260-B4260-058 NVCC Renovate 3rd Floor Lab - BID SET Drawings.pdf
PDF 7 MB Posted
- Attached to
- 260-B4260-058 NVCC Renovate 3rd Floor Lab
- Solicitation number
- IFB-126793
- Issued by
- Fairfax County, Virginia
About this file
This is a bid set of construction drawings for the Northern Virginia Community College (NVCC) Annandale Campus renovation project, specifically for reconfiguring the third-floor laboratory and classroom spaces in the CM-McDiarmid Building. The project, identified as 260-B4260-058, involves the selective demolition of the existing partition wall separating rooms CM311 (Group Study/Computer Class Room) and CM365 (Oral Communication Center), resulting in a combined 1,331 square feet of renovated space. The scope includes removal and replacement of affected floor finishes and ceiling grid elements, patching and painting of wall areas, installation of new floor and wall-mounted power outlets, and provision of new electronic door access (EDA) systems to existing fire-rated doors. The drawings were issued for the bid set on August 5, 2026, and were prepared by Dewberry Engineering Inc. The building is located at 8333 Little River Turnpike, Annandale, Virginia 22003, and is owned by the Commonwealth of Virginia State Board of Community Colleges. The project must comply with the 2021 Virginia Construction Code, International Building Code, International Mechanical Code, International Plumbing Code, NFPA 70 National Electric Code (2020), and Virginia Energy Conservation Code (2021).
The renovation is classified as an Alteration Level 2 project under the Virginia Existing Building Code, with a work area of 1,433 square feet representing less than 50 percent of the building's total 58,912 square foot gross area. The building, originally constructed in 1993, is classified as Use Group B (Business) with Construction Classification IIB (Unprotected) and contains automatic sprinkler, fire alarm, and standpipe systems. The design includes fire-rated partition assemblies, mechanical systems with fan-powered terminal units, fire protection systems including sprinkler and standpipe coordination, and complete electrical systems including lighting, fire alarm, power distribution, and emergency circuits. The project incorporates compliance with ADA Title II accessibility standards and high-performance building considerations, though the renovation cost does not exceed 50 percent of building value and is therefore exempt from certain High Performance Building Act requirements. Energy compliance must achieve performance equal to or less than 80 percent of the standard reference design building per VECC standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
/4
/2
:0
:0
P M
COVER SHEET
MD
RT
JO
08/05/2026
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
E N
O V
A T
E
R D
F L
O O
R
LA
B #2
-B
-0
/L
N V
N V
C C
A
N N
A N
D A
LE
C
A M
P U
S
IS
S
U E
D F
O R
B
ID
S E
T
L
IT
T
LE
R
IV
E R
T U
R N
P
IK
E
A N
N A
N D
A
LE
V
A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
G-001
NVCC ANNANDALE CAMPUS - CM - MCDIARMID BUILDING
RENOVATE 3RD FLOOR LAB
PROJECT #260-B4260-058/L24NV548
ISSUED FOR BID SET
AUGUST 05, 2026
CONSULTANTS
ARCHITECTURE & MEP
BUILDING LOCATION:
NVCC ANNANDALE CAMPUS CM - McDiarmid BUILDING:
8333 LITTLE RIVER TURNPIKE, ANNANDALE VA 2003
SITE INFORMATION
OWNER OF BUILDING:
COMMONWEALTH OF VIRGINIA
STATE BOARD OF COMMUNITY COLLEGES
PRIMARY CONTACTS:
OWNER: NORTHERN VIRGINIA COMMUNITY COLLEGE
FACILITIES PLANNING AND SUPPORT SERVICES
8333 LITTLE RIVER TURNPIKE, CW BUILDING
SUITE 311, ANNANDALE, VA 22003-3796
PHONE: 703.323.3551
APPLICABLE CODE AND CRITERIA:
ALL WORK SHALL COMPLY WITH THE FOLLOWING CODES:
VIRGINIA CONSTRUCTION CODE (VCC) -
INTERNATIONAL BUILDING CODE -
INTERNATIONAL MECHANICAL CODE -
INTERNATIONAL PLUMBING CODE -
NFPA 70 NATIONAL ELECTRIC CODE (NEC) -
VIRGINIA ENERGY CONSERVATION CODE (VECC) -
VIRGINIA EXISTING BUILDING CODE (VEBC). ALT 2-
VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC) -
ADA 90 TITLE II: ASAD CHAPTER 2 FOR SCOPING -
ICC A117.1- CHAPTER 1 AND 3 THRU 11 FOR TECHNICAL REQUIRED
VIRGINIA COMMUNITY COLLEGE SYSTEM
CONSTRUCTION AND PROFESSIONAL SERVICES
MANUAL, (CPSM), .........................................................................2025 REV (0) 03/17/25
IN THE EVENT OF A CONFLICT, THE MOST RESTRICTIVE CODE
SHALL PREVAIL
CALL BEFORE YOU DIG:
VIRGINIA ONE CALL
811 OR 1-800-552-3120
3 WORKING DAYS UTILITY NOTIFICATION
PRIOR TO CONSTRUCTION
DEWBERRY
8401 ARLINGTON BLVD
FAIRFAX, VA 22031
T: 703.849.0100 F: 703.698.9040
DRAWING LIST
SHEET NO. SHEET TITLE. .
