260-B5260-065 NVCC LA Medical Oxygen Generator - Drawings.pdf

PDF 5 MB Posted

Attached to
260-B5260-065 LA Add Medical Oxygen Generator
Solicitation number
IFB-125907
Issued by
Virginia

About this file

This is a design and construction drawings document for a capital project undertaken by Northern Virginia Community College (NVCC) at its Loudoun Campus in Sterling, Virginia, under the oversight of the Virginia Community College System (VCCS). The project, identified as 260-B5260-065, involves the specification and installation of a new medical oxygen generator system to replace existing oxygen bottle cylinders currently stored in Room 127A of the LA Building. The scope of work includes selective demolition of existing equipment, relocation of the existing water heater, construction of a new partition wall to divide mechanical room 127 into two separate spaces (the oxygen generator room 127A and mechanical equipment room 127), installation of new electrical power supply for the oxygen generator, integration of the system with existing medical gas distribution piping, and coordination with building management systems. The project encompasses approximately 227 square feet of mechanical room work, 443 square feet of total scope area, and requires compliance with the 2021 Virginia Building Code, Virginia Mechanical Code, and NFPA standards. The documents are issued for bid as of July 15, 2026, with detailed drawings prepared by Dewberry Engineers, Inc.

The oxygen generator system specified includes a Novair OG-175 unit capable of producing 70 standard cubic feet per hour at 93% purity, operating at 115 volts single-phase with 15-amp requirements, along with a Novair OST-120 medical-grade oxygen storage tank (120 gallons) and an Atlas Copco GA 7 VSD+MED air compressor system (10 horsepower, 190 CFM output). The project requires installation of a master alarm panel for monitoring oxygen concentration levels, integration with the facility's energy management and control system (EMCS) via Bacnet gateway, and provision of high-visibility alarm capabilities with remote signal inputs. The contractor must provide branch circuit wiring, overcurrent protection, firestop sealing materials compliant with UL standards, new concrete equipment pads, and all coordination with existing building systems. The work must comply with ADA accessibility requirements, maintain fire-rated wall integrity through proper penetration sealing, and include comprehensive testing, documentation, and one-year warranty of workmanship and materials upon system acceptance by the owner.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPROVED BY

CHECKED BY

A

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

SEAL

No. Description Date

REVISIONS

23456

B

C

D

E

F

DEB PROJECT NUMBER :

DEWBERRY PROJECT NUMBER:

FACILITIES PLANNING & SUPPORT SERVICES

8333 LITTLE RIVER TURNPIKE

ANNANDALE, VA 22003

Dewberry Engineers, Inc.

8401 ARLINGTON BLVD

FAIRFAX, VA 22031

703.849.0100 Phone

/2

/2

:0

:1

A

M

Q P

R O

J E

C T

S \5

N V

C C

L A

A D

D O

X Y

G E

N G

E N

E R

A T

O R

\C A

D \G

E N

E R

A L

\G -0

C O

V E

R S

H E

E T

.D W

G

06-17-2026

NORTHERN VIRGINIA COMMUNITY COLLEGE

LOUDOUN CAMPUS LA ADD MEDICAL OXYGEN

GENERATOR

ISSUE FOR BID

T: 703.849.0100

F: 703.698.9040

BUILDING LOCATIONS:

NVCC LA BUILDING 21200 CAMPUS DRIVE, STERLING, VA 20164

OWNER OF BUILDING:

COMMONWEALTH OF VIRGINIA

STATE BOARD OF COMMUNITY COLLEGES

BUILDING DETAILS:

BUILDING TYPE: TYPE II

BUILDING OCCUPANCY GROUP: GROUP B

CONTAINS SPRINKLER SYSTEM: YES

CONTAINS FIRE ALARM SYSTEM: YES

BUILDING AREA:

AREA OF BUILDING:

TOTAL FLOOR AREA = 11,480 S.F.

BUILDING HEIGHT

TOTAL BUILDING HEIGHT = 1 STORY, 20'

REFER TO DRAWING G-002 FOR CODE PLAN FOR DETAIL CODE ANALYSIS

PRIMARY CONTACTS:

OWNER: NORTHERN VIRGINIA COMMUNITY COLLEGE

FACILITIES PLANNING AND SUPPORT SERVICES

8333 LITTLE RIVER TURNPIKE, CW BUILDING

SUITE 311, ANNANDALE, VA 22003-3796

PHONE: 703-323-3551

AGENCY REPRESENTATIVE:

MIKE JONES

CAPITAL OUTLAY PROGRAM MANAGER

VIRGINIA COMMUNITY COLLEGE SYSTEM

300 ARBORETUM PLACE SUITE 200

RICHMOND, VA 23236

PHONE: 832-428-4678

EMAIL: MJONES@VCCS.EDU

PROJECT #260-B5260-065

MEP

DEWBERRY ENGINEERS INC

8401 ARLINGTON BLVD

FAIRFAX, VA 22031

VIRGINIA CONSTRUCTION CODE(USBC) 2021

VIRGINIA BUILDING CODE 2021

VIRGINIA MECHANICAL CODE 2021

VIRGINIA PLUMBING CODE 2021

VIRGINIA STATEWIDE FIRE PREVENTION CODE (VSFPC) 2021

INTERNATIONAL FIRE CODE (IFC) 2021

AS REFERENCED BYTHE VIRGINIA CODES

NFPA 70 (NATIONAL ELECTRICAL CODE) 2020

NFPA 72 (NATIONAL FIRE ALARM AND SIGNALING CODE) 2019

NFPA 80 (STANDARD FOR FIRE DOORS AND OTHER 2019

OPENING PROTECTIVES)

VIRGINIA ENERGY CONSERVATION CODE 2021

VIRGINIA COMMUNITY COLLEGE SYSTEMS - 2025 REV(0) 03/17/2025

CONSTRUCTION AND PROFESSIONAL SERVICES

MANUAL (VCCS-CPSM)

VIRGINIA UNIFORM STATEWIDE BUILDING CODE(VUSBC) 2021

VIRGINIA EXISTING BUILDING CODE(VEBC) 2021

ADA90- TITLE II: (2010 ASAD) CHAPTER 2 FOR

SCOPING, ICC A117.1-2017 CHAPTERS 1 & 3 THRU

11 FOR TECHNICAL REQUIREMENTS

VIBSR (VIRGINIA INDUSTRIALIZED BUILDING SAFETY REGULATIONS :13VAC5-91),

FOR VIRGINIA COMMUNITY COLLEGE SYSTEM (VCCS)

PROJECT NAME: LOUDOUN CAMPUS LA ADD MEDICAL OXYGEN

GENERATOR

BUILDING LOCATION: 21200 CAMPUS DRIVE

STERLING, VA 20164

PROJECT DESCRIPTION:

THIS PROJECT WILL PROVIDE THE SPECIFICATION AND INSTALLATION OF A NEW

MEDICAL OXYGEN GENERATOR SYSTEM FOR THE LA BUILDING. NEW OXYGEN

GENERATOR WILL CONNECT TO THE EXISTING MEDICAL GAS SYSTEM IN ROOM

127A. NEW OXYGEN GENERATOR WILL BE LOCATED IN ROOM 127A.

HIGH PERFORMANCE BUILDINGS ACT NOTICE:

IN ACCORD WITH THE HIGH PERFORMANCE BUIDLING ACT, THE BUILDINGS ARE

EXEMPT FROM COMPLIANCE BECAUSE THE COST OF THE RENOVATIONS DOES

NOT EXCEED 50% OF THE VALUE OF EACH BUILDING.

ASBESTOS COMPLIANCE STATEMENT (ALL BUILDINGS):

AN ASBESTOS INSPECTION WAS NOT PERFORMED BECAUSE ALL PORTIONS OF

THE EXISTING BUILDING THAT MAY BE AFFECTED BY THE WORK WERE

ORIGINALLY CONSTRUCTED AFTER JANUARY 1, 1985.

NO ASBESTOS CONTAINING MATERIALS TO BE USED IN THIS PROJECT

LEAD COMPLIANCE STATEMENT (ALL BUILDINGS):

AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING

COMPONENTS HAS NOT BEEN CONDUCTED BECAUSE THE BUILDING WAS

CONSTRUCTED AFTER JANUARY 1, 1985 AND THE OWNER HAS NO KNOWLEDGE

OF LEAD CONTAINING OR COATED BUILDING COMPONENTS IN THE BUILDING. IT

IS THE CONTRACTOR’S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA

OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN

TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED BUILDING

COMPONENTS SHALL BE RECYCLED TO THE EXTENT POSSIBLE

DW

CB

06-17-2026

260-B5260-065

260-B5260-065

50187099

PROJECT LOCATION

BUILDING LA

PROJECT FIRE STOPPING REQUIREMENTS:

SEAL ALL PIPE PENETRATIONS IN FIRE RATED CONSTRUCTION WITH FACTORY BUILT DEVICES

OR WITH MANUFACTURED FILL, VOID OR CAVITY MATERIALS “CLASSIFIED” BY UNDERWRITERS

LABORATORIES, INC. FOR USE AS A THROUGH PENETRATION FIRESTOP. ALL FIRESTOP

DEVICES AND SYSTEMS SHALL BE APPROVED BY THE OWNER. THE FIRESTOP SYSTEM USED

SHALL MAINTAIN THE FIRE RESISTANCE RATING OF THE BUILDING COMPONENT THAT IS

PENETRATED. FIRESTOP SYSTEMS AND DEVICES SHALL COMPLY WITH ASTM E 814 (UL 1479)

FOR ALL TYPES OF PENETRATIONS BEING SEALED. SUBMITTAL DATA FOR FIRESTOP SYSTEMS

SHALL INCLUDE THE APPLICABLE UL SYSTEM NUMBERS. EXCESSIVE SHRINKAGE OF THE

FIRESTOP MATERIALS, WHICH WOULD PERMIT THE TRANSMISSION OF SMOKE OR WATER PRIOR

TO EXPOSURE TO A FIRE CONDITION, IS UNACCEPTABLE. FIRESTOP SHALL NOT PERMIT

CRACKS AND SHALL BE WATERPROOF. WHERE A MASTIC COATING IS USED TO SEAL THE

SURFACE OF THE FIRESTOP, THE MASTIC SHALL BE NON-HARDENING. THE FIRESTOP SYSTEM

USED SHALL ACCOMMODATE EXPANSION AND CONTRACTION OF THE FLOATING MECHANICAL

PIPING SYSTEMS WITHOUT DAMAGING THE FIRESTOP OR REDUCING ITS EFFECTIVENESS AS A

SMOKE BARRIER OR WATER SEAL. THE FIRESTOP MANUFACTURER'S REPRESENTATIVES SHALL

INSTRUCT THE SUBCONTRACTOR'S REPRESENTATIVES IN THE PROPER INSTALLATION

PROCEDURES SO THAT THE PENETRATIONS ON THE PROJECT WILL BE INSTALLED IN

ACCORDANCE WITH THE UL LISTING AND THE MANUFACTURER'S RECOMMENDATIONS. IF IT

COMPLIES WITH THESE SPECIFICATIONS, FIRESTOP SEALING COMPONENT/SYSTEM AS

MANUFACTURED BY ONE OF THE FOLLOWING MANUFACTURERS WILL BE ACCEPTABLE:

1. TREMCO FIRE RESISTIVE JOINT SYSTEM USING DYMERIC SEALANT AND

CERABLANKET-FS MINERAL FILLER.

