36C24418B0072-005.pdf
PDF 4 MB Posted
- Attached to
- Renovate Building #2 West Project 542-16-114 Federal contract opportunity
- Solicitation number
- 36C24418B0072
About this file
36C24418B0072 542-16-114_IFB SPEC_Vol 2 08-12.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24418B0072-00008000.docx | DOCX document | |
| 36C24418B0072-00007000.docx | DOCX document | |
| 36C24418B0072-00006001.pdf | ||
| 36C24418B0072-00006000.docx | DOCX document | |
| 36C24418B0072-00005000.docx | DOCX document | |
| 36C24418B0072-00004001.pdf | ||
| 36C24418B0072-00004003.pdf | ||
| 36C24418B0072-00004000.docx | DOCX document | |
| 36C24418B0072-00004002.pdf | ||
| 36C24418B0072-00003000.docx | DOCX document | |
| 36C24418B0072-00002000.docx | DOCX document | |
| 36C24418B0072-00002002.pdf | ||
| 36C24418B0072-00002001.pdf | ||
| 36C24418B0072-00001000.docx | DOCX document | |
| 36C24418B0072-00001002.pdf | ||
| 36C24418B0072-00001003.pdf | ||
| 36C24418B0072-00001001.pdf | ||
| 36C24418B0072-004.pdf | ||
| 36C24418B0072-007.pdf | ||
| 36C24418B0072-006.pdf | ||
| 36C24418B0072-001.docx | DOCX document | |
| 36C24418B0072-003.pdf | ||
| 36C24418B0072-002.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specifications
Coatesville VA Medical Center
1400 Blackhorse Hill Rd. Coatesville, PA 19320
Renovate Building 2 West
Station Project No. 542-16-114
ISSUED FOR BID DOCUMENT
October 13, 2017
Volume 2
Divisions 08-12
DIVISION 08
DOORS AND WINDOWS
Coatesville, Pennsylvania 19320
Renovate Building 2 West
Bancroft Architects + Engineers
TIL Ver. 08-01-16
Station Project No. 542-16-114 08 11 13-1 10/13/2017
SECTION 08 11 13
HOLLOW METAL DOORS AND FRAMES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Hollow metal doors and transom panels hung in hollow metal frames at interior locations.
2. Hollow metal door frames for wood doors and borrowed lights at interior locations.
3. Glazed openings in hollow metal doors.
1.2 RELATED REQUIREMENTS
A. Frames fabricated of structural steel: Section 05 50 00, METAL
FABRICATIONS.
B. Aluminum frames entrance work: Section 08 41 13, ALUMINUM-FRAMED
ENTRANCES AND STOREFRONTS.
C. Door Hardware: Section 08 71 00, DOOR HARDWARE.
D. Glazing: Section 08 80 00, GLAZING.
E. Card Readers and Biometric Devices: Section 28 13 00, PHYSICAL ACCESS
CONTROL SYSTEM.
F. Security Monitors: Section 28 23 00, VIDEO SURVEILLANCE.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American National Standard Institute (ANSI):
1. A250.8-2014 - Standard Steel Doors and Frames.
C. ASTM International (ASTM):
1. A240/A240M-15b - Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications.
2. A653/A653M-15 - Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron
Alloy-Coated (Galvannealed) by the Hot-Dip.
3. A1008/A1008M-15 - Steel, Sheet, Cold-Rolled, Carbon, Structural, High Strength Low Alloy and High Strength Low Alloy with Improved
Formability, Solution Hardened, and Bake Hardenable.
4. B209-14 - Aluminum and Aluminum-Alloy Sheet and Plate.
5. B209M-14 - Aluminum and Aluminum-Alloy Sheet and Plate (Metric).
Renovate Building 2 West
Station Project No. 542-16-114 08 11 13-2 10/13/2017
6. B221-14 - Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes.
7. B221M-13 - Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric).
8. D3656/D3656M-13 - Insect Screening and Louver Cloth Woven from Vinyl
Coated Glass Yarns.
9. E90-09 - Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements.
D. Federal Specifications (Fed. Spec.):
1. L-S-125B - Screening, Insect, Nonmetallic.
E. Master Painters Institute (MPI):
1. No. 18 - Primer, Zinc Rich, Organic.
F. National Association of Architectural Metal Manufacturers (NAAMM):
1. AMP 500-06 - Metal Finishes Manual.
G. National Fire Protection Association (NFPA):
1. 80-16 - Fire Doors and Other Opening Protectives.
H. UL LLC (UL):
1. 10C-09 - Positive Pressure Fire Tests of Door Assemblies.
2. 1784-15 - Air Leakage Tests of Door Assemblies and Other Opening
Protectives.
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Include schedule showing each door and frame requirements, fire label, and smoke control label for openings.
3. Installation instructions.
D. Sustainable Construction Submittals:
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
E. Test reports: Certify products comply with specifications.
1. Sound rated door.
Renovate Building 2 West
Station Project No. 542-16-114 08 11 13-3 10/13/2017
F. Qualifications: Substantiate qualifications comply with specifications.
1. Manufacturer with project experience list.
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications:
1. Regularly manufactures specified products.
2. Manufactured specified products with satisfactory service on five similar installations for minimum five years.
1.6 DELIVERY
A. Fasten temporary steel spreaders across the bottom of each door frame before shipment.
B. Deliver products in manufacturer's original sealed packaging.
C. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.
D. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.7 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight facility.
B. Protect products from damage during handling and construction operations.
1.8 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
PART 2 - PRODUCTS
2.1 SYSTEM PERFORMANCE
A. Design hollow metal doors and frames complying with specified performance:
1. Fire Doors and Frames: UL 10C; NFPA 80 labeled.
a. Fire Ratings: See drawings.
2. Smoke Control Doors and Frames: UL 1784; NFPA 80 labeled, maximum
0.15424 cu. m/s/sq. m (3.0 cfm/sf) at 24.9 Pa (0.10 inches water gage) pressure differential.
2.2 MATERIALS
A. Sheet Steel: ASTM A1008/A1008M, cold-rolled.
Renovate Building 2 West
Station Project No. 542-16-114 08 11 13-4 10/13/2017
B. Aluminum Sheet: ASTM B209M (ASTM B209).
C. Aluminum Extrusions: ASTM B221M (ASTM B221).
2.3 PRODUCTS - GENERAL
A. Provide hollow metal doors and frames from one manufacturer.
B. Sustainable Construction Requirements:
1. Steel Recycled Content: 30 percent total recycled content, minimum.
2. Stainless Steel Recycled Content: 70 percent total recycled content, minimum.
3. Aluminum Recycled Content: 80 percent total recycled content, minimum.
2.4 HOLLOW METAL DOORS
A. Hollow Metal Doors: ANSI A250.8; 44 mm (1-3/4 inches) thick. See drawings for sizes and designs.
B. Door Faces:
1. Interior Doors: Sheet steel.
2. Exterior Doors: Galvanized sheet steel minimum Z120 or ZF120 (G40 or
A40) coating.