GENERAL
G-001 COVER SHEET
G-002 STANDARD ABBREVIATIONS & SYMBOLS
G-003 BUILDING CODE PLAN - THIRD FLOOR
G-004 PENETRATION DETAILS
G-005 UL DESIGN ASSEMBLY & PARTITION WALL
ARCHITECTURAL
A-111 THIRD FLOOR DEMO WORK PLAN
A-112 THIRD FLOOR NEW WORK PLAN
A-201 FINISH/ FURNITURE PLAN & DOOR SCHEDULE
MECHANICAL
M-001 MECHANICAL SYMBOLS, LEGEND, NOTES
M-111 MECHANICAL THIRD FLOOR NEW WORK PLAN
FIRE PROTECTION
FP-111 FIRE PROTECTION THIRD FLOOR NEW WORK PLAN
ELECTRICAL
E-001 ELECTRICAL SYMBOLS, LEGENDS, NOTES
E-002 ELECTRICAL ABBREVIATIONS
E-110 ELECTRICAL THIRD FLOOR OVERALL FLOOR PLAN
E-111 ELECTRICAL THIRD FLOOR NEW WORK LTG & FIRE ALARM PLAN
E-112 ELECTRICAL THIRD FLOOR NEW WORK POWER PLAN
E-601 ELECTRICAL RISER DIAGRAM PANEL SCHEDULES
DRAWING INDEXGENERAL INFORMATION
ASBESTOS COMPLIANCE STATEMENT (ALL BUILDING):
AN ASBESTOS INSPECTION WAS NOT TO BE PERFORMED BECAUSE ALL PORTIONS OF THE
EXISTING BUILDING THAT MAY BE AFFECTED BY THE WORK WERE ORIGINALLY CONSTRUCTED
AFTER JANUARY 1, 1985.
NO ASBESTOS CONTAINING MATERIAL SHALL BE USED ON THIS PROJECT.
LEAD COMPLIANCE STATEMENT (ALL BUILDING):
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS
NOT BEEN CONDUCTED BECAUSE THE BUILDING WAS CONSTRUCTED AFTER JANUARY 1, 1985
AND THE OWNER HAS NO KNOWLEDGE OF LEAD CONTAINING OR COATED BUILDING
COMPONENTS IN THE BUILDING. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH
ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN
TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED BUILDING COMPONENTS
SHALL BE RECYCLED TO THE EXTENT POSSIBLE.
HIGH PERFORMANCE BUILDINGS ACT NOTICE:
IN ACCORD WITH THE HIGH PERFORMANCE BUILDING ACT, THE BUILDINGS ARE EXEMPT
FROM COMPLIANCE BECAUSE THE COST OF THE RENOVATIONS DOES NOT EXCEED 50%
OF THE VALUE OF EACH BUILDING.
PROJECT NAME: NVCC ANNANDALE CAMPUS - CM BUILDING 3RD FLOOR LAB RENOVATION
PROPOSED SCOPE OF WORK:
• SELECTIVE DEMOLITION OF EXISTING PARTITION WALL THAT SEPARATES THE FOLLOWING ROOMS;
GROUP STUDY (#311) AND ORAL COMMUNICATION CENTER (#365).