2. SPECIFIED TECHNOLOGIES, INC. SPECSEAL SYSTEMS.

3. 3M FIRE BARRIER PENETRATION SEALING SYSTEMS.

4. GE PENSIL FIRESTOP SEALANT BY GENERAL ELECTRIC.

5. INTERNATIONAL PROTECTIVE COATINGS CORP. FLAME SAFE SYSTEMS.

6. THERMAL CERAMICS FIRE MASTER FIRESTOP FIRE PROTECTION SYSTEMS.

7. HILTI FS-601 SYSTEMS.

ALL UNUSED SLEEVES SHALL BE SEALED WITH FIRESTOP DEVICES AND SYSTEMS TO MAINTAIN

THE FIRE RATING OF THE CONSTRUCTION PENETRATED.

WHERE ALLOWED BY APPLICABLE CODES, RULES, REGULATIONS AND MANUFACTURER

RECOMMENDATIONS, THE CONTRACTOR SHALL HAVE THE OPTION OF UTILIZING

THROUGH-PENETRATION FIRE STOP PRODUCTS IN LIEU OF THE SLEEVES AND FIRE STOPPING

MATERIALS SPECIFIED HEREIN FOR ALL PIPING AND FITTING PENETRATIONS OF FIRE-RATED

ASSEMBLIES. THROUGH-PENETRATION FIRE STOP PRODUCTS SHALL COMPLY WITH ASTM E-814

STANDARDS AND SHALL BE THE PRODUCTS OF PROSET SYSTEMS OR APPROVED EQUAL. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER SELECTION, PLACEMENT AND

INSTALLATION OF THESE PRODUCTS. EACH THROUGH-PENETRATION FIRE STOP PRODUCT

SHALL BE COMPATIBLE WITH THE PIPE SIZE, PIPE MATERIAL, AND FIXTURE SERVED.

FIRE STOPPING

G-001

COVER SHEET

L O

U D

O U

N C

A M

P U

S L

A A

D D

M E

D

IC

A L O

X Y

G E

N

G E

N E

R A

T O

R

N O

R T

H E

R N

V

IR

G

IN

IA

C

O M

M U

N

IT

Y C

O L L E

G E

C

A M

P U

S D

R

IV

E

S T

E R

L

IN

G

V A

-B

-0

-1

-2

I

S S

U E

F O

R B

ID

VICINITY MAP

SCALE 1" = 2000'

VICINITY MAP

SITE

DRAWING LIST

Sheet Number Sheet Title

G-001 COVER SHEET

G-002 CODE PLAN

G-003 WALL PENETRATION DETAILS

A-111 FLOOR PLAN - DEMOLITION & NEW WORK & DOOR

SCHEDULE

E-001 ELECTRICAL COVER SHEET

E-101 ELECTRICAL NEW WORK FLOOR PLAN

E-501 ELECTRICAL DETAIL SHEET

P-001 PLUMBING COVER SHEET

P-101 PLUMBING NEW WORK FLOOR PLAN

P-501 PLUMBING DETAIL SHEET

01/06/202601/06/20263020606301012020//0766 03/103/1452452201272027

G E

N E

R A

T O

R

-1

-2

I

S S

U E

F O

R B

ID

07-15-2026

07-15-2026

VET LAB

FELINE

HOLDING

AREA STORAGE

JAN.

ANIMAL

HOLDING

AREA

CONNECTOR

100C

CORRIDOR

GROOMING

116B

STORAGE

116C

116F

ANIMAL

QUARTERS

116E

ANIMAL

QUARTERS

116D

CLEANUP

AREA

116A

ANIMAL

QUARTERS

CANINE

HOLDING

AREA

STORAGE

/CHANGE

ROOMISOLATION

MECH.

CORRIDOR

100B

RADIOLOGY

SURGERY

111A

DARK

ROOM

PREP.

ROOM

109A

SCRUB

ROOM

MEN'S

WOMEN'S

FOYER

EXAM

ROOM

OFFICE

100D

LOBBY

LOBBY

SEATING

RECOVERY

ROOMS 137

EXAM

ROOM

EXAM

ROOM

STUDY

RADIOLOGY

JANITOR

UNISEX

COMPUTER

TELCO

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

MECH

UNISEX

100G

CORRIDOR

RECOVERY

AUTOCLAVE

144B

CHANGING

ROOM

150B

ANIMAL

PREP

150C

SURGEONS

SCRUB

150A

OPERATING

ROOM

TEACHING

LAB

P A

T H

-A

1 11 1 1 1 1 1 1

1 11 1 1 1 1 1

11 1

1 1

EXISTING EQUIPMENT PAD.

53 SF

OXYGEN

GENERATOR RM

127A

162 SF

MECHANICAL

EQUIPMENT RM

TRAVEL DISTANCE

PATH A = 22 FEET

APPROXIMATE EXTENT OF

WORK AREA = 227 SQ.FT

(MECHANCIAL RM #127).

180 SF

ELECTRICAL

CLOSET

104A

48 SF

PLUMBING

104B

ROOM SIGNAGE - A

6 3/32"PARTN TYPE WIDTH

O

PN

G P

ER

R

AT

ED

AS

SE

M

BL

Y

FIRESTOP DEVICE

1 TO 7 GANG

CABLES

RATED PARTN

TYPE AS

SCHEDULED

RATING NO:

MAX 4 HR, UL W-L-3218

OR EQ

6 3/32"PARTN TYPE WIDTH

/3 2"

O

PN

G P

ER

R

AT

ED

AS

SE

M

BL

Y

FIRE RATED SEALANT

INTUMESCENT

WRAP STRIP AT

PERIMETER OF

CABLE TRAY

BED CABLE IN FIRE

RATED SEALANT, PER

THE RATED

ASSEMBLY

INSULATED

CABLES AND

STEEL TRAY

INTUMESCENT SHEET

RATED PARTN

TYPE AS

SCHEDULED

RATING NO:

MAX 2 HR, UL W-L-4004,

OR EQ

1"

/8

/4

/8

/2

/2

1/2" 7" 1/2"

TOP PANEL

PANEL SIZE: 3" X 8"

PANEL MATERIAL: EITHER ABS OR ALUMINUM

PANEL COLOR: TO MATCH EXISTING - NAVY BLUE

TEXT FONT: 162 POINT FRUTIGER NEXT PRO MEDIUM CONDENSED

TEXT THICKNESS: AT LEAST 1/32" THICKNESS

TEXT COLOR: WHITE

BRAILLE: TYPE II BRAILLE TO MATCH BACKGROUND OF PANEL FACE

BOTTOM PANEL

PANEL SIZE: 1" X 8"

PANEL DESCRIPTION: WINDOW INSERT TO ACCOMODATE A POST-

PRINTED PAPER INSERT

BOTTOM

PANEL

TOP

PANEL

EXTRUDED ALUMINUM END CAPS

CENTER OF TACTILE NUMBERS ON 9" FROM DOOR FRAME

' M

A X

. H E

IG

H

T T

O B

A S

E L

IN

E

O F

T A

C T

IL

E

L E

T T

E R

S

' M

IN

IM

U M

H E

IG

H

T T

O B

A S

E

LI

N E

O F

T A

C T

IL

E

L E

T T

E R

S

9" 9"

18" CLEAR

FLOOR SPACE

SCREW INTO WALL

(PREFERRED METHOD)

EXTUDED ALUMINUM

BACK PLATE RAIL

SYSTEM

REFER TO

ELEVATION

4/G-002

WALL AS SCHEDULED

1. REFER TO SHEET G-002 FOR INTERIOR SIGNAGE LOCATION ON FLOOR PLAN.

2. GC TO SUBMIT SIGNAGE SHOP DRAWINGS FOR APPROVAL OF SIGNAGE ROOM

NAME, NUMBERS, AND COLORS FOR APPROVAL WITH OWNER BEFORE ANY

FABRICATION AND INSTALLATION

SIGNAGE SCHEDULE

SIGN TYPE ROOM NUMBER ROOM NAME SIGNAGE TEXT COMMENTS

A 127A OXYGEN GENERATOR ROOM SINGLE ID SLOT +

STAFF ONLY SIGN

SIGNAGE - GENERAL NOTE

OXYGEN GENERATOR ROOM

A

B

C

D

E

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

SEAL

REVISIONS

DEWBERRY PROJECT NUMBER:

DBE PROJECT NUMBER:

F

23456

50187099

FACILITIES PLANNING & SUPPORT SERVICES

8333 LITTLE RIVER TURNPIKE

ANNANDALE, VA 22003

/2

/2

:3

:1

P

M

CODE PLAN &

SIGNAGE DETAIL

MD

DW

JO

2/13/2026

260-B5260-065

L A

A D

D M

E D

IC

A

L O

X Y

G E

N G

E N

E R

A T

O R

N O

R T

H E

R N

V

IR

G

IN

IA

C

O M

U N

IT

Y

C O

L

LE

G E

LO

U D

O U

N C

A M

P U

S

IS

S

U E

D F

O R

B

ID

C

A M

P U

S D

R

IV

E

S T

E R

LI

N

G

V A

Dewberry Engineering Inc.

8401 ARLINGTON BOULEVARD

FAIRFAX, VA 22031 -4666

703.849.0100

G-002

260-B5260-065

0-

B

-0

Scale: 3/32" = 1'-0"1 FIRST FLOOR EXISTING LIFE SAFETY PLAN

BUILDING ADDRESS:

21200 CAMPUS DRIVE, STERLING VA 20164

PROJECT DESCRIPTION:

THE WORK INCLUDES TO DIVIDE THE EXISTING

MECHANICAL ROOM #127, INTO TWO ROOMS: OXYGEN

GENERATOR AND MECHANICAL ROOM. THE WORK

INCLUDES:

A. SELECTIVE DEMOLITION OF EXISTING EQUIPMENT

CONCRETE PAD AND RELOCATION OF EXISTING WATER

HEATER.

B. TO PROVIDE NEW PARTITION WALL AND A DOOR.

C. REMOVE EXISTING OXYGEN TANKS AND MANIFOLD AND

PROVIDE NEW OXYGEN GENERATOR.

APPLICABLE CODES:

VIRGINIA CONSTRUCTION CODE (VCC) -

VIRGINIA BUILDING CODE -

VIRGINIA MECHANICAL CODE -

VIRGINIA PLUMBING CODE -

VIRGINIA STATEWIDE FIRE PREVENTION CODE-

INTERNATIONAL FIRE CODE-

AS REFERENCED BY THE VIRGINIA CODE

NFPA 70 (NATIONAL ELECTRIC COD) -

NFPA 72-

(NATIONAL FIRE ALARM AND SIGNALING CODE)

NFPA 80 (STANDARD FOR FIRE DOORS AND

OTHER OPENING PROTECTIVES) -

VIRGINIA ENERGY CONSERVATION CODE (VECC) -

VIRGINIA EXISTING BUILDING CODE (VEBC). ALT 2-

VIRGINIA UNIFORM STATEWIDE BUILDING CODE -

ADA 90 TITLE II: ASAD CHAPTER 2 FOR SCOPING -

ICC A117.1- CHAPTER 1 AND 3 THRU 11 FOR

TECHNICAL REQUIRED

VIRGINIA COMMUNITY COLLEGE SYSTEM

CONSTRUCTION AND PROFESSIONAL SERVICES

MANUAL, (CPSM), .......................2025 REV (0) ISSUED 03/17/25

CLASSIFICATION OF WORK: VEBC 601.2.2 LEVEL 2 ALTERATIONS SHALL COMPLY

WITH THE APPLICABLE PROVISIONS OF SECTIONS 602 AND 603 AND SHALL

INCLUDE THE FOLLOWING:

1. THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW.

2. THE ADDITION OR ELIMINATION OF ANY WALL, FLOOR, OR CEILING

ASSEMBLY.

3. THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM.

4. THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT, MATERIALS,

ELEMENTS, OR FIXTURES.

• BUILDING FUNCTION: OFFICE, TEACHING LABS & ANIMAL MEDICAL FACILITY

(BUILDING NOT TO BE USED AS EMERGENCY SHELTER)

• BUILDING USE GROUP: B (BUSINESS) (UNCHANGED)

• CONSTRUCTION TYPE IIB, (SPRINKLERED): (UNCHANGED)

• GROSS BUILDING AREA: 11,480 SQ.FT (UNCHANGED)

• BUILDING HEIGHT = ONE STORY = 20 FT (UNCHANGED)

• RENOVATED AREA USE GROUP

( ACCESSORY STORAGE AREA MECHANICAL ROOM) : (UNCHANGED)

• TOTAL OCCUPANCY LOAD = 91 (UNCHANGED)

• SCOPE OF WORK AREA: = 443 SQ.FT

PROJECT BUILDING CODE INFORMATION

Scale: 3" = 1'-0"2 TYPICAL - FIRESTOP DEVICE - THRU GYP BD WALL Scale: 3" = 1'-0"3 TYP CABLE TRAY THRU FIRE RATED GYP BOARD WALL

0' 10' 20'5'

SCALE: 3/32" = 1' - 0"

NORTH

0' 6"3" 9"

SCALE: 3" = 1' - 0"

NO. DESCRIPTION DATE

1 PERMIT REVISION-01 06.12.26

2 PERMIT REVISION-02 07.15.26

Scale: 6" = 1'-0"4 ROOM SIGNAGE Scale: 3/4" = 1'-0"5 INTERIOR SIGNAGE MOUNTING

Scale: 6" = 1'-0"6 INTERIOR SIGNAGE MOUNTING DETAIL

0' 2'1' 3'

SCALE: 3/4" = 1' - 0"

0' 2" 4"1"

SCALE: 6" = 1' - 0"

2/13/2026 ehoffman Snapshot ehoffman Snapshot

PARTN TYPE WIDTH

O P

N G

P E

R

R A

T E

D

A S

S E

M B

LY

FIRESTOP

DEVICE

1 TO 7 GANG

CABLES

RATED PARTN

TYPE AS

SCHEDULED

RATING NO:

MAX 4 HR, UL W-L-3218

OR EQ

FIRE RATED SEALANT

INTUMESCENT WRAP

STRIP AT PERIMETER

OF CABLE TRAY

BED CABLE IN FIRE

RATED SEALANT, PER

THE RATED ASSEMBLY

INSULATED CABLES

AND STEEL TRAY

INTUMESCENT SHEET

RATING NO:

3 HR UL C-AJ-4003,

OR EQ

CONCRETE

CMU

WALL,

AS

SCHED

O

PN

G P

ER

R

AT

ED

A

SS

EM

BL

Y

PARTN TYPE WIDTH

O P

N G

P E

R R

A T

E D

A S

S E

M B

LY

FIRE RATED SEALANT

INTUMESCENT WRAP

STRIP AT PERIMETER

OF CABLE TRAY

BED CABLE IN FIRE

RATED SEALANT, PER

THE RATED ASSEMBLY

INSULATED CABLES

AND STEEL TRAY

INTUMESCENT SHEET

RATED PARTN TYPE

AS SCHEDULED

RATING NO:

MAX 2 HR, UL W-L-4004,

OR EQ

M

IN

METAL JUNCTION

BOX, SEPARATE

BACK TO BACK

BOXES 24" MIN

CMU PARTITION

TYPE AS

SCHEDULED

TYPICAL METAL

JUNCTION BOX,

MOUNT FLUSH W/

FACE OF CMU, AND

GROUT SOLID

AROUND BOX

PLAN

SECTION

RATED

PARTITION, AS

SCHEDULED

ACOUSTICAL

INSUL AS

SCHEDULED

TELEPHONE OR

ELECTRICAL COVER

PLATE

CONTINUOUS

ACOUS SEALANT

AROUND TEL & MET

ELEC OUTLET BOX

MOLDABLE FIRE-

STOPPING AROUND

TELEPHONE OR

ELEC OUTLET BOX

FILL BEHIND THE BOX

WITH FIRE BLANKET

INSULATION

" M

IN

N

TS

PARTITION AS SCHEDULED

ACOUSTICAL INSULATION

COVER PLATE

METAL STUDS

FLEX CABLE BETWEEN

"J" BOXES, WHERE

OCCURS

OUTLET BOX PAD

AROUND "J" BOXES

CONT ACOUS SEALANT

AROUND "J" BOXES

TYP MET "J" BOX

MOUNT ADJOINING "J"

BOXES IN SEPARATE

STUD CAVITIES

FIRE RATED SEALANT

EA SIDE OF PARTN W/

BACKER ROD

MET DUCT

UL COMPLYING STL BENT PLATE

RETAINING ANGLES, BOTH SIDES

OF PARTN, ATTACH TO DUCT W/

UL COMPLYING SM SCREWS,

OVERLAP PARTN OPNG 1" MIN

RATING NO:

MAX 2 HR, UL W-L-7008,

OR EQ

RATED GYP BD

PARTN, AS SCHED

DBL STUD FRAMED

OPNG, TYP

STOP DUCT INSUL @ FO

PARTN, SEAL VAPOR

BARRIER TO GYP BD

WHERE OCCURS

METAL SLEEVE WHERE

REQUIRED BY CONTRACT

DOCUMENTS

FIRE RATED SEALANT AND

PACKING - DEPTH AS REQ'D

BY RATED ASSEMBLY

ANNULAR SPACE PER

RATED ASSEMBLY

METAL PIPE

FILL AROUND SLEEVE IN

MASONRY CONSTRUCTION

W/ CEMENT MORTAR

RATING NO:

MAX 3 HR, UL C-AJ-1017,

OR EQ

CONCRETE

MASONRY

PARTN TYPE WIDTH

FIRESTOP

DEVICE

1 TO 7 GANG

CABLES

CMU/CONC PARTN

TYPE AS

SCHEDULED

RATING NO:

MAX 4 HR, UL W-J-3098

OR EQ

A

B

C

D

E

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

SEAL

REVISIONS

DEWBERRY PROJECT NUMBER:

DBE PROJECT NUMBER:

F

23456

50187099

FACILITIES PLANNING & SUPPORT SERVICES

8333 LITTLE RIVER TURNPIKE

ANNANDALE, VA 22003

/1

/2

:2

:1

P

M

WALL

PENETRATION

DETAILS

MD

DW

JO

2/13/2026

260-B5260-065

L A

A D

D M

E D

IC

A

L O

X Y

G E

N G

E N

E R

A T

O R

N O

R T

H E

R N

V

IR

G

IN

IA

C

O M

U N

IT

Y

C O

LL

E

G E

LO

U D

O U

N C

A M

P U

S

IS

S

U E

D F

O R

B

ID

C

A M

P U

S D

R

IV

E

S T

E R

LI

N

G

V A

Dewberry Engineering Inc.

8401 ARLINGTON BOULEVARD

FAIRFAX, VA 22031 -4666

703.849.0100

G-003

260-B5260-065

0-

B

0-

Scale: 3" = 1'-0"9

TYP CABLE FIRESTOP DEVICE

THRU GYP BD

Scale: 3" = 1'-0"8

TYP CABLE TRAY

THRU CONC/CMU RATED WALL

Scale: 3" = 1'-0"7

TYP CABLE TRAY

THRU RATED GYP BD PARTN

Scale: 1 1/2" = 1'-0"6 TYP J BOX @ CMU PARTN Scale: 3" = 1'-0"5

TYP "J" BOX @ RATED

GYP BD PARTN

Scale: 3" = 1'-0"4

TYP "J" BOX @ GYP BD

PARTN W/ ACOUS INSUL

Scale: 3" = 1'-0"2

TYP MET DUCT

THRU RATED GYP BD PARTN

Scale: 3" = 1'-0"1

TYP PIPE/CONDUIT THRU

CONC/CMU RATED WALL

Scale: 3" = 1'-0"3

TYP. CABLE FIRESTOP DEVICE

THRU CONC/CMU

0' 8" 16"4"

SCALE: 1 1/2" = 1' - 0"

0' 6"3" 9"

SCALE: 3" = 1' - 0"

NO. DESCRIPTION DATE

07/16/2026

06-17-202607-15-2026

PREP.

ROOM

109A

SCRUB

ROOM

MEN'S

WOMEN'S

FOYER

VET LAB

FELINE

HOLDING

AREA STORAGE

JAN.

ANIMAL

HOLDING

AREA

CONNECTOR

100C

CORRIDOR

GROOMING

116B

STORAGE

116C

116F

ANIMAL

QUARTERS

116E

ANIMAL

QUARTERS

116D

CLEANUP

AREA

116A

ANIMAL

QUARTERS

CANINE

HOLDING

AREA

STORAGE

/CHANGE

ROOMISOLATION

MECH.

CORRIDOR

100B

RADIOLOGY

SURGERY

111A

DARK

ROOM

PREP.

ROOM

109A

SCRUB

ROOM

MEN'S

WOMEN'S

FOYER

EXAM

ROOM

OFFICE

100D

LOBBY

LOBBY

SEATING

RECOVERY

ROOMS 137

EXAM

ROOM

EXAM

ROOM

STUDY

RADIOLOGY

140A

ELEC

JANITOR

UNISEX

PLUMBING

COMPUTER

TELCO

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

MECH

UNISEX

100G

CORRIDOR

RECOVERY

AUTOCLAVE

144B

CHANGING

ROOM

150B

ANIMAL

PREP

150C

SURGEONS

SCRUB

150A

OPERATING

ROOM

TEACHING

LAB

PREP.

ROOM

109A

SCRUB

ROOM

MEN'S

WOMEN'S

FOYER

GENERAL NOTES - NEW WORK PLAN

1. NO ASBESTOS CONTAINING MATERIAL SHALL BE USED ON THIS PROJECT.

2. DIMENSIONS ARE SHOWN AS FOLLOWS, U.N.O.

A. ALL DIMENSIONS ARE SHOWN TO THE FINISHED FACE, U.N.O.

B. DIMENSIONS NOTED AS "CLEAR" (CLR.) ARE TO THE FACE OF FINISHED

SURFACE AND TAKE PRECEDENT OVER ALL OTHER DIMENSIONS.

C. DISCREPANCIES IN DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE

ATTENTION OF THE ARCHITECT, WHO WILL ISSUE WRITTEN CLARIFICATION.

