260-B5260-065 NVCC LA Medical Oxygen Generator - Drawings.pdf
PDF 5 MB Posted
- Attached to
- 260-B5260-065 LA Add Medical Oxygen Generator
- Solicitation number
- IFB-125907
- Issued by
- Virginia
About this file
This is a design and construction drawings document for a capital project undertaken by Northern Virginia Community College (NVCC) at its Loudoun Campus in Sterling, Virginia, under the oversight of the Virginia Community College System (VCCS). The project, identified as 260-B5260-065, involves the specification and installation of a new medical oxygen generator system to replace existing oxygen bottle cylinders currently stored in Room 127A of the LA Building. The scope of work includes selective demolition of existing equipment, relocation of the existing water heater, construction of a new partition wall to divide mechanical room 127 into two separate spaces (the oxygen generator room 127A and mechanical equipment room 127), installation of new electrical power supply for the oxygen generator, integration of the system with existing medical gas distribution piping, and coordination with building management systems. The project encompasses approximately 227 square feet of mechanical room work, 443 square feet of total scope area, and requires compliance with the 2021 Virginia Building Code, Virginia Mechanical Code, and NFPA standards. The documents are issued for bid as of July 15, 2026, with detailed drawings prepared by Dewberry Engineers, Inc.
The oxygen generator system specified includes a Novair OG-175 unit capable of producing 70 standard cubic feet per hour at 93% purity, operating at 115 volts single-phase with 15-amp requirements, along with a Novair OST-120 medical-grade oxygen storage tank (120 gallons) and an Atlas Copco GA 7 VSD+MED air compressor system (10 horsepower, 190 CFM output). The project requires installation of a master alarm panel for monitoring oxygen concentration levels, integration with the facility's energy management and control system (EMCS) via Bacnet gateway, and provision of high-visibility alarm capabilities with remote signal inputs. The contractor must provide branch circuit wiring, overcurrent protection, firestop sealing materials compliant with UL standards, new concrete equipment pads, and all coordination with existing building systems. The work must comply with ADA accessibility requirements, maintain fire-rated wall integrity through proper penetration sealing, and include comprehensive testing, documentation, and one-year warranty of workmanship and materials upon system acceptance by the owner.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPROVED BY
CHECKED BY
A
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
No. Description Date
REVISIONS
23456
B
C
D
E
F
DEB PROJECT NUMBER :
DEWBERRY PROJECT NUMBER:
FACILITIES PLANNING & SUPPORT SERVICES
8333 LITTLE RIVER TURNPIKE
ANNANDALE, VA 22003
Dewberry Engineers, Inc.
8401 ARLINGTON BLVD
FAIRFAX, VA 22031
703.849.0100 Phone
/2
/2
:0
:1
A
M
Q P
R O
J E
C T
S \5
N V
C C
L A
A D
D O
X Y
G E
N G
E N
E R
A T
O R
\C A
D \G
E N
E R
A L
\G -0
C O
V E
R S
H E
E T
.D W
G
06-17-2026
NORTHERN VIRGINIA COMMUNITY COLLEGE
LOUDOUN CAMPUS LA ADD MEDICAL OXYGEN
GENERATOR
ISSUE FOR BID
T: 703.849.0100
F: 703.698.9040
BUILDING LOCATIONS:
NVCC LA BUILDING 21200 CAMPUS DRIVE, STERLING, VA 20164
OWNER OF BUILDING:
COMMONWEALTH OF VIRGINIA
STATE BOARD OF COMMUNITY COLLEGES
BUILDING DETAILS:
BUILDING TYPE: TYPE II
BUILDING OCCUPANCY GROUP: GROUP B
CONTAINS SPRINKLER SYSTEM: YES
CONTAINS FIRE ALARM SYSTEM: YES
BUILDING AREA:
AREA OF BUILDING:
TOTAL FLOOR AREA = 11,480 S.F.
BUILDING HEIGHT
TOTAL BUILDING HEIGHT = 1 STORY, 20'
REFER TO DRAWING G-002 FOR CODE PLAN FOR DETAIL CODE ANALYSIS
PRIMARY CONTACTS:
OWNER: NORTHERN VIRGINIA COMMUNITY COLLEGE
FACILITIES PLANNING AND SUPPORT SERVICES
8333 LITTLE RIVER TURNPIKE, CW BUILDING
SUITE 311, ANNANDALE, VA 22003-3796
PHONE: 703-323-3551
AGENCY REPRESENTATIVE:
MIKE JONES
CAPITAL OUTLAY PROGRAM MANAGER
VIRGINIA COMMUNITY COLLEGE SYSTEM
300 ARBORETUM PLACE SUITE 200
RICHMOND, VA 23236
PHONE: 832-428-4678
EMAIL: MJONES@VCCS.EDU
PROJECT #260-B5260-065
MEP
DEWBERRY ENGINEERS INC
8401 ARLINGTON BLVD
FAIRFAX, VA 22031
VIRGINIA CONSTRUCTION CODE(USBC) 2021
VIRGINIA BUILDING CODE 2021
VIRGINIA MECHANICAL CODE 2021
VIRGINIA PLUMBING CODE 2021
VIRGINIA STATEWIDE FIRE PREVENTION CODE (VSFPC) 2021
INTERNATIONAL FIRE CODE (IFC) 2021
AS REFERENCED BYTHE VIRGINIA CODES
NFPA 70 (NATIONAL ELECTRICAL CODE) 2020
NFPA 72 (NATIONAL FIRE ALARM AND SIGNALING CODE) 2019
NFPA 80 (STANDARD FOR FIRE DOORS AND OTHER 2019
OPENING PROTECTIVES)
VIRGINIA ENERGY CONSERVATION CODE 2021
VIRGINIA COMMUNITY COLLEGE SYSTEMS - 2025 REV(0) 03/17/2025
CONSTRUCTION AND PROFESSIONAL SERVICES
MANUAL (VCCS-CPSM)
VIRGINIA UNIFORM STATEWIDE BUILDING CODE(VUSBC) 2021
VIRGINIA EXISTING BUILDING CODE(VEBC) 2021
ADA90- TITLE II: (2010 ASAD) CHAPTER 2 FOR
SCOPING, ICC A117.1-2017 CHAPTERS 1 & 3 THRU
11 FOR TECHNICAL REQUIREMENTS
VIBSR (VIRGINIA INDUSTRIALIZED BUILDING SAFETY REGULATIONS :13VAC5-91),
FOR VIRGINIA COMMUNITY COLLEGE SYSTEM (VCCS)
PROJECT NAME: LOUDOUN CAMPUS LA ADD MEDICAL OXYGEN
GENERATOR
BUILDING LOCATION: 21200 CAMPUS DRIVE
STERLING, VA 20164
PROJECT DESCRIPTION:
THIS PROJECT WILL PROVIDE THE SPECIFICATION AND INSTALLATION OF A NEW
MEDICAL OXYGEN GENERATOR SYSTEM FOR THE LA BUILDING. NEW OXYGEN
GENERATOR WILL CONNECT TO THE EXISTING MEDICAL GAS SYSTEM IN ROOM
127A. NEW OXYGEN GENERATOR WILL BE LOCATED IN ROOM 127A.
HIGH PERFORMANCE BUILDINGS ACT NOTICE:
IN ACCORD WITH THE HIGH PERFORMANCE BUIDLING ACT, THE BUILDINGS ARE
EXEMPT FROM COMPLIANCE BECAUSE THE COST OF THE RENOVATIONS DOES
NOT EXCEED 50% OF THE VALUE OF EACH BUILDING.
ASBESTOS COMPLIANCE STATEMENT (ALL BUILDINGS):
AN ASBESTOS INSPECTION WAS NOT PERFORMED BECAUSE ALL PORTIONS OF
THE EXISTING BUILDING THAT MAY BE AFFECTED BY THE WORK WERE
ORIGINALLY CONSTRUCTED AFTER JANUARY 1, 1985.
NO ASBESTOS CONTAINING MATERIALS TO BE USED IN THIS PROJECT
LEAD COMPLIANCE STATEMENT (ALL BUILDINGS):
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING
COMPONENTS HAS NOT BEEN CONDUCTED BECAUSE THE BUILDING WAS
CONSTRUCTED AFTER JANUARY 1, 1985 AND THE OWNER HAS NO KNOWLEDGE
OF LEAD CONTAINING OR COATED BUILDING COMPONENTS IN THE BUILDING. IT
IS THE CONTRACTOR’S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA
OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN
TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED BUILDING
COMPONENTS SHALL BE RECYCLED TO THE EXTENT POSSIBLE
DW
CB
06-17-2026
260-B5260-065
260-B5260-065
50187099
PROJECT LOCATION
BUILDING LA
PROJECT FIRE STOPPING REQUIREMENTS:
SEAL ALL PIPE PENETRATIONS IN FIRE RATED CONSTRUCTION WITH FACTORY BUILT DEVICES
OR WITH MANUFACTURED FILL, VOID OR CAVITY MATERIALS “CLASSIFIED” BY UNDERWRITERS
LABORATORIES, INC. FOR USE AS A THROUGH PENETRATION FIRESTOP. ALL FIRESTOP
DEVICES AND SYSTEMS SHALL BE APPROVED BY THE OWNER. THE FIRESTOP SYSTEM USED
SHALL MAINTAIN THE FIRE RESISTANCE RATING OF THE BUILDING COMPONENT THAT IS
PENETRATED. FIRESTOP SYSTEMS AND DEVICES SHALL COMPLY WITH ASTM E 814 (UL 1479)
FOR ALL TYPES OF PENETRATIONS BEING SEALED. SUBMITTAL DATA FOR FIRESTOP SYSTEMS
SHALL INCLUDE THE APPLICABLE UL SYSTEM NUMBERS. EXCESSIVE SHRINKAGE OF THE
FIRESTOP MATERIALS, WHICH WOULD PERMIT THE TRANSMISSION OF SMOKE OR WATER PRIOR
TO EXPOSURE TO A FIRE CONDITION, IS UNACCEPTABLE. FIRESTOP SHALL NOT PERMIT
CRACKS AND SHALL BE WATERPROOF. WHERE A MASTIC COATING IS USED TO SEAL THE
SURFACE OF THE FIRESTOP, THE MASTIC SHALL BE NON-HARDENING. THE FIRESTOP SYSTEM
USED SHALL ACCOMMODATE EXPANSION AND CONTRACTION OF THE FLOATING MECHANICAL
PIPING SYSTEMS WITHOUT DAMAGING THE FIRESTOP OR REDUCING ITS EFFECTIVENESS AS A
SMOKE BARRIER OR WATER SEAL. THE FIRESTOP MANUFACTURER'S REPRESENTATIVES SHALL
INSTRUCT THE SUBCONTRACTOR'S REPRESENTATIVES IN THE PROPER INSTALLATION
PROCEDURES SO THAT THE PENETRATIONS ON THE PROJECT WILL BE INSTALLED IN
ACCORDANCE WITH THE UL LISTING AND THE MANUFACTURER'S RECOMMENDATIONS. IF IT
COMPLIES WITH THESE SPECIFICATIONS, FIRESTOP SEALING COMPONENT/SYSTEM AS
MANUFACTURED BY ONE OF THE FOLLOWING MANUFACTURERS WILL BE ACCEPTABLE:
1. TREMCO FIRE RESISTIVE JOINT SYSTEM USING DYMERIC SEALANT AND
CERABLANKET-FS MINERAL FILLER.