• THE SCOPE INCLUDES:
1. REMOVING OF THE AFFECTED FLOOR FINISH AREA TO REPLACE IT IN KIND
2. REMOVING THE AFFECTED CEILING PANEL/ CEILING GRIDS TO REPLACE IT IN KIND
3. PATCHING AND PAINTING AFFECTED WALL AREA
4. PROVIDE NEW FLOOR AND WALL MOUNTED POWER OUTLETS
5. PROVIDE NEW ELECTRONIC DOOR ACCESS (EDA) TO EXISTING FIRE RATED DOORS
VICINITY MAP
BUILDING ORIGINALLY PERMITTED WITH:
1993 VIRGINIA UNIFORM STATEWIDE BUILDING CODE
1988 UNIFORM FEDERAL ACCESSIBILITY
1988 CAPITAL OUTLAY MANUAL STANDARDS
1990 AMERICANS WITH DISABILITY ACT (ADA)
OCCUPANCY USE GROUP: B (BUSINESS)
CONSTRUCTION CLASSIFICATION: IIB (UNPROTECTED)
AUTOMATIC SPRINKLER SYSTEM: YES
CONTAINS FIRE ALARM SYSTEM: YES
CONTAINS STANDPIPE SYSTEM: YES
CONTAINS FIRE EXTINGUISHER: YES
TOTAL BUILDING GROSS AREA: 58,912.40 SQUARE FOOT
TOTAL BUILDING VOLUME: 863,138.80 CUBIC FOOT
REFER TO SHEET G-003 FOR CODE AND LIFE SAFETY ANALYSIS.
CODE COMPLIANCE (ORIGINALLY CONSTRUCTED)
LOCATION MAP
NO. DESCRIPTION DATE
FOR VIRGINIA COMMUNITY COLLEGE SYSTEM
VECC 2021 COMPLIANCE PATH:
IN ACCORD WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING SHALL
COMPLY WITH VECC SECTIONS C402.5, C403.1.1, C403.1.2, C403.2, C403.3, C403.4 (EXCEPT C403.4.3 - C403.4.5), C403.5.5, C403.7 (EXCEPT C403.7.4.1), C403.8 (EXCEPT C403.8.6), C403.9, C403.11 (EXCEPT C403.11.3), C403.12, C403.13, C404, C405 (EXCEPT C405.3), C407 AND C408.
THE BUILDING ANNUAL ENERGY COST SHALL BE EQUAL TO OR LESS THAN EIGHTY (80)
PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
SECTIONS C402.5 AND C404 ARE NOT APPLICABLE TO THIS PROJECT..
08/05/2026
A101
SIM
APC-X
8' - 0"
A
X#XX 1HR
SF01
Area Name
150 SF
FIRST FLOOR
100' - 0"
PT-X
RB-X
CPT-X
NOTES: 22
ROOM NAME
ROOM NAME
A101
SIM
GB-01
Scale:1 View Name 1/8" = 1'-0" 1/A101
A101
SIM
CALLOUT
BUILDING/WALL
SECTION
DETAIL SECTION
ROOM TAG
ROOM FINISH
TAG
CEILING TAG
DOOR / BORROWED
LITE TAG
WINDOW TAG
WALL TAG
FURNITURE,
CASEWORK, &
EQUIPMENT TAG
REVISION TAG
KEYNOTE TAG00 00 00.A1
AREA TO BE
ENLARGED SHEET REF.
PLAN / DETAIL
REF.
SECTION REF.
SHEET REF.
DETAIL REF.
SHEET REF.
LEVEL LINE
AREA SQUARE
FOOTAGE
ROOM NUMBER
EXTERIOR
ELEVATION
INTERIOR
ELEVATION
ELEVATION REF.
SHEET REF. A101
A101
1ELEVATION REF.
SHEET REF.