C. Door Cores:
1. Interior Doors: Kraft paper honeycomb.
2. Exterior Doors: Polystyrene
3. Fire Doors: Manufacturer's standard complying with specified fire rating performance.
2.5 HOLLOW METAL FRAMES
A. Hollow Metal Frames: ANSI A250.8; face welded. See drawings for sizes and designs.
1. Interior Frames:
a. Level 1 Hollow Metal Doors: 1.0 mm (0.042 inch) thick.
b. Wood Doors and Borrowed Lights: 1.0 mm (0.042 inch) thick.
2. Interior Borrowed Light Frames: 1.3 mm (0.051 inch) thick.
B. Frame Materials:
1. Interior Frames: Sheet steel.
2. Exterior Frames: Galvanized sheet steel minimum Z120 or ZF120 (G40 or A40) coating.
Renovate Building 2 West
Station Project No. 542-16-114 08 11 13-5 10/13/2017
2.6 LOUVERS (NOT USED)
2.7 FABRICATION
A. Hardware Preparation: ANSI A250.8; for hardware specified in Section
08 71 00, DOOR HARDWARE.
B. Hollow Metal Door Fabrication:
1. Close top edge of exterior doors flush and seal to prevent water intrusion.
2. Fill spaces between vertical steel stiffeners with insulation.
C. Fire Doors:
1. Close top and vertical edges flush.
2. Apply steel astragal to active leaf at pair and double egress doors.
a. Exception: Where vertical rod exit devices are specified for both leaves swinging in same direction.
3. Fire Door Clearances: NFPA 80.
D. Custom Metal Hollow Doors:
1. Provide custom hollow metal doors where nonstandard steel doors are shown on drawings.
a. Provide door sizes, design, materials, construction, gages, and finish as specified for standard steel doors.
E. Transom Panel Fabrication:
1. Fabricate panels as specified for doors.
2. Fabricate bottom edge with rabbet stop where no transom bar occurs.
F. Hollow Metal Frame Fabrication:
1. Fasten mortar guards to back of hardware reinforcements, except on lead-lined frames.
2. Terminated Stops: ANSI A250.8.
3. Borrowed Light Frames:
a. Provide integral stop on exterior, corridor, or secure side of door.
b. Design rabbet width and depth to receive glazing material or panel shown on drawings.
4. Frame Anchors:
a. Floor anchors:
1) Provide extension type floor anchors to compensate for depth of floor fills.
Renovate Building 2 West
Station Project No. 542-16-114 08 11 13-6 10/13/2017
2) Provide 1.3 mm (0.053 inch) thick steel clip angles welded to jamb and drilled to receive floor fasteners.
3) Provide 50 mm by 50 mm by 9 mm (2 inch by 2 inch by 3/8 inch) clip angle for lead lined frames, drilled for floor fasteners.
4) Provide mullion 2.3 mm (0.093 inch) thick steel channel anchors, drilled for two floor fasteners and frame anchor screws.
5) Provide continuous 1 mm (0.042 inch) thick steel rough bucks drilled for floor fasteners and frame anchor screws for sill sections.
a) Space floor bolts50 mm (24 inches) on center.
b. Jamb anchors:
1) Place anchors on jambs:
a) Near top and bottom of each frame.
b) At intermediate points at maximum 600 mm (24 inches) spacing.
2) Form jamb anchors from steel minimum 1 mm (0.042 inch) thick.
3) Anchors set in masonry: Provide adjustable anchors designed for friction fit against frame and extended into masonry minimum 250 mm (10 inches). Provide one of following types:
a) Wire Loop Type: 5 mm (3/16 inch) diameter wire.
b) T-Shape type.
c) Strap and stirrup type: Corrugated or perforated sheet steel.
4) Anchors for stud partitions: Provide tabs for securing anchor to sides of studs. Provide one of the following:
a) Welded type.
b) Lock-in snap-in type.
5) Anchors for frames set in prepared openings:
a) Steel pipe spacers 6 mm (1/4 inch) inside diameter, welded to plate reinforcing at jamb stops, or hat shaped formed strap spacers 50 mm (2 inches) wide, welded to jamb near stop.
b) Drill jamb stop and strap spacers for 6 mm (1/4 inch) flat head bolts to pass through frame and spacers.
Renovate Building 2 West
Station Project No. 542-16-114 08 11 13-7 10/13/2017
c) Two piece frames: Subframe or rough buck drilled for 6 mm
(1/4 inch) bolts.
6) Anchors for observation windows and other continuous frames set in stud partitions.
a) Weld clip anchors to sills and heads of continuous frames over 1200 mm (4 feet) long.
b) Space maximum 600 mm (24 inches) on centers.
7) Modify frame anchors to fit special frame and wall construction.
8) Provide special anchors where shown on drawings and where required to suit application.
2.8 FINISHES
A. Steel and Galvanized Steel: ANSI A250.8; shop primed.
B. Finish exposed surfaces after fabrication.
2.9 ACCESSORIES
A. Primers: ANSI A250.8.
B. Barrier Coating: ASTM D1187/D1187M.
C. Welding Materials: AWS D1.1/D1.1M, type to suit application.
D. Clips Connecting Members and Sleeves: Match door faces.
E. Fasteners: Galvanized steel.
1. Metal Framing: Steel drill screws.
2. Masonry and Concrete: Expansion bolts and power actuated drive pins.
F. Anchors: Galvanized steel.
G. Galvanizing Repair Paint: MPI No. 18.
H. Insulation: Unfaced mineral wool.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
B. Protect existing construction and completed work from damage.
C. Apply barrier coating to metal surfaces in contact with cementitious materials to minimum 0.7 mm (30 mils) dry film thickness.
3.2 INSTALLATION - GENERAL
A. Install products according to manufacturer's instructions and approved submittal drawings.
Renovate Building 2 West
Station Project No. 542-16-114 08 11 13-8 10/13/2017
1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.