2. SPECIFIED TECHNOLOGIES, INC. SPECSEAL SYSTEMS.
3. 3M FIRE BARRIER PENETRATION SEALING SYSTEMS.
4. GE PENSIL FIRESTOP SEALANT BY GENERAL ELECTRIC.
5. INTERNATIONAL PROTECTIVE COATINGS CORP. FLAME SAFE SYSTEMS.
6. THERMAL CERAMICS FIRE MASTER FIRESTOP FIRE PROTECTION SYSTEMS.
7. HILTI FS-601 SYSTEMS.
ALL UNUSED SLEEVES SHALL BE SEALED WITH FIRESTOP DEVICES AND SYSTEMS TO MAINTAIN
THE FIRE RATING OF THE CONSTRUCTION PENETRATED.
WHERE ALLOWED BY APPLICABLE CODES, RULES, REGULATIONS AND MANUFACTURER
RECOMMENDATIONS, THE CONTRACTOR SHALL HAVE THE OPTION OF UTILIZING
THROUGH-PENETRATION FIRE STOP PRODUCTS IN LIEU OF THE SLEEVES AND FIRE STOPPING
MATERIALS SPECIFIED HEREIN FOR ALL PIPING AND FITTING PENETRATIONS OF FIRE-RATED
ASSEMBLIES. THROUGH-PENETRATION FIRE STOP PRODUCTS SHALL COMPLY WITH ASTM E-814
STANDARDS AND SHALL BE THE PRODUCTS OF PROSET SYSTEMS OR APPROVED EQUAL. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER SELECTION, PLACEMENT AND
INSTALLATION OF THESE PRODUCTS. EACH THROUGH-PENETRATION FIRE STOP PRODUCT
SHALL BE COMPATIBLE WITH THE PIPE SIZE, PIPE MATERIAL, AND FIXTURE SERVED.
FIRE STOPPING
G-001
COVER SHEET
L O
U D
O U
N C
A M
P U
S L
A A
D D
M E
D
IC
A L O
X Y
G E
N
G E
N E
R A
T O
R
N O
R T
H E
R N
V
IR
G
IN
IA
C
O M
M U
N
IT
Y C
O L L E
G E
C
A M
P U
S D
R
IV
E
S T
E R
L
IN
G
V A
-B
-0
-1
-2
I
S S
U E
F O
R B
ID
VICINITY MAP
SCALE 1" = 2000'
VICINITY MAP
SITE
DRAWING LIST
Sheet Number Sheet Title
G-001 COVER SHEET
G-002 CODE PLAN
G-003 WALL PENETRATION DETAILS
A-111 FLOOR PLAN - DEMOLITION & NEW WORK & DOOR
SCHEDULE
E-001 ELECTRICAL COVER SHEET
E-101 ELECTRICAL NEW WORK FLOOR PLAN
E-501 ELECTRICAL DETAIL SHEET
P-001 PLUMBING COVER SHEET
P-101 PLUMBING NEW WORK FLOOR PLAN
P-501 PLUMBING DETAIL SHEET
01/06/202601/06/20263020606301012020//0766 03/103/1452452201272027
G E
N E
R A
T O
R
-1
-2
I
S S
U E
F O
R B
ID
07-15-2026
07-15-2026
VET LAB
FELINE
HOLDING
AREA STORAGE
JAN.
ANIMAL
HOLDING
AREA
CONNECTOR
100C
CORRIDOR
GROOMING
116B
STORAGE
116C
116F
ANIMAL
QUARTERS
116E
ANIMAL
QUARTERS
116D
CLEANUP
AREA
116A
ANIMAL
QUARTERS
CANINE
HOLDING
AREA
STORAGE
/CHANGE
ROOMISOLATION
MECH.
CORRIDOR
100B
RADIOLOGY
SURGERY
111A
DARK
ROOM
PREP.
ROOM
109A
SCRUB
ROOM
MEN'S
WOMEN'S
FOYER
EXAM
ROOM
OFFICE
100D
LOBBY
LOBBY
SEATING
RECOVERY
ROOMS 137
EXAM
ROOM
EXAM
ROOM
STUDY
RADIOLOGY
JANITOR
UNISEX
COMPUTER
TELCO
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
MECH
UNISEX
100G
CORRIDOR
RECOVERY
AUTOCLAVE
144B
CHANGING
ROOM
150B
ANIMAL
PREP
150C
SURGEONS
SCRUB
150A
OPERATING
ROOM
TEACHING
LAB
P A
T H
-A
1 11 1 1 1 1 1 1
1 11 1 1 1 1 1
11 1
1 1
EXISTING EQUIPMENT PAD.
53 SF
OXYGEN
GENERATOR RM
127A
162 SF
MECHANICAL
EQUIPMENT RM
TRAVEL DISTANCE
PATH A = 22 FEET
APPROXIMATE EXTENT OF
WORK AREA = 227 SQ.FT
(MECHANCIAL RM #127).
180 SF
ELECTRICAL
CLOSET
104A
48 SF
PLUMBING
104B
ROOM SIGNAGE - A
6 3/32"PARTN TYPE WIDTH
O
PN
G P
ER
R
AT
ED
AS
SE
M
BL
Y
FIRESTOP DEVICE
1 TO 7 GANG
CABLES
RATED PARTN
TYPE AS
SCHEDULED
RATING NO:
MAX 4 HR, UL W-L-3218
OR EQ
6 3/32"PARTN TYPE WIDTH
/3 2"
O
PN
G P
ER
R
AT
ED
AS
SE
M
BL
Y
FIRE RATED SEALANT
INTUMESCENT
WRAP STRIP AT
PERIMETER OF
CABLE TRAY
BED CABLE IN FIRE
RATED SEALANT, PER
THE RATED
ASSEMBLY
INSULATED
CABLES AND
STEEL TRAY
INTUMESCENT SHEET
RATED PARTN
TYPE AS
SCHEDULED
RATING NO:
MAX 2 HR, UL W-L-4004,
OR EQ
1"
/8
/4
/8
/2
/2
1/2" 7" 1/2"
TOP PANEL
PANEL SIZE: 3" X 8"
PANEL MATERIAL: EITHER ABS OR ALUMINUM
PANEL COLOR: TO MATCH EXISTING - NAVY BLUE
TEXT FONT: 162 POINT FRUTIGER NEXT PRO MEDIUM CONDENSED
TEXT THICKNESS: AT LEAST 1/32" THICKNESS
TEXT COLOR: WHITE
BRAILLE: TYPE II BRAILLE TO MATCH BACKGROUND OF PANEL FACE
BOTTOM PANEL
PANEL SIZE: 1" X 8"
PANEL DESCRIPTION: WINDOW INSERT TO ACCOMODATE A POST-
PRINTED PAPER INSERT
BOTTOM
PANEL
TOP
PANEL
EXTRUDED ALUMINUM END CAPS
CENTER OF TACTILE NUMBERS ON 9" FROM DOOR FRAME
' M
A X
. H E
IG
H
T T
O B
A S
E L
IN
E
O F
T A
C T
IL
E
L E
T T
E R
S
' M
IN
IM
U M
H E
IG
H
T T
O B
A S
E
LI
N E
O F
T A
C T
IL
E
L E
T T
E R
S
9" 9"
18" CLEAR
FLOOR SPACE
SCREW INTO WALL
(PREFERRED METHOD)
EXTUDED ALUMINUM
BACK PLATE RAIL
SYSTEM
REFER TO
ELEVATION
4/G-002
WALL AS SCHEDULED
1. REFER TO SHEET G-002 FOR INTERIOR SIGNAGE LOCATION ON FLOOR PLAN.
2. GC TO SUBMIT SIGNAGE SHOP DRAWINGS FOR APPROVAL OF SIGNAGE ROOM
NAME, NUMBERS, AND COLORS FOR APPROVAL WITH OWNER BEFORE ANY
FABRICATION AND INSTALLATION
SIGNAGE SCHEDULE
SIGN TYPE ROOM NUMBER ROOM NAME SIGNAGE TEXT COMMENTS
A 127A OXYGEN GENERATOR ROOM SINGLE ID SLOT +
STAFF ONLY SIGN
SIGNAGE - GENERAL NOTE
OXYGEN GENERATOR ROOM
A
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
DEWBERRY PROJECT NUMBER:
DBE PROJECT NUMBER:
F
23456
50187099
FACILITIES PLANNING & SUPPORT SERVICES
8333 LITTLE RIVER TURNPIKE
ANNANDALE, VA 22003
/2
/2
:3
:1
P
M
CODE PLAN &
SIGNAGE DETAIL
MD
DW
JO
2/13/2026
260-B5260-065
L A
A D
D M
E D
IC
A
L O
X Y
G E
N G
E N
E R
A T
O R
N O
R T
H E
R N
V
IR
G
IN
IA
C
O M
U N
IT
Y
C O
L
LE
G E
LO
U D
O U
N C
A M
P U
S
IS
S
U E
D F
O R
B
ID
C
A M
P U
S D
R
IV
E
S T
E R
LI
N
G
V A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
G-002
260-B5260-065
0-
B
-0
Scale: 3/32" = 1'-0"1 FIRST FLOOR EXISTING LIFE SAFETY PLAN
BUILDING ADDRESS:
21200 CAMPUS DRIVE, STERLING VA 20164
PROJECT DESCRIPTION:
THE WORK INCLUDES TO DIVIDE THE EXISTING
MECHANICAL ROOM #127, INTO TWO ROOMS: OXYGEN
GENERATOR AND MECHANICAL ROOM. THE WORK
INCLUDES:
A. SELECTIVE DEMOLITION OF EXISTING EQUIPMENT
CONCRETE PAD AND RELOCATION OF EXISTING WATER
HEATER.
B. TO PROVIDE NEW PARTITION WALL AND A DOOR.
C. REMOVE EXISTING OXYGEN TANKS AND MANIFOLD AND
PROVIDE NEW OXYGEN GENERATOR.
APPLICABLE CODES:
VIRGINIA CONSTRUCTION CODE (VCC) -
VIRGINIA BUILDING CODE -
VIRGINIA MECHANICAL CODE -
VIRGINIA PLUMBING CODE -
VIRGINIA STATEWIDE FIRE PREVENTION CODE-
INTERNATIONAL FIRE CODE-
AS REFERENCED BY THE VIRGINIA CODE
NFPA 70 (NATIONAL ELECTRIC COD) -
NFPA 72-
(NATIONAL FIRE ALARM AND SIGNALING CODE)
NFPA 80 (STANDARD FOR FIRE DOORS AND
OTHER OPENING PROTECTIVES) -
VIRGINIA ENERGY CONSERVATION CODE (VECC) -
VIRGINIA EXISTING BUILDING CODE (VEBC). ALT 2-
VIRGINIA UNIFORM STATEWIDE BUILDING CODE -
ADA 90 TITLE II: ASAD CHAPTER 2 FOR SCOPING -
ICC A117.1- CHAPTER 1 AND 3 THRU 11 FOR
TECHNICAL REQUIRED
VIRGINIA COMMUNITY COLLEGE SYSTEM
CONSTRUCTION AND PROFESSIONAL SERVICES
MANUAL, (CPSM), .......................2025 REV (0) ISSUED 03/17/25
CLASSIFICATION OF WORK: VEBC 601.2.2 LEVEL 2 ALTERATIONS SHALL COMPLY
WITH THE APPLICABLE PROVISIONS OF SECTIONS 602 AND 603 AND SHALL
INCLUDE THE FOLLOWING:
1. THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW.
2. THE ADDITION OR ELIMINATION OF ANY WALL, FLOOR, OR CEILING
ASSEMBLY.
3. THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM.
4. THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT, MATERIALS,
ELEMENTS, OR FIXTURES.
• BUILDING FUNCTION: OFFICE, TEACHING LABS & ANIMAL MEDICAL FACILITY
(BUILDING NOT TO BE USED AS EMERGENCY SHELTER)
• BUILDING USE GROUP: B (BUSINESS) (UNCHANGED)
• CONSTRUCTION TYPE IIB, (SPRINKLERED): (UNCHANGED)
• GROSS BUILDING AREA: 11,480 SQ.FT (UNCHANGED)
• BUILDING HEIGHT = ONE STORY = 20 FT (UNCHANGED)
• RENOVATED AREA USE GROUP
( ACCESSORY STORAGE AREA MECHANICAL ROOM) : (UNCHANGED)
• TOTAL OCCUPANCY LOAD = 91 (UNCHANGED)
• SCOPE OF WORK AREA: = 443 SQ.FT
PROJECT BUILDING CODE INFORMATION
Scale: 3" = 1'-0"2 TYPICAL - FIRESTOP DEVICE - THRU GYP BD WALL Scale: 3" = 1'-0"3 TYP CABLE TRAY THRU FIRE RATED GYP BOARD WALL
0' 10' 20'5'
SCALE: 3/32" = 1' - 0"
NORTH
0' 6"3" 9"
SCALE: 3" = 1' - 0"
NO. DESCRIPTION DATE
1 PERMIT REVISION-01 06.12.26
2 PERMIT REVISION-02 07.15.26
Scale: 6" = 1'-0"4 ROOM SIGNAGE Scale: 3/4" = 1'-0"5 INTERIOR SIGNAGE MOUNTING
Scale: 6" = 1'-0"6 INTERIOR SIGNAGE MOUNTING DETAIL
0' 2'1' 3'
SCALE: 3/4" = 1' - 0"
0' 2" 4"1"
SCALE: 6" = 1' - 0"
2/13/2026 ehoffman Snapshot ehoffman Snapshot
PARTN TYPE WIDTH
O P
N G
P E
R
R A
T E
D
A S
S E
M B
LY
FIRESTOP
DEVICE
1 TO 7 GANG
CABLES
RATED PARTN
TYPE AS
SCHEDULED
RATING NO:
MAX 4 HR, UL W-L-3218
OR EQ
FIRE RATED SEALANT
INTUMESCENT WRAP
STRIP AT PERIMETER
OF CABLE TRAY
BED CABLE IN FIRE
RATED SEALANT, PER
THE RATED ASSEMBLY
INSULATED CABLES
AND STEEL TRAY
INTUMESCENT SHEET
RATING NO:
3 HR UL C-AJ-4003,
OR EQ
CONCRETE
CMU
WALL,
AS
SCHED
O
PN
G P
ER
R
AT
ED
A
SS
EM
BL
Y
PARTN TYPE WIDTH
O P
N G
P E
R R
A T
E D
A S
S E
M B
LY
FIRE RATED SEALANT
INTUMESCENT WRAP
STRIP AT PERIMETER
OF CABLE TRAY
BED CABLE IN FIRE
RATED SEALANT, PER
THE RATED ASSEMBLY
INSULATED CABLES
AND STEEL TRAY
INTUMESCENT SHEET
RATED PARTN TYPE
AS SCHEDULED
RATING NO:
MAX 2 HR, UL W-L-4004,
OR EQ
M
IN
METAL JUNCTION
BOX, SEPARATE
BACK TO BACK
BOXES 24" MIN
CMU PARTITION
TYPE AS
SCHEDULED
TYPICAL METAL
JUNCTION BOX,
MOUNT FLUSH W/
FACE OF CMU, AND
GROUT SOLID
AROUND BOX
PLAN
SECTION
RATED
PARTITION, AS
SCHEDULED
ACOUSTICAL
INSUL AS
SCHEDULED
TELEPHONE OR
ELECTRICAL COVER
PLATE
CONTINUOUS
ACOUS SEALANT
AROUND TEL & MET
ELEC OUTLET BOX
MOLDABLE FIRE-
STOPPING AROUND
TELEPHONE OR
ELEC OUTLET BOX
FILL BEHIND THE BOX
WITH FIRE BLANKET
INSULATION
" M
IN
N
TS
PARTITION AS SCHEDULED
ACOUSTICAL INSULATION
COVER PLATE
METAL STUDS
FLEX CABLE BETWEEN
"J" BOXES, WHERE
OCCURS
OUTLET BOX PAD
AROUND "J" BOXES
CONT ACOUS SEALANT
AROUND "J" BOXES
TYP MET "J" BOX
MOUNT ADJOINING "J"
BOXES IN SEPARATE
STUD CAVITIES
FIRE RATED SEALANT
EA SIDE OF PARTN W/
BACKER ROD
MET DUCT
UL COMPLYING STL BENT PLATE
RETAINING ANGLES, BOTH SIDES
OF PARTN, ATTACH TO DUCT W/
UL COMPLYING SM SCREWS,
OVERLAP PARTN OPNG 1" MIN
RATING NO:
MAX 2 HR, UL W-L-7008,
OR EQ
RATED GYP BD
PARTN, AS SCHED
DBL STUD FRAMED
OPNG, TYP
STOP DUCT INSUL @ FO
PARTN, SEAL VAPOR
BARRIER TO GYP BD
WHERE OCCURS
METAL SLEEVE WHERE
REQUIRED BY CONTRACT
DOCUMENTS
FIRE RATED SEALANT AND
PACKING - DEPTH AS REQ'D
BY RATED ASSEMBLY
ANNULAR SPACE PER
RATED ASSEMBLY
METAL PIPE
FILL AROUND SLEEVE IN
MASONRY CONSTRUCTION
W/ CEMENT MORTAR
RATING NO:
MAX 3 HR, UL C-AJ-1017,
OR EQ
CONCRETE
MASONRY
PARTN TYPE WIDTH
FIRESTOP
DEVICE
1 TO 7 GANG
CABLES
CMU/CONC PARTN
TYPE AS
SCHEDULED
RATING NO:
MAX 4 HR, UL W-J-3098
OR EQ
A
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
DEWBERRY PROJECT NUMBER:
DBE PROJECT NUMBER:
F
23456
50187099
FACILITIES PLANNING & SUPPORT SERVICES
8333 LITTLE RIVER TURNPIKE
ANNANDALE, VA 22003
/1
/2
:2
:1
P
M
WALL
PENETRATION
DETAILS
MD
DW
JO
2/13/2026
260-B5260-065
L A
A D
D M
E D
IC
A
L O
X Y
G E
N G
E N
E R
A T
O R
N O
R T
H E
R N
V
IR
G
IN
IA
C
O M
U N
IT
Y
C O
LL
E
G E
LO
U D
O U
N C
A M
P U
S
IS
S
U E
D F
O R
B
ID
C
A M
P U
S D
R
IV
E
S T
E R
LI
N
G
V A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
G-003
260-B5260-065
0-
B
0-
Scale: 3" = 1'-0"9
TYP CABLE FIRESTOP DEVICE
THRU GYP BD
Scale: 3" = 1'-0"8
TYP CABLE TRAY
THRU CONC/CMU RATED WALL
Scale: 3" = 1'-0"7
TYP CABLE TRAY
THRU RATED GYP BD PARTN
Scale: 1 1/2" = 1'-0"6 TYP J BOX @ CMU PARTN Scale: 3" = 1'-0"5
TYP "J" BOX @ RATED
GYP BD PARTN
Scale: 3" = 1'-0"4
TYP "J" BOX @ GYP BD
PARTN W/ ACOUS INSUL
Scale: 3" = 1'-0"2
TYP MET DUCT
THRU RATED GYP BD PARTN
Scale: 3" = 1'-0"1
TYP PIPE/CONDUIT THRU
CONC/CMU RATED WALL
Scale: 3" = 1'-0"3
TYP. CABLE FIRESTOP DEVICE
THRU CONC/CMU
0' 8" 16"4"
SCALE: 1 1/2" = 1' - 0"
0' 6"3" 9"
SCALE: 3" = 1' - 0"
NO. DESCRIPTION DATE
07/16/2026
06-17-202607-15-2026
PREP.
ROOM
109A
SCRUB
ROOM
MEN'S
WOMEN'S
FOYER
VET LAB
FELINE
HOLDING
AREA STORAGE
JAN.
ANIMAL
HOLDING
AREA
CONNECTOR
100C
CORRIDOR
GROOMING
116B
STORAGE
116C
116F
ANIMAL
QUARTERS
116E
ANIMAL
QUARTERS
116D
CLEANUP
AREA
116A
ANIMAL
QUARTERS
CANINE
HOLDING
AREA
STORAGE
/CHANGE
ROOMISOLATION
MECH.
CORRIDOR
100B
RADIOLOGY
SURGERY
111A
DARK
ROOM
PREP.
ROOM
109A
SCRUB
ROOM
MEN'S
WOMEN'S
FOYER
EXAM
ROOM
OFFICE
100D
LOBBY
LOBBY
SEATING
RECOVERY
ROOMS 137
EXAM
ROOM
EXAM
ROOM
STUDY
RADIOLOGY
140A
ELEC
JANITOR
UNISEX
PLUMBING
COMPUTER
TELCO
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
MECH
UNISEX
100G
CORRIDOR
RECOVERY
AUTOCLAVE
144B
CHANGING
ROOM
150B
ANIMAL
PREP
150C
SURGEONS
SCRUB
150A
OPERATING
ROOM
TEACHING
LAB
PREP.
ROOM
109A
SCRUB
ROOM
MEN'S
WOMEN'S
FOYER
GENERAL NOTES - NEW WORK PLAN
1. NO ASBESTOS CONTAINING MATERIAL SHALL BE USED ON THIS PROJECT.
2. DIMENSIONS ARE SHOWN AS FOLLOWS, U.N.O.
A. ALL DIMENSIONS ARE SHOWN TO THE FINISHED FACE, U.N.O.
B. DIMENSIONS NOTED AS "CLEAR" (CLR.) ARE TO THE FACE OF FINISHED
SURFACE AND TAKE PRECEDENT OVER ALL OTHER DIMENSIONS.
C. DISCREPANCIES IN DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE
ATTENTION OF THE ARCHITECT, WHO WILL ISSUE WRITTEN CLARIFICATION.
3. FINAL PARTITION WALL FINISH - PAINT TO MATCH COLOR W/ EXISTING WALLS.
4. COORDINATE ELECTRICAL OUTLET LOCATIONS - REFER TO ELECTRICAL
DRAWINGS. BACK-TO-BACK OUTLETS CANNOT OCCUPY SAME STUD CAVITY
SPACE.