VIEW NAME
VIEW SCALE
VIEW DESIGNATION
VIEW REF/SHEET REF WHERE
VIEW IS REFERENCED
VIEW TITLE
WALL FINISH
BASE FINISH
FLOOR FINISH
AREA TAG
CEILING TYPE
CEILING HEIGHT
(ABOVE FINISH FLOOR)
LEVEL NAME
LEVEL ELEVATION
GRID LINE
NORTH INDICATOR
GRID NUMBER OR
LETTER
INDICATES PLAN NORTH
INDICATES TRUE NORTH
A101
SPOT ELEVATION
SYMBOL
NOTES
(AS NEEDED)
ROOM NUMBER
NEW DOOR EXISTING DOOR EXISTING DOOR
TO BE DEMOLISHED
WALL MOUNTED
LAVATORY
FLOOR MOUNTED
WATER CLOSET
WALL MOUNTED
TANKLESS WATER
CLOSET
COUNTER MOUNTED
LAVATORY
FLOOR MOUNTED
TANKLESS WATER
CLOSET
ELECTRIC WATER
COOLER
TOILET PARTITIONS
LOCKERS
SINGLE
DOUBLE
TRIPLE
QUAD
GRAB BARWALL MOUNTED
URINAL
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
/4
/2
:0
:0
P M
STANDARD
ABBREVIATIONS
& SYMBOLS
MD
DW
JO
08/05/2026
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
E N
O V
A T
E
R D
F L
O O
R
LA
B #2
-B
-0
/L
N V
N V
C C
A
N N
A N
D A
LE
C
A M
P U
S
IS
S
U E
D F
O R
B
ID
S E
T
L
IT
T
LE
R
IV
E R
T U
R N
P
IK
E
A N
N A
N D
A
LE
V
A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
G-002
AB ANCHOR BOLT
ACST ACOUSTIC(AL)
ADDL ADDITIONAL
ADDN ADDITION
ADH ADHESIVE
ADJ ADJACENT, ADJOINING,
ADJUSTABLE
AED AUTOMATED EXTERNAL
DEFIBRILLATOR
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
ANCH ANCHOR
ANOD ANODIZE(D)
AP ACCESS PANEL
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
ASPH ASPHALT
AUTO AUTOMATIC
AVE AVERAGE
AWT ACOUSTICAL WALL TREATMENT
BAL SHT BALANCE SHEET
BC BRICK COLOR
BCS BABY CHANGING STATION
BD BOARD
BG BUMPER GUARD
BITUM BITUMINOUS
BLDG BUILDING
BLKG BLOCKING (WOOD)
BOT BOTTOM
BRDG BRIDGING
BRG BEARING
BRK PV BRICK PAVERS
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT UP ROOFING
CAB CABINET
CB CHALKBOARD
CC CUBICLE CURTAIN
CCT CUBICLE CURTAIN TRACK
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CFMF COLD-FORMED METAL FRAMING
CG CORNER GUARD
CH COAT HOOK
CIP CONC CAST-IN-PLACE CONCRETE
CJ CONTROL JOING, CONSTRUCTION
JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEAN OUT, CASED OPENING
COL COLUMN
COMB COMBINATION, COMBINED
COMP COMPRESSIBLE
COMPT COMPARTMENT
CONC CONCRETE
CONC CTG CONCRETE COATING
COND CONDITION
CONT CONTINUOUS
CONTR CONTRACTOR
CORR CORRIDOR
CPRS COMPRESSIBLE
CPT CARPET
CR CLOSET ROD
CRL CRASH RAIL
CRS COLD-ROLLED STEEL
CTR CENTER(S)
CUH CABINET UNIT HEATER
CUV CABINET UNIT VENTILATOR
CW CURTAINWALL
D DEEP, DEPTH, PENNY NAIL
DC DISPLAY CASE
DET DETAIL
DETN DETENTION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DP DECORATIVE PANEL
DR DOOR
DS DOWNSPOUT
DWG DRAWING(S)
EHD ELECTRIC HAND DRYER
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT
EMER EMERGENCY
EPDM ETHYLENE PROPYLENE DIENE
MONOMER
EQ EQUAL
EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FAB FABRIC
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FHC FIRE HOSE CABINET
FIN FINISH
FLASH FLASHING
FLP FLOOR PATTERN
FLR FLOOR
FRP FIBER REINFORCED PLASTIC
FTG FOOTING
FURG C FURRING CHANNEL
FURN FURNACE
FWC FABRIC WALLCOVERING
GA GAGE, GAUGE
GALV GALVANIZED
GB GRAB BAR
GFRC GLASS-FIBER REINFORCED
CONCRETE
GL GLASS
GL BLK GLASS BLOCK
GLZ CMU GLAZED CONCRETE MASONRY UNIT
GRFG GLASS-FIBER REINFORCED GYPSUM
GT GROUT
GWH GAS FIRED WATER HEATER
GYP BD GYPSUM WALL BOARD
H HIGH, HATCH (ROOF)
HB HOSE BIB
