36C24718R0489-0002003.pdf

PDF 19 MB Posted

Attached to
Renovate 4 South Operating Room Suite, Bldg. 100 Federal contract opportunity
Solicitation number
36C24718R0489
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7

About this file

36C24718R0489 0002 Renovate 4 South OR Drawings2.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Renovate 4 South Operating Room Suite, Bldg. 100, newest first.
File Type Posted
36C24718C0223-000.docx DOCX document
36C24718R0489-0009000.docx DOCX document
36C24718R0489-0008002.pdf PDF
36C24718R0489-0008000.docx DOCX document
36C24718R0489-0008001.pdf PDF
36C24718R0489-0007001.pdf PDF
36C24718R0489-0007000.docx DOCX document
36C24718R0489-0007002.pdf PDF
36C24718R0489-0007003.pdf PDF
36C24718R0489-0006001.pdf PDF
36C24718R0489-0006009.pdf PDF
36C24718R0489-0006003.pdf PDF
36C24718R0489-0006011.pdf PDF
36C24718R0489-0006010.pdf PDF
36C24718R0489-0006007.pdf PDF
36C24718R0489-0006002.pdf PDF
36C24718R0489-0006000.docx DOCX document
36C24718R0489-0006005.pdf PDF
36C24718R0489-0006012.pdf PDF
36C24718R0489-0006004.pdf PDF
36C24718R0489-0006008.pdf PDF
36C24718R0489-0006006.pdf PDF
36C24718R0489-0005000.docx DOCX document
36C24718R0489-0004000.docx DOCX document
36C24718R0489-0003001.pdf PDF
36C24718R0489-0003000.docx DOCX document
36C24718R0489-0002004.pdf PDF
36C24718R0489-0002001.docx DOCX document
36C24718R0489-0002002.pdf PDF
36C24718R0489-0001000.docx DOCX document
36C24718R0489-004.pdf PDF
36C24718R0489-001.docx DOCX document
36C24718R0489-002.pdf PDF
36C24718R0489-003.pdf PDF
36C24718R0489-000.docx DOCX document
Show all 35

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

544-16-100

6439 GARNERS FERRY ROAD COLUMBIA, SC

100% BID SET

SAP12/21/2017

WILLIAM JENNINGS BRYAN DORN

VA MEDICAL CENTER

DATE-1DESCRIPTION-1

(706) 774-1020

ING CONSULTING INC

1201 Broad Street, Suite 1-A Augusta, GA 30901

(706) 724-3551

ELECTRICAL DESIGN CONSULTANTS

550 11th Street Augusta, GA 30901

(706) 556-0197

VETERANS 1ST ARCHITECTURE

110-A North Louisville Street Harlem, GA 30814

DATE-2DESCRIPTION-2

DATE-3DESCRIPTION-3

DATE-4DESCRIPTION-4

DATE-5DESCRIPTION-5

DATE-6DESCRIPTION-6

DATE-7DESCRIPTION-7

DATE-8DESCRIPTION-8

DATE-9DESCRIPTION-9

RENOVATE OR SUITE

PLUMBING LEGEND, ABBREVIATIONS

& NOTES

PL000

12/21/2017

6439 GARNERS FERRY ROAD COLUMBIA, SC

100% BID SET

SAP12/21/2017

WILLIAM JENNINGS BRYAN DORN

VA MEDICAL CENTER

DATE-1DESCRIPTION-1

(706) 774-1020

ING CONSULTING INC

1201 Broad Street, Suite 1-A Augusta, GA 30901

(706) 724-3551

ELECTRICAL DESIGN CONSULTANTS

550 11th Street Augusta, GA 30901

(706) 556-0197

VETERANS 1ST ARCHITECTURE

110-A North Louisville Street Harlem, GA 30814

DATE-2DESCRIPTION-2

DATE-3DESCRIPTION-3

DATE-4DESCRIPTION-4

DATE-5DESCRIPTION-5

DATE-6DESCRIPTION-6

DATE-7DESCRIPTION-7

DATE-8DESCRIPTION-8

DATE-9DESCRIPTION-9

RENOVATE OR SUITE

PLUMBING SCHEDULES

PL001

PLUMBING NARRATIVE MATRIX

SYSTEMS SHEET ABBREV. PIPING / FITTING TYPE JOINING TYPE VALVE INSULATION

TYPE

BELOW SLAB

2"-4" DIA

SANITARY/WASTE

SAN SERVICE WEIGHT CAST IRON

ASTM A 888

NO-HUB COUPLING - HEAVY DUTY

ASTM C 1540

- 1" THICKNESS

ASJ-SSL FIBERGLASS

FLOOR DRAIN BODIES, TRAPS &

PIPING FROM FLOOR DRAINS TO 5'