5. REFER TO G-002 FOR EXISTING CODE PLANS AND FOR GRAPHIC
REPRESENTATION .
6. REFER TO G-003 FOR WALL PENETRATION DETAILS.
LEGEND FLOOR PLAN
EXISTING WALL TO REMAIN
NEW DOOR
EXISTING CONCRET PAD TO REMAIN
NEW PARTITION WALL
EXISTING DOOR TO REMAIN
AREA OUTSIDE THE PROJECT SCOPE
NEW 4" EQUIPMENT CONCRET PAD ON
EXISTING CONCRETE FLOOR LEVEL
OXYGEN
GENERATOR RM
127A
MECHANICAL
EQUIPMENT RM
A
0"
V .I.
F
9' - 1 7/8" +/- V.I.F.
4' - 0"
+/- V.I.F
1' - 6"
AC OG
OST
NEW 4" CONCRETE EQUIPMENT
PAD ON EX.CONCRETE FLOOR
MATCH THE TOP LEVEL W/
EXISTING CONCRETE PAD -
SEE DETAIL 9/A-111
A-111
SCOPE OF WORK
(MECHANICAL RM #127)
SCOPE OF WORK
(ELECTRICAL RM #140A)
SCOPE OF WORK
(PLUMBING RM #142)
ROUGHEN THE EXISTING
CONCRETE FLOOR IN
PREPARATION FOR THE NEW 4"
CONCRETE EQUIPMENT PAD
EXISTING FLOOR DRAIN.
TO REMAIN, TYPICAL
EXISTING CONCRETE
PAD. EL + 4", TO REMAIN
EXISTING CONCRETE
PAD. EL + 4", TO REMAIN
MECHANICAL
EQUIPMENT RM
4"
0"
4"
4"
EXISTING LOUVER
5'-0"(w) X 2'-2" (h) TO
REMIAN, TYPCIAL
V .I.
F
9' - 1 7/8" +/- V.I.F.
EXISTING CONCRETE
PAD. EL + 4", TO REMAIN
V.I.F
1' - 6"
V .I.
F
V .I.
F
4' - 0" V.I.F
DEMOLITION PLAN GENERAL NOTES
1. VISIT SITE AND VERIFY EXISTING CONDITIONS PRIOR TO BID SUBMISSION.
DISCREPANCIES BETWEEN CONSTRUCTION INDICATED ON DRAWINGS AND
ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO ARCHITECT’S ATTENTION
IMMEDIATELY IN WRITING.
2. DEMOLISHED ITEMS NOT INDICATED TO BE “DELIVERED TO OWNER” OR “TO BE
RELOCATED” SHALL BE REMOVED FROM SITE AS SOON AS POSSIBLE UNLESS
THEY ARE TO BE USED FOR REQUIRED PATCHING AND INFILLING OF EXISTING
CONSTRUCTION THAT IS TO REMAIN. NO OTHER DEMOLISHED ITEMS SHALL BE
STORED ON SITE.
3. DEMOLISHED ITEMS NOTED AS “DELIVER TO OWNER” OR “TO BE RELOCATED”
SHALL BE REMOVED OR DISASSEMBLED IN SUCH A MANNER THAT WILL NOT
DAMAGE THE ITEM AND PREVENT IT FROM BEING RELOCATED. REPAIR OR
REPLACE SUCH ITEMS, IF DAMAGED. NOTIFY OWNER’S REPRESENTATIVE
IMMEDIATELY IF DAMAGE HAS OCCURRED, AND SUBMIT A REPAIR SOLUTION TO
ARCHITECT FOR REVIEW.
4. TEMPORARILY STORE ITEMS INDICATED AS “DELIVER TO THE OWNER” IN ONSITE
LOCATION, DESIGNATED BY THE OWNER. OWNER SHALL MOVE ITEM(S), AS
NECESSARY, TO NOT HINDER OR DELAY PERFORMANCE OF WORK IN AREA.
5. TEMPORARILY STORE ITEMS INDICATED AS “TO BE RELOCATED” IN LOCATION
ONSITE AND PROTECT ITEMS FROM DAMAGE PRIOR TO INSTALLATION IN NEW
LOCATION.
6. ITEMS INDICATED “TO REMAIN” THAT ARE DAMAGED DURING THE PERFORMANCE
OF THE DEMOLITION WORK. SUCH DAMAGE SHALL BE REPORTED TO OWNER’S
REPRESENTATIVE IMMEDIATELY, AND SUBMIT A REPAIR SOLUTION TO ARCHITECT
FOR REVIEW.
7. COORDINATE DEMOLITION WORK WITH NEW CONSTRUCTION WORK IN EACH
AREA OF DEMOLITION. EXISTING CONSTRUCTION IN AREAS ADJACENT TO
DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO MATCH ORIGINAL
EXISTING CONDITION AS REQUIRED TO PROVIDE FOR NEW CONSTRUCTION
WORK IN AREA OF DEMOLITION.
8. ITEMS INDICATED TO BE REMOVED BY OWNER SHALL BE COMPLETED PRIOR TO
COMMENCEMENT OF WORK.
9. AT LOCATIONS WHERE A PORTION OF EXISTING CONSTRUCTION IS TO BE
REMOVED AND PREPARED FOR NEW INFILL CONSTRUCTION, OR AN OPENING IN A
WALL, ROOF, OR FLOOR IS CREATED BY DEMOLITION WORK, CONSTRUCT INFILL
WITH SAME MATERIALS AND METHOD OF CONSTRUCTION AS EXISTING ADJACENT
CONSTRUCTION, UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL DRAWINGS
FOR INFILL CONSTRUCTION. INFILL CONSTRUCTION SHALL SMOOTHLY BUTT
ADJACENT SURFACES AND MATCH THE FINISH, U.N.O.
10. AT LOCATIONS WHERE AN ITEM IS TO BE REMOVED FROM A SURFACE THAT IS TO
REMAIN, PATCH AND REPAIR EXISTING SURFACE TO MATCH EXISTING ADJACENT
SURFACE, UNLESS INDICATED OTHERWISE.
11. EXISTING ITEMS ANCHORED TO CONSTRUCTION THAT IS INDICATED TO BE
DEMOLISHED SHALL BE CONSIDERED A PART OF DEMOLISHED CONSTRUCTION
AND SHALL BE DEMOLISHED WITH THE INDICATED CONSTRUCTION, UNLESS
NOTED OTHERWISE.
12. IN CONDITIONS WHERE A WALL OR FLOOR FINISH IS DEMOLISHED CREATING A
DISSIMILAR ELEVATION IN ADJACENT FLOOR FINISHES, INSTALL AN APPROVED
LEVELING MATERIAL TO BRING LOWER FLOOR FINISH ELEVATION UP TO AN
ELEVATION FLUSH WITH ADJACENT FLOOR.
13. CONSTRUCT TEMPORARY DUST PARTITIONS TO CONTAIN DEMOLITION WORK
AND PREVENT CONSTRUCTION DUST FROM ENTERING ADJACENT EXISTING
CONSTRUCTION. SUBMIT LOCATIONS OF THESE PARTITIONS FOR APPROVAL BY
OWNER’S REPRESENTATIVE. PARTITION LOCATIONS SHALL NOT IMPEDE OR
HINDER EMERGENCY EGRESS FROM BUILDING. REFER TO SPECIFICATIONS FOR
CONSTRUCTION OF DUST PARTITIONS.
14. RETAIN DEMOLISHED MATERIALS AS NEEDED FOR INFILLING OPENINGS IN
EXISTING CONSTRUCTION SO THAT FINISH MATERIALS WILL PROPERLY ALIGN
WITH EXISTING AND MATCH THE EXISTING FINISH. IF DEMOLISHED MATERIALS
ARE NOT SALVAGEABLE, NOTIFY OWNER’S REPRESENTATIVE, SO THAT
ALTERNATE SOLUTIONS MAY BE DETERMINED.
15. IF EXISTING CONSTRUCTION IS REVEALED NOT CONSTRUCTED OR FINISHED IN A
MANNER THAT MATCHES ADJACENT SURFACES, PATCH AREA AS NECESSARY
WITH APPROPRIATE MATERIALS AND METHODS OF CONSTRUCTION TO MATCH
EXISTING ADJACENT FINISH, OR PREPARE SURFACE FOR INSTALLATION OF NEW
FINISH. CONTACT OWNER’S REPRESENTATIVE AS SOON AS POSSIBLE SO THAT
CONCEALED CONSTRUCTION MAY BE IDENTIFIED AND SCOPE OF POSSIBLE
ADDITIONAL WORK DETERMINED.
16. WHEN EXISTING SURFACE IS INDICATED TO BE “PATCHED AND REPAIRED” OR
“PREPARED” TO RECEIVE NEW FINISH MATERIAL, PROVIDE A CONSTRUCTION
SURFACE THAT IS CAPABLE OF RECEIVING NEW FINISH MATERIAL.
17. WHEN THE TERM ‘ENTIRETY’ IS DIRECTED TO A SPECIFIC ITEM OR ASSEMBLY,
DEMOLISH AND REMOVE IDENTIFIED ITEM AND ASSOCIATED CONSTRUCTION
PERTINENT TO THE ITEM, INCLUDING, BUT NOT LIMITED TO UNDERGROUND AND
CONCEALED CONSTRUCTION, SUCH AS FOOTINGS AND FOUNDATIONS, SEWER,
PLUMBING, AND ELECTRICAL WORK. THIS DEMOLITION WORK SHALL BE
COORDINATED WITH THE CIVIL, STRUCTURAL, PLUMBING, MECHANICAL,
ELECTRICAL, AND TECHNOLOGY DRAWINGS.
18. CONTRACTOR TO PROVIDE HOURLY FIRE WATCH FOR ANY FIRE ALARM OR
SPRINKLER IMPAIRMENTS 1-HOUR OR LONGER. FIRE WATCH TO INCLUDE
WALKING THE ENTIRE BUILDING HOURS. FIRE WATCH TO BE DOCUMENTED ON A
FIRE WATCH LOG. PROVIDE THE FIRE WATCH LOG TO THE PROJECT MANAGER.
REFER TO SPEC SECTION 01 0010 FOR DETAILS.
1/2"1/2"
2"
VARIES
SEALANT ALL AROUND,
BOTH SIDES
HOLLOW METAL FRAME
PARTITION AS SCHEDULED
DOOR AS SCHEDULED
/2
/2
2"
V A
R
IE
S
PARTITION AS SCHEDULED
HOLLOW METAL FRAME
JAMB ANCHOR CLIP
DOOR AS SCHEDULED
SEALANT ALL AROUND,
BOTH SIDES
D O
O R
H E
IG
H
T
WIDTH
DOOR
M
IN
6"X8" SIGNAGE - A
EQ EQ
H E
IG
H
T
8" WIDE
SIGNAGE - A
SIGNAGE - A: TO BE LOCATED
ON ROOM #127A DOOR.