HDNR HARDENER
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HANDRAIL
HT HEIGHT
HTG HEATING
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
ID INSIDE DIAMETER, INSIDE
DIMENSION
IF INSIDE FACE
INCL INCLUDED
INSUL INSULATION
INT INTERIOR
INV INVERT
JT JOINT
KD KNOCKED DOWN
KOP KNOCK OUT PANEL
L LONG, ANGLE
LAM LAMINATE(D)
LAV LAVATORY
LH LEFT HAND
LINO LINOLEUM
LKR LOCKER
LL LIVE LOAD, LOW LEVEL
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
LVL LEVEL
LVR LOUVER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MARKERBOARD
MBH MOB/BROOM HOLDER
MECH MECHANICAL
MED MEDIUM
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE
MI MIRROR
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODEL, MODULE, MODULAR
MSB MOP SERVICE BASIN
MT MOUNT
MTL METAL
NDU NEEDLE DISPOSAL UNIT
NIC NOT IN CONTRACT, NOISE ISOLATION
CLASS
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER, OUTSIDE
DIMENSION
OF OUTSIDE FACE
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OFD OVERFLOW DRAIN
OFOI OWNER FURNISHED OWNER
INSTALLED
OH OVERHEAD
OH DR OVERHEAD DOOR
OP OPERABLE PARTITION
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OS OVERFLOW SCUPPER
PC PORTLAND CEMENT, POINT
OF CURVE, POLYCARBONATE
PCC PRECAST CONCRETE
PERIM PERIMETER
PJ PROJECTOR
PL PLATE, PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PS PROJECTION SCREEN
PSF POUNDS PER SQUARE FOOT
PT PAINT
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER &
RECEPTACLE
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
PVC POLYVINYL CHLORIDE
PVG PAVING
R RISER, RADIUS, THERMAL
RESISTANCE (R-VALUE)
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN, ROAD
REF REFERENCE, REFRIGERATOR
REINF REINFORCE
REQD REQUIRED
RF RESILIENT FLOORING
RFG ROOFING
RFM REMOVABLE FLOOR MAT
RH RIGHT HAND
RO ROUGH OPENING
RSF RESINOUS FLOORING
RST REINFORCING STEEL
RTF RESILIENT TILE FLOORING
RV ROOF VENT, ROOF VENTILATOR
SC SEALED CONCRETE
SCHED SCHEDULE
SCR SHOWER CURTAIN ROD
SCWD SOLID CORE WOOD DOOR
SD SOAD DISPENSER
SECT SECTION
SF STOREFRONT
SH SHINGLES, SINGLE HUNG (WINDOW)
SHT SHEET
SHTHG SHEATHING
SHV SHELVING
SLNT SEALANT
SND SANITARY NAPKIN DISPENSER
SNDU SANITARY NAPKIN DISPOSAL UNIT
SOG SLAB ON GRADE
SPCG SPACING
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
SS SERVICE SINK , SOLID SURFACING
SST STAINLESS STEEL, SHOWER SEAT
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STL LNTL STEEL LINTEL
STL PL STEEL PLATE
STL RF DK STEEL ROOF DECK
STL TR STEEL TRUSS
STN STAIN
STRUCT STRUCTURAL
SUSP SUSPEND
SV SHEET VINYL
SWP SHEET WALL PROTECTION
SYMM SYMMETRICAL
SYNTH SYNTHETIC
T TILE, TREAD
T&G TONGUE AND GROOVE
T/S TUB/SHOWER
TB TOWEL BAR, TACKBOARD
TC TOILET COMPARTMENT
TD TRENCH DRAIN
TER TERRAZZO
THK THICK
TOB TOP OF BEAM
TOC TOP OF CONCRETE, TOP OF CURB
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOS TOP OF SLAB, TOP OF STEEL
TOW TOP OF WALL
TPH TOILET PAPER HOLDER
TR TOWEL RACK
TS TUBE STEEL, TRANSITION STRIP
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W WIDE, WEST
WC WALL COVERING
WD WOOD, WOOD DOOR
WDW WINDOW
WP WALL PATTERN, WATERPROOFING
WT WEIGHT, WINDOW TREATMENT
WWF WELDED WIRE FABRIC
STANDARD ABBREVIATIONS
STANDARD DETAILING SYMBOLS
STANDARD DRAFTING SYMBOLS
NO. DESCRIPTION DATE
239 SF
CONF. RM.