3. FINAL PARTITION WALL FINISH - PAINT TO MATCH COLOR W/ EXISTING WALLS.

4. COORDINATE ELECTRICAL OUTLET LOCATIONS - REFER TO ELECTRICAL

DRAWINGS. BACK-TO-BACK OUTLETS CANNOT OCCUPY SAME STUD CAVITY

SPACE.

5. REFER TO G-002 FOR EXISTING CODE PLANS AND FOR GRAPHIC

REPRESENTATION .

6. REFER TO G-003 FOR WALL PENETRATION DETAILS.

LEGEND FLOOR PLAN

EXISTING WALL TO REMAIN

NEW DOOR

EXISTING CONCRET PAD TO REMAIN

NEW PARTITION WALL

EXISTING DOOR TO REMAIN

AREA OUTSIDE THE PROJECT SCOPE

NEW 4" EQUIPMENT CONCRET PAD ON

EXISTING CONCRETE FLOOR LEVEL

OXYGEN

GENERATOR RM

127A

MECHANICAL

EQUIPMENT RM

A

0"

V .I.

F

9' - 1 7/8" +/- V.I.F.

4' - 0"

+/- V.I.F

1' - 6"

AC OG

OST

NEW 4" CONCRETE EQUIPMENT

PAD ON EX.CONCRETE FLOOR

MATCH THE TOP LEVEL W/

EXISTING CONCRETE PAD -

SEE DETAIL 9/A-111

A-111

SCOPE OF WORK

(MECHANICAL RM #127)

SCOPE OF WORK

(ELECTRICAL RM #140A)

SCOPE OF WORK

(PLUMBING RM #142)

ROUGHEN THE EXISTING

CONCRETE FLOOR IN

PREPARATION FOR THE NEW 4"

CONCRETE EQUIPMENT PAD

EXISTING FLOOR DRAIN.

TO REMAIN, TYPICAL

EXISTING CONCRETE

PAD. EL + 4", TO REMAIN

EXISTING CONCRETE

PAD. EL + 4", TO REMAIN

MECHANICAL

EQUIPMENT RM

4"

0"

4"

4"

EXISTING LOUVER

5'-0"(w) X 2'-2" (h) TO

REMIAN, TYPCIAL

V .I.

F

9' - 1 7/8" +/- V.I.F.

EXISTING CONCRETE

PAD. EL + 4", TO REMAIN

V.I.F

1' - 6"

V .I.

F

V .I.

F

4' - 0" V.I.F

DEMOLITION PLAN GENERAL NOTES

1. VISIT SITE AND VERIFY EXISTING CONDITIONS PRIOR TO BID SUBMISSION.

DISCREPANCIES BETWEEN CONSTRUCTION INDICATED ON DRAWINGS AND

ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO ARCHITECT’S ATTENTION

IMMEDIATELY IN WRITING.

2. DEMOLISHED ITEMS NOT INDICATED TO BE “DELIVERED TO OWNER” OR “TO BE

RELOCATED” SHALL BE REMOVED FROM SITE AS SOON AS POSSIBLE UNLESS

THEY ARE TO BE USED FOR REQUIRED PATCHING AND INFILLING OF EXISTING

CONSTRUCTION THAT IS TO REMAIN. NO OTHER DEMOLISHED ITEMS SHALL BE

STORED ON SITE.

3. DEMOLISHED ITEMS NOTED AS “DELIVER TO OWNER” OR “TO BE RELOCATED”

SHALL BE REMOVED OR DISASSEMBLED IN SUCH A MANNER THAT WILL NOT

DAMAGE THE ITEM AND PREVENT IT FROM BEING RELOCATED. REPAIR OR

REPLACE SUCH ITEMS, IF DAMAGED. NOTIFY OWNER’S REPRESENTATIVE

IMMEDIATELY IF DAMAGE HAS OCCURRED, AND SUBMIT A REPAIR SOLUTION TO

ARCHITECT FOR REVIEW.

4. TEMPORARILY STORE ITEMS INDICATED AS “DELIVER TO THE OWNER” IN ONSITE

LOCATION, DESIGNATED BY THE OWNER. OWNER SHALL MOVE ITEM(S), AS

NECESSARY, TO NOT HINDER OR DELAY PERFORMANCE OF WORK IN AREA.

5. TEMPORARILY STORE ITEMS INDICATED AS “TO BE RELOCATED” IN LOCATION

ONSITE AND PROTECT ITEMS FROM DAMAGE PRIOR TO INSTALLATION IN NEW

LOCATION.

6. ITEMS INDICATED “TO REMAIN” THAT ARE DAMAGED DURING THE PERFORMANCE

OF THE DEMOLITION WORK. SUCH DAMAGE SHALL BE REPORTED TO OWNER’S

REPRESENTATIVE IMMEDIATELY, AND SUBMIT A REPAIR SOLUTION TO ARCHITECT

FOR REVIEW.

7. COORDINATE DEMOLITION WORK WITH NEW CONSTRUCTION WORK IN EACH

AREA OF DEMOLITION. EXISTING CONSTRUCTION IN AREAS ADJACENT TO

DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO MATCH ORIGINAL

EXISTING CONDITION AS REQUIRED TO PROVIDE FOR NEW CONSTRUCTION

WORK IN AREA OF DEMOLITION.

8. ITEMS INDICATED TO BE REMOVED BY OWNER SHALL BE COMPLETED PRIOR TO

COMMENCEMENT OF WORK.

9. AT LOCATIONS WHERE A PORTION OF EXISTING CONSTRUCTION IS TO BE

REMOVED AND PREPARED FOR NEW INFILL CONSTRUCTION, OR AN OPENING IN A

WALL, ROOF, OR FLOOR IS CREATED BY DEMOLITION WORK, CONSTRUCT INFILL

WITH SAME MATERIALS AND METHOD OF CONSTRUCTION AS EXISTING ADJACENT

CONSTRUCTION, UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL DRAWINGS

FOR INFILL CONSTRUCTION. INFILL CONSTRUCTION SHALL SMOOTHLY BUTT

ADJACENT SURFACES AND MATCH THE FINISH, U.N.O.

10. AT LOCATIONS WHERE AN ITEM IS TO BE REMOVED FROM A SURFACE THAT IS TO

REMAIN, PATCH AND REPAIR EXISTING SURFACE TO MATCH EXISTING ADJACENT

SURFACE, UNLESS INDICATED OTHERWISE.

11. EXISTING ITEMS ANCHORED TO CONSTRUCTION THAT IS INDICATED TO BE

DEMOLISHED SHALL BE CONSIDERED A PART OF DEMOLISHED CONSTRUCTION

AND SHALL BE DEMOLISHED WITH THE INDICATED CONSTRUCTION, UNLESS

NOTED OTHERWISE.

12. IN CONDITIONS WHERE A WALL OR FLOOR FINISH IS DEMOLISHED CREATING A

DISSIMILAR ELEVATION IN ADJACENT FLOOR FINISHES, INSTALL AN APPROVED

LEVELING MATERIAL TO BRING LOWER FLOOR FINISH ELEVATION UP TO AN

ELEVATION FLUSH WITH ADJACENT FLOOR.

13. CONSTRUCT TEMPORARY DUST PARTITIONS TO CONTAIN DEMOLITION WORK

AND PREVENT CONSTRUCTION DUST FROM ENTERING ADJACENT EXISTING

CONSTRUCTION. SUBMIT LOCATIONS OF THESE PARTITIONS FOR APPROVAL BY

OWNER’S REPRESENTATIVE. PARTITION LOCATIONS SHALL NOT IMPEDE OR

HINDER EMERGENCY EGRESS FROM BUILDING. REFER TO SPECIFICATIONS FOR

CONSTRUCTION OF DUST PARTITIONS.

14. RETAIN DEMOLISHED MATERIALS AS NEEDED FOR INFILLING OPENINGS IN

EXISTING CONSTRUCTION SO THAT FINISH MATERIALS WILL PROPERLY ALIGN

WITH EXISTING AND MATCH THE EXISTING FINISH. IF DEMOLISHED MATERIALS

ARE NOT SALVAGEABLE, NOTIFY OWNER’S REPRESENTATIVE, SO THAT

ALTERNATE SOLUTIONS MAY BE DETERMINED.

15. IF EXISTING CONSTRUCTION IS REVEALED NOT CONSTRUCTED OR FINISHED IN A

MANNER THAT MATCHES ADJACENT SURFACES, PATCH AREA AS NECESSARY

WITH APPROPRIATE MATERIALS AND METHODS OF CONSTRUCTION TO MATCH

EXISTING ADJACENT FINISH, OR PREPARE SURFACE FOR INSTALLATION OF NEW

FINISH. CONTACT OWNER’S REPRESENTATIVE AS SOON AS POSSIBLE SO THAT

CONCEALED CONSTRUCTION MAY BE IDENTIFIED AND SCOPE OF POSSIBLE

ADDITIONAL WORK DETERMINED.

16. WHEN EXISTING SURFACE IS INDICATED TO BE “PATCHED AND REPAIRED” OR

“PREPARED” TO RECEIVE NEW FINISH MATERIAL, PROVIDE A CONSTRUCTION

SURFACE THAT IS CAPABLE OF RECEIVING NEW FINISH MATERIAL.

17. WHEN THE TERM ‘ENTIRETY’ IS DIRECTED TO A SPECIFIC ITEM OR ASSEMBLY,

DEMOLISH AND REMOVE IDENTIFIED ITEM AND ASSOCIATED CONSTRUCTION

PERTINENT TO THE ITEM, INCLUDING, BUT NOT LIMITED TO UNDERGROUND AND

CONCEALED CONSTRUCTION, SUCH AS FOOTINGS AND FOUNDATIONS, SEWER,

PLUMBING, AND ELECTRICAL WORK. THIS DEMOLITION WORK SHALL BE

COORDINATED WITH THE CIVIL, STRUCTURAL, PLUMBING, MECHANICAL,

ELECTRICAL, AND TECHNOLOGY DRAWINGS.

18. CONTRACTOR TO PROVIDE HOURLY FIRE WATCH FOR ANY FIRE ALARM OR

SPRINKLER IMPAIRMENTS 1-HOUR OR LONGER. FIRE WATCH TO INCLUDE

WALKING THE ENTIRE BUILDING HOURS. FIRE WATCH TO BE DOCUMENTED ON A

FIRE WATCH LOG. PROVIDE THE FIRE WATCH LOG TO THE PROJECT MANAGER.

REFER TO SPEC SECTION 01 0010 FOR DETAILS.

1/2"1/2"

2"

VARIES

SEALANT ALL AROUND,

BOTH SIDES

HOLLOW METAL FRAME

PARTITION AS SCHEDULED

DOOR AS SCHEDULED

/2

/2

2"

V A

R

IE

S

PARTITION AS SCHEDULED

HOLLOW METAL FRAME

JAMB ANCHOR CLIP

DOOR AS SCHEDULED

SEALANT ALL AROUND,

BOTH SIDES

D O

O R

H E

IG

H

T

WIDTH

DOOR

M

IN

6"X8" SIGNAGE - A

EQ EQ

H E

IG

H

T

8" WIDE

SIGNAGE - A

SIGNAGE - A: TO BE LOCATED

ON ROOM #127A DOOR.