2. Install fire doors and frames according to NFPA 80.
3. Install smoke control doors and frames according to NFPA 105.
3.3 FRAME INSTALLATION
A. Apply barrier coating to concealed surfaces of frames built into masonry.
B. Plumb, align, and brace frames until permanent anchors are set.
1. Use triangular bracing near each corner on both sides of frames with temporary wood spreaders at midpoint.
2. Use wood spreaders at bottom of frame when shipping spreader is removed.
3. Where construction permits concealment, leave shipping spreaders in place after installation, otherwise remove spreaders when frames are set and anchored.
4. Remove wood spreaders and braces when walls are built and jamb anchors are secured.
C. Floor Anchors:
1. Anchor frame jambs to floor with two expansion bolts.
a. Lead Lined Frames: Use 9 mm (3/8 inch) diameter bolts.
b. Other Frames: Use 6 mm (1/4 inch) diameter bolts.
2. Power actuated drive pins are acceptable to secure frame anchors to concrete floors.
D. Jamb Anchors:
1. Masonry Walls:
a. Embed anchors in mortar.
b. Fill space between frame and masonry with grout or mortar as walls are built.
2. Metal Framed Walls: Secure anchors to sides of studs with two fasteners through anchor tabs.
3. Prepared Masonry and Concrete Openings:
a. Direct Securement: 6 mm (1/4 inch) diameter expansion bolts through spacers.
b. Subframe or Rough Buck Securement:
Renovate Building 2 West
Station Project No. 542-16-114 08 11 13-9 10/13/2017
1) 6 mm (1/4 inch) diameter expansion bolts on 600 mm (24 inch) centers.
2) Power activated drive pins on 600 mm (24 inches) centers.
c. Secure two-piece frames to subframe or rough buck with machine screws on both faces.
E. Frames for Sound Rated Doors: Fill frames with insulation.
F. Lead Lined Frames:
1. Extend jambs and anchor with clip angles to structure above.
a. Fasteners to Concrete: Minimum two, 9 mm (3/8 inch) diameter expansion bolts.
b. Connection to Structural Steel: Welded.
G. Touch up damaged factory finishes.
1. Repair galvanized surfaces with galvanized repair paint.
2. Repair painted surfaces with touch up primer.
3.4 DOOR INSTALLATION
A. Install doors plumb and level.
B. Adjust doors for smooth operation.
C. Touch up damaged factory finishes.
1. Repair galvanized surfaces with galvanized repair paint.
2. Repair painted surfaces with touch up primer.
3.5 CLEANING
A. Clean exposed door and frame surfaces. Remove contaminants and stains.
3.6 PROTECTION
A. Protect doors and frames from traffic and construction operations.
B. Remove protective materials immediately before acceptance.
C. Repair damage.
- - - E N D - - -
Renovate Building 2 West
Station Project No. 542-16-114 08 11 13-10 10/13/2017
Renovate Building 2 West
TIL Ver. 02-01-16
Station Project No. 542-16-114 08 14 00-1 10/13/2017
SECTION 08 14 00
INTERIOR WOOD DOORS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Interior flush wood doors transparent finish.
a. Fire rated doors.
b. Smoke rated doors.
2. Interior stile and rail wood doors transparent finish.
1.2 RELATED REQUIREMENTS
A. Paints and Coatings and Composite Wood and Agrifiber VOC Limits:
Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.
B. Door Hardware including hardware location (height): Section 08 71 00, DOOR HARDWARE.
C. Installation of Doors and Hardware: Section 08 11 13, HOLLOW METAL
DOORS AND FRAMES; Section 08 71 00, DOOR HARDWARE.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American National Standards Institute/Window and Door Manufacturers
Association (ANSI/WDMA):
1. I.S. 1A-13 - Architectural Wood Flush Doors.
2. I.S. 6A-13 - Interior Architectural Stile and Rails Doors.
C. ASTM International (ASTM):
1. E90-09 - Laboratory Measurements of Airborne Sound Transmission Loss of Building Partitions and Elements.
D. National Fire Protection Association (NFPA):
1. 80-16 - Fire Doors and Other Opening Protectives.
2. 252-12 - Fire Tests of Door Assemblies.
E. UL LLC (UL):
1. 10C-09 - Positive Pressure Fire Tests of Door Assemblies.
F. Window and Door Manufacturers Association (WDMA):
1. TM 7-14 - Cycle-Slam Test.
2. TM 8-14 - Hinge Loading Test.
3. TM 10-14 - Screw Holding Capacity.
Renovate Building 2 West
Station Project No. 542-16-114 08 14 00-2 10/13/2017
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
2. Include details of glazing.
3. Indicate project specific requirements not included in
Manufacturer's Literature and Data submittal.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Fire rated doors showing conformance with NFPA 80.
D. Samples:
1. Corner section of flush veneered door 300 mm (12 inches) square, showing details of construction, labeled to show grade and type number and conformance to specified standard.
2. Veneer sample 200 mm by 275 mm (8 inch by 11 inch) showing specified wood species sanded to receive a transparent finish. Factory finish veneer sample where the prefinished option is accepted.
E. Sustainable Construction Submittals:
1. Low Pollutant-Emitting Materials:
a. Show volatile organic compound types and quantities.
F. Test Reports: Indicate products comply with specifications.
1. Screw Holding Capacity Test.
2. Cycle-Slam Test.
3. Hinge-Loading Test.
G. Operation and Maintenance Data:
1. Care instructions for each exposed finish product.
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications:
1. Regularly and presently manufactures specified products.
2. Manufactures specified products with satisfactory service on five similar installations for minimum five years.
1.6 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
Renovate Building 2 West
Station Project No. 542-16-114 08 14 00-3 10/13/2017
1. Minimum 0.15 mm (6 mil) polyethylene bags or cardboard packaging to remain unbroken during delivery and storage.
B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, and manufacture date.
1. Identify door opening corresponding to Door Schedule.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.7 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight conditioned facility.
1. Store doors according to ANSI/WDMA I.S. 1A.
B. Protect products from damage during handling and construction operations.
1.8 FIELD CONDITIONS
A. Environment:
1. Product Temperature: Minimum 21 degrees C (70 degrees F) for minimum
48 hours before installation.
2. Work Area Ambient Temperature Range: 21 to 27 degrees C (70 to
80 degrees F) continuously, beginning 48 hours before installation.
3. Install products when building is permanently enclosed and when wet construction is completed, dried, and cured.
a. Comply with door manufacturer's instructions for relative humidity.
1.9 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction.".
B. Manufacturer's Warranty: Warrant interior factory finished flush wood doors against material and manufacturing defects.
1. Warranty Period: Lifetime of original installation.
PART 2 - PRODUCTS
2.1 PRODUCTS - GENERAL
A. Provide each product from one manufacturer.
B. Sustainable Construction Requirements:
Renovate Building 2 West
Station Project No. 542-16-114 08 14 00-4 10/13/2017
1. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:
a. Paints and coatings.
b. Composite wood and agrifiber.
