRST & SECOND FLOOR ICRA PLAN AND NOTES
FOURTH FLOOR ICRA PLAN AND NOTES
ARCHITECTURAL DEMOLITION PLANS
LIFE SAFETY PLANS
GROUND AND FIRST FLOOR PLANS
SECOND AND THIRD FLOOR PLANS
FOURTH FLOOR PLAN
FOURTH FLOOR EQUIPMENT PLANS
FOURTH FLOOR LEAD LINING PLAN
ROOF PLAN
DOOR TYPES, DETAILS & SCHEDULE
WINDOW TYPES & DETAILS
REFLECTED CEILING PLANS
INTERIOR ELEVATIONS
INTERIOR ELEVATIONS
FINISH SCHEDULE & PATTERN PLAN
HAZARDOUS MATERIALS REMOVAL PLAN
MECHANICAL SCHEDULE
MECHANICAL DETAILS
MECHANICAL SCHEMATIC
MECHANICAL DEMOLITION PLAN
MECHANICAL DEMOLITION PLAN
MECHANICAL NEW WORK PLAN
MECHANICAL NEW WORK PLAN
MECHANICAL NEW WORK HYDRONIC PIPING PLAN
MECHANICAL NEW WORK ROOF PLAN
MECHANICAL ROOM SCHEMATIC
TEA CART ELEVATOR ROOM NEW WORK PLAN
FIRE HAZARD SPRINKLER ANALYSIS PLAN
FIRE HAZARD SPRINKLER HEAD LOCATIONS
PLUMBING LEGEND, ABBREVIATIONS AND NOTES
PLUMBING SCHEDULES
MED GAS SCHEDULE
PLUMBING DETAILS
SANITARY, VENT AND ROOF DRAIN PIPING DEMO PLANS
DOMESTIC, HOT AND MED GAS PIPING DEMO PLANS
SANITARY, VENT & ROOF DRAIN PLAN BELOW FLOOR
SANITARY, VENT & ROOF DRAIN PLAN ABOVE CEILING
DOMESTIC HOT, CIRCULATION WATER PIPING PLAN
MEDICAL GAS PIPING PLAN
SANITARY VENT AND ROOF DRAIN PIPING ISOMETRIC
DOMESTIC AND HOT WATER PIPING ISOMETRIC
LEGEND, FIXTURE SCHEDULE, NOTES & DETAILS
ELECTRICAL DEMOLITION DRAWING
LIGHTING SCHEMATIC DRAWING
POWER SCHEMATIC DRAWING
ENLARGED POWER PLAN
MECHANICAL POWER SCHEMATIC DRAWING
FIRE ALARM SCHEMATIC DRAWING
VOICE/DATA SCHEMATIC DRAWING
ELECTRICAL RISER & PANELBOARD SCHEDULES
PANELBOARD SCHEDULES
SPECS AND EQUIPMENT SUPPORT DETAILS
4TH FLOOR DETAILS AND ROOF PLAN
HEALTHCARE TECHNOLOGY FLOOR PLAN
RISER DIAGRAM
PTS LAYOUT - PARTIAL LEVEL 4 SOUTH A
DOORS TO BE RATED A MINIMUM OF 20 MINUTES PER NFPA 101-18.3.7.6 AND NFPA 101-19.3.7.6 (4).
CLOSERS ARE REQUIRED PER NFPA 101-8.5.4.4.
CROSS-CORRIDOR DOORS SHALL BE OPPOSITE SWINGING, BUT DO NOT REQUIRE POSITIVE LATCHING.
ALL OTHER DOORS DO NOT REQUIRE POSITIVE LATCHING PER NFPA 101-18.3.7.8 (2) AND NFPA 101-19.3.7.8 (2).
GROSS AREA FOR CONSTRUCTION (IBC TABLE 503):
OCCUPANCY CLASSIFICATION (LSC CH. 6 & 18):
CONSTRUCTION TYPE LIMITATIONS (LSC TABLE 18.1.6.1):
BUILDING HEIGHT (IBC TABLE 503):
BUILDING DATA:
SHAFT ENCLOSURES (TABLE 8.3.4.2):
VERTICAL EXIT ENCLOSURES (TABLE 8.3.4.2):
STAIRWAY FIRE DOOR (TABLE 8.3.4.2):
MECHANICAL FIRE PROTECTION (TABLE 508.2):
DRAFT STOPPING REQUIRED (LSC 8.6.11.1):
FIRE BLOCKING REQUIRED (IBC 717):
LIFE SAFETY SYSTEM:
SMOKE BARRIER REQUIRED (IBC 905):
STANDPIPES REQUIRED (IBC 905):
DEAD END LIMIT (LSC 18.2.5.2):
EMERGENCY EXIT REQUIREMENTS: (2nd Floor)
INTERNATIONAL BUILDING CODE 2015 ED.
INTERNATIONAL PLUMBING CODE 2015 ED.
INTERNATIONAL MECHANICAL CODE 2015 ED.
INTERNATIONAL FUEL GAS CODE 2015 ED.
LIFE SAFETY CODE NFPA 101 2015 ED.
INTERNATIONAL FIRE CODE 2015 ED.
NATIONAL ELECTRIC CODE 2014
INTERNATIONAL ENERGY CONSERVATION 2015 ED.
AMERICANS WITH DISABILITIES ACT (ADA) 2010 ED.
APPLICABLE CODES:
NEW HEALTHCARE (LSC 6.1.5)
TYPE II (222)
2 HR
2 HR (EXIST)
90 MIN (EXIST)
YES
YES
YES
NO
1 HR
CODE SUMMARY:
SUITE BY DESIGN: 16,500 SF
ALLOWED: EXISTING
EXISTING: 5 STORIES
OCCUPANCY LOAD (PER IBC TABLE 1004.1 AND LSC 7.3.1.2):
SUITE: 63 OCCUPANTS @ 240SF/ OCCUPANT
SPRINKLERS REQUIRED (LSC 43.7.2.1 (2)): YES
30'-0"
TRAVEL DISTANCE LIMIT (LSC 18.2.5.7.2.4 (B)): 200'-0"
TRAVEL DISTANCE TO EXITS (LSC 18.2.6.2.1): 200'-0"
FIRE ALARM SYSTEM REQUIRED (LSC 19.3.4.1): YES
COMMON PATH OF TRAVEL (LSC 18.2.5.3): 100'-0"
544-16-100
6439 GARNERS FERRY ROAD COLUMBIA, SC
100% BID SET
RENOVATE OR SUITE
GENERAL INFORMATION AND NOTES
GI100
MSDLPB312/21/2017DATE-1DESCRIPTION-1
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Office of Construction and Facilities Management
Scale: 1/8"=1'-0"
DESCRIPTION-2
DESCRIPTION-3
DESCRIPTION-4
DESCRIPTION-5
DESCRIPTION-6
DESCRIPTION-7
DESCRIPTION-8
DESCRIPTION-9
DATE-2
DATE-3
DATE-4
DATE-5
DATE-6
DATE-7
DATE-8
DATE-9
(706) 774-1020
ING CONSULTING INC
1201 Broad Street, Suite 1-A Augusta, GA 30901
(706) 724-3551 Office (706) 724-8507 Fax
ELECTRICAL DESIGN CONSULTANTS
550 11th Street Augusta, GA 30901
(706) 556-0197
VETERANS 1ST ARCHITECTURE
110-A North Louisville Street Harlem, GA 30814 WM. JENNINGS BRYAN DORN
Project Location
VA MEDICAL CENTERProject Number: V16-01
Project Number: 16110
1'-6"
2' -5
2' -1
0"
2' -5
2' -1
0"
8"
1'-6" 3"
1'-6"
1'-5" 1'-6" 1'-6"
2'-6"
3' -8
OWNER FURNISH / CONTRACTOR INSTALL
FLOOR FINISH
STEEL JOIST
H A
N D
LE
ROUND
EXIST GR
FA
DW
STL LNTL
CEMENTITOUS (BACKER) BOARD
VOLT
DISHWASHER
OWNER FURNISH / OWNER INSTALL
EXISTING GRADE
FLR FIN
V
STEEL LINTEL
SEE NOTES OR SPECS
STL JST
BOARD
H E
IG
H
T
(M
IN
PERPENDICULAR
SAFB SOUND ATTENUATION FIRE BLANKET
2 / A1.1 1 / A1.1
A1.1
A
ROOM NAME
A1.1
1A1.1
ALPHA CHARACTER STARTING CLOCKWISE FROM THE CORRIDOR
ACCESS DOOR OPENING.