REINFORCED PLASTIC F

H E

IG

H

T

WIDTH

DOOR

CONCRETE SLAB

DOOR PANEL

/2

SECTION AT TOP

STOP GYP BOARD BELOW

MECHANICAL DUCTS

SECTION AT BASE

(1) LAYER 5/8'' GYPSUM

BOARD, BOTH SIDES,

MOISTURE & MOLD

RESISTANT

3 5/8" THICK, 20 GA METAL

STUD @ 16'' O.C.

DIAGONAL BRACING 3 5/8"

METAL STUD 20G, @ 16" O.C

BOTH SIDES AS REQUIRED

WALL TYPE - A - NON FIRE RATED

EX. UNDERSIDE OF METAL

ROOF ABOVE

SEALANT - BOTH SIDES

G Y

P B

O A

R D

F U

L L

S T

U D

H E

IG

H

T

3'

-0

M A

X

CONTINUOUS RUBBERIZED

MOISTURE ISOLATION UNER

LOWER TRACK

CONCRETE FLOOR

USE 16 GA STEPPED

BOTTOM PLATE AS NEEDED

1. ALL FRAMES TO BE 2" WIDE UNLESS NOTED OTHERWISE.

2. HOLLOW METAL DOORS AND FRAMES TO BE PAINTED THE SAME COLOR TO

EXISTING DOOR AND FRAMES.

3. LOCATED DOORS IN PARTITIONS NEAR ADJACENT WALLS 4 INCHES FROM FACE

OF ADJACENT WALL TO EDGE OF DOOR U.N.O.

4. FOR DOOR FRAMES HEAD, JAMB, THRESHOLD SEE DOOR SCHEDULE.

5. FOR DOOR HARDWARE TYPES AND INSTALLATION REFER TO SPEC 08 71 00.

DOOR GENERAL NOTE

3"

C

LE

A R

EXISTING

EQUIPMENT

PAD

#4 AT 12" O.C. EACH WAY

DRILL 5/8" DIA. X 4" DEEP

HOLES INTO EXISTING PAD

AND SET REBAR IN HIGH

STRENGTH EPOXY

DOWELING SYSTEM

#4 DOWELS WITH 8" LEGS AT 12"

O.C. MAXIMUM SPACING AROUND

PERIMETER OF PAD DIRECTION.

DRILL 5/8" DIA. X 3" DEEP HOLES

INTO EXISTING SLAB AND SET

DOWELS IN HIGH STRENGTH EPOXY

DOWELING SYSTEM.

EXISTING SLAB-ON-GRADE

SCARIFY SLAB SURFACE AT

PAD LOCATION AND APPLY

EPOXY BONDING ADHESIVE

M A

T C

H E

X

IS

T

IN

G

3/4" CHAMFER

EQUIPMENT HOUSEKEEPING PAD EXTENSION NOTES:

1. PAD CONCRETE SHALL HAVE A MINIMUM 28-DAYS COMPRESSIVE STRENGTH OF 4,000 PSI.

2. HOUSE KEEPING PAD EXTENSION SHALL EXTEND A MINIMUM O F4" BEYOND EQUIPMENT

FOOTPRINT OR AS SHOWN ON DRAWINGS.

3. APPLY EPOXY BONDING ADHESIVE ON SIDE OF EXISTING PAD PRIOR TO POURING PAD

EXTENSION.

4. COORDINATE EXACT PAD LOCATION WITH MECHANICAL PLAN.

5. IF PAD EXTENSION IS POURED AGAINST AND EXISTING WALL, PLACE 1/2" EXPANSION JOINT

MATERIAL BETWEEN A WALL AND A SLAB.

EX. METAL EXTERIOR WALL

EX. METAL EXTERIOR

LOUVER 2' (H) X 4' (W)

@ 4" A.F.F

PARTITION WALL - A

PROVIDE 24GA GALVANIZED

METAL COVER AS SHOWN AT

WALL END FOR 3'-0" HIGH.

PROVID ADDITIONAL STUD

STRAP AT LOWER TRACK AS

REQUIRED

1 1/2"

A

B

C

D

E

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

SEAL

REVISIONS

DEWBERRY PROJECT NUMBER:

DBE PROJECT NUMBER:

F

23456

50187099

FACILITIES PLANNING & SUPPORT SERVICES

8333 LITTLE RIVER TURNPIKE

ANNANDALE, VA 22003

/1

/2

:2

:2

P

M

FLOOR PLAN -

DEMOLITION &

NEW WORK &

DOOR SCHEDULE

MD

DW

JO

2/13/2026

260-B5260-065

L A

A D

D M

E D

IC

A

L O

X Y

G E

N G

E N

E R

A T

O R

N O

R T

H E

R N

V

IR

G

IN

IA

C

O M

U N

IT

Y

C O

LL

E

G E

LO

U D

O U

N C

A M

P U

S

IS

S

U E

D F

O R

B

ID

C

A M

P U

S D

R

IV

E

S T

E R

LI

N

G

V A

Dewberry Engineering Inc.

8401 ARLINGTON BOULEVARD

FAIRFAX, VA 22031 -4666

703.849.0100

A-111

260-B5260-065

0-

B

0-

0' 8" 16"4"

SCALE: 1 1/2" = 1' - 0"

NORTH

Scale: 1/4" = 1'-0"2 NEW WORK FLOOR PLAN

Scale: 1" = 40'-0"- KEY PLAN

Scale: 1/4" = 1'-0"1 DEMOLITION FLOOR PLAN

DOOR SCHEDULE

D O

O R

N U

M B

E

R DOOR FRAME DETAILS

F

IR

E L

A B

E L

H A

R D

W A

R E

R E

M A

R K

S

D O

O R

N U

M B

E R

LE

A

F Q

T Y

SIZE

T Y

P E

M A

T E

R

IA

L

G

LA

Z

IN

G

T Y

P E

M A

T E

R

IA

L

G

LA

Z

IN

G

SIDELIGHT

WIDTH

TRANSOM

HEIGHT HEAD JAMB SILLWIDTH

WIDTH (IF

UNEVEN) HEIGHT THICKNESS

127 1 3' - 0" 7' - 0" 1 3/4" F HM - HM - H-1 J-1 S-1 - 01 ADD SIGNAG- A ON

DOOR

Scale: 1 1/2" = 1'-0"7 INTERIOR DOOR HEAD (H-1) Scale: 1 1/2" = 1'-0"6 INTERIOR DOOR JAMB (J-1)

Scale: 1/4" = 1'-0"4 DOOR FRAME TYPES Scale: 1/4" = 1'-0"5 DOOR PANEL TYPES

Scale: 6" = 1'-0"8 INTERIOR DOOR SILL (S-1)

Scale: 1" = 1'-0"3 PARTITION WALL - TYPE A

Scale: 1" = 1'-0"9 TYPICAL - CONCRETE EQUIPMENT PAD ADDITION

0' 12" 24"6"

SCALE: 1" = 1' - 0"

0' 4' 8'2'

SCALE: 1/4" = 1' - 0"

Scale: 1 1/2" = 1'-0"10 PLAN DETAIL

0' 2" 4"1"

SCALE: 6" = 1' - 0"

NO. DESCRIPTION DATE

07/16/2026

CB

07-15-2026

260-B5260-065

260-B5260-065

50187099

APPROVED BY

CHECKED BY

A

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

SEAL

No. Description Date

REVISIONS

23456

B

C

D

E

F

DEB PROJECT NUMBER :

DEWBERRY PROJECT NUMBER:

FACILITIES PLANNING & SUPPORT SERVICES

8333 LITTLE RIVER TURNPIKE

ANNANDALE, VA 22003

Dewberry Engineers, Inc.

8401 ARLINGTON BLVD

FAIRFAX, VA 22031

703.849.0100 Phone

260-B5260-065

50187099

/2

/2

:0

:1

A

M

Q

P R

O J E

C T

S \5

N V

C C

L A

A D

D O

X Y

G E

N G

E N

E R

A T

O R

\C A

D \E

L E

C T

R

IC

A L \E

-0 E

L E

C T

R

IC

A L C

O V

E R

S H

E E

T .D

W G

ELECTRICAL NOTES

GENERAL

1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE CODES AS

INDICATED ON UNDER THE "APPLICABLE CODES AND CRITERIA" SECTION ON DRAWING G-001.

ALL TRADES SHALL COORDINATE ON PLACEMENT OF NEW EQUIPMENT. REFER TO THE

GENERAL NOTES AND DEMOLITION NOTES FOR ADDITIONAL REQUIREMENTS.

2. UNLESS NOTED OTHERWISE ALL EXISTING ELECTRICAL FIXTURES AND DEVICES SHALL

REMAIN (THOSE INSTALLED UNDER PREVIOUS CONTRACT).

3. CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO DETERMINE EXACT SCOPE OF WORK.

CONTRACTOR SHALL PROVIDE NOTICE AND COORDINATE SITE VISIT IN ADVANCE WITH NVCC

PROJECT MANAGER.

4. ALL WORK SHALL BE PERFORMED IN SUCH A MANNER TO CREATE MINIMAL POWER OUTAGES

FOR THE OWNER. ALL SUCH OUTAGES SHALL BE COORDINATED WITH THE NVCC PROJECT

MANAGER AT LEAST 4 DAYS PRIOR TO VISIT SO THAT POWER TO ESSENTIAL SERVICES CAN BE

MAINTAINED.

5. CONTRACTOR SHALL GUARANTEE HIS WORKMANSHIP AND ALL MATERIALS AND EQUIPMENT

FOR A PERIOD OF ONE YEAR IN WRITING COMMENCING UPON ACCEPTANCE OF INSTALLATION

BY OWNER.

6. CONTRACTOR SHALL MAINTAIN ACCESS, SAFETY, AND CLEANLINESS IN AREA THAT AFFECTS

THE FLOW OF PEDESTRIAN TRAFFIC IN THE BUILDING, DUE TO RENOVATION.

7. CONTRACTOR SHALL PROVIDE 24/7 HOURLY FIRE WATCH ANY TIME THE FIRE ALARM SYSTEM

IS IMPAIRED. FIRE WATCH SHALL INCLUDE ADJACENT AREAS INSIDE AND OUTSIDE OF THE

BUILDING EFFECTED BY FIRE ALARM SYSTEM OUTAGE.

8. THE BUILDING PERMIT WILL BE OBTAINED AND PAID FOR BY THE OWNER.

9. CONTRACTOR SHALL PROVIDE BRANCH CIRCUIT WIRING, CONDUIT, AND OVERCURRENT

PROTECTION MEETING SUBMITTED AND APPROVED EQUIPMENTS RESPECTIVE NAMEPLATE

DATA AT NO ADDITIONAL COST (MAXIMUM OVERCURRENT PROTECTION (MOP) AND MINIMUM

CIRCUIT AMPACITY (MCA)).

10. PIPING, DUCTWORK, LIGHTING FIXTURES, CABLE TRAYS, CONDUIT, CABLES, WIRING,

RACEWAYS, JUNCTION BOXES, INSULATION, AND OTHER ITEMS LOCATED WITHIN THE RETURN

AIR CEILING PLENUM SHALL BE COORDINATED, ARRANGED AND INSTALLED TO NOT

OBSTRUCT OR OTHERWISE ADVERSELY AFFECT THE FLOW OF RETURN AIR FROM THE

OCCUPIED SPACE, THROUGH THE RETURN AIR PATH, BACK TO THE RESPECTIVE HVAC UNIT.