2.2 FLUSH WOOD DOORS
A. General:
1. ANSI/WDMA I.S. 1A, Extra Heavy Duty.
2. Adhesive: Type II.
3. Core: Structural composite lumber, except when mineral core is required for fire rating.
4. Thickness: 44 mm (1-3/4 inches) unless otherwise shown or specified.
B. Faces:
1. ANSI/WDMA I.S. 1A.
2. One species throughout project unless scheduled or otherwise shown.
3. Transparent Finished Faces: Premium Grade. rotary cut, red oak
a. A Grade face veneer.
b. Match face veneers for doors for uniform effect of color and grain at joints.
c. Door Edges: Same species as door face veneer, except maple is acceptable for stile face veneer on birch doors.
d. In existing buildings, where doors are required to have transparent finish, use wood species, grade, and assembly of face veneers to match adjacent existing doors.
4. Painted Finishes: Custom Grade, mill option close grained hardwood, premium or medium density overlay.
5. Factory sand doors for finishing.
C. Wood For Stops, Louvers, Muntins and Moldings For Flush Doors Required to Have Transparent Finish:
1. Solid wood of same species as face veneer, except maple is acceptable on birch doors.
2. Glazing:
a. On non-fire-rated doors, use applied wood stops nailed tightly on room side and attached on opposite side with flathead, Renovate Building 2 West
Station Project No. 542-16-114 08 14 00-5 10/13/2017 countersunk wood screws, spaced approximately 125 mm (5 inches) on center.
D. Fire-Rated Wood Doors:
1. Fire Resistance Rating:
a. C Label: 3/4 hour.
2. Labels:
a. Comply with NFPA 252, UL 10C, and labeled by qualified testing and inspection agency showing fire resistance rating.
b. Metal labels with raised or incised markings.
3. Performance Criteria for Stiles of Doors Utilizing Standard Mortise
Leaf Hinges:
a. Hinge Loading: WDMA TM 8. Average of 10 test samples for Extra
Heavy Duty doors.
b. Direct Screw Withdrawal: WDMA TM 10 for Extra Heavy Duty doors.
Average of 10 test samples using a steel, fully threaded #12 wood screw.
c. Cycle-Slam: 1,000,000 cycles with no loose hinge screws or other visible signs of failure when tested according to WDMA TM 7.
4. Hardware Reinforcement:
a. Provide fire smoke rated doors with hardware reinforcement blocking.
b. Size of lock blocks as required to secure hardware specified.
c. Top, Bottom and Intermediate Rail Blocks: Minimum 125 mm
(5 inches) by full core width.
d. Reinforcement blocking in compliance with labeling requirements.
e. Mineral material similar to core is not acceptable.
5. Other Core Components: Manufacturer's standard as allowed by labeling requirements.
6. Glazed Vision Panel Frame: Steel approved for use in labeled doors.
E. Smoke Barrier Doors:
1. Glazed Vision Panel Frame: Steel approved for use in labeled doors.
2.3 STILE AND RAIL WOOD DOORS
A. Doors: ANSI/WDMA I.S. 6A; Grade Premium, size and design shown on drawings.
B. Species: Ponderosa pine.
Renovate Building 2 West
Station Project No. 542-16-114 08 14 00-6 10/13/2017
C. Door Panels:
1. Grain of face of panels parallel with longest dimensions of panel.
2. Flat panels: Veneered composite core, minimum 16 mm (5/8 inch) thick.
a. For 44 mm (1-3/4 inch) thick doors: 28 mm (1-1/8 inch) thick.
3. Where armor plate is required for paneled doors, provide panels with plywood fillers, glued in place, and finished.
D. Stops and Molds:
1. Solid sticking both sides, same material as stiles and rails, coped joints.
2. Glazed Vision Panel Frame: Applied wood stops nailed on interior side of door.
2.4 FABRICATION
A. Factory machine interior wood doors to receive hardware, bevels, undercuts, cutouts, accessories and fitting for frame.
1. Factory fit fire rated doors according to NFPA 80.
B. Rout doors for hardware using templates and location heights specified in Section 08 71 00, DOOR HARDWARE.
C. Factory fit doors to frame, bevel lock edge of doors 3 mm (1/8 inch) for each 50 mm (2 inches) of door thickness undercut where shown .
D. Clearances between Doors and Frames and Floors:
1. Fire Rated Doors: Comply with NFPA 80.
a. Doors with Automatic Bottom Seal: Maximum clearance 10 mm
(3/8 inch) at threshold.
b. Other Door Bottoms: Maximum 3 mm (1/8 inch) clearance at the jambs, heads, and meeting stiles, and a 19 mm (3/4 inch) clearance at bottom, except as otherwise specified.
2. Door Jambs, Heads, and Meeting Stiles: Maximum 3 mm (1/8 inch).
E. Provide cutouts for glazed openings.
F. Finish surfaces, including both faces, top and bottom and edges of the doors smooth to touch.
G. Identify each door on top edge.
1. Mark with stamp, brand or other indelible mark, giving manufacturer’s name, door’s trade name, construction of door, date of manufacture and quality.
Renovate Building 2 West
Station Project No. 542-16-114 08 14 00-7 10/13/2017
2. Mark door or provide separate certification including name of inspection organization.
3. Identify door manufacturing standard, including glue type.
4. Identify veneer and quality certification.
5. Identification of preservative treatment for stile and rail doors.
2.5 FINISHES
A. Factory Transparent Finish:
1. Factory finish flush wood doors.
a. ANSI/WDMA I.S. 1A Section F-3 Finish System Descriptions for
System 5, Conversion Varnish or System 7, Catalyzed Vinyl.
b. Use stain when required to produce finish specified in Finish
Schedule on Drawings.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
1. Verify door frames are properly anchored.
2. Verify door frames are plumb, square, in plane, and within tolerances for door installation.
B. Protect existing construction and completed work from damage.
C. Install astragal on active leaf of pair of smoke doors and one leaf of double egress smoke doors.
3.2 INSTALLATION
A. Install products according to manufacturer's instructions and approved submittal drawings.
1. Install fire rated doors according to NFPA 80.
2. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.
3.3 PROTECTION
A. After installation, place shipping container over door and tape in place.
1. Do not apply tape to door faces and edges.
B. Provide protective covering over exposed hardware in addition to covering door.
Renovate Building 2 West
Station Project No. 542-16-114 08 14 00-8 10/13/2017
C. Maintain covering in good condition until removal is directed by
Contracting Officer's Representative.