DOOR OPENING IN A ROOM EXISTS, DOOR OPENINGS WITHIN THAT
ROOM ARE IDENTIFIED BY THE ROOM NUMBER FOLLOWED BY AN
SAME AS THE SECURE SIDE ROOM NUMBER. IF MORE THAN ONE
IF A ROOM HAS ONE DOOR OPENING, THE DOOR OPENING IS THE
R
WBL WOOD BLOCKING
RECEPTIONRECP
OF/OI
FF&E FURNITURE, FIXTURE & EQUIPTMENT
FIN GR FINISHED GRADE
FC BRK FACE BRICK
EXIST EXISTING
COORDINATECOORD
BRG PL BEARING PLATE
WWM WELDED WIRE MESH
WH WEEP HOLE
WC WATER CLOSET
W WATTS
VWC VINYL WALL COVERING
R THERMAL RESISTANCE
TOPOGRAPHYTOPO
UTIL UTILITY
CROSS BRACE
XL
X BRACE
EXTRA LARGE
SYMM SYMETRICAL
STEEL TUBINGSTL TB
STEEL TRUSSSTL TR
STEEL ROOF DECKSTL RF DK
STANDING SEAM (ROOF)SS
SOLID CORE WOOD DOORSCWD
SMALLSM
SV SHEET VINYL
SEALANTSLNT
RBR RUBBER
RCP REFLECTED CEILING PLAN
PL POLYETHYLENE (PLASTIC)
OH OVERHANG
OCCUPANCYOCC
NATURAL GASNG
MC MEDICINE CABINET
METALMTL
MANUFACTURERMFR
LAM LAMINATE
KITCHENKIT
JS JANITOR SINK
HS HAND SINK
HYDR HYDRAULIC
HM HOLLOW METAL
GLAZED CONCRETE MASONRY UNIT
GLASS- FIBER REINFORCED PLASTER
GLASS- FIBER REINFORCED PLASTIC
GLASS- FIBER REINFORCED GYPSUM
GLAZINGGLZ
GLZ CMU
GFRG
GFRP
GFRP
GEN GENERAL
FFB
FFA
FROM FLOOR BELOW
FROM FLOOR ABOVE
FLG FLOORING
FLR FLOOR
FRP FIBERGLASS REINFORCED PLASTIC
E EAST
CONTROLCTRL
COMPUTERCOMP
CLL COLUMN LINE
CL OR C
CBB
CO CASED OPENING
BELOWBLW
ACOUSTIC WALL TREATMENT
ACOUSTIC PANEL CEILINGAPC
AWT
ADDENDUMADDM
(CURRENT REVISIONS SHALL BE SHOWN
ENCIRCLED BY A FREEFORM LINE)
LAMINATED GLASS
INSULATION
JANITOR CLOSET
INSTALL
IDENTIFICATION
(MAX.) (MIN.)
1 1/2" 1'
-0
(M
IN
.)(MIN.)
7' -0
(MIN.)
1'-3" (MIN.)
BRKT
BTWN
BSMT
BM
BD
BM
BFF
BRG
B PL
BRACKET
CORR
CNTR
CONST
CONT
BENCH MARK
BETWEEN
BEAM
BELOW FINISH FLOOR
BEARING
BASE PLATE
BASEMENT
CMU
CONF
CONC
COL
CLO
CPT
ALUM/AL
AUX
APPROX
ARCH
ANC
ANOD
AB
ALT
A/C
ARCHITECT/ARCHITECTURAL
AUXILIARY
AT
CLRM
CT
CHFR
ANCHOR
ANCHOR BOLT
AND
ANODIZED
APPROXIMATE
ALUMINUM
AIR CONDITIONING
ALTERNATE
CNTR
CLG
ADMIN
ABBREVIATIONS
AFG
AFF
LAVATORY
ADJ
ACT
ABV
A
ABOVE FINISH GRADE
ABOVE FINISH FLOOR
ACOUSTIC CEILING TILE
ADMINISTRATION
ADJUSTABLE / ADJACENT
ABOVE
C
CAB
BUR
BN
BLKHD
BLDG
(M
IN
(M A
X
VANITY
(MAX.)
(MIN.)
(MIN.)
(M
IN
(M A
X
LIGHT
FEC FIRE EXTINGUISHER CABINET
LT
FUTURE
FURNISH/FURNISHED
FOOTING
FOUNDATION
FRAME
FRAMING
FOOT, FEET
FLUORESCENT
FIXTURE
CORRIDOR/CORRUGATED
COUNTER
CONSTRUCTION
CONTINUE/CONTINUOUS
EMER
EQUIP
EPDM
EQ
ENTR
ENGR
EWC
ELEV
CONCRETE MASONRY UNIT
CONFERENCE
CONCRETE
COLUMN
CLOSET
EA
ELEC
ESMT
E
FLOR
ETHYLENE PROPYLENE DIENE MONOMER
EMERGENCY
ENTRANCE/ENTRY
EQUIPMENT
EQUAL
ENGINEER
ELECTRIC WATER COOLER
ELEVATION
FURN
FUT
FRMG
FDTN
FR
FTG
FT
EACH
ELECTRIC/ELECTRICAL
EASMENT
FIXT
HIGH STRENGTH
HYDRANT
HORIZONTAL
HOLLOW METAL FRAME
HOLLOW CORE
HOLLOW METAL DOOR
HOLD OPEN
HYD
HR HOUR
HMF
HMD
HOSP
HOR
HOSPITAL
HC
HO
HS
LW
LTG
LIGHTWEIGHT
LIGHTING
EXTERIOR GYPSUM SHEATHING BOARD
EXTERIOR INSULATION FINISH SYSTEM
EXPANSION JOINT
EXPOSED
EXTERIOR
EXPANSION
ESTIMATE
FIRE ALARM
FIRE EXTINGUISHER
FIBERGLASS
FIBER REINFORCED GYPSUM
FINISH/FINISHED
FINISH FLOOR
FEET/FOOT
2'-6"
(B.F. MIN.)
EIFS
EXT
CARPET
CLASSROOM
CERAMIC TILE
CHAMFER
DWR
DWG
DN
DR
DR
DBL
CENTERLINE
CENTER
CEILING
DIM
DEPT
DET
DEMO
DRAWER
DRAWING
DOWN
DRAIN
DOOR
DOUBLE
FIN FLR
FIN
FE
FT or '
FRG
FGL
DIMENSION
DEMOLISH, DEMOLITION
DEPARTMENT
DETAIL
EGSB
F
4"
CABINET
BUILDING
BUILT-UP ROOFING
BULLNOSE
BULKHEAD
D
DMPR
1' -5
1/ 2"
URINAL
(B .F
. M A
X.
7"-9" (TYP)
G.B.
(M
IN
DAMPER
EXP
EJ
EXP
EST
WATER CLOSET
G.B.
1'-6"
4' -0
2' -9
SANITARY
NAPKIN
DISPENSER
(M A
X
2' -9
3' -0
LAVATORY
GYPSUM WALL BOARD
HEATING, VENTILATING,
& AIR CONDITIONING
HEAVY DUTY
HARDWOOD
HANDICAPPED
HANDRAIL
HCP
HD
HT
HVAC
HEIGHT
HDR
HDWD
HNDRL
HEADER
GT GROUT
H
GWB
GDR GUARD RAIL
G
GRTG
GROUND
GRATING
LAM GL
LDG
LG
LAV
LANDING
LARGE
LAVATORY
LAB
L
LABORATORY
KPL
KW
KB
KS
K
KICK PLATE
KILOWATT
KNEE SPACE
KNEE BRACE
JAN CLO
J
GRAB BAR
GENERAL CONTRACTOR
GALVANIZED
GC
GFRC
GB
GL
GLASS- FIBER REINFORCED CONCRETE
GLASS
GALV
G
2' -5
2' -1
0"
NOTE: ANY ELEC. OUTLET
NEAR SINKS IN B.F. TOILET
ROOMS TO BE MOUNTED
33" TO 36" AFF.
ELECT. OUTLET
(SEE BELOW)
(M
IN
(M A
X.
3' -0
INFO INFORMATION
INSUL
INT
INSTL
INTERIOR
orIN "
ID
I
INCH/INCHES
NOTES: 1. MOUNTING HEIGHTS SHOWN ARE PROPOSED FOR ALL ACCESSORIES AND FIXTURES REQUIRED
UNLESS OTHERWISE NOTED OR DIMENSIONED ON DRAWINGS FOR SPECIFIC CONDITIONS.
TOWEL
BAR AND
SHELF
POSITION
FOLDED
ELEVATOR
PUSH
BUTTONS
E.W.C. OR
DRINKING
FOUNTAINS
(M
IN
6' -0
2' -9
3' -8
4' -0
3' -6
9"
(M
IN
.-M A
X
WATER CLOSET
(T O
T O
P O
F
SE
AT
FLUSH VALVE 4'
-0
B
.F . M
A X)
1' -5
B
.F . M
IN
1' -5
B
.F . M
IN
1' -7
B
.F . M
A X.
(MIN.)
TOILET
PAPER
HOLDER
LINE OF WALL
2' -3
TOILET
TISSUE
DISPENSER
SHOWER
SEAT (B.F.)
1' -7
(M
IN
.-A
D A
1' -6
LIGHT
SWITCH
FIRE ALARM
PULL BOX (ABOVE)
DUPLEX OUTLET
(B.F. / TYP HEIGHT)
THERMOSTAT
(M A
X.
PAY PHONE
(B.F. / F.A.)
4' -0
TO
C O
IN
S
LO
T
4' -0
2' -3
2' -3
3' -0
WALL MOUNTED
OR EMERGENCY
PHONE (B.F. / F.A.)
(M A
X.
1' -3
SHOWER
CURTAIN ROD
SHELF
(ABOVE)
MAILSLOT
TYPICAL MOUNTING HEIGHTS
3' -4
"2' -9
3' -4
3' -8
1' -3
15" A.F.F. MIN.
SOAP
DISH
SOAP
DISPENSER
SANITARY
NAPKIN
RECEPTICLE
48" A.F.F. MAX.
3' -8
3' -8
(T
Y P
H T)
2' -1
0"
SHOWER HEAD
AND VALVES
6' -8
"7' -4
7' -4
5' -0
VA
R
IE
S
(O R
A S
N O
TE
D
(O R
A S
N O
TE
D
7' -0
LINE OF WALL
3' -8
M
A X.