DOWNSTREAM

ABOVE SLAB

1 1/4"-1 1/2" DIA

SANITARY/WASTE

SAN COPPER DWV

ASTM B 306

SOLDERED

ASTM B 813

SANITARY/WASTE

VENT

V SERVICE WEIGHT CAST IRON

ASTM A 888

NO-HUB COUPLING - HEAVY DUTY

ASTM C 1540

DOMESTIC COLD DCW COPPER TYPE L

HARD DRAWN TUBE

WROUGHT - COPPER PRESSURE FITTINGS

ASTM B 88

SOLDERED

ASTM B 16.18

LEAD-FREE

1"-3" BALL VALVE

FULL PORT TWO PIECE W/ HANDLE EXTENSION

MSS SP-110

PRESSURE RATING 150PSIG

ASJ-SSL FIBERGLASS

1" THICKNESS: 1/2" - 3"

DOMESTIC HOT DHWS COPPER TYPE L

HARD DRAWN TUBE

WROUGHT - COPPER PRESSURE FITTINGS

ASTM B 88

SOLDERED

ASTM B 16.18

LEAD-FREE

1"-3" BALL VALVE

FULL PORT TWO PIECE W/ HANDLE EXTENSION

MSS SP-110

PRESSURE RATING 150PSIG

ASJ-SSL FIBERGLASS

1" THICKNESS: 1/2" - 1 1/4"

2" THICKNESS: 1 1/2" - 3"

HOT WATER RETURN DHWR COPPER TYPE L

HARD DRAWN TUBE

WROUGHT - COPPER PRESSURE FITTINGS

ASTM B 88

SOLDERED

ASTM B 16.18

LEAD-FREE

1"-3" BALL VALVE

FULL PORT TWO PIECE W/ HANDLE EXTENSION

MSS SP-110

PRESSURE RATING 150PSIG

ASJ-SSL FIBERGLASS

1" THICKNESS: 1/2" - 1 1/4"

2" THICKNESS: 1 1/2" - 3"

ROOF DRAIN RD SERVICE WEIGHT CAST IRON

ASTM A 888

NO-HUB COUPLING - XTRA HEAVY DUTY

ASTM C 1540

JOINT RESTRAINTS

- ASJ-SSL FIBERGLASS

ROOF DRAIN BODIES AND ALL

HORIZONTAL & VERTICAL PIPING

MEDICAL GAS O2, MA, CO2, N2, N2O COPPER TYPE L

SEAMLESS DRAWN TEMPERED TUBING PURGE CAPPED

LABELED FOR OXY/MED

WROUGHT-COPPER FITTINGS

CLEANED BAGGED

BRAZED JOINT

AWS A5.8/A5.8M, BCUP SERIES, COPPER-PHOSPHORUS

ALLOYS.

1"-3" BALL VALVE

FULL PORT THREE PIECE LOCKABLE HANDLE

MSS SP-110

PRESSURE RATING 300PSIG

MEDICAL VACUUM VAC COPPER TYPE L

SEAMLESS DRAWN TEMPERED TUBING PURGE CAPPED

LABELED FOR OXY/MED

WROUGHT-COPPER FITTINGS

CLEANED BAGGED

BRAZED JOINT

AWS A5.8/A5.8M, BCUP SERIES, COPPER-PHOSPHORUS

ALLOYS.