- - E N D - -
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-1 10/13/2017
SECTION 08 17 10
INTEGRATED DOOR ASSEMBLIES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Integrated door assemblies including metal door frame, door, and hardware, unless specified in another Section, installed at cross-corridor locations.
B. Smoke and draft control seals, unless specified in another Section.
1.2 RELATED REQUIREMENTS
A. Non-Flooring Adhesives and Sealants and Paints and Coatings VOC Limits:
Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.
B. Lock Cylinders: Section 08 71 00, DOOR HARDWARE.
C. Automatic Door Operators: Section 08 71 13, AUTOMATIC DOOR OPERATORS.
D. Electrical Power: DIVISION 26, ELECTRICAL.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. Builders Hardware Manufacturers Association (BHMA):
1. A156.3-14 - Exit Devices.
2. A156.26-06 - Continuous Hinges.
3. A156.32-14 - Integrated Door Opening Assemblies.
C. ASTM International (ASTM):
1. A1011/A1011M-14 - Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with
Improved Formability, and Ultra-High Strength.
2. E2180-07(2012) - Determining the Activity of Incorporated
Antimicrobial Agents in Polymeric or Hydrophobic Materials.
D. Door and Hardware Institute (DHI):
1. Recommended Locations for Architectural Hardware for Standard Doors
& Frames (2004).
2. Recommended Locations for Builders' Hardware Custom Steel Doors &
Frames (1996).
E. National Fire Protection Association (NFPA):
1. 105-16 - Smoke Door Assemblies and Other Opening Protectives.
2. 252-12 - Fire Tests of Door Assemblies.
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-2 10/13/2017
F. Steel Door Institute (SDI):
1. A250.3-11 - Test Procedure and Acceptance Criteria for Factory
Applied Finish Coatings for Steel Doors and Frames.
2. A250.8-14 - Specifications for Standard Steel Doors and Frames.
3. A250.10-11 - Test Procedure and Acceptance Criteria for Prime
Painted Steel Surfaces for Steel Doors and Frames.
G. UL LLC (UL):
1. 10C-09 - Positive Pressure Fire Tests of Door Assemblies.
2. 1784-15 - Air Leakage Tests of Door Assemblies and Other Opening
Protectives.
1.4 PREINSTALLATION MEETINGS
A. Conduct preinstallation meeting at project site minimum 30 days before beginning Work of this section.
1. Required Participants:
a. Contracting Officer's Representative.
b. Contractor.
c. Installer.
d. Other installers responsible for adjacent and intersecting work, including electrical.
2. Meeting Agenda: Distribute agenda to participants minimum 3 days before meeting.
a. Installation schedule.
b. Installation sequence.
c. Preparatory work.
d. Protection before, during, and after installation.
e. Installation.
f. Transitions and connections to other work.
g. Other items affecting successful completion.
3. Document and distribute meeting minutes to participants to record decisions affecting installation.
1.5 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-3 10/13/2017
2. For each opening, list finish hardware items included in assembly, finish, degree of opening, and electrical rough-in requirements according to Door Schedule.
3. Submit templates to door and frame manufacturers to ensure proper size and location of hardware.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Installation instructions.
D. Sustainable Construction Submittals:
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
2. Low Pollutant-Emitting Materials:
a. Show volatile organic compound types and quantities.
E. Certificates: Indicate integrated door assemblies comply with specifications.
1. Show fire rated integrated door assembly is UL Listed for specified application.
F. Qualifications: Substantiate qualifications comply with specifications.
1. Installer.
G. Operation and Maintenance Data:
1. Care instructions for each exposed finish product.
2. Maintenance and adjustment instructions for integrated door assemblies.
1.6 QUALITY ASSURANCE
A. Installer Qualifications:
1. Regularly installs specified products.
2. Installed specified products with satisfactory service on five similar installations for minimum five years.
a. Provide contact names and addresses for completed projects when requested by Contracting Officer's Representative.
1.7 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
B. Mark packaging, legibly. Indicate manufacturer's name.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-4 10/13/2017
1.8 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight facility.
B. Protect products from damage during handling and construction operations.
1.9 FIELD CONDITIONS
A. Field Measurements: Verify field conditions affecting integrated door assembly fabrication and installation. Show field measurements on
Submittal Drawings.
1. Coordinate field measurement and fabrication schedule to avoid delay.
2. Coordinate electrical work for electrified hardware installation.
1.10 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
B. Manufacturer's Warranty: Warrant door closers and hinges against material and manufacturing defects.
1. Warranty Periods:
a. Door Closers: 10 years.
b. Steel Pinned Continuous Hinges: 10 years.
PART 2 - PRODUCTS
2.1 SYSTEM PERFORMANCE
A. Design integrated door assemblies complying with specified performance:
1. BHMA A156.32: Grade 1: 1,000,000 cycles.
B. Fire Rated Doors:
1. Fire Resistance Rating: As shown in Door Schedule.
2. Label: Comply with NFPA 252, UL 10C, and labeled by qualified testing and inspection agency showing fire resistance rating.
C. Smoke Rated Doors:
1. Smoke Resistance Rating: As shown in Door Schedule.
2. Label: Comply with NFPA 105, UL 1784, and labeled by qualified testing and inspection agency showing smoke resistance rating.
2.2 PRODUCTS - GENERAL
A. Provide each integrated door assembly from one manufacturer.
B. Sustainable Construction Requirements:
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-5 10/13/2017
1. Steel Recycled Content: 30 percent total recycled content, minimum.
2. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:
a. Non-flooring adhesives and sealants.
b. Paints and coatings.
2.3 INTEGRATED DOOR ASSEMBLY
A. Metal Doors: SDI A250.8; Level 2 and Physical Performance Level B, heavy duty; Model 2 seamless.
1. Face: ASTM A1011/A1011M; cold rolled steel, 1.0 mm (0.04 inches) thick, minimum.
2. Core: Kraft paper honeycomb or polystyrene.
3. Thickness: 44 mm (1-3/4 inch).
4. Reinforce door for hardware installation.
B. Metal Frames: SDI A250.8 Level 2.
1. Metal: ASTM A1011/A1011M; cold rolled steel, 1.3 mm (0.05 inches) thick, minimum.
2. Construction: Continuously welded.
3. Reinforce frame for hardware.
a. Continuous Hinges: 2.3 mm (0.09 inches) thick.
b. Other Hardware: Comply with SDI A250.8.