6' -8
6' -0
1'-0"
MEDICINE
CABINET (B.F.)
URINAL
SHIELD
URINAL
PARTITION
TO
S
H E
LF
IN
C A
B
IN
E T
MOP STRIP
AND SHELF
3'-6"
3'-0"
ELECTRIC DUPLEX,
PHONE, OR TV
OUTLET WITH
LIGHT SWITCH
1' -6
CLOCK WALL
SPEAKER
6' -4
3' -8
M
A X
3' -4
2' -0
3'-0"6"
URINAL (B.F.)
1' -5
STANDARD
URINAL
(S
TD
.) (S
TD
SIGNAGE
OR PLAQUE
CHALKBOARD
OR TACKBOARD
(S E
E S
P E
C
FIRE VALVE
CABINET
3' -3
4' -0
5' -4
2' -3
5' -0
HIGH-LOW
E.W.C. OR
DRINKING
FOUNTAIN
(M
IN
(M
IN
FIRE EXTINGUISHER
CABINET
TOWEL
BAR
PURSE
SHELF
HOOKS
7' -0
" T Y
P
5' -0
4' -6
M
A X.
B .F
4' -6
VARIES
FIRE EXTINGUISHER
AND WALL BRACKET
FIRE HOSE
RACK OR VALVE
CUP
DISPENSER
FACIAL
TISSUE
DISPENSER
HAND DRYER ASH TRAY
4' -0
6' -0
C.O.
5"
DOOR
HARDWARE
TY
P
IC
A
L
HAND HELD
SHOWER HEAD
& CONTROLS (B.F.)
LINE OF WALL
(M A
X.
3' -2
(M
IN
WALL C.O.
LOCKSET
LOCATION
WALL BASE
COVER
WALL LINE
5'-0" MIN. LENGTH HOSE
WITH HAND HELD OR
ADJUSTABLE SPRAY
UNIT ON BAR
(MAX.)
1'-3"
SHOWER
4' -6
(M
A X.
1' -0
COAT ROD
& HAT SHELF
BOOT RACK (BELOW)
ELECTRIC
PANEL
HANDRAIL
VARIES
MIRROR
AND SINK
LAV
3' -4
5' -4
3' -8
(T
Y P
H T)
SEAT
COVER
DISPENSER
TOWEL
DISPENSER
TOWEL
DISPENSOR
AND WASTE
RECEPTACLE
6' -0
3' -2
1' -6
WASTE
RECEPTACLE
8" (M
IN
FULL LENGTH
MIRROR
(A
FF
M
IN
2' -5
3' -2
4' -0
2' -1
0"
1'-0" (TYP.)
HANDRAIL EXTENSION
MIRROR AND
VANITY COUNTER
1'-11" AT BOTTOM
OF STAIRS ONLY
LINE OF RISER
OR END OF
RAMP
BABY CHANGING
STATION
NOM NOMINAL
OA
OF/CI
OH DR
ORIG
OZ
OVERALL
OVERHEAD DOOR
ORIGINAL
OUNCE
O
OC
OPNG
OPP
OFF
NIC
NTS
NO or
NORM
N
ON CENTER
OPPOSITE
OPENING
OFFICE
NOT-IN-CONTRACT
NOT-TO-SCALE
NUMBER
NORMAL
NORTH
REF
REC
RLG
R
REFERENCE
RECESSED
RADIUS
RAILING
QTY
QTR RND
QT
QTR
Q
QUARTER ROUND
QUARRY TILE
QUANTITY
QUARTER
SQ SQUARE
SPKLR SPRINKLER
STL
STL PL
STRUCT
STOR
SF
STD
SP
STEEL
STORAGE
STRUCTURAL
STEEL PLATE
SQUARE FEET/SQUARE FOOT
STANDARD
STANDPIPE
SC
S
SPEC
SP EL
SIM
SOLID CORE
SPECIFICATIONS
SPOT ELEVATION
SOUTH
SIMILAR
U
URINAL
UNDERCUT
UNDER GROUND
UNFINISHED
UR
UNFIN
UC
UGND
TRANSOM
TYPICAL
TRANSFER GRILLE
TRANS
TYP
TG
MECHANICALMECH
PER FOOT (OR INCH)PER FT
MECHANICAL ROOM
MODIFIED BITMENMOD BIT
MULL
N
NEUT
MTD
MLDG
MTG
MULLION
NEUTRAL
MOULDING
MOUNTED
MEETING/MOUNTING
MIN
MISC
MEZZ
MLWK
MT
MWP
MED
MEMB
MECH RM
MEZZANINE
MILLWORK
MINIMUM
MISCELLANEOUS
METAL THRESHOLD
MEDIUM
MEMBRANE
MEMBRANE WATERPROOFING
# / LB
PLF
POS
POUND
POUNDS PER LINEAR FOOT
POSITION
PLBG
PLYWD
PL
PERF
PERM
PERP
PLASTIC LAMINATE
PLUMBING
PLYWOOD
PERFORATED
PERMANENT
DRAWING IDENTIFICATION NUMBER / SHEET IDENTIFICATION NUMBER
MAINT
MO
MATL
MAX
MFD
MACH
M
MAINTENANCE
MANUFACTURERED
MASONRY OPENING
MATERIAL
MAXIMUM
MACHINE
MATCH LINE INDICATION
MATCHLINE A
MATCHLINE A
PAR
PRKG
PTN
PNL
PT
P
PARALLEL / PARAPET
PARTITION
PARKING
PANEL
PAINT
SCH
SCRN
SHTHG
SECT
SM
SAN
S
SCHEDULE
SHEET METAL
SCREEN
SHEATHING
SECTION
SANITARY
RM
RO
RND
RD
ROUGH OPENING
ROOM
ROAD
THICK/ THICKNESS
THROUGHTHRU
THK
SYMBOL
TELEVISION
TERRAZZO
TANGENT
TER
TV
TAN
T
SYM
REINFORCE
REQ
RES
REV
RPM
REF
REINF
REQUIRED
REVISED/REVISION
REVOLUTIONS PER MINUTE
RESILIENT
REFRIGERATOR
SURFACE
SUSPEND
SURF
SUSP
Y
YR
YD
YEAR
YARD
WITHOUT
WOOD / WOOD DOOR
X
W/ W/O
WD
WITH
WEIGHT
WELDED WIRE FABRIC
WATER
WATER HEATER
WATERPROOFING
WEATHERSTRIPWS
WT
WWF
W
WP
WEST
WTR
WH
WALL CABINET
WAINSCOT
VOLUME
VINYL COMPOSITION TILE
VESTIBULE
VOL
W
WSCT
W CAB
VCT
VEST
VAPOR RETARDER
VENTILATOR / VENTILATION
VERSUS
VARIATION / VARIES
VENEER
VENT
VS
VNR
VR
VAR
V
DRAWING DIMENSION LINE INDICATION
EXISTING DOOR SWING
INDICATION (TO BE REMOVED)
FIRST FLOOR 101
(INDICATES SHEET NUMBER WHERE ELEVATION IS DRAWN)
ELEVATION IDENTIFICATION NUMBER(S)
SHEET IDENTIFICATION NUMBER
INDICATES DIRECTION OF VIEW OR MULTIPLE VIEWS
(INDICATES SHEET NUMBER WHERE SECTION IS DRAWN)
SHEET IDENTIFICATION NUMBER
ELEVATION INDICATION
SECTION LOCATION INDICATION
NUMBER OF TREADS
(OR RISERS) AND SIZE
IN STAIR RUN
TO FLOOR ABOVE (UP)
OR BELOW (DN)
DEMOLITION KEY NOTE IDENTIFICATION
(SEE GENERAL DEMOLITION NOTES)
STAIR DIRECTION
STAIR DIRECTION NOTATION
10 R @ 7"
UP
/D
N
2060.A
5'-0"
DESCRIPTION ORIGINATES AT
WALL SURFACE DESIGNATED
WALL CONSTRUCTION TYPE INDICATION
COLUMN IDENTIFICATION LETTER OR
NUMBER FOR NEW CONSTRUCTION
KEYED NOTE INDICATION
WALL TYPE NOTATION
A
COLUMN INDICATION
CONTINUE FOR AS MANY FLOORS REQUIRED.
THIRD FLOOR
SECOND FLOOR
REVISION INDICATION
NORTH INDICATION
(SAME NUMBER ON SHEET WHERE DRAWN OR REFERENCED)
(INDICATES SHEET NUMBER WHERE DRAWING IS SHOWN)
DETAIL IDENTIFICATION NUMBER
SHEET IDENTIFICATION NUMBER
(INDICATES SHEET NUMBER WHERE DETAIL IS DRAWN)
DRAWING IDENTIFICATION NUMBER
SHEET IDENTIFICATION NUMBER
A1.1
DETAIL LOCATION INDICATION
REFERENCE SYMBOLS
DRAWING IDENTIFICATION
1 DRAWING TITLE
SCALE: 1/8" = 1'-0"
ROOM NAME AND NUMBER INDICATION
ROOM IDENTIFICATION BY FLOOR AND/OR
BASEMENT
ZONE SHALL BE AS FOLLOWS:
DOOR SWING INDICATION
NEW DOOR SWING
INDICATION
DOOR IDENTIFICATION
EXISTING DOOR
SWING INDICATION
PROPORTIONS OTHER
THAN 1:1
DRAWINGS WITHOUT
GRAPHIC SCALES WITH
NOTE: DO NOT SCALE
(MIN.)
