36C24718R0489-0006006.pdf
PDF 1 MB Posted
- Attached to
- Renovate 4 South Operating Room Suite, Bldg. 100 Federal contract opportunity
- Solicitation number
- 36C24718R0489
About this file
36C24718R0489 0006 Revised Mechanical Drawings.pdf
View the file
Other files for this federal contract opportunity
Show all 35
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECT/ENGINEERS: Office of
Construction and Facilities
Management
CONSULTANTS:
DateRevisions: Dwg. of
Drawn
Drawing Number
Project Number
Building Number
Checked
Location
Date
Project Title
Project Location
Drawing Title
VA MEDICAL CENTER
WILLIAM JENNINGS BRYAN DORN
12/21/2017 SAP
100% BID SET
SCCOLUMBIA,6439 GARNERS FERRY ROAD
544-16-100
RENOVATE OR SUITE
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Harlem, GA 30814
110-A North Louisville Street
VETERANS 1ST ARCHITECTURE
(706) 556-0197
Augusta, GA 30901
550 11th Street
ELECTRICAL DESIGN CONSULTANTS
(706) 724-3551
Augusta, GA 30901
1201 Broad Street, Suite 1-A
ING CONSULTING INC
(706) 774-1020
Office of
Construction and Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
MECHANICAL SCHEDULES
M-001
SCC
TERMINAL UNIT SCHEDULE
TAG MANUFACTURER MODEL PRIMARY INLET (")
DESIGN COOLING
AIRFLOW (CFM)
MIN COOLING
AIRFLOW (CFM)
HEATING
AIRFLOW (CFM)
MAX INLET S.P.
(in-wg)
APD @ COOLING
AIRFLOW (in-wg)
PRIMARY EDB
(°F)
HEATING UNIT
LAT (°F)
COIL HEATING
CAPACITY
(BTUh)
HEATING ENT
FLUID TEMP (°F)
HEATING
DELTA T (°F)
HEATING
FLOWRATE (GPM)
OPTIONS
TU-1 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-2 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-3 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-4 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-5 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-6 TRANE VCWF 5" 250 250 250 0.75 0.750 55 80 6,759 180 20 0.68 1, 2, 3, 4, 5, 6
TU-7 TRANE VCWF 5" 145 145 145 0.75 0.000 55 80 3,920 180 20 0.39 1, 2, 3, 4, 5, 6
TU-8 TRANE VCWF 5" 145 145 145 0.75 0.000 55 80 3,920 180 20 0.39 1, 2, 3, 4, 5, 6
TU-9 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-10 TRANE VCWF 8" 875 875 875 0.75 0.750 55 80 23,657 180 20 2.36 1, 2, 3, 4, 5, 6
TU-11 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-12 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-13 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-14 TRANE VCWF 4" 125 125 125 0.75 0.750 55 95 5,407 180 20 0.54 1, 2, 3, 4, 5, 6
TU-15 TRANE VCWF 4" 125 225 225 0.75 0.750 55 80 3,380 180 20 0.34 1, 2, 3, 4, 5, 6
TU-16 TRANE VCWF 4" 125 125 125 0.75 0.750 55 80 3,380 180 20 0.34 1, 2, 3, 4, 5, 6
TU-17 TRANE VCWF 4" 125 125 125 0.75 0.750 55 80 3,380 180 20 0.34 1, 2, 3, 4, 5, 6
TU-18 TRANE VCWF 4" 175 225 225 0.75 0.750 55 80 4,731 180 20 0.47 1, 2, 3, 4, 5, 6
TU-19 TRANE VCWF 4" 175 175 175 0.75 0.750 55 80 4,731 180 20 0.47 1, 2, 3, 4, 5, 6
TU-20 TRANE VCWF 8" 700 700 700 0.75 0.750 55 95 30,280 180 20 3.03 1, 2, 3, 4, 5, 6
AIR HANDLER SCHEDULE
TAG
BASIS OF DESIGN
SUPPLY AIR
FLOW (CFM)
MIN. OUTSIDE
AIR FLOW
(CFM)
RETURN FAN SUPPLY FAN PRE-HEAT COIL PERFORMANCE COOLING PERFORMANCE
WEIGHT
(LBS)
OPTIONS
MANUFACTURER MODEL
AIRFLOW
(CFM)
E.S.P.
(in.wg.)
T.S.P.
(in.wg)
HP
FAN
QTY
VOLTAGE AIRFLOW
E.S.P.
(in.wg.)
T.S.P.
(in.wg)
HP
FAN
QTY.
VOLTAGE SYSTEM TYPE
FACE AREA
(sq.ft.)
FACE VELOCITY
(ft/min)
ROWS
EAT D.B.
(°F)
LAT D.B.
(°F)
TOTAL CAP.
(BTUh)
E.W.T.
(°F)
L.W.T.
(°F)
STEAM
PRESSURE
(PSI)
CONDENSATE
RATE (LBS/HR)
FLUID FLOW
(GPM)
SYSTEM TYPE
FACE AREA
(sq.ft)
FACE VELOCITY
(ft/min)
ROWS
EAT DB
(°F)
EAT WB
(°F)
LAT DB
(°F)
LAT WB
(°F)
TOTAL CAPACITY
(BTUh)
SENSIBLE CAPACITY
(BTUh)
EWT
(°F)
LWT
(°F)
FLUID FLOW
RATE (GPM)
AHU-1 TRANE CSAA SIZE 40 17,500 4,500 17,500 1.50 2.30 8 2 460 21,000 2.50 5.94 20 2 460 STEAM 38 560 1 60 84 549,757 180 160 15.00 685 CHILLED WATER 39 550 6 79 65 53 53 726,236 592,723 46 56 180 11,065 1, 3, 4, 5, 6, 7, 8, 9, 10, 12, 13
RTU-1 TRANE CSAA SIZE 10 4,500 1,300 4,000 2.00 3.24 5 2 460 4,000 2.00 6.23 7.5 2 460 HOT WATER 8 530 1 57 95 164,840 180 160 19 CHILLED WATER 8 500 6 82 67 53 53 173,810 127,250 46 56 35 4,202 1, 2, 5, 6, 7, 8, 9, 11, 13, 14, 15
AIR DEVICE SCHEDULE
TAG MANUFACTURER SERIES DESCRIPTION BORDER TYPE MODULE SIZE OPTIONS
A TITUS OMNI ARCHITECTURAL SQUARE PLAQUE DIFFUSER LAY-IN 24 x 24 1, 2
B TITUS OMNI ARCHITECTURAL SQUARE PLAQUE DIFFUSER SURFACE MOUNT 24 x 24 1, 2
D TITUS OMNI ARCHITECTURAL SQUARE PLAQUE DIFFUSER SURFACE MOUNT 12 x 12 1, 2
E TITUS 50 EGGCRATE RETURN/EXHAUST GRILLE LAY-IN 24 x 24 2
F TITUS 50 EGGCRATE RETURN/EXHAUST GRILLE SURFACE MOUNT 24 x 24 2
G TITUS 50 EGGCRATE RETURN/EXHAUST GRILLE LAY-IN 12 x 12 2
H TITUS 50 EGGCRATE RETURN/EXHAUST GRILLE SURFACE MOUNT 12 x 12 2
I TITUS TLF LAMINAR PATTERN DIFFUSER SURFACE MOUNT 48 x 24 2
J TITUS 350 LOUVERED RETURN GRILLE SURFACE MOUNT 16 x 16 2
K TITUS 350 STAINLESS STEEL LOUVERED RETURN GRILLE SURFACE MOUNT 18 x 30 2
COMPUTER ROOM AIR CONDITIONING UNIT SCHEDULE
TAG MANUFACTURER MODEL
TOTAL CAPACITY
(BTUh)
SENSIBLE CAPACITY
(BTUh)
CHILLED WATER
FLOW RATE (GPM)
VOLTAGE MCA MOCP OPTIONS
CRAC-1 DATA AIRE GFCU-00734 25,000 21,900 6 460 11.30 15 1, 2, 3
HOT WATER HEATING COIL SCHEDULE
TAG MANUFACTURER
AIRFLOW
(CFM)
ENT. AIR.