4. Frame Anchors: Provide adjustable type anchors coordinated with wall construction, minimum 4 per jamb.
C. Integrated Hardware:
1. Exit Device: BHMA A156.3; Grade 1, passage function, inset in door face, clean and unobtrusive in design.
a. Push Bar End Caps: Metal, plated satin nickel (BHMA 619) finish.
b. Exit Device Trim: Lever matching door hardware specified in
Section 08 71 00, DOOR HARDWARE.
2. Continuous Hinges: BHMA A156.26.
a. Plastic Laminate Clad Doors: Wrap-around style hinge guards and provide stainless steel wrap-around edge guards at strike edge of door.
3. Other Hardware: As scheduled in this section.
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-6 10/13/2017
2.4 FINISHES
A. Hardware Finish Symbols:
Table 1 Hardware Finish Symbols
US BHMA 156.18 Description
USP 600 Primed for field painting
US15 619 Dull Nickel Plated
US26D 626/652 Satin Chrome Plated
US28 628 Satin Aluminum
US32 629 Bright Stainless
US32D 630 Satin Stainless
N/A 689 Aluminum Painted
B. Finish Requirements:
1. Door Faces: Factory Pre-Finished, SDI A250.3
2. Frames: Prime painted, SDI A250.10.
3. Door Hardware:
a. Continuous Hinges: BHMA 630.
b. Push Bar: BHMA 630 clad with BHMA 619 end caps.
c. Exit Device Trim: BHMA 630.
d. Push/Pull Trim: BHMA 626.
e. Door Closers: BHMA 689.
f. Miscellaneous: To match other finishes.
4. Anti-Microbial Coating: ASTM E2180; ionic silver coating.
5. Apply coating to hand-operated hardware including levers, pulls, push bars, push plates, and paddles.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
B. Protect existing construction and completed work from damage.
3.2 INSTALLATION - INTEGRATED DOOR ASSEMBLIES
A. Install products according to manufacturer's instructions and approved submittal drawings.
B. Install door hardware at locations indicated in DHI Recommended
Locations for Architectural Hardware for Standard Steel Doors & Frames
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-7 10/13/2017 and DHI Recommended Locations for Builders' Hardware Custom Steel Doors
& Frames, unless otherwise indicated, or to comply with requirements of governing regulations, or if otherwise directed by Contracting
Officer's Representative.
C. Install door hardware in compliance with manufacturers' instructions, and templates. Comply with specified degree of opening for doors with automatic operators and overhead door closers. Securely fasten hardware. Confirm operating parts move freely and smoothly without binding, sticking, and excessive clearance.
D. Coordinate installation and interface wiring with fire alarm and smoke detection systems. Provide auxiliary contacts, relays, and interface for fire alarm and security systems.
E. Remove or protect door hardware, before painting and finishing performed after integrated door assembly installation.
F. Adjust and check door assembly and each operating hardware item to ensure correct operation and function. Replace products which cannot be adjusted to operate as intended.
G. Final Adjustment: Perform final hardware check and adjustment maximum one month before building acceptance or partial building occupancy.
3.3 CLEANING
A. Clean exposed surfaces, including hardware. Do not use cleaners that will harm finishes.
3.4 PROTECTION
A. Protect integrated door assemblies from construction operations.
3.5 SCHEDULES
A. The following is a general listing of the Integrated Door Assembly requirements and is not intended for use as a final door submittal.
Provide hardware items required by established standards and practices, and to meet IBC and NFPA 101 whether specified or not in the following listed groups.
HW-6D
Each [ADO] Integrated Door to
Have:
RATED
1 Steel Frame
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-8 10/13/2017
1 Integrated Door w/Exit
Device
Q2131 x TYPE 8 ELECTRIC DEVICE (E04) x F08 LEVER
1 Continuous Transfer Hinge A51031B x 8-THRUWIRE
TRANSFER x IN-HINGE ACCESS PANEL
1 Power Supply BY EXIT DEVICE MFR. FOR E04 FUNCTION
1 Armor Plate J101 x 1.275 mm (0.050 inch)
THICKNESS
1 Floor Stop L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0E154
Each [ADO] Integrated Door to Have:
POWER TRANSFER SHARED BY ELECTRIC PANIC AND RE-ACTIVATION SENSOR WIRING
(RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.
AUTO DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR
OPERATORS.
HW-8
Each [MHO] Pair Integrated Doors to Have:
RATED
1 Steel Frame
1 Integrated Pair Doors w/Auto
Flush Bolts & Push/Pull Trim
Q2241 x TYPE 25 LESS BOTTOM BOLT
AUTO
FLUSH BOLT (INACTIVE LEAF) x ACTIVE
CONCEALED VERTICAL LATCH (ACTIVE
LEAF)
2 Continuous Hinges A51031B x WIDE THROW AS REQUIRED TO
ACHIEVE FULL DOOR SWING
1 Coordinator TYPE 21A
1 Self-Adhesive Astragal R0Y_14
2 Closers C02011 (PT4D, PT4H) x 180° SWING
2 Magnetic Holders C00011 TRI-VOLTAGE
1 Set Self-Adhesive Seals R0E154
POWER, WIRING, CONDUIT, AND FIRE ALARM CONNECTION BY DIVISION 26.
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-9 10/13/2017
HW-12A
Each [MHO] Pair Integrated Doors to Have:
RATED
1 Steel Frame
1 Integrated Pair Doors w/Exit
Devices and Pull Trim
Q2231 x TYPE 8 EXIT DEVICES
(F01/ACTIVE FLUSH PULL PASSAGE TRIM)
2 Continuous Hinges A51031B
1 Self-Adhesive Astragal R0Y_14
2 Closers C02011/C02021 (PT4D, PT4H)
2 Magnetic Holders C00011 TRI-VOLTAGE
1 Set Self-Adhesive Seals R0E154
POWER, WIRING, CONDUIT, AND FIRE ALARM CONNECTION BY DIVISION 26.
HW-12B
Each [ADO] Pair Integrated Doors to Have:
RATED
1 Steel Frame
1 Integrated Pair Doors w/Elec
Exit Devices
Q2231 x TYPE 8 (E04) ELECTRIC EXIT
DEVICES (F01/F08)
2 Continuous Transfer Hinges A51031B x 8-THRUWIRE
TRANSFER x IN-HINGE ACCESS PANEL
1 Power Supply BY EXIT DEVICE MFR. FOR E04 FUNCTION
1 Self-Adhesive Astragal R0Y_14
2 Armor Plates J101 x 1.275 mm (0.050 inch)
THICKNESS
2 Floor Stops L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0E154
POWER, WIRING, CONDUIT, AND FIRE ALARM CONNECTION BY DIVISION 26.