B
LINEAR FEET/FOOT
or #LBS
LVR
POUNDS
LOUVER
LOC
LKR
LR
LF
LOCATION
LOCKER
LIVING ROOM
PRESERVATIVE TREATED
PREFINISHEDPREFIN
PT
PROJ PROJECT/PROJECTION
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PRCST
PREFAB
PSF
PSI
PCF POUNDS PER CUBIC FOOT
PREFABRICATED
PRECAST
FV FIELD VERIFY
A1.1
(SAME NUMBER ON SHEET WHERE DRAWN OR REFERENCED)
SECTION IDENTIFICATION NUMBER
(SAME NUMBER ON SHEET WHERE DRAWN OR REFERENCED)
MATCHLINE A
MATCHLINE A
2 / A1.1 1 / A1.1
DRAWING IDENTIFICATION NUMBER / SHEET IDENTIFICATION NUMBER
(SAME NUMBER ON SHEET WHERE DRAWN OR REFERENCED)
FIRST FLOOR 101
CONTINUE FOR AS MANY FLOORS REQUIRED.
THIRD FLOOR
SECOND FLOOR
DOOR IDENTIFICATION BY FLOOR AND/OR
BASEMENT
ZONE SHALL BE AS FOLLOWS:
100A100100A
ROOM NAME
A
N
SECTION NOTE IDENTIFICATION
(SEE SECTION KEY NOTES)
01000.A.1
3"
TRUE NORTH
PROJECT NORTH AXIS
(NOT SHOWN)
REVISION OR
ADDENDUM NUMBER
11 T @ 11"
WINDOW OR FRAME IDENTIFICATION
AAA
2. REFER TO LIFE SAFETY PLANS FOR CODE REQUIREMENTS
3. OPERABLE CONTROLS SHALL FALL WITHIN FORWARD REACH RANGES REQUIRED BY CODE REGULATIONS
4. B.F. REFERS TO A BARRIER FREE MOUNTING
15" A.F.F. MIN.
48" A.F.F. MAX.
FIRE EXTINGUISHER
AND WALL CABINET
15" A.F.F. MIN.
48" A.F.F. MAX.
2' -9
1'
-3
L
SANITARY
NAPKIN
DISPENSER
5. F.A. REFERS TO A FRONT APPROACH MOUNTING
TELEPHONE
SHELF (B.F. / F.A.)
MEDICINE
CABINET
(S
TD
WATER CLOSET
1' -4
6439 GARNERS FERRY ROAD COLUMBIA, SC
100% BID SET
RENOVATE OR SUITE
GROUND & FIRST FLOOR ICRA PLAN
& NOTES
GC200
MSDLPB312/21/2017DATE-1DESCRIPTION-1
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Office of Construction and Facilities Management
Scale: 1/8"=1'-0"
DESCRIPTION-2
DESCRIPTION-3
DESCRIPTION-4
DESCRIPTION-5
DESCRIPTION-6
DESCRIPTION-7
DESCRIPTION-8
DESCRIPTION-9
DATE-2
DATE-3
DATE-4
DATE-5
DATE-6
DATE-7
DATE-8
DATE-9
(706) 774-1020
ING CONSULTING INC
1201 Broad Street, Suite 1-A Augusta, GA 30901
(706) 724-3551 Office (706) 724-8507 Fax
ELECTRICAL DESIGN CONSULTANTS
550 11th Street Augusta, GA 30901
(706) 556-0197
VETERANS 1ST ARCHITECTURE
110-A North Louisville Street Harlem, GA 30814 WM. JENNINGS BRYAN DORN
Project Location
VA MEDICAL CENTERProject Number: V16-01
Project Number: 16110
INSPECTION AND NON-INVASIVE ACTIVITIES. INCLUDES,
BUT IS NOT LIMITED TO:
1. REMOVAL OF CEILING TILES FOR VISUAL INSPECTION
LIMITED TO 1 TILE PER 50 SQUARE FEET
2. PAINTING (BUT NOT SANDING)
3. WALLCOVERING, ELECTRICAL TRIM WORK, MINOR
PLUMBING, AND ACTIVITIES WHICH DO NOT GENERATE
DUST OR REQUIRE CUTTING OF WALLS OR ACCESS TO
CEILINGS OTHER THAN FOR VISUAL INSPECTION
SMALL SCALE, SHORT DURATION ACTIVITIES WHICH
CREATE MINIMAL DUST INCLUDES, BUT IS NOT LIMITED TO:
1. INSTALLATION OF TELEPHONE AND COMPUTER CABLING
2. ACCESS TO CHASE SPACES
3. CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION
CAN BE CONTROLLED.
WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF
DUST OR REQUIRES DEMOLITION OR REMOVAL OF ANY
FIXED BUILDING COMPONENTS OR ASSEMBLIES INCLUDES,
BUT IS NOT LIMITED TO:
1. SANDING OF WALLS FOR PAINTING OR WALL COVERING
2. REMOVAL OF FLOORCOVERINGS, CEILING TILES AND
CASEWORK
3. NEW WALL CONSTRUCTION
4. MINOR DUCT WORK OR ELECTRICAL WORK ABOVE
CEILINGS
5. MAJOR CABLING ACTIVITIES
6. ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A
SINGLE WORKSHIFT.
MAJOR DEMOLITION AND CONSTRUCTION PROJECTS
INCLUDES, BUT IS NOT LIMITED TO:
1. ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS
2. REQUIRES HEAVY DEMOLITION OR REMOVAL OF A
COMPLETE CABLING SYSTEM
3. NEW CONSTRUCTION.
TYPE A
TYPE B
TYPE C
TYPE D
GROUP 1 LOW RISK GROUP 2 MEDIUM RISK
GROUP 3 MED-HIGH RISK GROUP 4 HIGH RISK
1) OFFICE AREAS
2) ENGINEERING
3) ENVIRONMENTAL
SERVICES
1) AT PATIENT CARE UNITS
(EXAMPLE: CARDIAC,
REHAB., ULTRASOUND)
2) OUTPATIENT AREAS
1) EMERGENCY ROOM
2) RADIOLOGY/MRI
3) POST-ANESTHESIA CARE UNIT
4) INTENSIVE CARE UNITS
5) NUCLEAR MEDICINE
6) ADMISSION/DISCHAR GE AREA
7) PT - TANK AREAS
8) CAFETERIA
9) ECHOCARDIOGRAPHY
10) LABORATORIES
11) DIALYSIS
12) CENTRAL STERILE SUPPLY
13) ONCOLOGY
14) CARDIOLOGY
1) OPERATING
ROOMS; STERILE
PROCESSING
2) INTENSIVE CARE
UNITS 3) CARDIAC
CATHETERIZATION
4) ANESTHESIA
AREAS
5) ALL ENDOSCOPY
AREAS
6) PHARMACY
IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE THE FOLLOWING INFECTION CONTROL PRECAUTIONS
DEPENDING ON THE AREA CLASS DESIGNATION
INTERIM MEASURE CLASS I
1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION OPERATIONS.
2. IMMEDIATELY REPLACE ANY CEILING TILE DISPLACED FOR VISUAL INSPECTION.
3. CLEANUP AND DISPOSAL AS APPROPRIATE.
INTERIM MEASURE CLASS II
1. PROVIDE ACTIVE MEANS TO PREVENT AIR-BORNE DUST FROM DISPERSING INTO ATMOSPHERE, INCLUDING WATER MIST WORK SURFACES TO CONTROL
DUST WHILE CUTTING.
2. SEAL UNUSED DOORS WITH MASKING TAPE
3. BLOCK OFF AND SEAL AIR VENTS.
4. CLEANUP AND DISPOSAL AS APPROPRIATE.
INTERIM MEASURE CLASS III
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM
2. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS OR IMPLEMENT CONTROL CUBE METHOD.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION FILTER AS REQUIRED ON A PER PROJECT BASIS.
4. CONTAIN CONSTRUCTION WASTE AND DURING TRANSPORT IN APPROPRIATE CONTAINER.
5. WET MOP AND/OR VACUUM WITH HEPA FILTERED VACUUM BEFORE LEAVING WORK AREAS.
6. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.
7. CLEAN CONSTRUCTION AREA BEFORE LEAVING WORK AREA DAILY.
INTERIM MEASURE CLASS IV
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS PER PROJECT BASIS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS AS REQUIRED ON A PER PROJECT BASIS.
4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING AN HEPA VACUUM CLEANER
BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE AS
REQUIRED PER PROJECT BASIS.
6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR APPROPRIATE PROTECTIVE CLOTHING AS REQUIRED BY THE AREA.
7. PROVIDE ADHESIVE/CARPET WALK-OFF MATS AT ENTRANCE TO WORK AREA WITHIN THE ANTEROOM. REPLACE USED MATS WITH NEW MATS IN
ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND/OR AS NEEDED.
8. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE VAMC’S SAFETY AND INFECTION CONTROL
DEPARTMENTS, COTR, AND THOROUGHLY CLEANED.
9. PROVIDE APPROPRIATE CLEAN UP DAILY.
10. WET MOP AREA WITH DISINFECTANT AS REQUIRED.
11. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION.
12. CONTAIN CONSTRUCTION WASTE BEFORE AND DURING TRANSPORT IN APPROPRIATE COVERED CONTAINERS.
1. REMOVE BARRIER MATERIALS CAREFULLY
TO MINIMIZE SPREADING OF DIRT AND
DEBRIS ASSOCIATED WITH CONSTRUCTION
2. CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS
3. COVER TRANSPORT CONTAINERS. TAPE
COVERING.