1"-3" BALL VALVE

FULL PORT THREE PIECE LOCKABLE HANDLE

MSS SP-110

PRESSURE RATING 300PSIG

STEAM LPS STEEL PIPING SCHED. 80

TYPE S GRADE B THREAED JOINTS

ASTM A 53 / A 53M BLACK STEEL

ASME B31.9

MALLEABLE IRON THREADED FITTINGS & UNIONS

ASME B16.3 CLASS 150

BALL VALVES: 600PSI WOG 150PSIG, TWO PIECE, FULL

PORT, STAINLESS-STEEL TRIM,

(FILLED OR REINFORCED) RPTFE SEAT

BRONZE GATE VALVES: CLASS 150 NRS

STEAM SERVICE RATED

BRONZE GLOBE VALVES: CLASS 150 NONMETALLIC DISC

STEAM SERVICE RATED

ASJ-SSL FIBERGLASS

2" THICKNESS REQUIRED FOR

STEAM PIPING, CONDENSATE

RETURN, CONDENSATE DRAIN,

CONDENSATE PUMP RECEIVER VENT

& OVERFLOW PIPING. JACKETED

WITH ALUMINUM JACKET AND

BANDS.

Demolition The existing plumbing waste, vent, domestic cold, hot, hot water return, med gas, & med vacuum, steam piping and associated fixtures will be removed and piping temporarily capped to allow for new work.

Existing vent terminal through roof will remain in existing locations until new work piping is in place for cut over.

New Work Sanitary waste piping will be show in the 3rd floor ceiling along with Phasing as required by Owner/Occupants. Existing vent piping will be re-routed and extended into newly created 4th floor wall cavities to connect in existing vent terminal through roof. Piping types will be per the above Plumbing Narrative Matrix.

New Roof drain piping will extend the existing Roof Drain piping system above the 4th floor ceiling into newly created 4th floor wall cavities to connect to existing piping in the 3rd floor ceiling cavity. Piping types will be per the above Plumbing Narrative Matrix.

Domestic cold, hot and hot water return piping will be shown to extend from existing piping above the 4th floor ceiling to new fixtures per the VA Standard Design Plates. Piping types will be per the above Plumbing Narrative Matrix.

Med Gas & Med Vacuum will be extended from existing piping above the 4th floor ceiling to new recessed zone valve boxes. New Med Gas & Med Vacuum will extend from the zone valve box to outlets located in each room per the VA Standard Design Plates. Piping types will be per the above Plumbing Narrative Matrix.

LPS Steam piping will extend existing steam piping in the mechanical room to connect to new Air Handler Unit internal steam humidifier. Piping types will be per the above Plumbing Narrative Matrix.

MEDICAL GAS ALARM PANEL SCHEDULE

LOCATION TYPE OF

PANEL

GAGES SERVICE INDICATOR LIGHTS

SURGERY CONTROL

ROOM

AREA ALARM

PANEL

YES OXYGEN LINE PRESSURE ABNORMAL

NITROUS OXIDE LINE PRESSURE ABNORMAL

NITROGEN LINE PRESSURE ABNORMAL

MEDICAL AIR LINE PRESSURE ABNORMAL

MEDICAL VACUUM LINE PRESSURE LOW

TEST BUTTON

RECOVERY ROOMS AREA

(ZONE)

ALARM

PANEL

YES OXYGEN LINE PRESSURE ABNORMAL

NITROUS OXIDE LINE PRESSURE ABNORMAL

NITROGEN LINE PRESSURE ABNORMAL

MEDICAL AIR LINE PRESSURE ABNORMAL

MEDICAL VACUUM LINE PRESSURE LOW

TEST BUTTON

PLUMBING FIXTURE UNIT CALCULATION

MARK DESCRIPTION

Quanity

Drainage F.U. Per Fixture

Potable F.U. Per Fixture

HOT F.U.