POWER TRANSFER SHARED BY ELECTRIC PANIC AND RE-ACTIVATION SENSOR WIRING
(RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.
AUTO DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR
OPERATORS.
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-10 10/13/2017
HW-12C
Each [ADO] Pair Integrated Double
Egress Doors to Have:
RATED
1 Steel Frame
1 Integrated Pair Doors w/Exit
DEVICES
Q2331 x TYPE 8 EXIT DEVICES (F01)
2 Continuous Hinges A51031B
1 Overlapping Astragal with
Self-Adhesive Seal
R5Y634 x R0E154 x THRU-BOLTS
2 Closers C02011/C02021 (PT4D, PT4H)
2 Magnetic Holders C00011 TRI-VOLTAGE
1 Set Self-Adhesive Seals R0E154
POWER, WIRING, CONDUIT, AND FIRE ALARM CONNECTION BY DIVISION 26.
HW-12D
Each [ADO] Pair Integrated Double
Egress Doors to Have:
RATED
1 Steel Frame
1 Integrated Pair Doors w/Elec
Exit Devices
Q2331 x TYPE 8 (E04) ELECTRIC EXIT
DEVICES (F01)
2 Continuous Transfer Hinges A51031B x 8-THRUWIRE
TRANSFER x IN-HINGE ACCESS PANEL
1 Power Supply BY EXIT DEVICE MFR. FOR E04 FUNCTION
1 Overlapping Astragal with
Self-Adhesive Seal
R5Y634 x R0E154 x THRU-BOLTS
2 Armor Plates J101 x 1.275 mm (0.050 inch)
THICKNESS
2 Floor Stops L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0E154
POWER, WIRING, CONDUIT, AND FIRE ALARM CONNECTION BY DIVISION 26.
POWER TRANSFER SHARED BY ELECTRIC PANIC AND RE-ACTIVATION SENSOR WIRING
(RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
AUTO DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR
OPERATORS.
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-11 10/13/2017
HW-SH-4
Each [AC, EL, REX, DPS]Integrated
Door to Have:
RATED
1 Steel Frame
1 Integrated Door w/Elec. Exit
Device
Q2131 x TYPE 8 ELECTRIC DEVICE (E01, E05/E06-VERIFY)x F13 LEVER
1 Continuous Transfer Hinge A51031B x 4-THRUWIRE TRANSFER x
IN-HINGE ACCESS PANEL
1 Power Supply
REGULATED, FILTERED, 24VDC, AMPERAGE
AS REQUIRED
1 Closer C02021 (PT4D, PT4F, PT4H)
1 Armor Plate J101 x 1.275 mm (0.050 inch)
THICKNESS
1 Floor Stop L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0E154
1 Alarm Contact
120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.
CARD READER BY DIVISION 28.
LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.
HW-SH-4A
Each [ADO, AC, ELR, REX, DPS]
Integrated Door to Have:
RATED
1 Steel Frame
1 Integrated Door w/Elec Exit
Device
Q2131 x TYPE 8 ELECTRIC DEVICE (E01, E04)x F13 LEVER
1 Continuous Transfer Hinge A51031B x 12-THRUWIRE TRANSFER x
IN-HINGE ACCESS PANEL
1 Power Supply BY EXIT DEVICE MFR. FOR E04 FUNCTION
1 Armor Plate J101 x 1.275 mm (0.050 inch)
THICKNESS
1 Floor Stop L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0E154
1 Alarm Contact
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-12 10/13/2017
120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.
AUTO DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR
OPERATORS.
CARD READER BY DIVISION 28.
POWER TRANSFER SHARED BY ELECTRIC PANIC AND RE-ACTIVATION SENSOR WIRING
(RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.
HW-SH-10
Each [AC, EL, REX, DPS] Pair
Integrated Doors to Have
RATED
1 Steel Frame
1 Integrated Pair Doors w/Elec
Exit Devices
Q2231 x TYPE 8 EXIT DEVICES
(F01-E01/F13-E01, E05/E06-VERIFY)
2 Continuous Transfer Hinges A51031B x 4-THRUWIRE TRANSFER x
IN-HINGE ACCESS PANEL
1 Power Supply Regulated, Filtered, 24VDC, Amperage
1 Self-Adhesive Astragal R0Y_14
2 Closers C02021 (PT4D, PT4F, PT4H)
2 Armor Plates J101 x 1.275 mm (0.050 inch)
THICKNESS
2 Floor Stops L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0E154
POWER, WIRING, AND CONDUIT BY DIVISION 26.
LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.
HW-SH-10A
Each [AC, ADO, EL, REX, DPS] Pair
Integrated Doors to Have:
RATED
1 Steel Frame
1 Integrated Pair Doors w/Elec. Exit Devices
Q2231 x TYPE 8 (E01, E04) ELECTRIC
EXIT DEVICES (F01/F08)
2 Continuous Transfer Hinges A51031B x 12-THRUWIRE TRANSFER x
IN-HINGE ACCESS PANEL
1 Power Supply BY EXIT DEVICE MFR. FOR E04 FUNCTION
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-13 10/13/2017
1 Self-Adhesive Astragal R0Y_14
2 Armor Plates J101 x 1.275 mm (0.050 inch)
THICKNESS
2 Floor Stops L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0E154
POWER, WIRING, CONDUIT, AND FIRE ALARM CONNECTION BY DIVISION 26.
POWER TRANSFER SHARED BY ELECTRIC PANIC AND RE-ACTIVATION SENSOR WIRING
(RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13).
LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.
AUTO DOOR OPERATOR AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR
OPERATORS.
HW-SH-12
Each [AC, ADO, EL, REX, DPS]
Integrated Door to Have:
NON-RATED
1 Steel Frame
1 Integrated Door w/Elec. Exit
Device
Q2131 x TYPE 8 ELECTRIC DEVICE (E01, E04) x F03 OUTSIDE CYLINDER ONLY
1 Continuous Transfer Hinge A51031B x 12-THRUWIRE TRANSFER x
IN-HINGE ACCESS PANEL
1 Power Supply BY EXIT DEVICE MFR. FOR E04 FUNCTION
1 Offset Pull J402 x 1” (25mm) DIAMETER x 12”
(305mm)CTC
1 Closer C02021 (PT4D, PT4F, PT4H)
1 Kick Plate J102
1 Floor Stop L02121 x 3 FASTENERS
1 Threshold J35130 x SILICONE GASKET
1 Door Sweep 90100CNB (PEMKO), OR EQUAL
1 Set Frame Seals
2891AS X CSK SCREWS (PEMKO), OR
EQUAL
1 Drip R0Y976
1 Alarm Contact
120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.