4. VACUUM WORK WITH HEPA-FILTERED
VACUUMS
5. WET MOP WITH DISINFECTANT AFTER
BARRIERS ARE REMOVED
6. REMOVE ISOLATION OF HVAC SYSTEM IN
AREAS WHERE WORK IS BEING PERFORMED
CONSTRUCTION ACTIVITY® TYPE “A” TYPE “B” TYPE “C” TYPE “D”
RISK LEVEL
GROUP 1 I II II III/IV
GROUP 2 I II III IV
GROUP 3 I III III/IV IV
GROUP 4 III III/IV III/IV IV
INFECTION CONTROL MATRIX
TYPE OF CONSTRUCTION ACTIVITY TABLE PATIENT RISK GROUP TABLE
4 SOUTH
"A"
4 NORTH
"A"
4 WEST
"B"
4 WEST
"C"
N M L K I H
DUST BARRIER TO BE
CONSTRUCTED AND
REMAIN UNTIL WORK
IN THIS AREA IS
COMPLETE.
PT
STATION
MEDIA WALL
KITCHEN AREA
MILLWORK UNIT
T - 4
S - 6 S - 5
T - 1
T - 2
T - 3
C121B
CORRIDOR
C111
RM
CONFERENCE
1A170
TOILETMALE1A123
1C187C
AND CLERKSECRETARY
1A128
BLOOD BANK
1A172DATA1A171
CHIEF1A131
TREATMENT
1A134
TREATMENT
1A139
RM
BREAK1A169A
OFFICEDENTIST
1A136
OFFICE1A169
SURGERYORAL 1A140
1C228
WAITING
1A125
1A127
STORAGE1C187A
RMDARK
1A135
SUPPLIES
1A130
TREATMENT
1A133
BREAK RM
CONFERENCE /
1A132
PANORAMIC
1A138
X-RAY1A137
SUPPLIES
1A142A
STERILINSTR
1A142
RM
CONFERENCE
1A189
1A114A
CONTROLALCOVE
DIAG
RAPIDIO /
1C227
CHESTAUTO1C190
CORRIDOR
C1 - 30
STORAGE
EQUIP1C191
CORRIDOR
C124
RADIOLOGYREADING RM
1C188
RECEPTION
1C186
WAITING RMRADIOLOGY
1C185
1C191A
OFFICE1C137CHIEF
OFFICE1C138
CLINICAL
OFFICE
PROJECTS
CORRIDOR
1C138A
BREAK RM
1C136
1C142
CONFERENCE /
TRAVEL
SEC
WAITING /
1C134
CORRIDOR
1C143
OFFICER
ADMIN 1C141
INPT
STORAGE
OUTPATIENT
STORAGE
STORAGE
BULK DRUG
1A113E
PREPACK
COMPOUNDING /
1A114B
OFFICEPROC1A121
MAIL / PKG
SHIP / RECG
1A122
CORRIDOR
1A118
OFFICE1A169B
1A126
1C187D 1C187
WAITING
ULTRASOUND
1C187E
1C187BOFFICE
1C187FOFFICE
ANDPREP
P N M L K I HO
DUST BARRIER TO BE
CONSTRUCTED BEFORE
ANY WORK BEGINS AND
REMAIN UNTIL WORK IN
THIS AREA IS COMPLETE.
DUST BARRIER TO BE
CONSTRUCTED AND
REMAIN UNTIL WORK
IN THIS AREA IS
COMPLETE.
CONSTRUCT METAL STUD
WALL WITH GWB EACH
SIDE TO MAINTAIN
CONSTRUCTION LIMITS.
DUST BARRIER TO BE
CONSTRUCTED BEFORE
ANY WORK BEGINS AND
REMAIN UNTIL WORK IN
THIS AREA IS COMPLETE.
DUST BARRIER TO BE
CONSTRUCTED BEFORE
ANY WORK BEGINS AND
REMAIN UNTIL WORK IN
THIS AREA IS COMPLETE.
T-1
T-2
T-3
T-4
STERILIZATION
WASH
MANUAL
WASHCART
STERILIZA-
TION
FEMALE
LA124HAC
LA147
PUMP RMLA148A
HAC
LA130
STER
SUPV
LA140
CLERK
COST ACCNT
LA136A
DIETICIAN
CHIEF ADMIN
LA136B
CORRIDOR
CL9
DISPATCH
LA123
IT
LA122
ELECTRICAL
EQUIPLA100TOILETMALE LA127
MALE
LOCKERS
LA126
STERILIZATION
LC125A
STERILIZATION
PREPARATION AND
LC104
STORAGE RM
STERILIZATION
LC104A
CART WASH
MANUAL
LA149
AND DECONTAM
SOILED RECVG
LA125
CACHE AREA
PHARMACY
LC135
DETERGENT
CENTRAL
LA136
STORAGE AREA
SPD DISPATCH AND
LC102
SEC
SPD
LC101
SPD
CHIEF
LC100
DISHES
SOILED
LA150
DISHES
CLEAN
LA148
WASHING
POT
LA146
RM
MACH
LA145
FREEZER
PREFABRICATED
LA143
IT
LA144
MEAT REFR
PREFABRICATED
LA142
CORRIDOR
CL11
CORRIDOR
CL12A
DAIRY REFR
PREFABRICATED
LA141
VEGET REFRIG
PREFABRICATED
LA139
CORRIDOR
CL12
SPD DISPATCH
LC125A
S-5S-6
AUTOCART
LOCKERS
PLAN
NORTH
SCALE: 1/64" = 1'-0"
24 FIRST FLOOR PLAN
GC200
SCALE: 1/8" = 1'-0"
16 FIRST FLOOR ICRA PLAN
GC200SCALE: 1/8" = 1'-0"
13 GROUND FLOOR ICRA PLAN
GC200
6439 GARNERS FERRY ROAD COLUMBIA, SC
100% BID SET
RENOVATE OR SUITE
SECOND & THIRD FLOOR ICRA PLAN
& NOTES
GC300
MSDLPB312/21/2017DATE-1DESCRIPTION-1
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Office of Construction and Facilities Management
Scale: 1/8"=1'-0"
DESCRIPTION-2
DESCRIPTION-3
DESCRIPTION-4
DESCRIPTION-5
DESCRIPTION-6
DESCRIPTION-7
DESCRIPTION-8
DESCRIPTION-9
DATE-2
DATE-3
DATE-4
DATE-5
DATE-6
DATE-7
DATE-8
DATE-9
(706) 774-1020
ING CONSULTING INC
1201 Broad Street, Suite 1-A Augusta, GA 30901
(706) 724-3551 Office (706) 724-8507 Fax
ELECTRICAL DESIGN CONSULTANTS
550 11th Street Augusta, GA 30901
(706) 556-0197
VETERANS 1ST ARCHITECTURE
110-A North Louisville Street Harlem, GA 30814 WM. JENNINGS BRYAN DORN
Project Location
VA MEDICAL CENTERProject Number: V16-01
Project Number: 16110
INSPECTION AND NON-INVASIVE ACTIVITIES. INCLUDES,
BUT IS NOT LIMITED TO:
1. REMOVAL OF CEILING TILES FOR VISUAL INSPECTION
LIMITED TO 1 TILE PER 50 SQUARE FEET
2. PAINTING (BUT NOT SANDING)
3. WALLCOVERING, ELECTRICAL TRIM WORK, MINOR
PLUMBING, AND ACTIVITIES WHICH DO NOT GENERATE
DUST OR REQUIRE CUTTING OF WALLS OR ACCESS TO
CEILINGS OTHER THAN FOR VISUAL INSPECTION
SMALL SCALE, SHORT DURATION ACTIVITIES WHICH
CREATE MINIMAL DUST INCLUDES, BUT IS NOT LIMITED TO:
1. INSTALLATION OF TELEPHONE AND COMPUTER CABLING
2. ACCESS TO CHASE SPACES
3. CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION
CAN BE CONTROLLED.
WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF
DUST OR REQUIRES DEMOLITION OR REMOVAL OF ANY
FIXED BUILDING COMPONENTS OR ASSEMBLIES INCLUDES,
BUT IS NOT LIMITED TO:
1. SANDING OF WALLS FOR PAINTING OR WALL COVERING
2. REMOVAL OF FLOORCOVERINGS, CEILING TILES AND
CASEWORK
3. NEW WALL CONSTRUCTION
4. MINOR DUCT WORK OR ELECTRICAL WORK ABOVE
CEILINGS
5. MAJOR CABLING ACTIVITIES
6. ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A
SINGLE WORKSHIFT.
MAJOR DEMOLITION AND CONSTRUCTION PROJECTS
INCLUDES, BUT IS NOT LIMITED TO:
1. ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS
2. REQUIRES HEAVY DEMOLITION OR REMOVAL OF A
COMPLETE CABLING SYSTEM
3. NEW CONSTRUCTION.
TYPE A
TYPE B
TYPE C
TYPE D
GROUP 1 LOW RISK GROUP 2 MEDIUM RISK
GROUP 3 MED-HIGH RISK GROUP 4 HIGH RISK
1) OFFICE AREAS
2) ENGINEERING
3) ENVIRONMENTAL
SERVICES
1) AT PATIENT CARE UNITS
(EXAMPLE: CARDIAC,
REHAB., ULTRASOUND)
2) OUTPATIENT AREAS
1) EMERGENCY ROOM
2) RADIOLOGY/MRI
3) POST-ANESTHESIA CARE UNIT
4) INTENSIVE CARE UNITS
5) NUCLEAR MEDICINE
6) ADMISSION/DISCHAR GE AREA
7) PT - TANK AREAS
8) CAFETERIA
9) ECHOCARDIOGRAPHY
10) LABORATORIES
11) DIALYSIS
12) CENTRAL STERILE SUPPLY
13) ONCOLOGY
14) CARDIOLOGY
1) OPERATING
ROOMS; STERILE
PROCESSING
2) INTENSIVE CARE
UNITS 3) CARDIAC
CATHETERIZATION
4) ANESTHESIA
AREAS
5) ALL ENDOSCOPY
AREAS
6) PHARMACY
IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE THE FOLLOWING INFECTION CONTROL PRECAUTIONS
DEPENDING ON THE AREA CLASS DESIGNATION
INTERIM MEASURE CLASS I
1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION OPERATIONS.