Per Fixture

Drainage Total

Potable Total HOT Total

P-101 TOILET- WALL

HUNG

4 4 10 16 40

P-401.0,1,2 LAVATORY 12 1 1.5 1.5 12 18 18

P-510 SINGLE BOWL

SINK COUNTER

MOUNTED

7 2 1.5 1.5 14 10.5 10.5

P-512 SINGLE BOWL

SINK COUNTER

MOUNTED WITH

EYEWASH

1 2 1.5 1.5 2 1.5 1.5

P-519 SCRUB SINK

DOUBLE

4 3 1.5 1.5 12 6 6

P-521 MOP BASIN 1 3 3 3 3 3 3

P-701 SHOWER 2 3 3 6 6

P-708 WALL MOUNTED

EYEWASH

1 0 0

IB-1 ICE VALVE BOX 2 1 2 0

ZVB-1 MED GAS 6-VALVE

ZONE BOX

4 0 0

ZVB-2 MED GAS 3-VALVE

ZONE BOX

1 0 0

FD FLOOR DRAIN 2 2 4 0 0

FCO FLOOR CLEANOUT 0 0

63 87 45

87 FU = 65 GPM 45 FU = 27 GPM

Total Demand

POTABLE = 65 GPM - 2-1/2"CW

SERVICE

HOT = 27 GPM - 1-1/2"HW

SERVICE

PLUMBING FIXTURE SCHEDULE

MARK DESCRIPTION BASIS OF DESIGN CONNECTIONS NOTES

MFR MODEL CW HW WASTE VENT

P-101 TOILET- WALL

HUNG

KOHLER

SLOAN

BEMIS

J.R. SMITH

K-4330 111-1.28

2155_SSCT

0419(L)(R)Y

1-1/4" - 4" 2" ADDITIONAL 2"NO HUB INLET-CONTRACTOR TO FIELD VERIFY LEFT AND RIGHT HAND

WITH INSTALLATION REQUIREMENTS

P-401.0 LAVATORY KOHLER

DELTA

TRUEBRO

K-1723

27C4875-TI

103EZ

1/2" 1/2" 1-1/4 " / 2" 2" C.P. CAST BRASS 17GA OFFSET GRID DRAIN, TRAP WITH CLEANOUT, RIGID C.P. BRASS

TUBE SUPPLIES, C.P. ANGLE STOPS

P-401.1 LAVATORY KOHLER

DELTA

J.R. SMITH

TRUEBRO

K-1723

27C4875-TI

103EZ

1/2" 1/2" 1-1/4 " / 2" 2" C.P. CAST BRASS 17GA OFFSET GRID DRAIN, TRAP WITH CLEANOUT, RIGID C.P. BRASS

TUBE SUPPLIES, C.P. ANGLE STOPS

P-401.2 LAVATORY KOHLER

DELTA

J.R. SMITH

TRUEBRO

K-1723

27C4875-TI

0710DZ

103EZ

1/2" 1/2" 1-1/4 " / 2" 2" C.P. CAST BRASS 17GA OFFSET GRID DRAIN, TRAP WITH CLEANOUT, RIGID C.P. BRASS

TUBE SUPPLIES, C.P. ANGLE STOPS

P-510 SINGLE BOWL SINK

COUNTER

MOUNTED

JUST

DELTA

SL-1815-A-GR

27C4975-TI

1/2" 1/2" 1-1/2" / 2" 2" MCGUIRE C.P. CAST BRASS 17GA OFFSET GRID DRAIN, TRAP WITH CLEANOUT, RIGID

C.P. BRASS TUBE SUPPLIES, C.P. ANGLE STOPS

P-512 SINGLE BOWL SINK

COUNTER

MOUNTED WITH

EYEWASH

JUST

DELTA

GUARDIAN

GUARDIAN

SL-1815-A-GR

27C4875-TI

G1893

G3602LF

1/2" 1/2" 1-1/2" / 2" 2" MCGUIRE C.P. CAST BRASS 17GA OFFSET GRID DRAIN, TRAP WITH CLEANOUT, RIGID

C.P. BRASS TUBE SUPPLIES, C.P. ANGLE STOPS & COUNTER MOUNT EYEWASH

LOCATED ALONG LEFT EDGE OF SINK PER MANUFACTUERS I.O.M. INSTALL SURFACE

MOUNT MIXING VALVE ABOVE CEILING.

P-519 SCRUB SINK DOUBLE JUST

DELTA

J-770-2

1501T3478TR-R7

1/2" 1/2" 2" 2" SURGEONS SCRUB SINK DOUBLE

P-521 MOP BASIN FLORESTONE

DELTA

28T9

1/2" 1/2" 3" 2" MOP BASIN, DELTA #28T9 FAUCET

P-701 SHOWER SYMMONS 3505-H321-V-CYL-B 1/2" 1/2" - - SYMMONS DIA #3501-CYL-B-LP-CHKS

P-708 WALL MOUNTED

EYEWASH

GAURDIAN

GUARDIAN

G1891

G3600LF

1/2" 1/2" 1-1/4" 2" WALL MOUNTED EYEWASH STATION

DB DRAIN BOX CHARLOTTE 2"x4" CAST IRON NO-HUB

INCREASER

- - 2" 2" 2"CAST IRON NO-HUB DRAIN PIPING PENETRATION W/ 2"TO 4" INCREASER EXPOSED

3' A.F.F. BEHIND STAINLESS STEEL WALL ACCESS DOOR TO EXCEPT DRAIN PIPING

FROM OVERHEAD WITH AIR GAP FITTING. SEE DETAIL 3 ON SHEET PL003.