REINFORCED PLASTIC F
H E
IG
H
T
WIDTH
DOOR
CONCRETE SLAB
DOOR PANEL
/2
SECTION AT TOP
STOP GYP BOARD BELOW
MECHANICAL DUCTS
SECTION AT BASE
(1) LAYER 5/8'' GYPSUM
BOARD, BOTH SIDES,
MOISTURE & MOLD
RESISTANT
3 5/8" THICK, 20 GA METAL
STUD @ 16'' O.C.
DIAGONAL BRACING 3 5/8"
METAL STUD 20G, @ 16" O.C
BOTH SIDES AS REQUIRED
WALL TYPE - A - NON FIRE RATED
EX. UNDERSIDE OF METAL
ROOF ABOVE
SEALANT - BOTH SIDES
G Y
P B
O A
R D
F U
L L
S T
U D
H E
IG
H
T
3'
-0
M A
X
CONTINUOUS RUBBERIZED
MOISTURE ISOLATION UNER
LOWER TRACK
CONCRETE FLOOR
USE 16 GA STEPPED
BOTTOM PLATE AS NEEDED
1. ALL FRAMES TO BE 2" WIDE UNLESS NOTED OTHERWISE.
2. HOLLOW METAL DOORS AND FRAMES TO BE PAINTED THE SAME COLOR TO
EXISTING DOOR AND FRAMES.
3. LOCATED DOORS IN PARTITIONS NEAR ADJACENT WALLS 4 INCHES FROM FACE
OF ADJACENT WALL TO EDGE OF DOOR U.N.O.
4. FOR DOOR FRAMES HEAD, JAMB, THRESHOLD SEE DOOR SCHEDULE.
5. FOR DOOR HARDWARE TYPES AND INSTALLATION REFER TO SPEC 08 71 00.
DOOR GENERAL NOTE
3"
C
LE
A R
EXISTING
EQUIPMENT
PAD
#4 AT 12" O.C. EACH WAY
DRILL 5/8" DIA. X 4" DEEP
HOLES INTO EXISTING PAD
AND SET REBAR IN HIGH
STRENGTH EPOXY
DOWELING SYSTEM
#4 DOWELS WITH 8" LEGS AT 12"
O.C. MAXIMUM SPACING AROUND
PERIMETER OF PAD DIRECTION.
DRILL 5/8" DIA. X 3" DEEP HOLES
INTO EXISTING SLAB AND SET
DOWELS IN HIGH STRENGTH EPOXY
DOWELING SYSTEM.
EXISTING SLAB-ON-GRADE
SCARIFY SLAB SURFACE AT
PAD LOCATION AND APPLY
EPOXY BONDING ADHESIVE
M A
T C
H E
X
IS
T
IN
G
3/4" CHAMFER
EQUIPMENT HOUSEKEEPING PAD EXTENSION NOTES:
1. PAD CONCRETE SHALL HAVE A MINIMUM 28-DAYS COMPRESSIVE STRENGTH OF 4,000 PSI.
2. HOUSE KEEPING PAD EXTENSION SHALL EXTEND A MINIMUM O F4" BEYOND EQUIPMENT
FOOTPRINT OR AS SHOWN ON DRAWINGS.
3. APPLY EPOXY BONDING ADHESIVE ON SIDE OF EXISTING PAD PRIOR TO POURING PAD
EXTENSION.
4. COORDINATE EXACT PAD LOCATION WITH MECHANICAL PLAN.
5. IF PAD EXTENSION IS POURED AGAINST AND EXISTING WALL, PLACE 1/2" EXPANSION JOINT
MATERIAL BETWEEN A WALL AND A SLAB.
EX. METAL EXTERIOR WALL
EX. METAL EXTERIOR
LOUVER 2' (H) X 4' (W)
@ 4" A.F.F
PARTITION WALL - A
PROVIDE 24GA GALVANIZED
METAL COVER AS SHOWN AT
WALL END FOR 3'-0" HIGH.
PROVID ADDITIONAL STUD
STRAP AT LOWER TRACK AS
REQUIRED
1 1/2"
A
B
C
D
E
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
DEWBERRY PROJECT NUMBER:
DBE PROJECT NUMBER:
F
23456
50187099
FACILITIES PLANNING & SUPPORT SERVICES
8333 LITTLE RIVER TURNPIKE
ANNANDALE, VA 22003
/1
/2
:2
:2
P
M
FLOOR PLAN -
DEMOLITION &
NEW WORK &
DOOR SCHEDULE
MD
DW
JO
2/13/2026
260-B5260-065
L A
A D
D M
E D
IC
A
L O
X Y
G E
N G
E N
E R
A T
O R
N O
R T
H E
R N
V
IR
G
IN
IA
C
O M
U N
IT
Y
C O
LL
E
G E
LO
U D
O U
N C
A M
P U
S
IS
S
U E
D F
O R
B
ID
C
A M
P U
S D
R
IV
E
S T
E R
LI
N
G
V A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
A-111
260-B5260-065
0-
B
0-
0' 8" 16"4"
SCALE: 1 1/2" = 1' - 0"
NORTH
Scale: 1/4" = 1'-0"2 NEW WORK FLOOR PLAN
Scale: 1" = 40'-0"- KEY PLAN
Scale: 1/4" = 1'-0"1 DEMOLITION FLOOR PLAN
DOOR SCHEDULE
D O
O R
N U
M B
E
R DOOR FRAME DETAILS
F
IR
E L
A B
E L
H A
R D
W A
R E
R E
M A
R K
S
D O
O R
N U
M B
E R
LE
A
F Q
T Y
SIZE
T Y
P E
M A
T E
R
IA
L
G
LA
Z
IN
G
T Y
P E
M A
T E
R
IA
L
G
LA
Z
IN
G
SIDELIGHT
WIDTH
TRANSOM
HEIGHT HEAD JAMB SILLWIDTH
WIDTH (IF
UNEVEN) HEIGHT THICKNESS
127 1 3' - 0" 7' - 0" 1 3/4" F HM - HM - H-1 J-1 S-1 - 01 ADD SIGNAG- A ON
DOOR
Scale: 1 1/2" = 1'-0"7 INTERIOR DOOR HEAD (H-1) Scale: 1 1/2" = 1'-0"6 INTERIOR DOOR JAMB (J-1)
Scale: 1/4" = 1'-0"4 DOOR FRAME TYPES Scale: 1/4" = 1'-0"5 DOOR PANEL TYPES
Scale: 6" = 1'-0"8 INTERIOR DOOR SILL (S-1)
Scale: 1" = 1'-0"3 PARTITION WALL - TYPE A
Scale: 1" = 1'-0"9 TYPICAL - CONCRETE EQUIPMENT PAD ADDITION
0' 12" 24"6"
SCALE: 1" = 1' - 0"
0' 4' 8'2'
SCALE: 1/4" = 1' - 0"
Scale: 1 1/2" = 1'-0"10 PLAN DETAIL
0' 2" 4"1"
SCALE: 6" = 1' - 0"
NO. DESCRIPTION DATE
07/16/2026
CB
07-15-2026
260-B5260-065
260-B5260-065
50187099
APPROVED BY
CHECKED BY
A
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
No. Description Date
REVISIONS
23456
B
C
D
E
F
DEB PROJECT NUMBER :
DEWBERRY PROJECT NUMBER:
FACILITIES PLANNING & SUPPORT SERVICES
8333 LITTLE RIVER TURNPIKE
ANNANDALE, VA 22003
Dewberry Engineers, Inc.
8401 ARLINGTON BLVD
FAIRFAX, VA 22031
703.849.0100 Phone
260-B5260-065
50187099
/2
/2
:0
:1
A
M
Q
P R
O J E
C T
S \5
N V
C C
L A
A D
D O
X Y
G E
N G
E N
E R
A T
O R
\C A
D \E
L E
C T
R
IC
A L \E
-0 E
L E
C T
R
IC
A L C
O V
E R
S H
E E
T .D
W G
ELECTRICAL NOTES
GENERAL
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE CODES AS
INDICATED ON UNDER THE "APPLICABLE CODES AND CRITERIA" SECTION ON DRAWING G-001.
ALL TRADES SHALL COORDINATE ON PLACEMENT OF NEW EQUIPMENT. REFER TO THE
GENERAL NOTES AND DEMOLITION NOTES FOR ADDITIONAL REQUIREMENTS.
2. UNLESS NOTED OTHERWISE ALL EXISTING ELECTRICAL FIXTURES AND DEVICES SHALL
REMAIN (THOSE INSTALLED UNDER PREVIOUS CONTRACT).
3. CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO DETERMINE EXACT SCOPE OF WORK.
CONTRACTOR SHALL PROVIDE NOTICE AND COORDINATE SITE VISIT IN ADVANCE WITH NVCC
PROJECT MANAGER.
4. ALL WORK SHALL BE PERFORMED IN SUCH A MANNER TO CREATE MINIMAL POWER OUTAGES
FOR THE OWNER. ALL SUCH OUTAGES SHALL BE COORDINATED WITH THE NVCC PROJECT
MANAGER AT LEAST 4 DAYS PRIOR TO VISIT SO THAT POWER TO ESSENTIAL SERVICES CAN BE
MAINTAINED.
5. CONTRACTOR SHALL GUARANTEE HIS WORKMANSHIP AND ALL MATERIALS AND EQUIPMENT
FOR A PERIOD OF ONE YEAR IN WRITING COMMENCING UPON ACCEPTANCE OF INSTALLATION
BY OWNER.
6. CONTRACTOR SHALL MAINTAIN ACCESS, SAFETY, AND CLEANLINESS IN AREA THAT AFFECTS
THE FLOW OF PEDESTRIAN TRAFFIC IN THE BUILDING, DUE TO RENOVATION.
7. CONTRACTOR SHALL PROVIDE 24/7 HOURLY FIRE WATCH ANY TIME THE FIRE ALARM SYSTEM
IS IMPAIRED. FIRE WATCH SHALL INCLUDE ADJACENT AREAS INSIDE AND OUTSIDE OF THE
BUILDING EFFECTED BY FIRE ALARM SYSTEM OUTAGE.
8. THE BUILDING PERMIT WILL BE OBTAINED AND PAID FOR BY THE OWNER.
9. CONTRACTOR SHALL PROVIDE BRANCH CIRCUIT WIRING, CONDUIT, AND OVERCURRENT
PROTECTION MEETING SUBMITTED AND APPROVED EQUIPMENTS RESPECTIVE NAMEPLATE
DATA AT NO ADDITIONAL COST (MAXIMUM OVERCURRENT PROTECTION (MOP) AND MINIMUM
CIRCUIT AMPACITY (MCA)).
10. PIPING, DUCTWORK, LIGHTING FIXTURES, CABLE TRAYS, CONDUIT, CABLES, WIRING,
RACEWAYS, JUNCTION BOXES, INSULATION, AND OTHER ITEMS LOCATED WITHIN THE RETURN
AIR CEILING PLENUM SHALL BE COORDINATED, ARRANGED AND INSTALLED TO NOT
OBSTRUCT OR OTHERWISE ADVERSELY AFFECT THE FLOW OF RETURN AIR FROM THE
OCCUPIED SPACE, THROUGH THE RETURN AIR PATH, BACK TO THE RESPECTIVE HVAC UNIT.