IN ALL AREAS OF THE RETURN AIR CEILING PLENUM, INCLUDING CONGESTED AREAS OF THE

CEILING PLENUM, THE RETURN AIR VELOCITY SHALL NOT EXCEED 500 FPM. REFER TO THE

MECHANICAL DRAWINGS FOR ADDITIONAL RETURN AIR PATH REQUIREMENTS.

11. ELECTRICAL EQUIPMENT REQUIRING ACCESS SUCH AS J-BOXES OR CONNECTIONS TO

EQUIPMENT SHALL NOT BE INSTALLED ABOVE INACCESSIBLE CEILINGS OR BEHIND WALLS.

CONTRACTOR SHALL REROUTE ANY EXISTING CONDUIT AND J-BOXES INCLUDING

CONNECTIONS TO ELECTRICAL EQUIPMENT TO AN ACCESSIBLE LOCATION WHETHER

INDICATED ON THE DRAWINGS OR NOT. EXISTING CONDUIT AND J-BOXES ABOVE

INACCESSIBLE CEILINGS/WALLS WHICH CANNOT BE RELOCATED SHALL BE ABANDONED WITH

ALL WIRING REMOVED. ANY EXCEPTIONS SHALL BE AUTHORIZED BY THE NVCC PROJECT

MANAGER.

12. CONTRACTOR IS TO X-RAY SLABS PRIOR TO PENETRATING STRUCTURE. X-RAYS, CONCRETE

CUTTING, AND CORE DRILLING SHALL TAKE PLACE AFTER REGULAR BUSINESS HOURS AND

SCHEDULED WITH PROJECT MANAGER.

13. AFTER FINAL INSTALLATION, CONTRACTOR WILL BE RESPONSIBLE FOR FILLING ALL VOIDS

AROUND CONDUIT PENETRATIONS AND OTHER CORE DRILLS/OPENINGS IN SLAB AND WALLS

WITH A FIRE SAFING REMOVABLE MASTIC. FILL SHALL EQUAL FIRE RATING OF FLOOR OR

WALL AND BE COMPATIBLE WITH CONSTRUCTION MATERIALS.

14. CONTRACTOR SHALL DETERMINE THE NUMBER AND SIZE OF CORE DRILLS NECESSARY FOR

INDICATED WORK AND SHALL DETERMINE RECOMMENDED LOCATION AND PROVIDE TO

STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL PRIOR TO COMMENCING WORK.

15. CONTRACTOR SHALL MAINTAIN INTEGRITY OF VAPOR BARRIER AND INSULATION FOR ALL

ELECTRICAL WORK AND DEVICES ON EXTERIOR AND PERIMETER WALLS.

16. FURRING DEPTH ON COLUMNS, SHAFT WALLS, AND FIRE-RATED WALLS IS LIMITED. THE

CONTRACTOR SHALL COORDINATE THE LOCATION OF COLUMN AND WALL MOUNTED

EQUIPMENT/DEVICES WITH AVAILABLE MOUNTING DEPTH AND WITH THE REQUIREMENTS OF

FIRE-RATED WALLS AND SHAFT ENCLOSURES. THE CONTRACTOR SHALL ADJUST THE

POSITION OF THE EQUIPMENT/DEVICE TO AN ALTERNATE WALL OR SIDE OF THE SAME

COLUMN AS REQUIRED TO ACCOMMODATE JOB SITE CONDITIONS AT NO ADDITIONAL COST.

17. ALL MATERIALS AND EQUIPMENT FURNISHED FOR THIS PROJECT SHALL BE NEW AND MATCH

BUILDING STANDARD(S) FOR MANUFACTURER AND TYPE OF EQUIPMENT FOR LIGHTS, EXIT

SIGNS, FIRE ALARM DEVICES, WIRING DEVICES, LIGHTING\POWER PANELS, TRANSFORMERS,

DISCONNECTS, ETC. WHERE NO BUILDING STANDARD EXISTS FOR ELECTRICAL EQUIPMENT,

EQUIPMENT SHALL BE NEW AND U.L. LISTED AS MANUFACTURED BY CUTLER HAMMER,

GENERAL ELECTRIC, SQUARE D, OR SIEMENS. MODIFICATIONS OR ADDITIONS TO EXISTING

EQUIPMENT SHALL MATCH EXISTING TO MAINTAIN ANY U.L. ASSEMBLY LISTING. CONTRACTOR

WILL BE RESPONSIBLE FOR CONTACTING AND COORDINATING WITH BUILDING OWNER ON

DETERMINING ANY STANDARDS. THE FAULT CURRENT RATING OF ALL EQUIPMENT ADDED TO

THE ELECTRICAL DISTRIBUTION SHALL MEET THE AVAILABLE FAULT CURRENT.

18. SUBMITTALS SHALL INCLUDE PANELBOARDS, DISCONNECTS, WIRING DEVICES,

TRANSFORMERS, AND CONDUCTORS. SUBMITTAL DATA SHALL CONTAIN ONLY INFORMATION

RELEVANT TO THE PARTICULAR EQUIPMENT OR MATERIALS TO BE FURNISHED FOR THIS

SPECIFIC PROJECT. CATALOG SHEETS WHICH DESCRIBE SEVERAL DIFFERENT ITEMS IN

ADDITION TO THOSE ITEMS TO BE USED SHALL NOT BE SUBMITTED UNLESS RELEVANT

INFORMATION IS CLEARLY MARKED. SIMILAR EQUIPMENT SHALL BE SUBMITTED IN ONE

COMPLETE SUBMITTAL PACKAGE (I.E. ALL PANELBOARDS, ALL LIGHTING FIXTURES, ETC.).

TOTAL NUMBER OF SUBMITTALS SHALL BE KEPT TO A MINIMUM. ALL SUBMITTALS SHALL BE

REVIEWED BY THE ENGINEER OF RECORD.

19. NEW REMOVABLE DIRECTORY CARDS SHALL BE PROVIDED AT COMPLETION OF WORK WITH

TYPED DESIGNATIONS INDICATING NAME, VOLTAGE, PHASE, ETC. AND FINAL CIRCUITING OF

PANELBOARDS DEPICTING EACH POLE POSITION IN A TWO COLUMN FASHION. ROOM

NUMBERS SHALL BE USED WHENEVER POSSIBLE ON CIRCUIT DESIGNATIONS. WHEN NEW

CARDS ARE TYPED, EXISTING INFORMATION ON THE EXISTING CARDS THAT REMAINS

APPLICABLE SHALL BE TRANSFERRED TO NEW CARDS, REGARDLESS OF DRAWING

DESIGNATIONS SUCH AS "EXISTING LOAD". NO HANDWRITTEN NOTES WILL BE ACCEPTED.

20. CONTRACTOR SHALL TRACE ALL CIRCUITS INDICATED ON THE DRAWINGS USED IN THE SCOPE

OF WORK AND INDICATED AS "SPARES" ON PANEL SCHEDULES AND CONFIRM CIRCUITS ARE

DEDICATED TO RENOVATED LEASE AREA AND NOT SERVING OTHER EXISTING OCCUPIED

SPACES. CONTRACTOR SHALL NOT USE CIRCUITS PRESENTLY BEING USED BY OTHER

OCCUPIED SPACES SO AS TO MINIMIZE ANY POTENTIAL INTERRUPTION OF SERVICE.

1.) CONTRACTOR SHALL IN THE PROCESS OF TRACING CIRCUITS, MAKE EFFORTS TO

UPDATE EXISTING CIRCUIT DESIGNATION FROM "EXISTING LOAD" TO A SPECIFIC

DESIGNATION TO INCLUDE, AT A MINIMUM, ROOM NUMBER AND DEVICE

CONTROLLED, TO BE USED WHEN UPDATING DIRECTORY CARDS IN NOTE 20 ABOVE.

21. AFTER COMPLETION OF WORK, CONTRACTOR SHALL OPEN (REMOVE AND REINSTALL COVERS

UPON INSPECTION) ALL ELECTRICAL EQUIPMENT THAT WAS AFFECTED BY WORK OF THIS

PROJECT FOR VISUAL INSPECTION TO INCLUDE BUT NOT LIMITED TO VISUALLY CONFIRM

TERMINATIONS, CLEANLINESS, COLOR CODING, CIRCUIT IDENTIFICATION, GROUNDING, AND

WIRING.

22. CONTRACTOR SHALL VACUUM CLEAN ALL DIRT AND DEBRIS FROM ELECTRICAL EQUIPMENT

(E.G., OUTLETS, SWITCHES, DISCONNECTS, MOTOR STARTERS, PANELBOARDS,

TRANSFORMERS, ETC.).

23. DURING THE PROGRESS OF THE WORK AND UPON COMPLETION, TESTS SHALL BE MADE AS

SPECIFIED HEREIN AND AS REQUIRED BY AUTHORITIES HAVING JURISDICTION INCLUDING

INSPECTORS, OWNER, AND ENGINEER. TESTS SHALL BE CONDUCTED BY THE CONTRACTOR

AS PART OF THE WORK OF THIS DIVISION AND SHALL INCLUDE THE SERVICES OF QUALIFIED

PERSONNEL AS WELL AS ALL EQUIPMENT, APPARATUS, AND SERVICES REQUIRED. TESTS

SHALL INCLUDE CONDUCTOR INSULATION RESISTANCE OF CONDUCTOR #6 AWG AND LARGER,

OPERATION OF ALL ELECTRICAL EQUIPMENT, OPERATION OF STANDBY LIGHTING, OPERATION

OF ALL DRY TYPE TRANSFORMERS BY RECORDING SECONDARY VOLTAGE TO ENSURE

PROPER TAP SETTINGS.

24. WITHIN 19 DAYS OF SYSTEM ACCEPTANCE, TMA FORMS SHALL BE PROVIDED TO THE OWNER

25. WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE

ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING AN

UPDATED SINGLE LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND

FLOOR PLANS INDICATING THE LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. AN

OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING

OWNER INCLUDING, AT A MINIMUM, SUBMITTAL DATA STATING EQUIPMENT RATING AND

SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE,

OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT

REQUIRING MAINTENANCE WITH REQUIRED ROUTINE MAINTENANCE ACTIONS CLEARLY

IDENTIFIED, NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY, AND A

COMPLETE NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE. WITHIN 90 DAYS

AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL

INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER INCLUDING, AT A MINIMUM, THE

LOCATION, LIGHTING EQUIPMENT.

DISTRIBUTION EQUIPMENT AND OVERCURRENT PROTECTION

1. INSTALL 1/16" THICK ENGRAVED MELAMINE PLASTIC-LAMINATE SIGN ON EACH NEW UNIT OF

ELECTRICAL EQUIPMENT ASSOCIATED WITH THE RENOVATION. PROVIDE SINGLE LINE OF

TEXT, 1/2" HIGH LETTERING ON 1-1/2" HIGH SIGN WITH WHITE LETTERING ON A FIELD OF BLACK.