IB-1 ICE VALVE BOX OATLEY 38570 1/2" - - - ICE MAKER VALVE BOX FOR RECESSED WALL MOUNTING T-HANDLE 1/4" TURN BALL

VALVE.

ZVB-1 MED GAS 6-VALVE

ZONE BOX

MEDAES ZVB6 - - - - 6-VALVE BOX RECESSED IN WALL. COORDINATE VALVE SIZES WITH PROJECT

REQUIREMENTS AND INSTALL PER NFPA 99, 2012 EDITION WITH SC AMENDMENTS.

ZVB-2 MED GAS 3-VALVE

ZONE BOX

MEDAES ZVB3 - - - - 3-VALVE BOX RECESSED IN WALL. COORDINATE VALVE SIZES WITH PROJECT

REQUIREMENTS AND INSTALL PER NFPA 99, 2012 EDITION WITH SC AMENDMENTS.

FD FLOOR DRAIN J.R. SMITH 2005Y-B-NB - - 3" 2" J.R.SMITH 2005Y-B-NB STRAINER W/ TRAP PRIMER

FCO FLOOR CLEANOUT J.R. SMITH 4052L-NB - - S.I.P. - J.R. SMITH 4052L-NB

ABBV. DESCRIPTION ABBV. DESCRIPTION ABBV. DESCRIPTION

F.V. FLUSH VALVE R.M. RECESSED WALL MOUNTED D.B. DRAIN BOX

T.T. TANK TYPE W.F. WALL FLANGE STYLE

W.M. WALL MOUNTED S.I.P. PROVIDE / INSTALL SIZE INDICATED ON PLANS

HAND HAND WAND/SLIDE A.C.M. ABOVE CEILING MOUNT

C.M. COUNTER MOUNTED C.P. CHROME POLISHED

SP-LVL SPLIT LEVEL ARRANGEMENT G.M. GROUND MOUNTED

F.M. FLOOR MOUNTED

PLUMBING FIXTURE AND ROUGH-IN NOTES:

1. MANUFACTURER'S AND MODEL NUMBERS SHOWN ABOVE ARE MINIMUM EQUIPMENT / FIXTURE REQUIREMENTS AND ARE THE BASIS OF DESIGN. CONTRACTOR SHALL REFERENCE SPECIFICATIONS FOR ADDITIONAL ACCEPTABLE MANUFACTURERS. PRODUCTS FROM OTHER LISTED MANUFACTURERS MUST MEET THE BASIS OF DESIGN. ALL EQUIPMENT AND INSTALL SHALL MEET PROJECT ISSUE DATE STATE'S ADOPTED IBC, IMC, IPC, NEC, IFGC, IECC AND

ASHRAE 90.1.

2. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE MOUNTING HEIGHTS. [ALL ACCESSIBLE FIXTURES SHALL COMPLY W/ AMERICAN DISABILITY ACT LATEST REVISION AS PUBLISHED BY DEPARTMENT OF JUSTICE ACCESS BOARD AND AMMENDED BY THE STATE OF GEORGIA. NON ACCESSIBLE FIXTURES SHALL COMPLY WITH ARCHITECTURAL DRAWINGS AND MANUFACTURER RECOMMENDED INSTALLATION HEIGHTS.

3. ALL FIXTURES SHALL BE WHITE IN COLOR. FLUSHING LEVERS SHALL BE MOUNTED TO WIDE SIDE OF TOILET.

4. ALL WATER HAMMER ARRESTERS VALVES TO BE INSTALLED IN AN ACCESSIBLE LOCATION, UNLESS SEALED PISTON TYPE APPROVED FOR CONCEALED CONSTRUCTUTION ARE INSTALLED.