IN ALL AREAS OF THE RETURN AIR CEILING PLENUM, INCLUDING CONGESTED AREAS OF THE
CEILING PLENUM, THE RETURN AIR VELOCITY SHALL NOT EXCEED 500 FPM. REFER TO THE
MECHANICAL DRAWINGS FOR ADDITIONAL RETURN AIR PATH REQUIREMENTS.
11. ELECTRICAL EQUIPMENT REQUIRING ACCESS SUCH AS J-BOXES OR CONNECTIONS TO
EQUIPMENT SHALL NOT BE INSTALLED ABOVE INACCESSIBLE CEILINGS OR BEHIND WALLS.
CONTRACTOR SHALL REROUTE ANY EXISTING CONDUIT AND J-BOXES INCLUDING
CONNECTIONS TO ELECTRICAL EQUIPMENT TO AN ACCESSIBLE LOCATION WHETHER
INDICATED ON THE DRAWINGS OR NOT. EXISTING CONDUIT AND J-BOXES ABOVE
INACCESSIBLE CEILINGS/WALLS WHICH CANNOT BE RELOCATED SHALL BE ABANDONED WITH
ALL WIRING REMOVED. ANY EXCEPTIONS SHALL BE AUTHORIZED BY THE NVCC PROJECT
MANAGER.
12. CONTRACTOR IS TO X-RAY SLABS PRIOR TO PENETRATING STRUCTURE. X-RAYS, CONCRETE
CUTTING, AND CORE DRILLING SHALL TAKE PLACE AFTER REGULAR BUSINESS HOURS AND
SCHEDULED WITH PROJECT MANAGER.
13. AFTER FINAL INSTALLATION, CONTRACTOR WILL BE RESPONSIBLE FOR FILLING ALL VOIDS
AROUND CONDUIT PENETRATIONS AND OTHER CORE DRILLS/OPENINGS IN SLAB AND WALLS
WITH A FIRE SAFING REMOVABLE MASTIC. FILL SHALL EQUAL FIRE RATING OF FLOOR OR
WALL AND BE COMPATIBLE WITH CONSTRUCTION MATERIALS.
14. CONTRACTOR SHALL DETERMINE THE NUMBER AND SIZE OF CORE DRILLS NECESSARY FOR
INDICATED WORK AND SHALL DETERMINE RECOMMENDED LOCATION AND PROVIDE TO
STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL PRIOR TO COMMENCING WORK.
15. CONTRACTOR SHALL MAINTAIN INTEGRITY OF VAPOR BARRIER AND INSULATION FOR ALL
ELECTRICAL WORK AND DEVICES ON EXTERIOR AND PERIMETER WALLS.
16. FURRING DEPTH ON COLUMNS, SHAFT WALLS, AND FIRE-RATED WALLS IS LIMITED. THE
CONTRACTOR SHALL COORDINATE THE LOCATION OF COLUMN AND WALL MOUNTED
EQUIPMENT/DEVICES WITH AVAILABLE MOUNTING DEPTH AND WITH THE REQUIREMENTS OF
FIRE-RATED WALLS AND SHAFT ENCLOSURES. THE CONTRACTOR SHALL ADJUST THE
POSITION OF THE EQUIPMENT/DEVICE TO AN ALTERNATE WALL OR SIDE OF THE SAME
COLUMN AS REQUIRED TO ACCOMMODATE JOB SITE CONDITIONS AT NO ADDITIONAL COST.
17. ALL MATERIALS AND EQUIPMENT FURNISHED FOR THIS PROJECT SHALL BE NEW AND MATCH
BUILDING STANDARD(S) FOR MANUFACTURER AND TYPE OF EQUIPMENT FOR LIGHTS, EXIT
SIGNS, FIRE ALARM DEVICES, WIRING DEVICES, LIGHTING\POWER PANELS, TRANSFORMERS,
DISCONNECTS, ETC. WHERE NO BUILDING STANDARD EXISTS FOR ELECTRICAL EQUIPMENT,
EQUIPMENT SHALL BE NEW AND U.L. LISTED AS MANUFACTURED BY CUTLER HAMMER,
GENERAL ELECTRIC, SQUARE D, OR SIEMENS. MODIFICATIONS OR ADDITIONS TO EXISTING
EQUIPMENT SHALL MATCH EXISTING TO MAINTAIN ANY U.L. ASSEMBLY LISTING. CONTRACTOR
WILL BE RESPONSIBLE FOR CONTACTING AND COORDINATING WITH BUILDING OWNER ON
DETERMINING ANY STANDARDS. THE FAULT CURRENT RATING OF ALL EQUIPMENT ADDED TO
THE ELECTRICAL DISTRIBUTION SHALL MEET THE AVAILABLE FAULT CURRENT.
18. SUBMITTALS SHALL INCLUDE PANELBOARDS, DISCONNECTS, WIRING DEVICES,
TRANSFORMERS, AND CONDUCTORS. SUBMITTAL DATA SHALL CONTAIN ONLY INFORMATION
RELEVANT TO THE PARTICULAR EQUIPMENT OR MATERIALS TO BE FURNISHED FOR THIS
SPECIFIC PROJECT. CATALOG SHEETS WHICH DESCRIBE SEVERAL DIFFERENT ITEMS IN
ADDITION TO THOSE ITEMS TO BE USED SHALL NOT BE SUBMITTED UNLESS RELEVANT
INFORMATION IS CLEARLY MARKED. SIMILAR EQUIPMENT SHALL BE SUBMITTED IN ONE
COMPLETE SUBMITTAL PACKAGE (I.E. ALL PANELBOARDS, ALL LIGHTING FIXTURES, ETC.).
TOTAL NUMBER OF SUBMITTALS SHALL BE KEPT TO A MINIMUM. ALL SUBMITTALS SHALL BE
REVIEWED BY THE ENGINEER OF RECORD.
19. NEW REMOVABLE DIRECTORY CARDS SHALL BE PROVIDED AT COMPLETION OF WORK WITH
TYPED DESIGNATIONS INDICATING NAME, VOLTAGE, PHASE, ETC. AND FINAL CIRCUITING OF
PANELBOARDS DEPICTING EACH POLE POSITION IN A TWO COLUMN FASHION. ROOM
NUMBERS SHALL BE USED WHENEVER POSSIBLE ON CIRCUIT DESIGNATIONS. WHEN NEW
CARDS ARE TYPED, EXISTING INFORMATION ON THE EXISTING CARDS THAT REMAINS
APPLICABLE SHALL BE TRANSFERRED TO NEW CARDS, REGARDLESS OF DRAWING
DESIGNATIONS SUCH AS "EXISTING LOAD". NO HANDWRITTEN NOTES WILL BE ACCEPTED.
20. CONTRACTOR SHALL TRACE ALL CIRCUITS INDICATED ON THE DRAWINGS USED IN THE SCOPE
OF WORK AND INDICATED AS "SPARES" ON PANEL SCHEDULES AND CONFIRM CIRCUITS ARE
DEDICATED TO RENOVATED LEASE AREA AND NOT SERVING OTHER EXISTING OCCUPIED
SPACES. CONTRACTOR SHALL NOT USE CIRCUITS PRESENTLY BEING USED BY OTHER
OCCUPIED SPACES SO AS TO MINIMIZE ANY POTENTIAL INTERRUPTION OF SERVICE.
1.) CONTRACTOR SHALL IN THE PROCESS OF TRACING CIRCUITS, MAKE EFFORTS TO
UPDATE EXISTING CIRCUIT DESIGNATION FROM "EXISTING LOAD" TO A SPECIFIC
DESIGNATION TO INCLUDE, AT A MINIMUM, ROOM NUMBER AND DEVICE
CONTROLLED, TO BE USED WHEN UPDATING DIRECTORY CARDS IN NOTE 20 ABOVE.
21. AFTER COMPLETION OF WORK, CONTRACTOR SHALL OPEN (REMOVE AND REINSTALL COVERS
UPON INSPECTION) ALL ELECTRICAL EQUIPMENT THAT WAS AFFECTED BY WORK OF THIS
PROJECT FOR VISUAL INSPECTION TO INCLUDE BUT NOT LIMITED TO VISUALLY CONFIRM
TERMINATIONS, CLEANLINESS, COLOR CODING, CIRCUIT IDENTIFICATION, GROUNDING, AND
WIRING.
22. CONTRACTOR SHALL VACUUM CLEAN ALL DIRT AND DEBRIS FROM ELECTRICAL EQUIPMENT
(E.G., OUTLETS, SWITCHES, DISCONNECTS, MOTOR STARTERS, PANELBOARDS,
TRANSFORMERS, ETC.).
23. DURING THE PROGRESS OF THE WORK AND UPON COMPLETION, TESTS SHALL BE MADE AS
SPECIFIED HEREIN AND AS REQUIRED BY AUTHORITIES HAVING JURISDICTION INCLUDING
INSPECTORS, OWNER, AND ENGINEER. TESTS SHALL BE CONDUCTED BY THE CONTRACTOR
AS PART OF THE WORK OF THIS DIVISION AND SHALL INCLUDE THE SERVICES OF QUALIFIED
PERSONNEL AS WELL AS ALL EQUIPMENT, APPARATUS, AND SERVICES REQUIRED. TESTS
SHALL INCLUDE CONDUCTOR INSULATION RESISTANCE OF CONDUCTOR #6 AWG AND LARGER,
OPERATION OF ALL ELECTRICAL EQUIPMENT, OPERATION OF STANDBY LIGHTING, OPERATION
OF ALL DRY TYPE TRANSFORMERS BY RECORDING SECONDARY VOLTAGE TO ENSURE
PROPER TAP SETTINGS.
24. WITHIN 19 DAYS OF SYSTEM ACCEPTANCE, TMA FORMS SHALL BE PROVIDED TO THE OWNER
25. WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE
ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING AN
UPDATED SINGLE LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND
FLOOR PLANS INDICATING THE LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. AN
OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING
OWNER INCLUDING, AT A MINIMUM, SUBMITTAL DATA STATING EQUIPMENT RATING AND
SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE,
OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT
REQUIRING MAINTENANCE WITH REQUIRED ROUTINE MAINTENANCE ACTIONS CLEARLY
IDENTIFIED, NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY, AND A
COMPLETE NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE. WITHIN 90 DAYS
AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL
INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER INCLUDING, AT A MINIMUM, THE
LOCATION, LIGHTING EQUIPMENT.
DISTRIBUTION EQUIPMENT AND OVERCURRENT PROTECTION
1. INSTALL 1/16" THICK ENGRAVED MELAMINE PLASTIC-LAMINATE SIGN ON EACH NEW UNIT OF
ELECTRICAL EQUIPMENT ASSOCIATED WITH THE RENOVATION. PROVIDE SINGLE LINE OF
TEXT, 1/2" HIGH LETTERING ON 1-1/2" HIGH SIGN WITH WHITE LETTERING ON A FIELD OF BLACK.
PROVIDE TEXT MATCHING DESIGNATION ON THE CONTRACT DOCUMENTS. PROVIDE SIGNS
FOR EACH UNIT OF PANELBOARDS, ELECTRICAL CABINETS, ENCLOSURES, MOTOR STARTERS,
DISCONNECT SWITCHES, ETC. FASTENERS SHALL BE SELF-TAPPING STAINLESS STEEL
SCREWS, EXCEPT USE CONTACT-TYPE PERMANENT ADHESIVE WHERE SCREWS CANNOT OR
SHOULD NOT PENETRATE SUBSTRATE.