D.B. (°F)
LVG. AIR
D.B. (°F)
ENT. WATER
TEMP. (°F)
LVG. WATER
TEMP (°F)
HEATING
DELTA T (°F)
HEATING FLOWRATE
(GPM)
HTG. CAPACITY
(BTUh)
OPTIONS
WC-01 TEMTROL 400 55 80 180 160 20 1.08 10,814 1, 2, 3
WC-02 TEMTROL 3,700 55 80 180 160 20 9.99 100,033 1, 2, 3
WC-03 TEMTROL 3,100 55 80 180 160 20 8.37 83,812 1, 2, 3
WC-04 TEMTROL 2,500 55 80 180 160 20 6.75 67,590 1, 2, 3
WC-05 TEMTROL 2,500 55 80 180 160 20 6.75 67,590 1, 2, 3
WC-06 TEMTROL 1,600 55 80 180 160 20 4.32 43,258 1, 2, 3
WC-07 TEMTROL 300 55 80 180 160 20 0.81 8,111 1, 2, 3
WC-08 TEMTROL 300 55 80 180 160 20 0.81 8,111 1, 2, 3
WC-09A TEMTROL 1,620 55 80 180 160 20 4.38 43,798 1, 2, 3
WC-09B TEMTROL 700 55 80 180 160 20 1.89 18,925 1, 2, 3
WC-10 TEMTROL 175 55 80 180 160 20 0.47 4,731 1, 2, 3
WC-11 TEMTROL 350 55 95 180 160 20 1.51 15,140 1, 2, 3
WC-12 TEMTROL 150 55 80 180 160 20 0.41 4,055 1, 2, 3
WC-13 TEMTROL 200 55 95 180 160 20 0.86 8,652 1, 2, 3
EXHAUST FAN SCHEDULE
TAG MANUFACTURER MODEL TYPE
AIRFLOW
(CFM)
STATIC
(IN.WC.)
FAN RPM MOTOR HP BHP DRIVE TYPE SONES VOLTAGE PHASE WEIGHT OPTIONS
EF-1 GREENHECK G-123 CENTRIFUGAL DOWNBLAST 805 0.50 1096 0.25 0.13 DIRECT 7.4 115 1 40 1, 3
EF-2 GREENHECK SWB-110-4
BACKWARD INCLINED
CENTRIGUGAL UTILITY FAN
500 0.50 1096 0.25 0.1 Belt 9 115 1 138 2, 3
EF-3 GREENHECK VEKTOR-H-10
HIGH PLUME DILUTION
BLOWER
460 1.50 2682 0.75 0.56 Belt 14 460 3 739 4, 5
OPTIONS:
1. SINGLE POINT ELECTRICAL CONNECTION FOR UNIT OPERATION. SEPERATE CIRCUITS FOR EACH LIGHTS, RECEPTACLES, ETC.
2. RH COIL CONNECTION, LH ACCESS DOORS, ELECTRICAL & CONTROLS MOUNT.
3. LH COIL CONNECTION, RH ACCESS DOORS, ELECTRICAL & CONTROLS MOUNT.
4. 2" FOAM INJECTED R-13 INSULATED CONSTRUCTION WITH THERMAL BREAK.
5. MARINE LED LIGHTS IN ALL SECTIONS
6. ACCESS SECTIONS, DOORS WITH THERMAL WINDOWS, TEST PORTS.
7. DIFFERENTIAL PRESSURE TEST PORTS & MAGNAHELIC GAUGE ACROSS FILTER SECTIONS.
8. COPPER COIL, COPPER FINS ON ALL COILS.
9. VFD PER FAN, 2x PLENUM FAN ARRAY, SUPPLY & RETURN.
10. INTEGRAL BASE FRAME SIZED FOR PROPER CONDENSATE TRAP DEPTH CLEARANCE FROM FLOOR SLAB.
11. 14 INCH ROOF CURB
12. STEAM HUMIDIFIER SECTION WITH SLOPED STAINLESS STEEL DRAIN PAN.
13. AIRFLOW MONITORING DEVICE EQUAL TO ACCUTROL MODEL IAQ-Tek 2000. TRANSDUCER AND PROBE QUANTITY TO BE DETERMINED BY FINAL
EQUIPMENT SELECTION. FINAL DUCT MOUNTING LOCATION TO BE DETERMINED BY MANUFACTURER RECOMMENDATIONS.
14. 2" FOAM INJECTED R-13 INSULATED CONSTRUCTION WITH THERMAL BREAK. CABINET TO BE SUITABLE FOR EXTERIOR USE WITH PITCHED ROOF
FOR DRAINAGE.
15. PIPE CHASE WITH WEATHERPROOF ACCESS DOOR FOR HYDRONIC PIPING FROM BELOW.
OPTIONS:
1. INSTALL PER MANUFACTURER'S IOM.
2. ACCESS DOORS AT INLET OF BOX AND AT REHEAT COIL.
3. DOUBLE WALL 1" SOLID METAL LINER INSULATED CABINET.
4. WALL MOUNTED THERMOSTAT WITH TEMPERATURE ADJUSTMENT AND DIGITAL DISPLAY INTERLOCKED WITH EMS AND ASSOCIATED TERMINAL UNIT.
5. DDC - PROPORTIONAL HOT WATER CONTROL VALVE PACKAGE.
6. ACTUATOR AND CONTROLS TRANSFORMER TO BE PROVIDED AND INSTALLED BY CONTROLS CONTRACTOR.
OPTIONS:
1. COORDINATE INSTALLATION WITH MANUFACTURER'S RECOMENDATIONS.
2. PROVIDE DUCT ACCESS DOOR DOWNSTREAM OF COIL.
3. DDC PROPORTIONAL HOT WATER CONTROL VALVE PACKAGE.
OPTIONS:
1. INSULATED BACK PAN WITH MINIMUM 6 R-VALUE.
2. MANUFACTURER'S STANDARD WHITE FINISH.
OPTIONS:
1. 3.4 KW STEAM GENERATOR
2. FLOOR STAND
3. MOUNT UNIT ON 4" HOUSEKEEPING PAD
OPTIONS:
1. PROVIDE 14" ROOF CURB
2. INSTALL ON 4" HOUSEKEEPING PAD.
3. FAN TO RUN CONTINUOUSLY. PROVIDE CURRENT TRANSDUCERS TO MONITOR OPERATION WITH ALARM TO EMS.
4. GREENHECK #MSEM MOTOR STARTER WITH NEMA 3R ENCLOSURE. INTEGRATE INTO EMS.
5. INSTALL EQUIPMENT SUPPORTS WITH BUILT IN CANTS AND BOLTED NEOPRENE ISOLATORS TO RAIL SUPPORT.
AIR FLOW CONTROL VALVE SCHEDULE
TAG MANUFACTURER ROOM NAME SERVICE TYPE MODEL
DESIGN AIRFLOW APD @ MAX
DESIGN (in-wg)
OPERATING RANGE
(CFM)
OPTIONS
MIN (CFM) MAX (CFM)
AVE-12 ACCUTROL ANTE ROOM EXHAUST H-AVC5147-06 200 200 0.19 30-315 1, 2, 3, 4
AVS-12 ACCUTROL ANTE ROOM SUPPLY H-AVC5147-06 150 150 0.35 30-315 1, 2, 3, 4, 5
AVR-05 ACCUTROL CARDIOTHORACIC OR RETURN H-AVC5247-18 1,150 2,200 0.34 0-3200 1, 2, 3, 4
AVS-05 ACCUTROL CARDIOTHORACIC OR SUPPLY H-AVC5247-18 1,300 2,500 0.28 0-3200 1, 2, 3, 4, 5
AVR-06 ACCUTROL CLEAN CORE RETURN H-AVC5147-12 500 1,090 0.21 180-1790 1, 2, 3, 4
AVS-06 ACCUTROL CLEAN CORE SUPPLY H-AVC5147-12 575 1,600 0.28 180-1790 1, 2, 3, 4, 5
AVS-11 ACCUTROL CORR. SUPPLY H-AVC5147-08 350 350 0.09 80-800 1, 2, 3, 4
AVR-11 ACCUTROL CORR./VEST. RETURN H-AVC5147-06 350 350 0.28 30-315 1, 2, 3, 4
AVR-02A ACCUTROL HYBRID OR RETURN H-AVC5147-14 800 1,600 0.14 250-2750 1, 2, 3, 4
AVR-02B ACCUTROL HYBRID OR RETURN H-AVC5147-14 800 1,600 0.14 250-2750 1, 2, 3, 4
AVS-02 ACCUTROL HYBRID OR SUPPLY H-AVC5247-36 1,800 3,700 0.16 0-6400 1, 2, 3, 4, 5
AVR-01 ACCUTROL HYBRID OR CONTROL RETURN H-AVC5147-08 200 400 0.17 80-800 1, 2, 3, 4
AVS-01 ACCUTROL HYBRID OR CONTROL SUPPLY H-AVC5147-08 200 400 0.12 80-800 1, 2, 3, 4
AVE-13 ACCUTROL ISO PACU EXHAUST H-AVC5147-06 300 300 0.14 30-315 1, 2, 3, 4
AVS-13 ACCUTROL ISO PACU SUPPLY H-AVC5147-06 200 200 0.35 30-315 1, 2, 3, 4, 5
AVR-04 ACCUTROL ORTHO OR RETURN H-AVC5247-18 1,150 2,200 0.17 0-3200 1, 2, 3, 4
AVS-04 ACCUTROL ORTHO OR SUPPLY H-AVC5247-18 1,300 2,500 0.28 0-3200 1, 2, 3, 4, 5
AVR-07 ACCUTROL PUMP ROOM RETURN H-AVC5147-08 80 260 0.07 80-800 1, 2, 3, 4
AVS-07 ACCUTROL PUMP ROOM SUPPLY H-AVC5147-08 90 300 0.07 80-800 1, 2, 3, 4
AVR-10 ACCUTROL RAD. STOR. RETURN H-AVC5147-06 90 175 0.15 30-315 1, 2, 3, 4
AVS-10 ACCUTROL RAD. STOR. SUPPLY H-AVC5147-06 90 175 0.15 30-315 1, 2, 3, 4
AVR-03A ACCUTROL ROBOTICS OR RETURN H-AVC5147-12 830 1,480 0.30 180-1790 1, 2, 3, 4
AVR-03B ACCUTROL ROBOTICS OR RETURN H-AVC5147-12 700 1,350 0.30 180-1790 1, 2, 3, 4
AVS-03 ACCUTROL ROBOTICS OR SUPPLY H-AVC5247-24 1,600 3,100 0.28 0-4000 1, 2, 3, 4, 5
AVR-08 ACCUTROL SAT. LAB RETURN H-AVC5147-08 350 350 0.08 80-800 1, 2, 3, 4
AVS-08 ACCUTROL SAT. LAB SUPPLY H-AVC5147-08 300 300 0.20 80-800 1, 2, 3, 4
AVR-09 ACCUTROL SEMI. RESTRICTED CORRIDOR RETURN H-AVC5247-18 0 0 0.17 0-3200 1, 2, 3, 4
AVS-09A ACCUTROL SEMI. RESTRICTED CORRIDOR SUPPLY H-AVC5147-12 810 1,620 0.36 180-1790 1, 2, 3, 4
AVS-09B ACCUTROL SEMI. RESTRICTED CORRIDOR SUPPLY H-AVC5147-08 700 350 0.09 80-800 1, 2, 3, 4
OPTIONS:
1. PROVIDE ACUDOR ADWT ACCESS DOOR FOR UNITS ABOVE OPERATING ROOM CEILINGS.
2. ALUMINUM CONSTRUCTION
3. INSULATED HOUSING
4. WALL MOUNTED THERMIDISTAT WITH TEMPERATURE ADJUSTMENT AND DIGITAL DISPLAY INTERLOCKED WITH EMS AND ASSOCIATED
CONTROL VALVE.
5. WALL MOUNTED ROOM PRESSURE AND CONDITION MONITOR EQUAL TO ACCUTROL SRCM. COORDINATE INSTALLATION LOCATION WITH
OWNER REQUIREMENTS AND INSTALLATION RECOMMENDATIONS.
OPERATING ROOM CEILING SYSTEM SCHEDULE
TAG MANUFACTURER MODEL DESCRIPTION 48"x24" 36"x24" 48" x 12"
ACCESS
PANELS
LIGHT TROFFERS
BY OTHERS
OVERALL SIZE OPTIONS
CS-1 PRICE HDCR HEAVY DUTY WELDED CEILING SYSTEM 16 0 2 12 18 20' x 20' 1
CS-2 PRICE HDCR HEAVY DUTY WELDED CEILING SYSTEM 9 2 0 13 12 20' x 16' 1
CS-3 PRICE HDCR HEAVY DUTY WELDED CEILING SYSTEM 9 2 0 14 11 22' x 16' 1
CS-4 PRICE HDCR HEAVY DUTY WELDED CEILING SYSTEM 8 3 0 10 13 20' x 16' 1
OPTIONS:
1. COORDINATE SHOP DRAWING, ELECTRICAL LIGHTING RING & INSTALLATION WITH MEDICAL EQUIPMENT SUPPLIER CEILING BOOM LOCATIONS &
ACCESSORIES.
HEPA FILTER BOX SCHEDULE
TAG /
QTY
MANUFACTURER MODEL
BOX DIMENSIONS
(W" x H" x D")
PRIMARY FILTER SIZE
(W" x H" x D")
FILTER QTY. OPTIONS
FB-1 FLANDERS C4F 24 x 27 x 24 24 x 24 x 11.5 1 1, 2, 3, 4, 5, 6
FB-2 FLANDERS C4F 48 x 24 x 24 24 x 24 x 11.5 2 1, 2, 3, 4, 5, 6
FB-3 FLANDERS C4F 48 x 52 x 24 24 x 24 x 11.5 4 1, 2, 3, 4, 5, 6
OPTIONS:
1. FLUID SEAL.
2. STAINLESS STEEL CONSTRUCTION.
3. MAGNAHELIC DIFFERENTIAL PRESSURE GAUGE.
4. DIFFERENTIAL PRESSURE MONITOR TIED IN TO BUILDING MANAGEMENT SYSTEM.
5. COORDINATE HAND OF UNIT & FINAL INSTALLATION LOCATION FOR SERVICE ACCESSIBILITY.
6. SUPPORT FROM STRUCTURE EACH CORNER WITH ALL THREAD ROD SPRING ISOLATORS SIZED BY
MANUFACTURER. SEE SPECIFICATIONS.