111 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
138 SF
FACULTY
OFFICE
126 SF
VESTIBULE
138 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
239 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
310 206 SF
STAIR
301B
122 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
120 SF
FACULTY
OFFICE
85 SF
ELEVATOR
301C
120 SF
FACULTY
OFFICE
813 SF
LOUNGE/LAB
261 SF
DIVISION
CHAIR
342A
9 SF
CLOSET
332A
271 SF
WOMEN
183 SF
WORK ROOM
621 SF
SECRETARY
241 SF
MEN'S
153 SF
ASSISTANT
DIVISION
CHAIR
342B
167 SF
ASSISTANT
DIVISION
CHAIR
342C
13 SF
STORAGE CLOSET
342D
230 SF
STAIR
122 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
206 SF
STAIR
301A
1538 SF
ART STUDIO
275 SF
PHOTOLAB
317B
27 SF
STORAGE
317D
23 SF
VESTIBULE
317A
35 SF
FILM
PROCESSING
317C
919 SF
DRAWING LAB
919 SF
DRAWING
LAB
580 SF
AMERICAN
CULTURE &
LANGUAGE
INSTITUTE
101 SF
ACLI OFFICE
327A
115 SF
ACLI OFFICE
327B
121 SF
ACLI OFFICE
327C
57 SF
ACLI LIBRARY
327D
69 SF
WORKROOM
327G
59 SF
WORKROOM
327H
75 SF
STORAGE
30 SF
COMM. CL.
154 SF
STORAGE
154 SF
FACULTY
OFFICE
119 SF
AV STOR
1107 SF
CORRIDOR
300D
1189 SF
CORRIDOR
300B
439 SF
CORRIDOR
300C
47 SF
ACLI LIBRARY
327E
14 SF
ELEC. CL.
122 SF
FACULTY
OFFICE
616 SF
CORRIDOR
300A
105 SF
BREAKROOM
327F
46 SF
JANITOR
2 22
2 22
1 11 1
1 11
1 11
1 11
1 11 1 1 1 1 1 1 1 1 1 1 1
1 11 1 1 1 1 1 1 1 1 1 1 1
2 2
2 2
1 11
1 11
EXISTING LIFE SAFETY LEGEND
1 - HR FIRE RATED PARTITION WALL
2 - HR FIRE RATED PARTITION WALL
EXISTING EXIT
EXISTING EXIT SIGN
AREA NOT IN SCOPE
EGRESS TRAVEL PATH
E
E
F
F
G
G
D
D
C
C
B1
B1
B
B
A
A
4 4
5 5
6 6
7 7
9 9
10 10
3 3
1 1
BUSINESS(CONCENTRATED)
1433 SF / 50 SF
LEGEND - OCCUPANCY AREA
BUSINESS(CONCENTRATED)
P A
T H
-A
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
/4
/2
:0
:0
P M
BUILDING CODE
PLAN - THIRD
FLOOR
MD
DW
JO
08/05/2026
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
E N
O V
A T
E
R D
F L
O O
R
LA
B #2
-B
-0
/L
N V
N V
C C
A
N N
A N
D A
LE
C
A M
P U
S
IS
S
U E
D F
O R
B
ID
S E
T
L
IT
T
LE
R
IV
E R
T U
R N
P
IK
E
A N
N A
N D
A
LE
V
A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
G-003 Scale: 3/32" = 1'-0"1 BUILDING CODE PLAN - THIRD FLOOR
NO. DESCRIPTION DATE
TRAVEL PATH DISTANCE SCHEDULE
PATH NAME PATH LENGTH
PATH-A
PATH-A 68' - 8 1/4"
APPLICABLE CODES: ALL WORK SHALL BE IN ACCORDANCE WITH VIRGINIA
UNIFORM STATE WIDE BUILDING CODES (VUSBC) PART II VIRGINIA
REHABILITATION CODE (VRC) - 2021
CLASSIFICATION OF WORK: IEBC C603.1 - ALTERATION LEVEL - 2
THIS INCLUDE THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF
ANY ADDITIONAL EQUIPMENT, AND SHALL APPLY WHERE THE WORK AREA IS
EQUAL TO OR LESS THAN 50 PERCENT OF THE BUILDING AREA.