PROVIDE TEXT MATCHING DESIGNATION ON THE CONTRACT DOCUMENTS. PROVIDE SIGNS

FOR EACH UNIT OF PANELBOARDS, ELECTRICAL CABINETS, ENCLOSURES, MOTOR STARTERS,

DISCONNECT SWITCHES, ETC. FASTENERS SHALL BE SELF-TAPPING STAINLESS STEEL

SCREWS, EXCEPT USE CONTACT-TYPE PERMANENT ADHESIVE WHERE SCREWS CANNOT OR

SHOULD NOT PENETRATE SUBSTRATE.

2. PANELBOARDS SHALL BE STANDARD CATALOG ITEMS COMPLYING WITH NEC, UL, AND NEMA

STANDARDS AND BEAR THE LABEL OF UNDERWRITER'S LABORATORIES. PROVIDE COPPER

FULL-SIZE PHASE AND NEUTRAL BUSSES WHICH HAVE BEEN RATED IN ACCORDANCE WITH UL

67 HEAT-RISE TESTS. BUS BAR CONNECTIONS SHALL BE COLUMN CONSECUTIVE

PHASE-SEQUENCE TYPE. BOTH 120/208 AND 277/480 VOLT PANELBOARDS SHALL HAVE BUS

BARS DRILLED AND EQUIPPED WITH ALL HARDWARE FOR BOLT-ON MOLDED CASE CIRCUIT

BREAKERS. PROVIDE A BOLTED ON COPPER GROUNDING BUS WITH MAIN LUG(S).

PANELBOARD SHORT CIRCUIT BRACING AND BREAKER INTERRUPTING CAPACITY SHALL BE AS

INDICATED ON THE DRAWINGS BUT SHALL NOT BE LESS THAN 14,000 AMPERES RMS

SYMMETRICAL FOR 277/480 VOLT SERVICE AND 10,000 AMPERES RMS SYMMETRICAL FOR

120/208 VOLT SERVICE. PROVIDE MANUFACTURER'S STANDARD #16-GAGE (MINIMUM)

GALVANEALED OR GALVANIZED SHEET STEEL CABINET WITH ENAMEL FRONT "HINGED DOOR

IN DOOR" COVERS, MASTER-KEYED DOOR LOCKS, MULTIPLE KNOCKOUTS, WIRING GUTTERS,

AND TYPED CIRCUIT DIRECTORY. PANELBOARD MAIN LUGS CONNECTED TO #6 AWG OR

LARGER COPPER CONDUCTORS SHALL BE FURNISHED TO ACCOMMODATE COMPRESSION

CONNECTORS. ADEQUATE WIRING SPACE SHALL BE PROVIDED TO ACCOMMODATE THE

COMPRESSION CONNECTORS. UNLESS OTHERWISE NOTED, ALL PANELBOARDS SHALL

INCLUDE FEED-THRU LUGS. PANELS RATED 400A OR HIGHER (FOR BOTH 120/208V AND

277/480V) SHALL BE CAPABLE OF HAVING CIRCUIT BREAKERS RATED 150A OR HIGHER

INSTALLED WITHOUT RENDERING THE FEED-THRU LUGS USELESS. NEW PANELBOARDS

SHALL MATCH EXISTING PANELBOARDS PROVIDED THE ABOVE MINIMUM REQUIREMENTS

HAVE BEEN MET. IT WOULD BE AN ACCEPTABLE OPTION FOR THE CONTRACTORS TO USE

ALUMINUM BUS WITHIN PANELBOARDS IN LIEU OF COPPER BUS WITHIN PANELBOARDS. THE

CONTRACTORS SHALL BE RESPONSIBLE FOR COORDINATING THE ADDITIONAL SPACE

REQUIRED DUE TO THE ALUMINUM EQUIPMENT.

3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTLY PHASING AND BALANCING THE

CIRCUITS IN THE PANELBOARDS. PROVIDE CIRCUITS WITH DEDICATED NEUTRAL

CONDUCTORS AS INDICATED ON THE DRAWINGS. PROVIDE CIRCUITS WITH SHARED NEUTRAL

CONDUCTORS AS INDICATED ON THE DRAWINGS. NEUTRAL CONDUCTORS SHALL NOT BE

COMBINED/SHARED WHERE NOT INDICATED ON THE DRAWINGS. WHERE NEUTRAL

CONDUCTORS ARE INDICATED TO BE SHARED, THE PHASE CONDUCTORS SHALL BE ON

OPPOSITE PHASES. PROVIDE JUNCTION BOXES AS REQUIRED FOR THE QUANTITY OF WIRES,

CONNECTORS, AND DEVICES CONTAINED THEREIN WHERE COMBINING HOMERUNS. ANY

INFORMATION IN QUESTION OR NOT CLEARLY EXPRESSED ON THE DRAWINGS SHALL BE

CONFIRMED WITH THE ENGINEER OF RECORD.

4. DISCONNECT SWITCHES INDICATED AND/OR SPECIFIED FOR 480 VOLT CIRCUITS SHALL BE

600-VOLT AND I²T RATED, DIRECT DRIVE, QUICK-MAKE, QUICK-BREAK TYPE SWITCHES WITH

SPRING-REINFORCED WIRE GRIPS AND SELF-ALIGNING SWITCH CONTACTS. SWITCHES SHALL

BE ENCLOSED IN A HEAVY SHEET METAL ENCLOSURE WITH HINGED INTERLOCKING COVER

WHICH SHALL PREVENT THE COVER FROM BEING OPENED WHEN SWITCH IS "ON". PROVIDE

REJECTION-TYPE FUSE CLIPS FOR CARTRIDGE FUSES IN SWITCHES AS INDICATED AND

ACCOMMODATION FOR R FUSES. SWITCHES SHALL BE NEMA TYPE HD. SWITCHES EXPOSED

TO MOISTURE ON THE EXTERIOR OR INTERIOR OF THE BUILDING SHALL HAVE NEMA 4

STAINLESS STEEL ENCLOSURES (WATER AND DUST TIGHT). FUSED DISCONNECT SWITCHES

SHALL BE SUBSTITUTED FOR NON-FUSED SWITCHES WHERE REQUIRED BY MANUFACTURER,

LOCAL INSPECTING AUTHORITY, AND/OR FUSE PROTECTION IS INDICATED ON MOTOR

NAMEPLATE AT NO ADDITIONAL COST. DISCONNECT SWITCHES FOR 208-VOLT CIRCUITS

SHALL BE SIMILAR EXCEPT RATED 240-VOLT NEMA TYPE HD. ALL SWITCHES SHALL HAVE

PROVISION FOR PADLOCKING.

5. TRANSFORMERS SHALL BE DRY TYPE 60 HERTZ, 480 VOLT, 3 PHASE, DELTA TO 120/208 VOLT, 3

PHASE, 4 WIRE, GROUNDED WYE, NEMA TP-1. TEMPERATURE CLASSIFICATION SHALL HAVE A

220°C INSULATION SYSTEM. WINDING TEMPERATURE RISE SHALL NOT EXCEED 150°C IN A

40°C AMBIENT. SOUND RATING SHALL BE IN ACCORDANCE WITH ANSI-C89.2. BIL RATINGS

SHALL BE IN ACCORDANCE WITH ANSI AND NEMA STANDARDS. TRANSFORMERS SHALL HAVE

FOUR 2-1/2% FULL LOAD TAPS BELOW RATED VOLTAGE AND TWO 2-1/2% FULL LOAD TAPS

ABOVE RATED VOLTAGE. USE COPPER BODIED COMPRESSION CONNECTORS FOR

TERMINATING CABLES TO TRANSFORMER LUGS. INTERNAL VIBRATION ISOLATION MOUNTS

SHALL BE PROVIDED. TRANSFORMERS SHALL BE GROUNDED PER NEC ARTICLE 250 TO

STRUCTURAL STEEL IF PRESENT OR GROUND RISER IF STEEL IS NOT PRESENT. MOUNT

TRANSFORMERS ON A FOUR INCH HIGH CONCRETE PAD APPROXIMATELY ONE INCH LARGER

ALL AROUND THAN THE TRANSFORMER PROVIDED. SUSPEND TRANSFORMERS AS INDICATED

ON THE CONTRACT DOCUMENTS AND WHERE REQUIRED DUE TO SPACE CONSTRAINTS.

TRANSFORMERS SHALL BE SUSPENDED IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS AND IN ACCORDANCE WITH THE STRUCTURAL DOCUMENTS.

6. MOLDED CASE CIRCUIT BREAKERS SHALL BE OPERATED BY A TOGGLE-TYPE HANDLE AND

SHALL HAVE A QUICK-MAKE, QUICK-BREAK, OVER-CENTER SWITCHING MECHANISM THAT IS

MECHANICALLY TRIP-FREE FROM THE HANDLE SO THAT THE CONTACTS CANNOT BE HELD

CLOSED AGAINST SHORT CIRCUITS AND ABNORMAL CURRENTS. TRIPPING DUE TO OVERLOAD

OR SHORT CIRCUIT SHALL BE CLEARLY INDICATED BY THE HANDLE AUTOMATICALLY

ASSUMING A POSITION MIDWAY BETWEEN THE MANUAL ON AND OFF POSITIONS. ALL LATCH

SURFACES SHALL BE GROUND AND POLISHED. POLES SHALL BE SO CONSTRUCTED THAT

THEY CAN OPEN, CLOSE AND TRIP SIMULTANEOUSLY. BREAKERS SHALL BE COMPLETELY

ENCLOSED IN A MOLDED CASE WITH THE AMPERE RATINGS CLEARLY VISIBLE. CONTACTS

SHALL BE NON-WELDING SILVER ALLOY. BREAKERS SHALL BE UL LISTED FOR USE WITH 75°C

AND 90°C INSULATED WIRE. CIRCUIT BREAKER RATINGS, MODIFICATIONS, ETC., SHALL BE AS

INDICATED ON THE DRAWINGS. MOLDED-CASE CIRCUIT BREAKERS SHALL BE AS FOLLOWS:

1) THERMAL MAGNETIC TYPE THAT PROVIDES INVERSE TIME-DELAY OVERLOAD AND

INSTANTANEOUS SHORT CIRCUIT PROTECTION BY MEANS OF A THERMAL MAGNETIC

ELEMENT.

2) AMBIENT COMPENSATED STANDARD THAT PROVIDES INVERSE TIME-DELAY OVERLOAD

AND INSTANTANEOUS SHORT CIRCUIT PROTECTION BY MEANS OF A THERMAL MAGNETIC

ELEMENT. COMPENSATION SHALL ALLOW THE BREAKER TO CARRY RATED CURRENT

BETWEEN 25°C AND 50°C WITH TRIPPING CHARACTERISTICS THAT ARE APPROXIMATELY

THE SAME THROUGHOUT THIS TEMPERATURE RANGE.

3) MULTI-POLE BREAKERS SHALL BE OF THE COMMON TRIP TYPE HAVING A SINGLE

OPERATING HANDLE, EXCEPT THAT 240-VOLT MULTI-POLE BREAKERS SMALLER THAN

50-AMPERES MAY CONSIST OF FACTORY-CONNECTED, SINGLE-POLE BREAKERS WITH A

COMMON TRIP HANDLE.

4) ALL CIRCUIT BREAKERS SHALL BE FULL SIZE AND BOLT-ON.

7. WHERE POSSIBLE, MOLDED CASE CIRCUIT BREAKERS WITHIN PANELBOARDS SHALL BE

INSTALLED IN THE ORDER INDICATED IN THE PANEL SCHEDULES.