FAN COIL SCHEDULE
TAG MANUFACTURER MODEL CABINET
OUTDOOR
UNIT TAG
FAN COOLING
CAPACITY (BTUH)
ELECTRICAL WEIGHT
(LBS)
OPTIONS
CFM E.S.P. ("W.C.) VOLTAGE PHASE
FC-1 CARRIER 40MHHC09 WALL MOUNTED AC-1 260 - 9,000 208 1 21 1, 2, 3
OPTIONS:
1. INDOOR UNIT TO RECIEVE POWER FROM OUTDOOR UNIT.
2. PROVIDE CONDENSATE PUMP, 53DS900118
3. PROVIDE WIRED WALL MOUNT 7-DAY PROGRAMMABLE CONTROLLER
MINI-SPLIT AIR CONDITIONER SCHEDULE
TAG MANUFACTURER MODEL
NOMINAL COOLING
CAP. (BTUh) VOLTAGE PHASE MCA MOCP
WEIGHT
(LBS.)
AC-1 CARRIER 38MHRC09A 9,000 208 1 8 15 60
1. PRE-SOLICITATION RFI 08/13/2018
LOUVER SCHEDULE
TAG MANUFACTURER MODEL
LOUVER
WIDTH
LOUVER
HEIGHT
LV-1 GREENHECK ESD-435X 8' - 0" 8' - 0"
OPTIONS:
ACTUAL HEIGHT OF LOUVER MAY BE FIELD DETERINED BY
MEASURING FROM THE TOP OF THE EXISTING LOUVER TO APPX.
12" ABOVE FINISHED FLOOR, BUT SHALL BE NO LESS THAN 8'-0"
TALL. INSTALL WITH BOTTOM OF LOUVER APPX. 12" ABOVE
FINISHED FLOOR.
08/10/2018
LEGEND
W = WIDTH
H = HEIGHT
D = DIAMETER
L = LINED DUCT
V.D. = MANUAL VOLUME DAMPER
WITH STANDOFF
A.D. = ACCESS DOOR
FD = TYPE "B" FIRE DAMPER
A.D.
FD
VERTICAL
RETURN
DUCT
VERTICAL
EXHAUST
DUCT
VERTICAL
SUPPLY
DUCT
W x H
L
DØ
VDVD
VD
V D
VD
VD
W x H
CROWN 3300-DS
OR EQUAL
1" THICK ACOUSTIC LINED DUCT.
DIMENSION IS OUTSIDE TO OUTSIDE
SHEET METAL DIMENSIONS
90° ELBOW WITH
DOUBLE THICKNESS
TURNING VANES
M A
X
IM
U M
FLEXIBLE DUCT. PROVIDE
SHEET METAL FITTINGS FOR
ALL CHANGES OF DIRECTION.
CROWN 314-DSO
OR EQUAL
BULLHEAD TEE WITH
TURNING VANES PER
SMACNA
HAND TIGHT PLUG
WATER SEAL
LINE SIZE OF CONDENSATE
CONNECTION ON UNIT
SLOPE TO DRAIN
H
H = FAN INLET PRESSURE
(IN. W.C.) + 1 INCH
H/2 MIN.
FROM COIL PAN
COIL
FULL PORT BALL VALE (TYP.)
UNION (TYP.)
PETE'S P/T
PLUG (TYP.)
BALANCING VALVE
WITH INTEGRAL TEST
PLUGS & CAPS
2-WAY CONTROL VALVE
45 DEGREE
ELBOW (TYP.)
CWS/CWR OR HWS/HWR MAINS
SEE PLAN
FLEXIBLE PIPE
CONNECTION (TYP.)
DRAIN W/ HOSE END
CONN. W/ CAP
MAV
NOTES:
1. PIPING CONNECTIONS FOR 2-WAY VALVE SHOWN ARE SCHEMATIC ONLY. REFER TO FINAL
CONTROL VALVE SUBMITTALS FOR ACTUAL PIPING CONFIGURATION.
2. PIPE WATER COILS FOR COUNTER FLOW. (ENTERING WATER CONTACTS LEAVING AIR.
12x12
12x12
12x12
RECTANGULAR DUCT (SUPPLY, RETURN, EXHAUST)
ROUND DUCT (SUPPLY, RETURN, EXHAUST
FLAT OVAL DUCT (SUPPLY, RETURN, EXHAUST
MPS MEDIUM PRESSURE SUPPLY
RA RETURN AIR DUCT
EA EXHAUST AIR DUCT
T WALL MOUNT THERMOSTAT
LPS PRESSURE SUPPLY
STAINLESS STEEL HATCH
AREA NOT IN CONTRACT HATCH
DEMOLITION HATCH
EGG CRATE RETURN GRILLE WITH
BORDER, FRAME & 22"x22" NECK
LAY-IN CEILING
ACCOUSTICALLY LINED PLENUM
RETURN/EXHAUST PLENUM
MEDIUM PRESSURE
SUPPLY AIR MAIN
CONICAL
TAKE OFF
MEDIUM PRESSURE
FLEX DUCT
TERMINAL UNIT
REDUCER TO MATCH
FLEX & BOX SIZES
LOW PRESSURE DUCT
MAX. LENGTH 4x DUCT DIAMETER
FASTEN & SEAL
DUCT CONNECTION.
TYP
NECK SIZE PER
SCHEDULE
COIL
FULL PORT BALL VALE (TYP.)
UNION (TYP.)
PETE'S P/T
PLUG (TYP.)
BALANCING VALVE
WITH INTEGRAL TEST
PLUGS & CAPS
2-WAY CONTROL VALVE
45 DEGREE
ELBOW (TYP.)
CWS/CWR MAINS
SEE PLAN
FLEXIBLE PIPE
CONNECTION (TYP.)
DRAIN W/ HOSE END
CONN. W/ CAP
MAV
NOTES:
1. PIPING CONNECTIONS FOR 2-WAY VALVE SHOWN ARE SCHEMATIC ONLY. REFER TO FINAL
CONTROL VALVE SUBMITTALS FOR ACTUAL PIPING CONFIGURATION.
2. PIPE WATER COILS FOR COUNTER FLOW. (ENTERING WATER CONTACTS LEAVING AIR.
TRANSITION ADAPTER
INTO TOP OF EXISTING
PIPE
EXISTING CONDENSATE
DRAIN SYSTEM
TO NEAREST DRAIN
TYPE L COPPER TUBING
CONDENSATE PUMP
CONNECTION
FAN COIL
NOTE: CONTRACTOR SHALL REFERENCE
FINAL EQUIPMENT MANUFACTURER
INSTALLATION INSTRUCTIONS FOR
FINAL DIMENSIONS AND PLACEMENT
REQUIREMENTS.
ARCHITECT/ENGINEERS: Office of
Construction and Facilities
Management
CONSULTANTS:
DateRevisions: Dwg. of
Drawn
Drawing Number
Project Number
Building Number
Checked
Location
Date
Project Title
Project Location
Drawing Title
VA MEDICAL CENTER
WILLIAM JENNINGS BRYAN DORN
12/21/2017 SAP
100% BID SET
SCCOLUMBIA,6439 GARNERS FERRY ROAD
544-16-100
RENOVATE OR SUITE
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Harlem, GA 30814
110-A North Louisville Street
VETERANS 1ST ARCHITECTURE
(706) 556-0197
Augusta, GA 30901
550 11th Street
ELECTRICAL DESIGN CONSULTANTS
(706) 724-3551
Augusta, GA 30901
1201 Broad Street, Suite 1-A
ING CONSULTING INC
(706) 774-1020
Office of
Construction and Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
MECHANICAL DETAILS
M-002
SCC
NOT TO SCALEM-002
3 TYPICAL SUPPLY OR RETURN DUCT DETAIL
NOT TO SCALEM-002
NEGATIVE PRESSURE CONDENSATE DRAIN TRAP
DETAIL
NOT TO SCALEM-002
2 TERMINAL UNIT HEATING COIL PIPING DETAIL
NOT TO SCALEM-002
6 RETURN/EXHAUST GRILLE
NOT TO SCALEM-002
8 TERMINAL UNIT CONNECTION DETAIL
MECHANICAL LEGEND
NOT TO SCALEM-002
1 TYPICAL COOLING COIL PIPING DETAIL
NOT TO SCALEM-002
4 CASSETTE COIL CONDENSATE PIPE DETAIL
1. PRE-SOLICITATION RFI 08/13/2018
EXHAUST AIR
D-2
M
ER
V-
P R E
FI
LT
ER
OUTSIDE
AIR
D-1
C O
IL
P R
EH
EA
T
C O
IL
C O O
LI
N G
MPS
V-2
V-1
CHR
CHS
RETURN FAN
SUPPLY FAN AFMD
V-3
LPS
V-4
STEAM HUMIDIFIER
TT
TT
TT TT MT
FT
M
ER
V-
P R E
FI
LT
ER
TT MT
AF
M D
HS
IT
VSMC
VSMC
3 6
SD
STEAM
COIL
CURRENT
TRANSMITTER
FOR FAN
STATUS ,TYP.