CARD READER BY DIVISION 28.
Renovate Building 2 West
Station Project No. 542-16-114 08 17 10-14 10/13/2017
LOCK CYLINDER BY SECTION 08 71 00, DOOR HARDWARE.
Renovate Building 2 West
Station Project No. 542-16-114 08 31 13-1 10/13/2017
SECTION 08 31 13
ACCESS DOORS AND FRAMES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Access doors and panels installed in walls and ceilings.
1.2 RELATED REQUIREMENTS
A. Lock Cylinders: Section 08 71 00, DOOR HARDWARE.
B. Field Painting: Section 09 91 00, PAINTING.
C. Access Doors for Control or Drain Valves: DIVISION 21, FIRE
SUPPRESSION.
D. Access Doors for Plumbing Valves: DIVISION 22, PLUMBING.
E. Locations of Access Doors for Mechanical Access: DIVISION 23, HEATING, VENTILATING, AND AIR CONDITIONING (HVAC).
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American Welding Society (AWS):
1. D1.3/D1.3M-08 - Structural Welding Code - Sheet Steel.
C. ASTM International (ASTM):
1. A653/A653M-15 - Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron
Alloy-Coated (Galvannealed) by the Hot-Sip Process.
2. A1008/A1008M-15 - Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved
Formability, Solution Hardened, and Baked Hardenable.
3. A666-15 - Annealed or Cold-Worked Austenitic Stainless Steel sheet, Strip, Plate, and Flat Bar.
4. E119-15 - Fire Test of Building Construction and Materials.
D. National Fire Protection Association (NFPA):
1. 80-16 - Fire Doors and Other Opening Protectives.
2. 251-12 - Fire Tests of Door Assemblies.
E. National Association of Architectural Metal Manufacturers (NAAMM):
1. AMP 500-06 - Metal Finishes Manual.
F. UL LLC (UL):
1. Listed - Online Certifications Directory.
2. 10B-08 - Standard for Fire Tests of Door Assemblies.
Renovate Building 2 West
Station Project No. 542-16-114 08 31 13-2 10/13/2017
3. 263-11 - Fire Tests of Building Construction and Materials.
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Installation instructions.
D. Sustainable Construction Submittals:
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
1.5 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.6 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight facility.
B. Protect products from damage during handling and construction operations.
1.7 FIELD CONDITIONS
A. Field Measurements: Verify field conditions affecting access door fabrication and installation. Show field measurements on Submittal
Drawings.
1. Coordinate field measurement and fabrication schedule to avoid delay.
1.8 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
Renovate Building 2 West
Station Project No. 542-16-114 08 31 13-3 10/13/2017
PART 2 - PRODUCTS
2.1 MATERIALS
A. Steel Sheet: ASTM A1008/A1008M.
B. Stainless Steel: ASTM A666; Type 302 or Type 304.
2.2 PRODUCTS - GENERAL
A. Provide each product from one manufacturer.
B. Sustainable Construction Requirements:
1. Steel Access Doors Recycled Content: 30 percent total recycled content, minimum.
2. Stainless Steel Access Doors Recycled Content: 70 percent total recycled content, minimum.
2.3 ACCESS DOORS, FIRE-RATED (NOT USED)
2.4 ACCESS DOORS, FLUSH PANEL, NON-RATED
A. Door Panel:
1. 1.9 mm (0.07 inch) thick steel sheet.
2. Reinforce to maintain flat surface.
B. Frame:
1. 1.5 mm (0.06 inch) thick steel or stainless steel sheet, depth and configuration to suit material and construction type where installed.
2. Frame Flange: Provide at units installed in concrete, masonry, and gypsum board.
3. Exposed Joints in Flange: Weld and grind smooth.
C. Hinge:
1. Concealed spring hinge, 175 degrees of opening.
2. Removable hinge pin to allow removal of door panel from frame.
D. Lock:
1. Flush, screwdriver-operated cam lock.
2.5 ACCESS DOOR, RECESSED PANEL, NON-RATED
A. Door Panel:
1. 1.2 mm (0.05 inch) thick steel or stainless steel sheet to form a
25 mm (1 inch) deep recessed pan to accommodate installation of acoustical units and other materials where shown in walls and ceiling.
Renovate Building 2 West
Station Project No. 542-16-114 08 31 13-4 10/13/2017
2. Reinforce to prevent sagging.
B. Frame:
1. 1.5 mm (0.06 inch) thick steel sheet of depth and configuration to suit installation in suspension system of ceiling or wall framing.
2. Extend sides of frame to protect edge of acoustical units when door panel is in open position.
3. Provide shims, bushings, clips and other devices necessary for installation.
C. Hinge: Continuous stainless steel hinge with stainless steel pin, or concealed hinge.
D. Lock:
1. Flush screwdriver-operated cam lock.
2. Plastic sleeve or stainless steel grommet to protect hole made in acoustical unit for screwdriver access to lock.
2.6 FABRICATION - GENERAL
A. Size: Minimum 600 mm (24 inches) square door unless otherwise shown or required to suit opening in suspension system of ceiling.
B. Component Fabrication: Straight, square, flat and in same plane where required.
1. Exposed Edges: Slightly rounded, without burrs, snags and sharp edges.
2. Exposed Welds: Continuous, ground smooth.
3. Welding: AWS D1.3/D1.3M.
C. Locks and Non-Continuous Hinges: Provide in numbers required to maintain alignment of door panel with frame.
D. Anchoring: Make provisions in frame for anchoring to adjacent construction. Provide anchors in size, number and location on four sides to secure access door to substrate.
2.7 FINISHES
A. Steel Paint Finish:
1. Powder-Coat Finish: Manufacturer's standard two-coat finish system consisting of the following:
a. One coat primer.
b. One coat thermosetting topcoat.
c. Dry-film Thickness: 0.05 mm (2 mils) minimum.
Renovate Building 2 West
Station Project No. 542-16-114 08 31 13-5 10/13/2017
B. Stainless Steel Exposed Surfaces: NAAMM AMP 500; No. 4 polished finish.
2.8 ACCESSORIES
A. Fasteners: Type and size recommended by access door manufacturer, to suit application.
1. Stainless Steel Access Doors: Stainless steel fasteners.
2. Other Access Doors: Stainless steel fasteners.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
1. Verify access door locations and sizes provide required maintenance access to installed building services components.
B. Protect existing construction and completed work from damage.
3.2 INSTALLATION - GENERAL
A. Install products according to manufacturer's…