36C24718B0637-0007001.pdf

PDF 666 KB Posted

Attached to
Renovate Wing 6A Amend release date of solicitation Federal contract opportunity
Solicitation number
36C24718B0637
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7

About this file

36C24718B0637 0007 RFI Answers Wing 6A due 9-10-18.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Wing 6A Amend release date of solicitation, newest first.
File Type Posted
36C24718B0637-0007000.docx DOCX document
36C24718B0637-0006001.pdf PDF
36C24718B0637-0006000.docx DOCX document
36C24718B0637-0005000.docx DOCX document
36C24718B0637-0005001.pdf PDF
36C24718B0637-0004002.pdf PDF
36C24718B0637-0004001.pdf PDF
36C24718B0637-0004000.docx DOCX document
36C24718B0637-0003003.pdf PDF
36C24718B0637-0003000.docx DOCX document
36C24718B0637-0003001.pdf PDF
36C24718B0637-0003002.pdf PDF
36C24718B0637-0002000.docx DOCX document
36C24718B0637-0001007.pdf PDF
36C24718B0637-0001002.docx DOCX document
36C24718B0637-0001004.pdf PDF
36C24718B0637-0001009.pdf PDF
36C24718B0637-0001005.pdf PDF
36C24718B0637-0001003.pdf PDF
36C24718B0637-0001006.pdf PDF
36C24718B0637-0001008.pdf PDF
36C24718B0637-010.docx DOCX document
36C24718B0637-001.docx DOCX document
36C24718B0637-000.docx DOCX document
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

From: Guest, Chantel To: Guest, Chantel Subject: FW: RFI Answers Date: Tuesday, September 18, 2018 2:50:34 PM Attachments: RFI ON RECEPTACLE QUESTIONS 9-4-18.pdf

DOOR MONITOR QUESTION 9-6-18.pdf SECURITY HARDWARE QUESTION 9-6-18.pdf

From: Brown, James A.

Sent: Tuesday, September 18, 2018 2:38 PM To: Guest, Chantel <Chantel.Guest@va.gov> Subject: RFI Answers

Question The detail for the door monitoring shows the enclosures being mounted at the Nurse stations, 6A-104 and 6A-132, however the note states to mount these at 48” AFF at door to exit stairway. Provide control at both locations

Also this same note needs some edits to make it clear as to what is needing to be done at the stair door location. Please submit an RFI.

The security system detail for the doors getting card readers show an “access control box” , “electric strike” and “card reader”. We assume this hardware and cabling is being provided and installed by “others” and not the electrical subcontractor since it must interface with the existing security system. Please submit and RFI to confirm as well.

Answer: Coordinate with third party access control vendor identified in the docs

In reference to the question about the access control please have the contractor refer to the general notes on EY101 which address the systems for this project.

In reference to the question about the Door Monitor there is a typo in the note. It should read as follows:

REFER TO DOOR ANNUNCIATOR DETAIL ON THIS SHEET. MOUNT BOXES AT NURSE STATIONS AT 48" ABOVE FINISHED FLOOR. AT DOOR TO EXIT STAIRWAY PROVIDE DOOR CONTACT ON STAIRWELL SIDE OF DOOR.

LEGRAND CORDMATE CHANNEL FROM JUST ABOVE DOOR FRAME TO ABOVE CORRIDOR CEILING AND TURN CONDUCTORS INTO CORRIDOR ABOVE CEILING. ROUTE CONDUITS TO ALARM BOXES IN 1/2" CONDUIT.

Receptacle Question

Answer: In reference to the question about the FC adjacent to the outlet at the Headwall that is not in the legend is to delineate the receptacle that is to go in the media cabinet. FC = Furniture Cabinet. However we also have note 10 on EP101 that tell the contractor to coordinate all receptacle at headwall with your drawing A403.

JB

mailto:Chantel.Guest@va.gov mailto:Chantel.Guest@va.gov

File details come from the government source that posted it.