RETURN
AIR
PSH
SMOKE
DETECTOR
VARIABLE SPEED
MOTOR
CONTROLLER, TYP.
ZC
FT
PDS
TT
HS
HC
SST
PSL
SD
SD
SD
SPSTSL
AFCV
AFCV
HEPA HEPA
TYP. 2 POSITION AIR
FLOW CONTROL VALVES
W/ REHEAT COIL & HEPA
FILTERS SERVING
OPERATING ROOMS AND
NON O.R. AREAS
ECC
NO
M
ER
V-
AF
TE
R
FI
LT
ER
PDS
AFMD
FT
AFCV
NON
OR
AREA
OR
(TYP.)
AFCV
MT
PLENUM
HOUSED OR
PRESSURE SWITCH LOW
(NEGATIVE) TO DISABLE RETURN
FAN WHEN SMOKE DAMPER IN
RETURN DUCT CLOSES
PRESSURE SWITCH HIGH
(POSITIVE) TO DISABLE
FAN WHEN HIGH
PRESSURE LIMIT
SETPOINT IS REACHED
ZC
D-3
ZC
HS
SST
ECC
IT
AIR FLOW CONTROL
VALVE (2 POSITION)
REHEAT COIL
HEPA FILTER
NOTE 2
NOTE 5
NOTE 4
S U
P P
L Y
A
IR
D U
C T
PDT
NOTE 6
NOTE 3
NOTE 1
NOTE:
1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3
TIMES THE DIAMETER OF INLET.
2. ALL DUCTWORK UPSTREAM OF THE HEPA FILTER SHALL BE GALVANIZED STEEL
3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE
BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS
SHOWN, DOES NOT EXCEED 10 FEET [3M]. FOR LONGER LENGTHS, INCREASE
THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT
STATIC PRESSURE DROP AT OR BELOW 0.1"/100' [0.6894Pa/m].
4. ALL DUCTWORK DOWNSTREAM OF THE HEPA FILTER SHALL BE STAINLESS
STEEL, PROVIDE ACCESS DOOR FOR CLEANING. SEE DETAIL SD233100-27 FOR
LOCATION.
5. PROVIDE SIDE ACCESS FOR FILTER SERVICE. SEE MANUFACTURER'S
SPECIFICATION FOR CLEARANCES.
6. PRESSURE DIFFERENTIAL TRANSMITTER TO EMS.
6" M
IN
[1 m m
DESIGNER NOTE:
PROVIDE ADDITIONAL CONTROLS FOR VAV OPERATION AND FOR
PREVENTING OVER SATURATION OF THE SUPPLY AIR.
STEAM
CONDENSATE
RETURN
TEMPERATURE
SWITCH
SCALE POCKET
HUMIDIFIER
CONTROL
VALVE
TO HUMIDISTAT
MANIFOLD PIPE ADAPTERS
STEAM SUPPLY
ON-OFF CONTROL VALVE DUCT CROSS SECTION
INVERTED BUCKET
TRAP ASSEMBLY
NOTE:
SEE MANUFACTURER'S PIPING RECOMMENDATIONS FOR
FINAL LAYOUT
DU
C T H
EI
GH
T H1/
H
1/ H
1/ H
SUPPLY AIR
STEAM SUPPLY
RETURN OR
EXHAUST AIR
PC
STEAM HUMIDIFIER CONTROL NOTES:
RETURN (OR EXHAUST) AIR HUMIDITY SHALL BE MONITORED. ON A CALL FOR HUMIDIFICATION, HUMIDIFIER VALVE V-1 SHALL MODULATE TO MAINTAIN THE RETURN (OR EXHAUST) AIR HUMIDITY SET POINT TO 30% (ADJUSTABLE). PRIOR TO ACTIVATION OF V-1, THE ON/OFF CONTROL VALVE V-2
SHALL BE ENABLED THROUGH ECC AND JACKET TEMPERATURE SENSED BY TSH SHALL BE WARM
ENOUGH TO PREVENT CONDENSATION. THE HIGH LIMIT HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR DUCT 3000MM [10 FEET] AWAY FROM THE HUMIDIFIER SHALL DISABLE THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE ECC, IF THE SUPPLY AIR HUMIDITY EXCEEDS 90% RH (ADJUSTABLE). THE
AIRFLOW SWITCH SHALL PROVE AIRFLOW BEFORE HUMIDITY CONTROLS ARE ACTIVATED.
TSH
ON/OFF CONTROL
VALVE V-2
RAH
ZC
AFS HHL
HUMIDIFIER TUBES
V-1
STEAM
JACKET
HUMIDIFIER TUBES AIR FLOW
SWITCH
HIGH HUMIDITY
LIMIT SWITCH
RETURN AIR
HUMIDITY
ZONE
CONTROL
PROGRAMMABLE
CONTROLLER
STEAM
CONDENSATE
TEMPERATURE
SENSOR
CONTROL VALVE AND
STEAM SEPARATOR
3000mm
[10'-0" MIN.]
T ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT
TT TEMPERATURE TRANSMITTER
M ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER - WALL MOUNT
MT MOISTURE (HUMIDITY) TRANSMITTER
PT PRESSURE TRANSMITTER
TT TEMPERATURE TRANSMITTER, AVERAGING ELEMENT
FT FLOW TRANSMITTER
IT CURRENT TRANSMITTER
CT CONDUCTIVITY TRANSMITTER
SPS STATIC PRESSURE SENSOR
SD SMOKE DETECTOR
PDT PRESSURE DIFFERENTIAL TRANSMITTER
KR LOCAL RECORDING TIME CLOCK (RUNTIME)
TSL TEMPERATURE SWITCH, LOW (FREEZESTAT)
HS HAND SWITCH (HAND-OFF-AUTO SWITCH)
ZC VALVE OR DAMPER POSITION CONTROLLER
LC LEVEL CONTROLLER
LT LEVEL TRANSMITTER
PDS PRESSURE DIFFERENTIAL SWITCH
TSH TEMPERATURE SWITCH, HIGH (FREEZESTAT)
CONTROLS SYMBOLS
EPT ELECTRONIC TO PNEUMATIC TRANSDUCER
AT CARBON DIOXIDE TRANSMITTER
CARBON MONOXIDE TRANSMITTER
CO2
AT
CO
OCCUPANCY SENSORAT
OC
LTCP LOCAL TEMPERATURE CONTROL PANEL
HVAC HVAC CONTROL PANEL
ECC
INTEGRATE CONTROL POINT ON REMOTE
GRAPHICS WORKSTATION AT ENERGY CONTROL
CENTER
TC TEMPERATURE CONTROLLER. SEE SEQUENCE
OF OPERATION
VSMC VARIABLE SPEED MOTOR CONTROLLER
PC PRESSURE CONTROLLER. SEE SEQUENCE OF
OPERATION
SC SPEED CONTROLLER. SEE SEQUENCE OF
OPERATION
FC FLOW CONTROLLER. SEE SEQUENCE OF
OPERATION
PSH PRESSURE SWITCH HIGH
FSH FLOW SWITCH HIGH
PSL PRESSURE SWITCH LOW
KC TIME CLOCK CONTROLLING EQUIPMENT ON A SCHEDULE
FSL FLOW SWITCH LOW
LENGTH IN DUCT WHEN SPACE PERMITS.)