6439 GARNERS FERRY ROAD COLUMBIA, SC

100% BID SET

SAP12/21/2017

WILLIAM JENNINGS BRYAN DORN

VA MEDICAL CENTER

DATE-1DESCRIPTION-1

(706) 774-1020

ING CONSULTING INC

1201 Broad Street, Suite 1-A Augusta, GA 30901

(706) 724-3551

ELECTRICAL DESIGN CONSULTANTS

550 11th Street Augusta, GA 30901

(706) 556-0197

VETERANS 1ST ARCHITECTURE

110-A North Louisville Street Harlem, GA 30814

DATE-2DESCRIPTION-2

DATE-3DESCRIPTION-3

DATE-4DESCRIPTION-4

DATE-5DESCRIPTION-5

DATE-6DESCRIPTION-6

DATE-7DESCRIPTION-7

DATE-8DESCRIPTION-8

DATE-9DESCRIPTION-9

RENOVATE OR SUITE

MED GAS SCHEDULE

PL002

PLUMBING SERVICES ROOM DATA SCHEDULE

ROOM NUMBER ROOM NAME MED GAS NEW EXISTING

ROOM NUMBER

EXISTING

ROOM NAME

EXISTING MED GAS

O₂ MED. COMPRESSED AIR VAC NITROGEN WAGD NITROUS OXIDE CARBON DIOXIDE O₂ MED. COMPRESSED AIR VAC

QTY. SCFM ROUGH

IN

QTY. SCFM ROUGH

IN

QTY. SCFM ROUGH

IN

QTY. SCFM ROUGH

IN

QTY. SCFM ROUGH

IN

QTY. SCFM ROUGH

IN

QTY. SCFM ROUGH

IN

QTY. SCFM ROUGH

IN

QTY. SCFM ROUGH

IN

QTY. SCFM ROUGH

IN

4A142 CORR. 4A140 SOCIAL WORKER

4A143 CLEAN UTILITY 4A141 STUDY CUBICLES

4A144 GAS CYL. STOR. 4A142 PULMO RES

4A145 WORK ROOM 4A143 CARDIO RES

4A146 SOILED UTILITY 4A144 SOCIAL WORKER

4A147 CORR. 4A145 MED SERVE ADMIN

4A148 PACU 1 1/2" 1 1/2" 1 3/4" 4A146 RES

4A149 PACU 1 1/2" 1 1/2" 1 3/4" 4A147 RES

4A150 PACU 1 1/2" 1 1/2" 1 3/4" 4A148 RES

4A151 PACU 1 1/2" 1 1/2" 1 3/4" 4A149 ASSIST CHIEF

4A152 PACU 1 1/2" 1 1/2" 1 3/4" 4A150 CHIEF

4A153 ANTE ROOM 4A151 SECY & WAIT

4A154 ISO. PACU 1 1/2" 1 1/2" 1 3/4" 4A153 CLERK

4A155 CORR. 4A154 MED SERV RES

4A156 MED. 4A155 RES

4A157 ANESTH. ROOM 4A156 RES

4A158 LOCKERS 4A158 MULTI BED ICU 16 1/2" 8 1/2" 24 3/4"

4A159 TLT 4A159 INTERVIEW AND CONS.

4A160 LOCKERS 4A160 CLEAN UTILITY

4A161 TLT 4A161 SOILED UTILITY

4A162 CORR. 4A162 H.A.C.

4A163 OR EQUIP. 4A163 TOILET

4A164 PRE-OP 1 1/2" 1 1/2" 1 3/4" 4A164 ISO-2 2 1/2" 1 1/2" 3 3/4"

4A165 PRE-OP 1 1/2" 1 1/2" 1 3/4" 4A165(6) EQUIPMENT STORAGE

4A166 PRE-OP 1 1/2" 1 1/2" 1 3/4" 4A166 WAITING

4A167 PRE-OP 1 1/2" 1 1/2" 1 3/4" 4A167 TOILET

4A168 PRE-OP 1 1/2" 1 1/2" 1 3/4" 4A168 ISO-1 2 1/2" 1 1/2" 3 3/4"

4A169 PRE-OP 1 1/2" 1 1/2" 1 3/4" 4A169 OBS-10 1 1/2" 1 1/2" 1 3/4"

4A170 PAT. TLT. 4A170 TOILET

4A171 ELEC 4A171 OBS-9 1 1/2" 1 1/2" 1 3/4"

4A172 CORR. 4A172 TOILET

4A173 STORAGE 4A173 OBS-8 1 1/2" 1 1/2" 1 3/4"

4A174 PAT. TLT. 4A174 TOILET

4A175 CORR. 4A175 H.A.C.