2. IMMEDIATELY REPLACE ANY CEILING TILE DISPLACED FOR VISUAL INSPECTION.
3. CLEANUP AND DISPOSAL AS APPROPRIATE.
INTERIM MEASURE CLASS II
1. PROVIDE ACTIVE MEANS TO PREVENT AIR-BORNE DUST FROM DISPERSING INTO ATMOSPHERE, INCLUDING WATER MIST WORK SURFACES TO CONTROL
DUST WHILE CUTTING.
2. SEAL UNUSED DOORS WITH MASKING TAPE
3. BLOCK OFF AND SEAL AIR VENTS.
4. CLEANUP AND DISPOSAL AS APPROPRIATE.
INTERIM MEASURE CLASS III
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM
2. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS OR IMPLEMENT CONTROL CUBE METHOD.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION FILTER AS REQUIRED ON A PER PROJECT BASIS.
4. CONTAIN CONSTRUCTION WASTE AND DURING TRANSPORT IN APPROPRIATE CONTAINER.
5. WET MOP AND/OR VACUUM WITH HEPA FILTERED VACUUM BEFORE LEAVING WORK AREAS.
6. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.
7. CLEAN CONSTRUCTION AREA BEFORE LEAVING WORK AREA DAILY.
INTERIM MEASURE CLASS IV
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS PER PROJECT BASIS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS AS REQUIRED ON A PER PROJECT BASIS.
4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING AN HEPA VACUUM CLEANER
BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE AS
REQUIRED PER PROJECT BASIS.
6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR APPROPRIATE PROTECTIVE CLOTHING AS REQUIRED BY THE AREA.
7. PROVIDE ADHESIVE/CARPET WALK-OFF MATS AT ENTRANCE TO WORK AREA WITHIN THE ANTEROOM. REPLACE USED MATS WITH NEW MATS IN
ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND/OR AS NEEDED.
8. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE VAMC’S SAFETY AND INFECTION CONTROL
DEPARTMENTS, COTR, AND THOROUGHLY CLEANED.
9. PROVIDE APPROPRIATE CLEAN UP DAILY.
10. WET MOP AREA WITH DISINFECTANT AS REQUIRED.
11. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION.
12. CONTAIN CONSTRUCTION WASTE BEFORE AND DURING TRANSPORT IN APPROPRIATE COVERED CONTAINERS.
1. REMOVE BARRIER MATERIALS CAREFULLY
TO MINIMIZE SPREADING OF DIRT AND
DEBRIS ASSOCIATED WITH CONSTRUCTION
2. CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS
3. COVER TRANSPORT CONTAINERS. TAPE
COVERING.
4. VACUUM WORK WITH HEPA-FILTERED
VACUUMS
5. WET MOP WITH DISINFECTANT AFTER
BARRIERS ARE REMOVED
6. REMOVE ISOLATION OF HVAC SYSTEM IN
AREAS WHERE WORK IS BEING PERFORMED
CONSTRUCTION ACTIVITY® TYPE “A” TYPE “B” TYPE “C” TYPE “D”
RISK LEVEL
GROUP 1 I II II III/IV
GROUP 2 I II III IV
GROUP 3 I III III/IV IV
GROUP 4 III III/IV III/IV IV
INFECTION CONTROL MATRIX
TYPE OF CONSTRUCTION ACTIVITY TABLE PATIENT RISK GROUP TABLE
4 SOUTH
"A"
4 NORTH
"A"
4 WEST
"B"
4 WEST
"C"
N
N
M
M
L
L
K
K
I
I
H
H1
DUST BARRIER TO BE
CONSTRUCTED AND
REMAIN UNTIL WORK
IN THIS AREA IS
COMPLETE.
NEW CONTROLS
FOR T-CART DOOR
ONLY, THIS
LOCATION
CONSTRUCT
TEMPORARY
WALL WITH DOOR
N
N
M
M
L
L
K
K
I
I
H
H1
DUST BARRIER TO BE
CONSTRUCTED AND
REMAIN UNTIL
COMPLETION.
NEW CONTROLS
FOR T-CART DOOR
ONLY, THIS
LOCATION
PLAN
NORTH
SCALE: 1/64" = 1'-0"
24 FIRST FLOOR PLAN
GC300
SCALE: 1/8" = 1'-0"
13 SECOND FLOOR ICRA PLAN
GC300 SCALE: 1/8" = 1'-0"
15 THIRD FLOOR ICRA PLAN
GC300
6439 GARNERS FERRY ROAD COLUMBIA, SC
100% BID SET
RENOVATE OR SUITE
FOURTH FLOOR ICRA PLAN & NOTES
GC400
MSDLPB312/21/2017DATE-1DESCRIPTION-1
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Office of Construction and Facilities Management
Scale: 1/8"=1'-0"
DESCRIPTION-2
DESCRIPTION-3
DESCRIPTION-4
DESCRIPTION-5
DESCRIPTION-6
DESCRIPTION-7
DESCRIPTION-8
DESCRIPTION-9
DATE-2
DATE-3
DATE-4
DATE-5
DATE-6
DATE-7
DATE-8
DATE-9
(706) 774-1020
ING CONSULTING INC
1201 Broad Street, Suite 1-A Augusta, GA 30901
(706) 724-3551 Office (706) 724-8507 Fax
ELECTRICAL DESIGN CONSULTANTS
550 11th Street Augusta, GA 30901
(706) 556-0197
VETERANS 1ST ARCHITECTURE
110-A North Louisville Street Harlem, GA 30814 WM. JENNINGS BRYAN DORN
Project Location
VA MEDICAL CENTERProject Number: V16-01
Project Number: 16110
INSPECTION AND NON-INVASIVE ACTIVITIES. INCLUDES,
BUT IS NOT LIMITED TO:
1. REMOVAL OF CEILING TILES FOR VISUAL INSPECTION
LIMITED TO 1 TILE PER 50 SQUARE FEET
2. PAINTING (BUT NOT SANDING)
3. WALLCOVERING, ELECTRICAL TRIM WORK, MINOR
PLUMBING, AND ACTIVITIES WHICH DO NOT GENERATE
DUST OR REQUIRE CUTTING OF WALLS OR ACCESS TO
CEILINGS OTHER THAN FOR VISUAL INSPECTION
SMALL SCALE, SHORT DURATION ACTIVITIES WHICH
CREATE MINIMAL DUST INCLUDES, BUT IS NOT LIMITED TO:
1. INSTALLATION OF TELEPHONE AND COMPUTER CABLING
2. ACCESS TO CHASE SPACES
3. CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION
CAN BE CONTROLLED.
WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF
DUST OR REQUIRES DEMOLITION OR REMOVAL OF ANY
FIXED BUILDING COMPONENTS OR ASSEMBLIES INCLUDES,
BUT IS NOT LIMITED TO:
1. SANDING OF WALLS FOR PAINTING OR WALL COVERING
2. REMOVAL OF FLOORCOVERINGS, CEILING TILES AND
CASEWORK
3. NEW WALL CONSTRUCTION
4. MINOR DUCT WORK OR ELECTRICAL WORK ABOVE
CEILINGS
5. MAJOR CABLING ACTIVITIES
6. ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A
SINGLE WORKSHIFT.
MAJOR DEMOLITION AND CONSTRUCTION PROJECTS
INCLUDES, BUT IS NOT LIMITED TO:
1. ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS
2. REQUIRES HEAVY DEMOLITION OR REMOVAL OF A
COMPLETE CABLING SYSTEM
3. NEW CONSTRUCTION.
TYPE A
TYPE B
TYPE C
TYPE D
GROUP 1 LOW RISK GROUP 2 MEDIUM RISK
GROUP 3 MED-HIGH RISK GROUP 4 HIGH RISK
1) OFFICE AREAS
2) ENGINEERING
3) ENVIRONMENTAL
SERVICES
1) AT PATIENT CARE UNITS
(EXAMPLE: CARDIAC,
REHAB., ULTRASOUND)
2) OUTPATIENT AREAS
1) EMERGENCY ROOM
2) RADIOLOGY/MRI
3) POST-ANESTHESIA CARE UNIT
4) INTENSIVE CARE UNITS
5) NUCLEAR MEDICINE
6) ADMISSION/DISCHAR GE AREA
7) PT - TANK AREAS
8) CAFETERIA
9) ECHOCARDIOGRAPHY
10) LABORATORIES
11) DIALYSIS
12) CENTRAL STERILE SUPPLY
13) ONCOLOGY
14) CARDIOLOGY
1) OPERATING
ROOMS; STERILE
PROCESSING
2) INTENSIVE CARE
UNITS 3) CARDIAC
CATHETERIZATION
4) ANESTHESIA
AREAS
5) ALL ENDOSCOPY
AREAS
6) PHARMACY
IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE THE FOLLOWING INFECTION CONTROL PRECAUTIONS
DEPENDING ON THE AREA CLASS DESIGNATION
INTERIM MEASURE CLASS I
1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION OPERATIONS.