2. PANELBOARDS SHALL BE STANDARD CATALOG ITEMS COMPLYING WITH NEC, UL, AND NEMA
STANDARDS AND BEAR THE LABEL OF UNDERWRITER'S LABORATORIES. PROVIDE COPPER
FULL-SIZE PHASE AND NEUTRAL BUSSES WHICH HAVE BEEN RATED IN ACCORDANCE WITH UL
67 HEAT-RISE TESTS. BUS BAR CONNECTIONS SHALL BE COLUMN CONSECUTIVE
PHASE-SEQUENCE TYPE. BOTH 120/208 AND 277/480 VOLT PANELBOARDS SHALL HAVE BUS
BARS DRILLED AND EQUIPPED WITH ALL HARDWARE FOR BOLT-ON MOLDED CASE CIRCUIT
BREAKERS. PROVIDE A BOLTED ON COPPER GROUNDING BUS WITH MAIN LUG(S).
PANELBOARD SHORT CIRCUIT BRACING AND BREAKER INTERRUPTING CAPACITY SHALL BE AS
INDICATED ON THE DRAWINGS BUT SHALL NOT BE LESS THAN 14,000 AMPERES RMS
SYMMETRICAL FOR 277/480 VOLT SERVICE AND 10,000 AMPERES RMS SYMMETRICAL FOR
120/208 VOLT SERVICE. PROVIDE MANUFACTURER'S STANDARD #16-GAGE (MINIMUM)
GALVANEALED OR GALVANIZED SHEET STEEL CABINET WITH ENAMEL FRONT "HINGED DOOR
IN DOOR" COVERS, MASTER-KEYED DOOR LOCKS, MULTIPLE KNOCKOUTS, WIRING GUTTERS,
AND TYPED CIRCUIT DIRECTORY. PANELBOARD MAIN LUGS CONNECTED TO #6 AWG OR
LARGER COPPER CONDUCTORS SHALL BE FURNISHED TO ACCOMMODATE COMPRESSION
CONNECTORS. ADEQUATE WIRING SPACE SHALL BE PROVIDED TO ACCOMMODATE THE
COMPRESSION CONNECTORS. UNLESS OTHERWISE NOTED, ALL PANELBOARDS SHALL
INCLUDE FEED-THRU LUGS. PANELS RATED 400A OR HIGHER (FOR BOTH 120/208V AND
277/480V) SHALL BE CAPABLE OF HAVING CIRCUIT BREAKERS RATED 150A OR HIGHER
INSTALLED WITHOUT RENDERING THE FEED-THRU LUGS USELESS. NEW PANELBOARDS
SHALL MATCH EXISTING PANELBOARDS PROVIDED THE ABOVE MINIMUM REQUIREMENTS
HAVE BEEN MET. IT WOULD BE AN ACCEPTABLE OPTION FOR THE CONTRACTORS TO USE
ALUMINUM BUS WITHIN PANELBOARDS IN LIEU OF COPPER BUS WITHIN PANELBOARDS. THE
CONTRACTORS SHALL BE RESPONSIBLE FOR COORDINATING THE ADDITIONAL SPACE
REQUIRED DUE TO THE ALUMINUM EQUIPMENT.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTLY PHASING AND BALANCING THE
CIRCUITS IN THE PANELBOARDS. PROVIDE CIRCUITS WITH DEDICATED NEUTRAL
CONDUCTORS AS INDICATED ON THE DRAWINGS. PROVIDE CIRCUITS WITH SHARED NEUTRAL
CONDUCTORS AS INDICATED ON THE DRAWINGS. NEUTRAL CONDUCTORS SHALL NOT BE
COMBINED/SHARED WHERE NOT INDICATED ON THE DRAWINGS. WHERE NEUTRAL
CONDUCTORS ARE INDICATED TO BE SHARED, THE PHASE CONDUCTORS SHALL BE ON
OPPOSITE PHASES. PROVIDE JUNCTION BOXES AS REQUIRED FOR THE QUANTITY OF WIRES,
CONNECTORS, AND DEVICES CONTAINED THEREIN WHERE COMBINING HOMERUNS. ANY
INFORMATION IN QUESTION OR NOT CLEARLY EXPRESSED ON THE DRAWINGS SHALL BE
CONFIRMED WITH THE ENGINEER OF RECORD.
4. DISCONNECT SWITCHES INDICATED AND/OR SPECIFIED FOR 480 VOLT CIRCUITS SHALL BE
600-VOLT AND I²T RATED, DIRECT DRIVE, QUICK-MAKE, QUICK-BREAK TYPE SWITCHES WITH
SPRING-REINFORCED WIRE GRIPS AND SELF-ALIGNING SWITCH CONTACTS. SWITCHES SHALL
BE ENCLOSED IN A HEAVY SHEET METAL ENCLOSURE WITH HINGED INTERLOCKING COVER
WHICH SHALL PREVENT THE COVER FROM BEING OPENED WHEN SWITCH IS "ON". PROVIDE
REJECTION-TYPE FUSE CLIPS FOR CARTRIDGE FUSES IN SWITCHES AS INDICATED AND
ACCOMMODATION FOR R FUSES. SWITCHES SHALL BE NEMA TYPE HD. SWITCHES EXPOSED
TO MOISTURE ON THE EXTERIOR OR INTERIOR OF THE BUILDING SHALL HAVE NEMA 4
STAINLESS STEEL ENCLOSURES (WATER AND DUST TIGHT). FUSED DISCONNECT SWITCHES
SHALL BE SUBSTITUTED FOR NON-FUSED SWITCHES WHERE REQUIRED BY MANUFACTURER,
LOCAL INSPECTING AUTHORITY, AND/OR FUSE PROTECTION IS INDICATED ON MOTOR
NAMEPLATE AT NO ADDITIONAL COST. DISCONNECT SWITCHES FOR 208-VOLT CIRCUITS
SHALL BE SIMILAR EXCEPT RATED 240-VOLT NEMA TYPE HD. ALL SWITCHES SHALL HAVE
PROVISION FOR PADLOCKING.
5. TRANSFORMERS SHALL BE DRY TYPE 60 HERTZ, 480 VOLT, 3 PHASE, DELTA TO 120/208 VOLT, 3
PHASE, 4 WIRE, GROUNDED WYE, NEMA TP-1. TEMPERATURE CLASSIFICATION SHALL HAVE A
220°C INSULATION SYSTEM. WINDING TEMPERATURE RISE SHALL NOT EXCEED 150°C IN A
40°C AMBIENT. SOUND RATING SHALL BE IN ACCORDANCE WITH ANSI-C89.2. BIL RATINGS
SHALL BE IN ACCORDANCE WITH ANSI AND NEMA STANDARDS. TRANSFORMERS SHALL HAVE
FOUR 2-1/2% FULL LOAD TAPS BELOW RATED VOLTAGE AND TWO 2-1/2% FULL LOAD TAPS
ABOVE RATED VOLTAGE. USE COPPER BODIED COMPRESSION CONNECTORS FOR
TERMINATING CABLES TO TRANSFORMER LUGS. INTERNAL VIBRATION ISOLATION MOUNTS
SHALL BE PROVIDED. TRANSFORMERS SHALL BE GROUNDED PER NEC ARTICLE 250 TO
STRUCTURAL STEEL IF PRESENT OR GROUND RISER IF STEEL IS NOT PRESENT. MOUNT
TRANSFORMERS ON A FOUR INCH HIGH CONCRETE PAD APPROXIMATELY ONE INCH LARGER
ALL AROUND THAN THE TRANSFORMER PROVIDED. SUSPEND TRANSFORMERS AS INDICATED
ON THE CONTRACT DOCUMENTS AND WHERE REQUIRED DUE TO SPACE CONSTRAINTS.
TRANSFORMERS SHALL BE SUSPENDED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS AND IN ACCORDANCE WITH THE STRUCTURAL DOCUMENTS.
6. MOLDED CASE CIRCUIT BREAKERS SHALL BE OPERATED BY A TOGGLE-TYPE HANDLE AND
SHALL HAVE A QUICK-MAKE, QUICK-BREAK, OVER-CENTER SWITCHING MECHANISM THAT IS
MECHANICALLY TRIP-FREE FROM THE HANDLE SO THAT THE CONTACTS CANNOT BE HELD
CLOSED AGAINST SHORT CIRCUITS AND ABNORMAL CURRENTS. TRIPPING DUE TO OVERLOAD
OR SHORT CIRCUIT SHALL BE CLEARLY INDICATED BY THE HANDLE AUTOMATICALLY
ASSUMING A POSITION MIDWAY BETWEEN THE MANUAL ON AND OFF POSITIONS. ALL LATCH
SURFACES SHALL BE GROUND AND POLISHED. POLES SHALL BE SO CONSTRUCTED THAT
THEY CAN OPEN, CLOSE AND TRIP SIMULTANEOUSLY. BREAKERS SHALL BE COMPLETELY
ENCLOSED IN A MOLDED CASE WITH THE AMPERE RATINGS CLEARLY VISIBLE. CONTACTS
SHALL BE NON-WELDING SILVER ALLOY. BREAKERS SHALL BE UL LISTED FOR USE WITH 75°C
AND 90°C INSULATED WIRE. CIRCUIT BREAKER RATINGS, MODIFICATIONS, ETC., SHALL BE AS
INDICATED ON THE DRAWINGS. MOLDED-CASE CIRCUIT BREAKERS SHALL BE AS FOLLOWS:
1) THERMAL MAGNETIC TYPE THAT PROVIDES INVERSE TIME-DELAY OVERLOAD AND
INSTANTANEOUS SHORT CIRCUIT PROTECTION BY MEANS OF A THERMAL MAGNETIC
ELEMENT.
2) AMBIENT COMPENSATED STANDARD THAT PROVIDES INVERSE TIME-DELAY OVERLOAD
AND INSTANTANEOUS SHORT CIRCUIT PROTECTION BY MEANS OF A THERMAL MAGNETIC
ELEMENT. COMPENSATION SHALL ALLOW THE BREAKER TO CARRY RATED CURRENT
BETWEEN 25°C AND 50°C WITH TRIPPING CHARACTERISTICS THAT ARE APPROXIMATELY
THE SAME THROUGHOUT THIS TEMPERATURE RANGE.
3) MULTI-POLE BREAKERS SHALL BE OF THE COMMON TRIP TYPE HAVING A SINGLE
OPERATING HANDLE, EXCEPT THAT 240-VOLT MULTI-POLE BREAKERS SMALLER THAN
50-AMPERES MAY CONSIST OF FACTORY-CONNECTED, SINGLE-POLE BREAKERS WITH A
COMMON TRIP HANDLE.
4) ALL CIRCUIT BREAKERS SHALL BE FULL SIZE AND BOLT-ON.
7. WHERE POSSIBLE, MOLDED CASE CIRCUIT BREAKERS WITHIN PANELBOARDS SHALL BE
INSTALLED IN THE ORDER INDICATED IN THE PANEL SCHEDULES.