4A176 VEST 4A176 OBS-7 1 1/2" 1 1/2" 1 3/4"

4A177 HYBRID OR CONTROL 4A177 TOILET

4A178 HYBRID OR 2 1/2" 1 1/2" 8 3/4" 2 1/2" 1 3/4" 1 1/2" 2 1/2" 4A178 STRETCH. SHOWER

4A179 VEST 4A179 OBS-6 1 1/2" 1 1/2" 1 3/4"

4A180 SAT. LAB. 4A180 TOILET

4A181 OR STORAGE 4A181 NOUR. KIT.

4A182 PUMP ROOM 4A182 OBS-5 1 1/2" 1 1/2" 1 3/4"

4A183 VEST 4A183 TOILET

4A184 RAD STORAGE 4A184 NURSE STATION

4A185 CORR. 4A185 TOILET

4A186 CARDIO THORACIC OR 2 1/2" 1 1/2" 8 3/4" 2 1/2" 1 3/4" 1 1/2" 2 1/2" 4A186 OBS-4 1 1/2" 1 1/2" 1 3/4"

4A187 ORTHO OR 2 1/2" 1 1/2" 8 3/4" 2 1/2" 1 3/4" 1 1/2" 2 1/2" 4A187 TOILET

4A188

EXIST MECH. 4A188 EXAM AND TREATMENT 1 1/2" 1 1/2" 1 3/4"

4A189 CORR. 4A189 OBS-3 1 1/2" 1 1/2" 1 3/4"

4A190 CLEAN CORE 4A190 TOILET

4A191 STORAGE 4A191 OBS-2 1 1/2" 1 1/2" 1 3/4"

4A192 IMMED. STERILE 4A192 TOILET

4A193 H.A.C. 4A193 OBS-1 1 1/2" 1 1/2" 1 3/4"

4A194 ROBOTICS OR 2 1/2" 1 1/2" 8 3/4" 2 1/2" 1 3/4" 1 1/2" 2 1/2" 4A194 TOILET

4A195 ROB. EQUIP 4A195 H.V.A.C.

4A196 RAD STORAGE 4A196 LOUNGE

4A197 COMP.NET 4A199 LOCKERS

4A198 CORR. 4A198 TOILET

48199 VEST 4A200 TOILET

TOTAL QTY. SCFM QTY. SCFM QTY. SCFM QTY. SCFM QTY. SCFM QTY. SCFM QTY. SCFM 4A201 ADD. STOR.

20 0 16 0 44 0 8 0 4 0 4 0 8 0 4A202 TUB TREAT

4A203 ON CALL BED

4A204 TOILET

4A205 DAY ROOM

4A206 WH. CH. STORAGE

4A207 CCU-1 2 1/2" 1 1/2" 3 3/4"

4A208 CCU-2 2 1/2" 1 1/2" 3 3/4"

4A209 CCU-3 2 1/2" 1 1/2" 3 3/4"

4A210 CCU-4 2 1/2" 1 1/2" 3 3/4"