2. IMMEDIATELY REPLACE ANY CEILING TILE DISPLACED FOR VISUAL INSPECTION.
3. CLEANUP AND DISPOSAL AS APPROPRIATE.
INTERIM MEASURE CLASS II
1. PROVIDE ACTIVE MEANS TO PREVENT AIR-BORNE DUST FROM DISPERSING INTO ATMOSPHERE, INCLUDING WATER MIST WORK SURFACES TO CONTROL
DUST WHILE CUTTING.
2. SEAL UNUSED DOORS WITH MASKING TAPE
3. BLOCK OFF AND SEAL AIR VENTS.
4. CLEANUP AND DISPOSAL AS APPROPRIATE.
INTERIM MEASURE CLASS III
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM
2. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS OR IMPLEMENT CONTROL CUBE METHOD.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION FILTER AS REQUIRED ON A PER PROJECT BASIS.
4. CONTAIN CONSTRUCTION WASTE AND DURING TRANSPORT IN APPROPRIATE CONTAINER.
5. WET MOP AND/OR VACUUM WITH HEPA FILTERED VACUUM BEFORE LEAVING WORK AREAS.
6. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.
7. CLEAN CONSTRUCTION AREA BEFORE LEAVING WORK AREA DAILY.
INTERIM MEASURE CLASS IV
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS PER PROJECT BASIS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS AS REQUIRED ON A PER PROJECT BASIS.
4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING AN HEPA VACUUM CLEANER
BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE AS
REQUIRED PER PROJECT BASIS.
6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR APPROPRIATE PROTECTIVE CLOTHING AS REQUIRED BY THE AREA.
7. PROVIDE ADHESIVE/CARPET WALK-OFF MATS AT ENTRANCE TO WORK AREA WITHIN THE ANTEROOM. REPLACE USED MATS WITH NEW MATS IN
ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND/OR AS NEEDED.
8. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE VAMC’S SAFETY AND INFECTION CONTROL
DEPARTMENTS, COTR, AND THOROUGHLY CLEANED.
9. PROVIDE APPROPRIATE CLEAN UP DAILY.
10. WET MOP AREA WITH DISINFECTANT AS REQUIRED.
11. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION.
12. CONTAIN CONSTRUCTION WASTE BEFORE AND DURING TRANSPORT IN APPROPRIATE COVERED CONTAINERS.
1. REMOVE BARRIER MATERIALS CAREFULLY
TO MINIMIZE SPREADING OF DIRT AND
DEBRIS ASSOCIATED WITH CONSTRUCTION
2. CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS
3. COVER TRANSPORT CONTAINERS. TAPE
COVERING.
4. VACUUM WORK WITH HEPA-FILTERED
VACUUMS
5. WET MOP WITH DISINFECTANT AFTER
BARRIERS ARE REMOVED
6. REMOVE ISOLATION OF HVAC SYSTEM IN
AREAS WHERE WORK IS BEING PERFORMED
CONSTRUCTION ACTIVITY® TYPE “A” TYPE “B” TYPE “C” TYPE “D”
RISK LEVEL
GROUP 1 I II II III/IV
GROUP 2 I II III IV
GROUP 3 I III III/IV IV
GROUP 4 III III/IV III/IV IV
INFECTION CONTROL MATRIX
TYPE OF CONSTRUCTION ACTIVITY TABLE PATIENT RISK GROUP TABLE
R
R
Q
Q
P
P
N
N
M
M
L
L
K
K
I
I
H
H1
O
O
1'-6"
TEMPORARY 1 HOUR
RATED WALL,
EXTEND TO DECK
ABOVE.
1 HR. DUST BARRIER TO
BE CONSTRUCTED AND
REMAIN UNTIL
COMPLETION.
TEMPORARY
WALL
CONSTRUCTION
ANTE ROOM
4 SOUTH
"A"
4 NORTH
"A"
4 WEST
"B"
4 WEST
"C"
PLAN
NORTH
SCALE: 1/8" = 1'-0"
13 FOURTH FLOOR ICRA PLAN
GC400
SCALE: 1/64" = 1'-0"
24 FIRST FLOOR PLAN
GC400
6439 GARNERS FERRY ROAD COLUMBIA, SC
100% BID SET
RENOVATE OR SUITE
ARCHITECTURAL DEMOLITION
PLANS
AD401
MSDLPB312/21/2017DATE-1DESCRIPTION-1
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Office of Construction and Facilities Management
Scale: 1/8"=1'-0"
DESCRIPTION-2
DESCRIPTION-3
DESCRIPTION-4
DESCRIPTION-5
DESCRIPTION-6
DESCRIPTION-7
DESCRIPTION-8
DESCRIPTION-9
DATE-2
DATE-3
DATE-4
DATE-5
DATE-6
DATE-7
DATE-8
DATE-9
(706) 774-1020
ING CONSULTING INC
1201 Broad Street, Suite 1-A Augusta, GA 30901
(706) 724-3551 Office (706) 724-8507 Fax
ELECTRICAL DESIGN CONSULTANTS
550 11th Street Augusta, GA 30901
(706) 556-0197
VETERANS 1ST ARCHITECTURE
110-A North Louisville Street Harlem, GA 30814 WM. JENNINGS BRYAN DORN
Project Location
VA MEDICAL CENTERProject Number: V16-01
Project Number: 16110
D1D1
R
R
Q
Q
P
P
N
N
M
M
L
L
K
K
I
I
H
H1
O
O
1'-6"
REMOVE PORTION
OF EXISTING FLOOR AND
STRUCTURE BELOW
FOR INSTALLATION OF NEW
DUMBWAITER TO
CONTINUE
FROM 2ND FLOOR TO THE
4TH FLOOR.
SEE STRUCTURAL PLANS
FOR REWORK OF EXISTING
STRUCTURAL COMPONETS.
REMOVE PORTION OF EXISTING
WALL FOR INSTALLATION OF
NEW DUMBWAITER DOOR AND
FRAME. REPAIR REMAINING
WALLS AND FLOORING TO
MATCH ADJACENT SURFACES.
PROVIDE SMOOTH CLEAN
SURFACE FOR INSTALLATION OF
NEW FINISHES.
REMOVE EXISTING DOOR AND
FRAME, AND ALL ASSOCATED
BLOCKING. REPAIR REMAINING
WALLS AND FLOORING TO
MATCH ADJACENT SURFACES.
PROVIDE SMOOTH CLEAN
SURFACE FOR INSTALLATION OF
NEW WALL.
REMOVE EXISTING DUMBWAITER
REMOVE PORTION OF EXISTING
WALL FOR INSTALLATION OF
NEW DOOR AND FRAME. REPAIR
REMAINING WALLS AND
FLOORING TO MATCH ADJACENT
SURFACES. PROVIDE SMOOTH
CLEAN SURFACE FOR
INSTALLATION OF NEW FINISHES.
REMOVE PORTION OF
EXISTING WALL FOR
INSTALLATION OF
NEW DOOR AND
FRAME. REPAIR
REMAINING WALLS
AND FLOORING TO
MATCH ADJACENT
SURFACES. PROVIDE
SMOOTH CLEAN
SURFACE FOR
INSTALLATION OF
NEW FINISHES.
REMOVE PORTION OF EXISTING
WALL FOR INSTALLATION OF
NEW DOOR AND FRAME. REPAIR
REMAINING WALLS AND
FLOORING TO MATCH ADJACENT
SURFACES. PROVIDE SMOOTH
CLEAN SURFACE FOR
INSTALLATION OF NEW
FINISHES.
TEMPORARY 1 HOUR
RATED WALL,
EXTEND TO DECK
ABOVE.
1 HR. DUST BARRIER TO
BE CONSTRUCTED AND
REMAIN UNTIL
COMPLETION.
TEMPORARY
WALL
REMOVE ALL EXTERIOR
WINDOWS, COMPLETE.
PROVIDE SMOOTH, CLEAN
SURFACE FOR
INSTALLATION OF NEW
WINDOW UNIT AND
PANNING SYSTEM.
REMOVE ALL GYPSUM
WALL BOARD ALONG
EXTERIOR WALL
FOR INSTALLATION OF NEW
INSULATION, TYPICAL ALL
EXTERIOR WALLS WITHIN
SUITE.
REMOVE ALL GYPSUM
WALL BOARD ALONG
EXTERIOR WALL
FOR INSTALLATION OF NEW
INSULATION, TYPICAL ALL
EXTERIOR WALLS WITHIN
SUITE.
REMOVE ALL EXTERIOR
WINDOWS, COMPLETE.
PROVIDE SMOOTH, CLEAN
SURFACE FOR
INSTALLATION OF NEW
WINDOW UNIT AND
PANNING SYSTEM.
ALL INTERIOR WALLS,
DOORS, FRAMES, CEILING,
FLOOR FINISHES,
PLUMBING FIXTURES,
CASEWORK, ETC. TO BE
REMOVED. PROVIDE
SMOOTH CLEAN SURFACE
FOR INSTALLATION OF NEW
WALLS, DOORS, FINISHES,
CEILINGS, ETC.
SEE ASSOCIATED
PLUMBING, MECHANICAL,
ELECTRICAL DEMOLITION
DRAWINGS FOR
REQUIREMENT WITH
THOSE BUILDING
COMPONETS.