A
TEMPERATURE SENSING ELEMENT FOR
TRANSMITTING TEMPERATURE TO EMCS
(PROVIDE 12 INCHES [200mm] MINIMUM
SENSOR WITH AVERAGING ELEMENT TO TRANSMIT
TEMPERATURE TO EMCS
MOTOR STARTER
M ELECTRIC OPERATED CONTROL DAMPER/OR VALVE
AFMD AIRFLOW MONITORING DEVICE
EXHAUST AIR
D-3
D-2
M
ER
V-
P R E-
FI
LT
ER
OUTSIDE
AIR
D-1
C O
IL
P R
EH
EA
T
C O
IL
C O O
LI
N G
LOCATE SENSOR
OUTSIDE UNDER
SHIELD
HWR
V-2
V-1
CHR
CHS
RETURN FAN
SUPPLY FAN
AF
M D
AF
M D
TT
TT
TT TT
FT
M
ER
V-
AF
TE
R
FI
LT
ER
TT MT
AF
M D
HS
IT
VSMC
HSVSMC
FT
3 6
H-1
SD
CURRENT
TRANSMITTER
FOR FAN
STATUS ,TYP.
RETURN
AIR
PSH
SMOKE
DETECTOR
VARIABLE SPEED
MOTOR
CONTROLLER, TYP.
ZC
ZC
ZC
FT
PDS
TT
SST
PSL
IT
SST
SD
SD
SD
SPSTSL
TSL-1
NO
ECC
ECC
MT
PRESSURE SWITCH LOW TO DISABLE
RETURN FAN WHEN SMOKE DAMPER
IN RETURN DUCT CLOSES
PRESSURE SWITCH HIGH
TO DISABLE FAN WHEN
HIGH PRESSURE LIMIT
SETPOINT IS REACHED
AFCV
OTHER
EXHAUST
AIR
ISO
AREA
AFCV
HWS
HSMTRST
IT
SST
ECC
TU
PACU
ROOM
1. GENERAL
UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. THE UNIT WILL NORMALLY OPERATE 24 HOUR/DAY. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS "OFF" D-1 AND D-3 SHALL BE FULLY CLOSED. WHEN THE UNIT IS "ON" SD-1 AND SD-2 SHALL BE FULLY OPEN. D-1, D-2 AND D-3 SHALL MODULATE IN ACCORDANCE
WITH THE FOLLOWING SEQUENCE:
2. TEMPERATURE CONTROL
SUPPLY AIR TEMPERATURE SETPOINT (AS SET BY ECC), SENSED BY SENSOR TT-1, SHALL BE MAINTAINED BY SEQUENCING V-1 AND V-2.
HEATING AND COOLING CONTROL VALVES SHALL BE MODULATED VIA PID CONTROL LOOP TO MAINTAIN THE SUPPLY AIR TEMP. VALVES V-1
AND V-2 SHALL NOT BE OPENED SIMULTANEOUSLY.
WHEN THE OUTSIDE AIR ENTHALPY AS CALCULATED BY TT-2 AND MT-3 IS LOWER THAN THE RETURN AIR ENTHALPY AS CALCULATED BY TT-4 AND MT-1 AND THE OUTSIDE AIR DRY BULB IS LESS THAN THE RETURN/EXHAUST DRY BULB TT-4 THE UNIT ECONOMIZER MODE SHALL BE ENABLED. WHEN THE ECONOMIZER IS ENABLED DAMPERS D-1, D-2, AND D-3 SHALL MODULATE TO MAINTAIN THE DISCHARGE AIR SETPOINT AS
SENSED BY THE DISCHARGE AIR SENSOR TT-1.
WHEN THE OUTSIDE AIR ENTHALPY, OR TEMPERATURE, IS HIGHER THAN THE RETURN AIR ENTHALPY, OR TEMPERATURE, THE ECONOMIZER SHALL BE DISABLED, DAMPER D-1 SHALL MODULATE TO MAINTAIN THE MINIMUM OUTSIDE AIR FLOW CFM SETPOINT AND D-2 AND D-3 SHALL
MODULATE TO MAINTAIN OVERALL AIRFLOW CFM SETPOINT.
3. AIR FLOW CONTROL
THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING THE SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER TO MAINTAIN THE TOTAL SUPPLY AIR CFM DURING OCCUPIED MODE. RESET SUPPLY AIR CFM AS EACH 2 POSITION AIR TERMINAL
UNIT SWITCHES TO UNOCCUPIED MODE.
THE DIGITAL CONTROL PANEL, USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS, SHALL RESET THE RETURN AIR FAN TO MAINTAIN A CONSTANT AIR FLOW DIFFERENCE BETWEEN THE SUPPLY AIR AND THE RETURN AIR EQUAL TO MINIMUM OUTSIDE AIR.
USING HIGH PRESSURE SENSOR PSH LOCATED AT THE SUPPLY FAN DISCHARGE, SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" [75mm] OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT PSH DOES EXCEED 3" [75mm] THE SUPPLY AIR FAN SHALL STOP.
PSH SHALL BE HARDWIRED TO THE SUPPLY FAN AND UNIT SHALL BE SHUTDOWN IN HAND, AUTO OR BYPASS MODE. PSH WILL REQUIRE
MANUAL RESET AT THE DEVICE.
USING LOW PRESSURE SENSOR PSL LOCATE AT THE RETURN FAN INLET, SHALL PREVENT
THE RETURN FAN FROM DEVELOPING OVER - 3" [75mm] OF NEGATIVE STATICE PRESSURE (FIELD ADJUSTABLE) IF STATIC PRESSURE AT PSL DOES EXCEED - 3" [75mm] THE RETURN AIR FAN SHALL STOP. PSL SHALL BE HARDWIRED TO THE RETURN FAN AND UNIT SHALL BE SHUTDOWN
IN HAND, AUTO OR BYPASS MODE. PSL WILL REQUIRE MANUAL RESET.
4. HUMIDITY CONTROL
WHEN THE DIGITAL CONTROL PANEL IS NOT CALLING FOR HUMIDITY, SENSED BY RETURN AIR HUMIDITY MT-1, 2-WAY "ON-OFF" CONTROL VALVE V-3 SHALL REMAIN CLOSED. WHEN THE DIGITAL CONTROL PANEL IS CALLING FOR HUMIDITY, V-3 SHALL REMAIN OPEN.
RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT OF 42° F [5.6° C] DEW POINT (ADJ) VIA DIGITAL CONTROL PANEL BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED HUMIDITY. THE DRYBULB TRANSMITTER T-4 AND HUMIDITY TRANSMITTER H-1 IN RETURN AIR SHALL BE USED TO CALCULATE RETURN AIR DEW POINT TEMPERATURE. V-3 SHALL BE CLOSED WHENEVER THE RETURN AIR DEWPOINT IS > 45° F [7°C]. DCP SHALL CLOSE VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH TO KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.
5. FREEZE PROTECTION
IF THE AIR TEMPERATURE AS SENSED BY TT-3 FALLS BELOW 45°F [7°C], AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F [4.4°C], AS SENSED BY THE TSL THE SUPPLY AND RETURN FANS SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. TSL SHALL BE HARDWIRED TO THE SUPPLY FAN AND RETURN FAN AND BOTH SHALL BE SHUTDOWN IN HAND, AUTO OR BYPASS MODE. TSL WILL REQUIRE MANUAL RESET AT THE DEVICE.