4A211 MED CABINET

4A212 TOILET

TOTAL QTY. SCFM QTY. SCFM QTY. SCFM

39 0 25 0 53 0

6439 GARNERS FERRY ROAD COLUMBIA, SC

100% BID SET

SAP12/21/2017

WILLIAM JENNINGS BRYAN DORN

VA MEDICAL CENTER

DATE-1DESCRIPTION-1

(706) 774-1020

ING CONSULTING INC

1201 Broad Street, Suite 1-A Augusta, GA 30901

(706) 724-3551

ELECTRICAL DESIGN CONSULTANTS

550 11th Street Augusta, GA 30901

(706) 556-0197

VETERANS 1ST ARCHITECTURE

110-A North Louisville Street Harlem, GA 30814

DATE-2DESCRIPTION-2

DATE-3DESCRIPTION-3

DATE-4DESCRIPTION-4

DATE-5DESCRIPTION-5

DATE-6DESCRIPTION-6

DATE-7DESCRIPTION-7

DATE-8DESCRIPTION-8

DATE-9DESCRIPTION-9

RENOVATE OR SUITE

PLUMBING DETAILS

PL003

C

B

A D

6439 GARNERS FERRY ROAD COLUMBIA, SC

100% BID SET

SAP12/21/2017

WILLIAM JENNINGS BRYAN DORN

VA MEDICAL CENTER

DATE-1DESCRIPTION-1

(706) 774-1020

ING CONSULTING INC

1201 Broad Street, Suite 1-A Augusta, GA 30901

(706) 724-3551

ELECTRICAL DESIGN CONSULTANTS

550 11th Street Augusta, GA 30901

(706) 556-0197

VETERANS 1ST ARCHITECTURE

110-A North Louisville Street Harlem, GA 30814

DATE-2DESCRIPTION-2

DATE-3DESCRIPTION-3

DATE-4DESCRIPTION-4

DATE-5DESCRIPTION-5

DATE-6DESCRIPTION-6

DATE-7DESCRIPTION-7

DATE-8DESCRIPTION-8

DATE-9DESCRIPTION-9

RENOVATE OR SUITE

SANITARY, VENT AND ROOF DRAIN

PIPING DEMOLITION PLANS

PD101

KEY PLAN

6439 GARNERS FERRY ROAD COLUMBIA, SC

100% BID SET

SAP12/21/2017

WILLIAM JENNINGS BRYAN DORN

VA MEDICAL CENTER

DATE-1DESCRIPTION-1

(706) 774-1020

ING CONSULTING INC

1201 Broad Street, Suite 1-A Augusta, GA 30901

(706) 724-3551

ELECTRICAL DESIGN CONSULTANTS

550 11th Street Augusta, GA 30901

(706) 556-0197

VETERANS 1ST ARCHITECTURE

110-A North Louisville Street Harlem, GA 30814

DATE-2DESCRIPTION-2

DATE-3DESCRIPTION-3

DATE-4DESCRIPTION-4

DATE-5DESCRIPTION-5

DATE-6DESCRIPTION-6

DATE-7DESCRIPTION-7

DATE-8DESCRIPTION-8

DATE-9DESCRIPTION-9

RENOVATE OR SUITE

DOMESTIC, HOT AND MED GAS PIPING

DEMOLITION PLANS

PD102

KEY PLAN

Scale: NTS

DETAIL

544-16-100

6439 GARNERS FERRY ROAD COLUMBIA, SC

100% BID SET

MRSLPB36/21/2017DATE-1DESCRIPTION-1

DESCRIPTION-2

DESCRIPTION-3

DESCRIPTION-4

DESCRIPTION-5

DESCRIPTION-6

DESCRIPTION-7

DESCRIPTION-8

DESCRIPTION-9

DATE-2

DATE-3

DATE-4

DATE-5

DATE-6

DATE-7

DATE-8

DATE-9

(706) 774-1020

ING CONSULTING INC

1201 Broad Street, Suite 1-A Augusta, GA 30901

(706) 724-3551

ELECTRICAL DESIGN CONSULTANTS

550 11th Street Augusta, GA 30901

(706) 556-0197

VETERANS 1ST ARCHITECTURE

110-A North Louisville Street Harlem, GA 30814 WILLIAM JENNINGS BRYAN DORN

VA MEDICAL CENTER

12.21.17

Scale: 3/4"=1'-0"

B1, B2 PLATE

Scale: 3/4"=1'-0"

C1, C2 PLATE

S-100

SPECS & E UIPMENT SUPPORT

DETAILS

R

N M

L K

L K

544-16-100

6439 GARNERS FERRY ROAD COLUMBIA, SC

100% BID SET

MRSLPB36/21/2017DATE-1DESCRIPTION-1

DESCRIPTION-2

DESCRIPTION-3

DESCRIPTION-4

DESCRIPTION-5

DESCRIPTION-6

DESCRIPTION-7

DESCRIPTION-8

DESCRIPTION-9

DATE-2

DATE-3

DATE-4

DATE-5

DATE-6

DATE-7

DATE-8

DATE-9

(706) 774-1020

ING CONSULTING INC

1201 Broad Street, Suite 1-A Augusta, GA 30901

(706) 724-3551

ELECTRICAL DESIGN CONSULTANTS

550 11th Street Augusta, GA 30901

(706) 556-0197

VETERANS 1ST ARCHITECTURE

110-A North Louisville Street Harlem, GA 30814 WILLIAM JENNINGS BRYAN DORN

VA MEDICAL CENTER

12.21.17

S-101

S-101

Scale: 1"=1'-0"

DETAIL

4TH FLOOR DETAILS & ROOF

PLAN