CONSTRUCTION
ANTE ROOM
N M L K
REMOVE PORTION
OF EXISTING FLOOR AND
STRUCTURE BELOW
FOR INSTALLATION OF NEW
DUMBWAITER TO
CONTINUE
FROM THE 2ND FLOOR TO
THE 4TH FLOOR.
SEE STRUCTURAL PLANS
FOR REWORK OF EXISTING
STRUCTURAL COMPONETS.
DUST BARRIER TO BE
CONSTRUCTED AND
REMAIN UNTIL
COMPLETION.
4 SOUTH
"A"
4 NORTH
"A"
4 WEST
"B"
4 WEST
"C"
N M L K I
DUST BARRIER TO BE
CONSTRUCTED BEFORE
ANY WORK BEGINS AND
REMAIN UNTIL WORK IN
THIS AREA IS COMPLETE.
DUST BARRIER TO BE
CONSTRUCTED AND
REMAIN UNTIL WORK
IN THIS AREA IS
COMPLETE.
REMOVE EXISTING
CART, RAILS, AND ALL
ASSOICATED
EQUIPMENT FOR THE
INSTALLATION OF NEW
CART, RAILS, AND
ASSOCIATED EQUIPMENT
CONSTRUCT METAL STUD
WALL WITH GWB EACH
SIDE TO MAINTAIN
CONSTRUCTION LIMITS.
DUST BARRIER TO BE
CONSTRUCTED BEFORE
ANY WORK BEGINS AND
REMAIN UNTIL WORK IN
THIS AREA IS COMPLETE.
DUST BARRIER TO BE
CONSTRUCTED BEFORE
ANY WORK BEGINS AND
REMAIN UNTIL WORK IN
THIS AREA IS COMPLETE.
T-1
T-2
T-3
T-4
STERILIZA-
TION
FEMALE
LA124HAC
LA147
PUMP RMLA148A
CORRIDOR
TOILETMALE LA127
MALE
LOCKERS
LA126
CART WASH
MANUAL
LA149
AND DECONTAM
SOILED RECVG
LA125
DISHES
SOILED
LA150
DISHES
CLEAN
LA148
WASHING
POT
LA146
RM
MACH
LA145
FREEZER
PREFABRICATED
LA143
IT
LA144
S-5S-6
LOCKERS
PLAN
NORTH
FIXTURE / CABINET TO BE REMOVED
DOOR, FRAME AND THRESHOLD TO BE REMOVED
EXISTING CONSTRUCTION TO BE REMOVED
EXISTING CONSTRUCTION TO REMAIN
DEMOLITION LEGEND
SCALE: 1/8" = 1'-0"
13 FOURTH FLOOR DEMOLITION
AD401
SCALE: 1/8" = 1'-0"
19 THIRD FLOOR DEMOLITION
AD401 SCALE: 1/64" = 1'-0"
24 KEY PLAN
AD401SCALE: 1/8" = 1'-0"
20 GROUND FLOOR DEMOLITION PLAN
AD401
6439 GARNERS FERRY ROAD COLUMBIA, SC
100% BID SET
RENOVATE OR SUITE
LIFE SAFETY PLAN
A400
MSDLPB312/21/2017DATE-1DESCRIPTION-1
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Office of Construction and Facilities Management
Scale: 1/8"=1'-0"
DESCRIPTION-2
DESCRIPTION-3
DESCRIPTION-4
DESCRIPTION-5
DESCRIPTION-6
DESCRIPTION-7
DESCRIPTION-8
DESCRIPTION-9
DATE-2
DATE-3
DATE-4
DATE-5
DATE-6
DATE-7
DATE-8
DATE-9
(706) 774-1020
ING CONSULTING INC
1201 Broad Street, Suite 1-A Augusta, GA 30901
(706) 724-3551 Office (706) 724-8507 Fax
ELECTRICAL DESIGN CONSULTANTS
550 11th Street Augusta, GA 30901
(706) 556-0197
VETERANS 1ST ARCHITECTURE
110-A North Louisville Street Harlem, GA 30814 WM. JENNINGS BRYAN DORN
Project Location
VA MEDICAL CENTERProject Number: V16-01
Project Number: 16110
EX
DISTANCE: 263'-0"
D
IS
TA
N
C E:
8'
-0
45 45
45 45
DISTANCE: 135'-0"
HORIZ.
EXIT
HORIZ.
EXIT
LATCH.
LATCH.
LATCH.
ELEC.
OPER.
ELEC.
OPER.
ELEC.
OPER.
ELEC.
OPER.
PACU SUITE: 5615 SFOR SUITE: 9,124 SF
EXIST.
MECH.
4A188
PUMP
ROOM
4A182
ORTHO OR
4A187
CARDIO
THORACIC OR
4A186
CLEAN
CORE
4A190
ROBOTICS OR
4A194
HYBRID OR
4A178
VEST.
4A183
RAD.
STOR.
4A196
COMP. NET
4A199
ROB.
EQUIP.
4A195
IMMED.
STERIL.
4A192
H.A.C 4A193
ANESTH.
WORK
ROOM
4A157
PACU.
4A151
PACU.
4A150
SOILED
UTILITY
4A146
GAS. CYL.
STOR.
4A144
PYXIS SUPPLY
4A173
PACU.
4A152
ISO.
PACU.
4A154
MED.
4A156
WORK
ROOM
4A145
HYBRID OR
CONTROL
4A177
ELEC.
4A171
PRE-
OP
4A166
PRE-
OP
4A168
CLEAN
UTILITY
4A143
VEST.
4A197
CORR.
4A198
HYBRID
EQUIP.
4A191
PACU.
4A149
PACU.
4A148
SAT.
LAB
4A180
PAT. TLT.
4A170
ANTE
ROOM
4A153
CORR.
4A142
CORR.
4A147
CORR.
4A155
CORR.
4A162
CORR.
4A172
CORR.
4A175
VEST.
4A179
CORR.
4A185
CORR.
4A189
PAT.
TLT.
4A174
PRE-
OP
4A164
PRE-
OP
4A165
PRE-
OP
4A167
PRE-
OP
4A169
LOCKERS
4A158
LOCKERS
4A160
TLT.
4A159
TLT.
4A161
VEST.
4A176
OR
STOR.
4A181
OR EQUIP.
4A163
1 HOUR FIRE BARRIER 2 HOUR FIRE BARRIER
ALL OPENINGS MUST BE SEALED WITH FIRE-STOPPING.
WALLS MUST RUN FROM FLOOR TO DECK ABOVE.
DAMPERS ARE REQUIRED AT DUCTS PER IBC 717.5.4
RATED 3/4 HOUR.
POSITIVE LATCHING PER IBC 716.5.9.1.
SELF CLOSING PER NFPA 101-8.3.3.3 AND IBC 716.5.9 AND
RELEASE UPON ACTIVATION OF FIRE ALARM.
ALL OPENINGS MUST BE SEALED WITH FIRE-STOPPING.
WALLS MUST RUN FROM FLOOR TO DECK ABOVE.
DAMPERS ARE REQUIRED PER IBC 717.5.4
RATED 1-1/2 HOUR.
POSITIVE LATCHING PER IBC 716.5.9.1.
SELF CLOSING PER NFPA 101-8.3.3.3 AND IBC 716.5.9 AND
RELEASE UPON ACTIVATION OF FIRE ALARM.
WALLS:
DOORS:
WALLS:
DOORS:
ALL OPENINGS MUST BE SEALED WITH FIRE-STOPPING.
WALLS MUST RUN FROM FLOOR TO DECK ABOVE.
DAMPERS ARE REQUIRED PER IBC 717.5.4. AND IBC 717.5.4.1.
RATED 1-1/2 HOUR.
POSITIVE LATCHING PER IBC 716.5.9.1.
SELF CLOSING PER NFPA 101-8.3.3.3 AND IBC 716.5.9 AND
RELEASE UPON ACTIVATION OF FIRE ALARM.
WALLS:
DOORS:
2 HOUR FIRE & SMOKE BARRIER
(PER NFPA 101, 2012 EDITION, AND 2012 IBC)
4 SOUTH
"A"
4 NORTH
"A"
4 WEST
"B"
4 WEST
"C"
PLAN
NORTH
LEGEND OF SYMBOLS
PATH OF EGRESS TRAVEL
1 HR-RATED BARRIER
RATED OPENING (MINUTES)
FIRE EXTINGUISHER -
CABINET MOUNTED
F.E.-1
2 HR-RATED BARRIER
EXIT
LEAD LINED WALL
LEAD LINED DOOR / WINDOWL
2 HR-RATED FIRE AND SMOKE BARRIER
FIRE EXTINGUISHER NOTE:
CONTRACTOR TO PROVIDE ALL FIRE EXTINGUISHERS, WITH ENGAGE SYSTEM
MONITOR ENGAGE. ALL EXTINGUISHERS TO USE FE 36 AND VERIFY THAT ALL
CABINETS HOLD AN EXTINGUISHER MEETING THESE REQUIREMENTS.
SCALE: 1/8" = 1'-0"
13 FOURTH FLOOR LIFE SAFETY PLAN
A400
SCALE: 1/64" = 1'-0"
A400
6439 GARNERS FERRY ROAD COLUMBIA, SC
100% BID SET
RENOVATE OR SUITE
GROUND AND FIRST FLOOR PLANS
A201
MSDLPB312/21/2017DATE-1DESCRIPTION-1
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e…