8. ALL FUSES SHALL BE DUAL-ELEMENT LOW PEAK CLASS RK1 AS MANUFACTURED BY BUSSMAN

OR LITTELFUSE. FUSE VOLTAGE RATING SHALL BE 250 VOLT FOR 120/208 VOLT SYSTEM AND

600 VOLT FOR 277/480 VOLT SYSTEM.

9. CONTRACTOR SHALL PROVIDE UPDATED INFORMATION ON ELECTRICAL EQUIPMENT TO

OWNER IN ARC FLASH STUDY FORMAT.

RACEWAYS AND CONDUCTORS

1. ALL CONDUCTORS SHALL BE COPPER. ALL CONDUCTORS #8 AWG AND LARGER SHALL BE

STRANDED. CONDUCTOR SIZES #10 AWG, #12 AWG, AND #14 AWG SHALL BE SOLID. ALL

CONDUCTORS SHALL BE STANDARD CODE TYPE "THW", "THHN", "THWN" OR "XHHW"

INSULATED EXCEPT AS REQUIRED OTHERWISE PER THE NEC. ALL CONDUCTORS SHALL BE

DURABLY MARKED ON THE SURFACE TO INDICATE RATED VOLTAGE, INSULATION CODE, USE,

MANUFACTURER, AND AWG SIZE. THE COLOR CODING SHALL BE CONTINUOUS AND SHALL

EXTEND TO PANELS AND MOTORS. WHERE INSULATION COLOR CODING IS NOT AVAILABLE

FOR CONDUCTORS #8 AWG AND LARGER, USE COLOR CODED PLASTIC TAPE AT EACH

CONDUCTOR TERMINATION. ALL #8 AWG AND SMALLER CONDUCTORS SHALL BE SPLICED

WITH PREINSULATED SPRING CONNECTORS. CONNECTORS SHALL BE SCOTCHLOCK,

BUCHANAN B-CAP, OR APPROVED EQUAL. ALL #6 AWG AND LARGER COPPER CONDUCTORS

TERMINATED ON LUGS OF PANELBOARDS SHALL BE TERMINATED WITH COPPER U.L. LISTED

COMPRESSION CONNECTORS SUCH AS THOMAS & BETTS #54100 OR #54200 SERIES

CONNECTORS. ALL #6 AWG AND LARGER COPPER CONDUCTOR TWO WAY SPLICES SHALL BE

MADE WITH BARREL CONNECTORS REQUIRING COMPRESSION ON EACH END. ALL #6 AWG

AND LARGER COPPER CONDUCTOR TAPPING AND PIGTAILING SHALL BE MADE USING "C" TYPE

COMPRESSION TAPS SUCH AS THOMAS AND BETTS #54700 SERIES CONNECTORS.

CONNECTOR SHALL BE U.L. LISTED FOR TYPE OF CONDUCTORS TO BE TAPPED. THE

MANUFACTURERS RECOMMENDED INSTALLING TOOLS WITH REQUIRED NUMBER OF

COMPRESSIONS SHALL BE USED FOR ALL TERMINATIONS.

2. AT THE CONTRACTOR'S OPTION, ALUMINUM CONDUCTORS MAY BE USED IN LIEU OF COPPER

CONDUCTORS FOR ALL CIRCUITS PROTECTED BY 100 AMPS AND GREATER OVER CURRENT

PROTECTION DEVICES EXCEPT FOR MOTOR LOADS INCLUDING BUT NOT LIMITED TO PUMPS,

FANS, AND AIR HANDLING UNITS OR AS INDICATED ON THE DRAWINGS. ALL CIRCUITS

PROTECTED BY OVER CURRENT PROTECTION DEVICES LESS THAN 100 AMPS ARE REQUIRED

TO BE COPPER. THE USE OF ALUMINUM FOR CIRCUITS PROTECTED BY OVER CURRENT

PROTECTION DEVICES LESS THAN 100 AMPS WILL NOT BE ACCEPTABLE. IF THIS OPTION IS

SELECTED BY THE CONTRACTOR, THE CONTRACTOR SHALL BE RESPONSIBLE FOR

COORDINATING THE ADDITIONAL WORK AND SPACE REQUIRED FOR THE LARGER OR

ADDITIONAL PARALLEL SETS OF CONDUIT AND CONDUCTORS REQUIRED TO MEET THE

COPPER CONDUCTOR BASIS OF DESIGN CURRENT CARRYING CAPACITY. IN ADDITION, THE

CONTRACTOR SHALL PROVIDE ALL THE NECESSARY ADDITIONAL HANGERS, CORE DRILLS,

SLEEVES, FIRE PROOFING, ETC. REQUIRED TO ACCOMMODATE THE OPTIONAL ALUMINUM

CONDUCTORS AND BUSSING AS INDICATED ON THE OPTIONAL ELECTRICAL DISTRIBUTION

DIAGRAM SYSTEM UTILIZING ALUMINUM CONDUCTORS. ALL ALUMINUM CONDUCTORS SHALL

BE TERMINATED WITH ALUMINUM U.L. LISTED COMPRESSION CONNECTORS. THE SMALLEST

ALLOWABLE ALUMINUM CONDUCTOR FOR THE OPTIONAL ALUMINUM SYSTEM SHALL BE #1/0

AWG.

3. ALL WIRE SIZES INDICATED ARE BASED ON DIRECT PATHS WITH 90° BENDS AS NECESSARY

FROM THE OUTLET/UTILIZATION EQUIPMENT TO THE PANELBOARD, WITH A MAXIMUM 2%

VOLTAGE DROP ON FEEDER CONDUCTORS AND A MAXIMUM VOLTAGE DROP OF 3% FOR

BRANCH CIRCUIT CONDUCTORS. WHERE FIELD CONDITIONS DO NOT ALLOW, OR IF FOR ANY

REASON THE ROUTE SELECTED IS DIFFERENT, THE WIRE SIZE (AND CONDUIT IF NECESSARY)

SHALL BE INCREASED TO MAINTAIN THESE MINIMUM VOLTAGE DROP REQUIREMENTS AT NO

ADDITIONAL COST TO THE OWNER. REGARDLESS, ALL 20 AMP, 120 VOLT HOMERUNS SHALL BE

A MINIMUM #12 AWG UNLESS LENGTHS EXCEED 60', THEN CONDUCTORS SHALL BE A MINIMUM

#10 AWG. ALL 20 AMP, 277 VOLT HOMERUNS SHALL BE A MINIMUM #12 AWG UNLESS LENGTHS

EXCEED 165'; THEN CONDUCTORS SHALL BE A MINIMUM #10 AWG.

4. RECEPTACLE NEUTRAL CONDUCTOR(S) SHALL BE A MINIMUM #10 AWG AT POINT WHERE

MORE THAN ONE 20 AMP PHASE CONDUCTOR IS CONNECTED TO A COMMON NEUTRAL BACK

TO PANELBOARD. #10 "AC" CABLE SHALL BE USED FOR ALL PHASES AND NEUTRAL FOR "AC"

CABLE INSTALLATIONS AT CONNECTION POINT OF COMMON NEUTRAL.

5. THE ACTUAL NUMBER OF WIRES REQUIRED MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY

THOSE WHERE CLARIFICATION IS NECESSARY. THE ELECTRICAL CONTRACTOR SHALL

PROVIDE ALL WIRES NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER

INDICATED ON THE DRAWINGS OR NOT AT NO ADDITIONAL COST.

6. ALL EMT AND FLEXIBLE CONDUIT SHALL BE U.L. LISTED. ALL CONDUIT SHALL BE SUITABLE

FOR THE INTENDED SERVICE AND LOCATION. ANY MATERIALS LOCATED WITHIN

ENVIRONMENTAL AIR PLENUMS SHALL BE U.L. LISTED FOR THE APPLICATION OR APPROVED IN

WRITING BY ALL APPLICABLE LOCAL CODE AUTHORITIES. THE CONTRACTOR SHALL

COORDINATE ALL RACEWAY SYSTEM COMPONENTS AND LOCATIONS WITH ALL NEW WORK.

CONTRACTOR SHALL COORDINATE WITH WORK OF OTHER TRADES. CONTRACTOR SHALL

COORDINATE WITH ALL EQUIPMENT WITH PLENUM AND CHASE LIMITATIONS AND

REQUIREMENTS OF DRAWINGS AND SPECIFICATIONS. CONTRACTOR IS RESPONSIBLE FOR

TIMELY PLACEMENT OF SLEEVES, CUTTING AND PATCHING OF NEW CONSTRUCTION TO FIT

WORK OF THIS SECTION, LOCATION OF CHASE SPACE FOR VERTICAL ROUTING OF RACEWAY

SYSTEMS AND LOCATION OF PLENUM SPACE FOR HORIZONTAL ROUTING OF RACEWAY

SYSTEMS. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF

SYSTEMS AND WORK. DRAWINGS ARE NOT TO BE SCALED. IN PREPARATION OF THE

DRAWINGS, A REASONABLE EFFORT TO COORDINATE RACEWAY SYSTEMS HAVE BEEN MADE,

HOWEVER, SPACE REQUIREMENTS, EQUIPMENT ARRANGEMENTS, AND SITE CONDITIONS

VARY, AND THE RESPONSIBILITY FOR ACCESS, LOCATION, PROPER FIT AND TIMELY

COMPLETION RESTS WITH THE CONTRACTOR.

EXPOSED INTERIOR:

ALL EXPOSED INTERIOR WIRING SHALL BE IN GALVANIZED STEEL OR ALUMINUM EMT USING

STEEL SET SCREW CONNECTORS. CONTRACTOR SHALL MINIMIZE EXPOSED INTERIOR

WIRING/CONDUIT WITHIN OUT INCREASING COST WHERE POSSIBLE.

CABLE:

BRANCH CIRCUIT WIRING CONCEALED IN A WALL OR CEILING CONNECTING RECEPTACLES

AND LIGHTS MAY BE “AC” OR “MC” CABLE. JUNCTION BOX LOCATION SHALL BE SELECTED TO

MINIMIZE THE ASSOCIATED REQUIRED AC/MC CABLES IN CEILINGS.

7. METALLIC CONDUIT WITH CONDUCTORS SHALL BE USED IN LIEU OF CABLE IN ALL VISIBLE

PUBLIC AREA AND BACK OF HOUSE LOCATIONS. "AC"/"MC" CABLE SHALL NOT BE TERMINATED

AT PANELBOARDS. CABLE SHALL TERMINATE OUTSIDE OF ELECTRICAL CLOSETS AND ROOMS

WITH GUTTERS. CONDUIT SHALL BE USED TO CONNECT GUTTERS TO PANELS.

8. ALL CONDUIT SHALL BE RIGIDLY SUPPORTED TIGHT TO THE BUILDING STRUCTURE. MAXIMUM

SPACING OF SUPPORTS, 10'-0" FOR VERTICAL, AND 8'-0" FOR HORIZONTAL RUNS. COUPLINGS

AND FITTINGS FOR EMT SHALL BE OF STEEL (CAST POT METAL IS NOT ACCEPTABLE) AND

SHALL BE OF THE COMPRESSION OR SET STEEL SCREW TYPE. NOT MORE THAN THE

EQUIVALENT OF FOUR QUARTER BENDS SHALL BE USED IN ANY RUN BETWEEN…