6. LOSS OF COOLING PROTECTION
IF THE AIR TEMPERATURE AS SENSED BY TT-1 RAISES ABOVE 65°F [18°C], AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE RAISES ABOVE 70°F [21°C], AS SENSED BY TT-1 THE SUPPLY AND RETURN FANS SHALL SHUT DOWN AND A CRITICAL ALARM
SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC.
7. AUTOMATIC SMOKE SHUTDOWN/RESTART
WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, SD, THE SUPPLY AND RETURN FANS SHALL SHUT "OFF" AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. ALL SMOKE DAMPERS IN THE SUPPLY AND RETURN DUCTS SHALL CLOSE.
EXHAUST FANS SERVING AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. SUPPLY AND RETURN FANS SHALL RESTART AND SMOKE
DAMPERS SHALL OPEN WHEN FIRE ALARM CIRCUIT IS RESET.
8. EMERGENCY CONSTANT SPEED OPERATION
UPON FAILURE OF THE VSMC, THE SUPPLY AND RETURN FANS SHALL BE STARTED/STOPPED MANUALLY AT THE DIGITAL CONTROL PANEL OR THE ECC THROUGH THE BY-PASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT SPEED.
SEQUENCE OF OPERATION FOR AIR HANDLING UNIT FOR SURGICAL SUITE (VAV)
SEQUENCE OF OPERATION FOR PACU AHU (VAV)
1. GENERAL
UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS "OFF" D-1, D-3, SHALL BE FULLY CLOSED. WHEN THE UNIT IS "ON" D-1, SD-1 AND SD-2 SHALL BE FULLY OPEN. D-2 AND D-3 SHALL MODULATE IN ACCORDANCE WITH THE FOLLOWING SEQUENCE:
2. TEMPERATURE CONTROL
SUPPLY AIR TEMPERATURE, SENSED BY TT-1, SHALL BE MAINTAINED AT SETPOINT VIA DIGITAL CONTROL PANEL BY MODULATING V-1 OR D-2 AND D-3
OR V-2 IN SEQUENCE.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS ABOVE 75°F (ADJ) [23.8°C], THE DIGITAL CONTROL PANEL SHALL PREVENT THE MODULATION OF D-2 AND D-3 AND SHALL ASSUME THE MINIMUM OUTSIDE AIR POSITION (D-2 FULLY OPENED AND D-3 FULLY CLOSED). THE DIGITAL CONTROL PANEL SHALL MODULATE V-1 TO MAINTAIN THE SUPPLY AIR TEMPERATURE, SENSED BY TT-1.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS BETWEEN 65°F [18.3°C] AND THE SUPPLY AIR TEMPERATURE SENSED BY TT-1, DAMPER D-2 SHALL FULLY CLOSE AND D1 AND D3 SHALL BE FULLY OPEN (MAXIMUM OUTSIDE AIR POSITION). THE DIGITAL CONTROL PANEL SHALL
MODULATE V-1 TO MAINTAIN THE SUPPLY AIR TEMPERATURE, SENSED BY TT-1.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS BELOW THE SUPPLY AIR TEMPERATURE, SENSED BY TT-1, DAMPERS D1, D-2 AND D-3 SHALL MODULATE TO MAINTAIN THE SCHEDULED SUPPLY AIR TEMPERATURE. IF D-2 IS OPEN AND D-3 IS CLOSED TO MINIMUM OUTSIDE AIR, V-2
SHALL MODULATE OPEN TO MAINTAIN THE SUPPLY AIR TEMPERATURE, SENSED BY TT-1.
3. AIR FLOW CONTROL
THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING THE SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER TO MAINTAIN 1.0" [25mm] OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE), SENSED BY SPS-1. RESET STATIC PRESSURE BASED ON
ACTUAL BUILDING LOAD BY POLLING ALL ATU
THE DIGITAL CONTROL PANEL, USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS, SHALL RESET THE RETURN AIR FAN VSMC TO MAINTAIN A CONSTANT AIR FLOW DIFFERENCE BETWEEN THE SUPPLY AIR AND THE RETURN AIR EQUAL TO MINIMUM OUTSIDE AIR PLUS 200 CFM FOR POSITIVE
BUILDING PRESSURIZATION.
USING HIGH PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE, SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" [75mm] OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 DOES EXCEED 3" [75mm] THE SUPPLY AIR FAN SHALL STOP. SPS-2 SHALL BE HARDWIRED TO THE SUPPLY FAN VSMC AND UNIT SHALL BE SHUTDOWN IN HAND,AUTO OR BYPASS MODE. SPS-2 WILL REQUIRE MANUAL
RESET AT THE DEVICE.
4. HUMIDITY CONTROL
WHEN THE DIGITAL CONTROL PANEL IS NOT CALLING FOR HUMIDITY, SENSED BY RETURN AIR HUMIDITY H-1, 2-WAY "ON-OFF" CONTROL VALVE V-3 SHALL REMAIN CLOSED. WHEN THE DIGITAL CONTROL PANEL IS CALLING FOR HUMIDITY, V-3 SHALL REMAIN OPEN.
RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT OF 35% RH (ADJ) VIA DIGITAL CONTROL PANEL BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED HUMIDITY. THE DCP SHALL OVERRIDE THIS CONTROL TO MAINTAIN HUMIDITY OF 80% AS SENSED BY H-2. DCP SHALL CLOSE VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH TO KEEP THE HUMIDIFIER OFF
UNTIL CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.
5. FREEZE PROTECTION
IF THE AIR TEMPERATURE AS SENSED BY TT-3 FALLS BELOW 45°F [7°C], AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F [4.4°C], AS SENSED BY THE TSL THE SUPPLY AND RETURN FANS SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. TSL SHALL BE HARDWIRED TO THE SUPPLY FAN UFD AND UNIT SHALL BE SHUTDOWN IN
HAND,AUTO OR BYPASS MODE. TSL WILL REQUIRE MANUAL RESET AT THE DEVICE.
6. AUTOMATIC SHUTDOWN/RESTART
WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, SD, THE SUPPLY AND RETURN FANS SHALL SHUT "OFF" AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. ALL SMOKE DAMPERS IN THE SUPPLY AND RETURN DUCTS SHALL CLOSE.
EXHAUST FANS SERVING AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. SUPPLY AND RETURN FANS SHALL RESTART AND SMOKE DAMPERS
SHALL OPEN WHEN FIRE ALARM CIRCUIT IS RESET.
7. EMERGENCY CONSTANT SPEED OPERATION
UPON FAILURE OF THE VSMC, THE SUPPLY AND RETURN FANS SHALL BE STARTED/STOPPED MANUALLY AT THE DIGITAL CONTROL PANEL OR THE ECC
THROUGH THE BY-PASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT SPEED.
ARCHITECT/ENGINEERS: Office of
Construction and Facilities
Management
CONSULTANTS:
DateRevisions: Dwg. of
Drawn
Drawing Number
Project Number
Building Number
Checked
Location
Date
Project Title
Project Location
Drawing Title
VA MEDICAL CENTER
WILLIAM JENNINGS BRYAN DORN
12/21/2017 SAP
100% BID SET
SCCOLUMBIA,6439 GARNERS FERRY ROAD
544-16-100
RENOVATE OR SUITE
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Harlem, GA 30814
110-A North Louisville Street
VETERANS 1ST ARCHITECTURE
(706) 556-0197
Augusta, GA 30901
550 11th Street
ELECTRICAL DESIGN CONSULTANTS
(706) 724-3551
Augusta, GA 30901
1201 Broad Street, Suite 1-A
ING CONSULTING INC
(706) 774-1020
Office of
Construction and Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
MECHANICAL SCHEMATICS
M-003
SCC
NOT TO SCALEM-003
4 AIR HANDLING UNIT FOR SURGICAL SUITE (VAV)
NOT TO SCALEM-003
1 AIR TERMINAL UNITS WITH HEPA FILTER
NOT TO SCALEM-003
3 STEAM HUMIDIFIER - PIPING CONNECTIONS
NOT TO SCALEM-003
2 JACKETED STEAM HUMIDIFIER CONTROLS
NOTE:
NOT ALL DETAILS REFERENCED IN THESE DETAILS AND
SCHEMATICS ARE SHOWN IN THESE DOCUMENTS.