8. ALL FUSES SHALL BE DUAL-ELEMENT LOW PEAK CLASS RK1 AS MANUFACTURED BY BUSSMAN
OR LITTELFUSE. FUSE VOLTAGE RATING SHALL BE 250 VOLT FOR 120/208 VOLT SYSTEM AND
600 VOLT FOR 277/480 VOLT SYSTEM.
9. CONTRACTOR SHALL PROVIDE UPDATED INFORMATION ON ELECTRICAL EQUIPMENT TO
OWNER IN ARC FLASH STUDY FORMAT.
RACEWAYS AND CONDUCTORS
1. ALL CONDUCTORS SHALL BE COPPER. ALL CONDUCTORS #8 AWG AND LARGER SHALL BE
STRANDED. CONDUCTOR SIZES #10 AWG, #12 AWG, AND #14 AWG SHALL BE SOLID. ALL
CONDUCTORS SHALL BE STANDARD CODE TYPE "THW", "THHN", "THWN" OR "XHHW"
INSULATED EXCEPT AS REQUIRED OTHERWISE PER THE NEC. ALL CONDUCTORS SHALL BE
DURABLY MARKED ON THE SURFACE TO INDICATE RATED VOLTAGE, INSULATION CODE, USE,
MANUFACTURER, AND AWG SIZE. THE COLOR CODING SHALL BE CONTINUOUS AND SHALL
EXTEND TO PANELS AND MOTORS. WHERE INSULATION COLOR CODING IS NOT AVAILABLE
FOR CONDUCTORS #8 AWG AND LARGER, USE COLOR CODED PLASTIC TAPE AT EACH
CONDUCTOR TERMINATION. ALL #8 AWG AND SMALLER CONDUCTORS SHALL BE SPLICED
WITH PREINSULATED SPRING CONNECTORS. CONNECTORS SHALL BE SCOTCHLOCK,
BUCHANAN B-CAP, OR APPROVED EQUAL. ALL #6 AWG AND LARGER COPPER CONDUCTORS
TERMINATED ON LUGS OF PANELBOARDS SHALL BE TERMINATED WITH COPPER U.L. LISTED
COMPRESSION CONNECTORS SUCH AS THOMAS & BETTS #54100 OR #54200 SERIES
CONNECTORS. ALL #6 AWG AND LARGER COPPER CONDUCTOR TWO WAY SPLICES SHALL BE
MADE WITH BARREL CONNECTORS REQUIRING COMPRESSION ON EACH END. ALL #6 AWG
AND LARGER COPPER CONDUCTOR TAPPING AND PIGTAILING SHALL BE MADE USING "C" TYPE
COMPRESSION TAPS SUCH AS THOMAS AND BETTS #54700 SERIES CONNECTORS.
CONNECTOR SHALL BE U.L. LISTED FOR TYPE OF CONDUCTORS TO BE TAPPED. THE
MANUFACTURERS RECOMMENDED INSTALLING TOOLS WITH REQUIRED NUMBER OF
COMPRESSIONS SHALL BE USED FOR ALL TERMINATIONS.
2. AT THE CONTRACTOR'S OPTION, ALUMINUM CONDUCTORS MAY BE USED IN LIEU OF COPPER
CONDUCTORS FOR ALL CIRCUITS PROTECTED BY 100 AMPS AND GREATER OVER CURRENT
PROTECTION DEVICES EXCEPT FOR MOTOR LOADS INCLUDING BUT NOT LIMITED TO PUMPS,
FANS, AND AIR HANDLING UNITS OR AS INDICATED ON THE DRAWINGS. ALL CIRCUITS
PROTECTED BY OVER CURRENT PROTECTION DEVICES LESS THAN 100 AMPS ARE REQUIRED
TO BE COPPER. THE USE OF ALUMINUM FOR CIRCUITS PROTECTED BY OVER CURRENT
PROTECTION DEVICES LESS THAN 100 AMPS WILL NOT BE ACCEPTABLE. IF THIS OPTION IS
SELECTED BY THE CONTRACTOR, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATING THE ADDITIONAL WORK AND SPACE REQUIRED FOR THE LARGER OR
ADDITIONAL PARALLEL SETS OF CONDUIT AND CONDUCTORS REQUIRED TO MEET THE
COPPER CONDUCTOR BASIS OF DESIGN CURRENT CARRYING CAPACITY. IN ADDITION, THE
CONTRACTOR SHALL PROVIDE ALL THE NECESSARY ADDITIONAL HANGERS, CORE DRILLS,
SLEEVES, FIRE PROOFING, ETC. REQUIRED TO ACCOMMODATE THE OPTIONAL ALUMINUM
CONDUCTORS AND BUSSING AS INDICATED ON THE OPTIONAL ELECTRICAL DISTRIBUTION
DIAGRAM SYSTEM UTILIZING ALUMINUM CONDUCTORS. ALL ALUMINUM CONDUCTORS SHALL
BE TERMINATED WITH ALUMINUM U.L. LISTED COMPRESSION CONNECTORS. THE SMALLEST
ALLOWABLE ALUMINUM CONDUCTOR FOR THE OPTIONAL ALUMINUM SYSTEM SHALL BE #1/0
AWG.
3. ALL WIRE SIZES INDICATED ARE BASED ON DIRECT PATHS WITH 90° BENDS AS NECESSARY
FROM THE OUTLET/UTILIZATION EQUIPMENT TO THE PANELBOARD, WITH A MAXIMUM 2%
VOLTAGE DROP ON FEEDER CONDUCTORS AND A MAXIMUM VOLTAGE DROP OF 3% FOR
BRANCH CIRCUIT CONDUCTORS. WHERE FIELD CONDITIONS DO NOT ALLOW, OR IF FOR ANY
REASON THE ROUTE SELECTED IS DIFFERENT, THE WIRE SIZE (AND CONDUIT IF NECESSARY)
SHALL BE INCREASED TO MAINTAIN THESE MINIMUM VOLTAGE DROP REQUIREMENTS AT NO
ADDITIONAL COST TO THE OWNER. REGARDLESS, ALL 20 AMP, 120 VOLT HOMERUNS SHALL BE
A MINIMUM #12 AWG UNLESS LENGTHS EXCEED 60', THEN CONDUCTORS SHALL BE A MINIMUM
#10 AWG. ALL 20 AMP, 277 VOLT HOMERUNS SHALL BE A MINIMUM #12 AWG UNLESS LENGTHS
EXCEED 165'; THEN CONDUCTORS SHALL BE A MINIMUM #10 AWG.
4. RECEPTACLE NEUTRAL CONDUCTOR(S) SHALL BE A MINIMUM #10 AWG AT POINT WHERE
MORE THAN ONE 20 AMP PHASE CONDUCTOR IS CONNECTED TO A COMMON NEUTRAL BACK
TO PANELBOARD. #10 "AC" CABLE SHALL BE USED FOR ALL PHASES AND NEUTRAL FOR "AC"
CABLE INSTALLATIONS AT CONNECTION POINT OF COMMON NEUTRAL.
5. THE ACTUAL NUMBER OF WIRES REQUIRED MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY
THOSE WHERE CLARIFICATION IS NECESSARY. THE ELECTRICAL CONTRACTOR SHALL
PROVIDE ALL WIRES NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER
INDICATED ON THE DRAWINGS OR NOT AT NO ADDITIONAL COST.
6. ALL EMT AND FLEXIBLE CONDUIT SHALL BE U.L. LISTED. ALL CONDUIT SHALL BE SUITABLE
FOR THE INTENDED SERVICE AND LOCATION. ANY MATERIALS LOCATED WITHIN
ENVIRONMENTAL AIR PLENUMS SHALL BE U.L. LISTED FOR THE APPLICATION OR APPROVED IN
WRITING BY ALL APPLICABLE LOCAL CODE AUTHORITIES. THE CONTRACTOR SHALL
COORDINATE ALL RACEWAY SYSTEM COMPONENTS AND LOCATIONS WITH ALL NEW WORK.
CONTRACTOR SHALL COORDINATE WITH WORK OF OTHER TRADES. CONTRACTOR SHALL
COORDINATE WITH ALL EQUIPMENT WITH PLENUM AND CHASE LIMITATIONS AND
REQUIREMENTS OF DRAWINGS AND SPECIFICATIONS. CONTRACTOR IS RESPONSIBLE FOR
TIMELY PLACEMENT OF SLEEVES, CUTTING AND PATCHING OF NEW CONSTRUCTION TO FIT
WORK OF THIS SECTION, LOCATION OF CHASE SPACE FOR VERTICAL ROUTING OF RACEWAY
SYSTEMS AND LOCATION OF PLENUM SPACE FOR HORIZONTAL ROUTING OF RACEWAY
SYSTEMS. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF
SYSTEMS AND WORK. DRAWINGS ARE NOT TO BE SCALED. IN PREPARATION OF THE
DRAWINGS, A REASONABLE EFFORT TO COORDINATE RACEWAY SYSTEMS HAVE BEEN MADE,
HOWEVER, SPACE REQUIREMENTS, EQUIPMENT ARRANGEMENTS, AND SITE CONDITIONS
VARY, AND THE RESPONSIBILITY FOR ACCESS, LOCATION, PROPER FIT AND TIMELY
COMPLETION RESTS WITH THE CONTRACTOR.
EXPOSED INTERIOR:
ALL EXPOSED INTERIOR WIRING SHALL BE IN GALVANIZED STEEL OR ALUMINUM EMT USING
STEEL SET SCREW CONNECTORS. CONTRACTOR SHALL MINIMIZE EXPOSED INTERIOR
WIRING/CONDUIT WITHIN OUT INCREASING COST WHERE POSSIBLE.
CABLE:
BRANCH CIRCUIT WIRING CONCEALED IN A WALL OR CEILING CONNECTING RECEPTACLES
AND LIGHTS MAY BE “AC” OR “MC” CABLE. JUNCTION BOX LOCATION SHALL BE SELECTED TO
MINIMIZE THE ASSOCIATED REQUIRED AC/MC CABLES IN CEILINGS.
7. METALLIC CONDUIT WITH CONDUCTORS SHALL BE USED IN LIEU OF CABLE IN ALL VISIBLE
PUBLIC AREA AND BACK OF HOUSE LOCATIONS. "AC"/"MC" CABLE SHALL NOT BE TERMINATED
AT PANELBOARDS. CABLE SHALL TERMINATE OUTSIDE OF ELECTRICAL CLOSETS AND ROOMS
WITH GUTTERS. CONDUIT SHALL BE USED TO CONNECT GUTTERS TO PANELS.
8. ALL CONDUIT SHALL BE RIGIDLY SUPPORTED TIGHT TO THE BUILDING STRUCTURE. MAXIMUM
SPACING OF SUPPORTS, 10'-0" FOR VERTICAL, AND 8'-0" FOR HORIZONTAL RUNS. COUPLINGS
AND FITTINGS FOR EMT SHALL BE OF STEEL (CAST POT METAL IS NOT ACCEPTABLE) AND
SHALL BE OF THE COMPRESSION OR SET STEEL SCREW TYPE. NOT MORE THAN THE
EQUIVALENT OF FOUR QUARTER BENDS SHALL BE USED IN ANY RUN BETWEEN…