REFER TO THE DEPARTMENT OF VETERANS AFFAIRS
WEBSITE FOR A COMPLETE LIST OF VA DETAILS.
https://www.cfm.va.gov/til/sDetail.asp
NOT TO SCALEM-003
5 AIR HANDLING UNIT FOR PACU (VAV)
1. PRE-SOLICITATION RFI 08/13/2018
ARCHITECT/ENGINEERS: Office of
Construction and Facilities
Management
CONSULTANTS:
DateRevisions: Dwg. of
Drawn
Drawing Number
Project Number
Building Number
Checked
Location
Date
Project Title
Project Location
Drawing Title
VA MEDICAL CENTER
WILLIAM JENNINGS BRYAN DORN
12/21/2017 SAP
100% BID SET
SCCOLUMBIA,6439 GARNERS FERRY ROAD
544-16-100
RENOVATE OR SUITE
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Harlem, GA 30814
110-A North Louisville Street
VETERANS 1ST ARCHITECTURE
(706) 556-0197
Augusta, GA 30901
550 11th Street
ELECTRICAL DESIGN CONSULTANTS
(706) 724-3551
Augusta, GA 30901
1201 Broad Street, Suite 1-A
ING CONSULTING INC
(706) 774-1020
Office of
Construction and Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
MECHANICAL DEMOLITION PLAN
MD001
SCC
N O
R T
H
6" = 1'-0"MD001
1 MECHANICAL ROOM DEMOLITION PLAN
MECHANICAL DEMOLITION PLAN KEY NOTES
DEMO & REMOVE EXISTING EXHAUST FAN. CONTRACTOR TO DETERMINE IF EXHAUST FAN CAN BE USED DURING CONSTRUCTION TO MAINTAIN NEGATIVE PRESSURIZATION IN SPACE.
DEMO & REMOVE EXISTING HOT WATER SUPPLY & RETURN, CHILLED WATER SUPPLY & RETURN, MEDIUM PRESSURE & LOW PRESSURE STEAM PIPING BACK TO NEAREST SHUT OFF
VALVE.
LOUVER TO REMAIN.
FAN & DUCT SERVING FLOOR BELOW TO REMAIN.
DEMO & REMOVE EXISTING AHU-11 & ALL ASSOCIATE MEDIUM PRESSURE SUPPLY & RETURN DUCTWORK
DEMO AND REMOVE EXISTING WALL LOUVER. PREPARE WALL PENETRATION FOR NEW WORK. REMOVE EXISTING EXHAUST FAN. SET ASIDE AND PREPARE FOR NEW WORK.
DEMO AND REMOVE EXISTING HOT WATER PIPING BACK TO 6" ABOVE FLOOR. PROVIDE LINESTOP AS REQUIRED FOR NEW WORK. PREPARE FOR NEW WORK.
1. PRE-SOLICITATION RFI 08/13/2018
QR
EF-2
2 1/2" HWR
20"ø EA
2 1/2" HWS
2" MPS
1 1/2" MPC
3"
4" CWS
5" CWS
4" CWR
5" CWR
EXISTING
EXHAUST LOUVER
EXISTING
INTAKE LOUVER
2 1/2" LPS
"x
E A
1" CWR
1" CWS
48"x24" MPS
"x
E A
CRAC-1
AHU-1
QR
2 1/2" HWR
2 1/2" HWS
2 1/2" CWR
2 1/2" CWS
C W
R
C W
S
UP
DWN
UP
DWN
LV-1
(E)
EXHAUST
FAN
/2
H W
S
ARCHITECT/ENGINEERS: Office of
Construction and Facilities
Management
CONSULTANTS:
DateRevisions: Dwg. of
Drawn
Drawing Number
Project Number
Building Number
Checked
Location
Date
Project Title
Project Location
Drawing Title
VA MEDICAL CENTER
WILLIAM JENNINGS BRYAN DORN
12/21/2017 SAP
100% BID SET
SCCOLUMBIA,6439 GARNERS FERRY ROAD
544-16-100
RENOVATE OR SUITE
o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Harlem, GA 30814
110-A North Louisville Street
VETERANS 1ST ARCHITECTURE
(706) 556-0197
Augusta, GA 30901
550 11th Street
ELECTRICAL DESIGN CONSULTANTS
(706) 724-3551
Augusta, GA 30901
1201 Broad Street, Suite 1-A
ING CONSULTING INC
(706) 774-1020
Office of
Construction and Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
MECHANICAL ROOM SCHEMATIC
MH105
SCC
N O
R T
H
1/4" = 1'-0"MH105
1 MECHANICAL NEW WORK PLAN - MECHANICAL ROOM
MECHANICAL NEW WORK KEYNOTES
1 EXISTING EXHAUST FAN SYSTEM
EXISTING COMMON PIPE, CIRCUIT SETTER, & 3-WAY PIPING ARRAINGEMENT TO REMAIN. NEW WORK TO
BEGIN AT EXISTING SHUT OFF VALVE.
INSTALL AHU-1 ON EXISTING HOUSEKEEPING PAD. EXTEND PAD AS NEEDED TO FIT NEW UNIT.
EXISTING EXHAUST FAN MOUNTED OVERHEAD.
AIRFLOW MONITORING DEVICE EQUAL TO ACCUTROL MODEL IAQ-Tek 2000. TRANSDUCER AND PROBE QUANTITY TO BE DETERMINED BY FINAL EQUIPMENT SELECTION. FINAL DUCT MOUNTING LOCATION TO BE
DETERMINED BY MANUFACTURER RECOMMENDATIONS.
REINSTALL EXISTING EXHAUST FAN IN SAME PLACE AND DUCT DISCHARGE TO LOUVER. PRIOR TO REINSTALLATION CLEAN FAN, REPLACE BELTS AND BEARINGS AND VERIFY THAT FAN IS GENERALLY IN GOOD OPERATING CONDITION. REPLACE PARTS AS REQUIRED. INFILL REMAINING LOUVER AREA WITH 16-GA, SEAMED SHEET METAL AND 3" THICK, POLYISOCYANURATE, CLOSED CELL, R-19 INSULATION BOARD. PAINT EXTERIOR FACING FLAT BLACK. PRIME AND PAINT INTERIOR SHEET METAL TO MATCH WALL COLOR.
ROUTE NEW HW SUPPLY PIPE LOW ACROSS SLAB, TO AVOID INTERFERENCE WITH NEW LOUVER, BEFORE TURNING UP TO ROUTE OVER NEW AIR HANDLING UNIT. PROVIDE NEW 2-1/2" FULL PORT BALL VALVE IN NEW
VERTICAL RISE, AND CAPPED TEE DOWNSTREAM OF BALL VALVE FOR FUTURE USE.
1. PRE-SOLICITATION RFI 08/13/2018
| Sheets |
| M-001 - MECHANICAL SCHEDULES |
| M-002 - MECHANICAL DETAILS |
| M-003 - MECHANICAL SCHEMATICS |
| MD001 - MECHANICAL DEMOLITION PLAN |
| MH105 - MECHANICAL ROOM SCHEMATIC |
File details come from the government source that posted it.