PROJECT AND CODE DATA (PROPOSED)
• CONSTRUCTION TYPE IIB: (UNCHANGED)
• GROSS BUILDING AREA: 58,912 SQ.FT (UNCHANGED)
• BUILDING HEIGHT = 58 FT (UNCHANGED)
• RENOVATED AREA USE GROUP : B (UNCHANGED)
• OCCUPANCY LOAD = 29
• PATH OF EGRESS: (UNCHANGED)
1. ALLOWED MAXIMUM TRAVEL DISTANCE = 250 FEET
2. PROVIDED MAXIMUM TRAVEL DISTANCE = 69 FEET
• SCOPE OF WORK AREA: 1,433 SQ.FT
• FULLY AUTOMATIC SPRINKLER SYSTEM THROUGHOUT THE BUILDING
PARTN TYPE WIDTH
O P
N G
P E
R
R
T E
D
S
S E
M B
L Y
FIRESTOP
DEVICE
1 TO 7 GANG
CABLES
RATED PARTN
TYPE AS
SCHEDULED
RATING NO:
MAX 4 HR, UL W-L-3218
OR EQ
FIRE RATED SEALANT
INTUMESCENT WRAP
STRIP AT PERIMETER
OF CABLE TRAY
BED CABLE IN FIRE
RATED SEALANT, PER
THE RATED ASSEMBLY
INSULATED CABLES
AND STEEL TRAY
INTUMESCENT SHEET
RATING NO:
3 HR UL C-AJ-4003,
OR EQ
CONCRETE
CMU
WALL,
AS
SCHED
O
PN
G P
ER
R
AT
ED
A
SS
EM
BL
Y
PARTN TYPE WIDTH
O P
N G
P E
R R
A T
E D
A S
S E
M B
LY
FIRE RATED SEALANT
INTUMESCENT WRAP
STRIP AT PERIMETER
OF CABLE TRAY
BED CABLE IN FIRE
RATED SEALANT, PER
THE RATED ASSEMBLY
INSULATED CABLES
AND STEEL TRAY
INTUMESCENT SHEET
RATED PARTN TYPE
AS SCHEDULED
RATING NO:
MAX 2 HR, UL W-L-4004,
OR EQ
M
IN
METAL JUNCTION
BOX, SEPARATE
BACK TO BACK
BOXES 24" MIN
CMU PARTITION
TYPE AS
SCHEDULED
TYPICAL METAL
JUNCTION BOX,
MOUNT FLUSH W/
FACE OF CMU, AND
GROUT SOLID
AROUND BOX
PLAN
SECTION
RATED
PARTITION, AS
SCHEDULED
ACOUSTICAL
INSUL AS
SCHEDULED
TELEPHONE OR
ELECTRICAL COVER
PLATE
CONTINUOUS
ACOUS SEALANT
AROUND TEL & MET
ELEC OUTLET BOX
MOLDABLE FIRE-
STOPPING AROUND
TELEPHONE OR
ELEC OUTLET BOX
FILL BEHIND THE BOX
WITH FIRE BLANKET
INSULATION
" M
IN
N
TS
PARTITION AS SCHEDULED
ACOUSTICAL INSULATION
COVER PLATE
METAL STUDS
FLEX CABLE BETWEEN
"J" BOXES, WHERE
OCCURS
OUTLET BOX PAD
AROUND "J" BOXES
CONT ACOUS SEALANT
AROUND "J" BOXES
TYP MET "J" BOX
MOUNT ADJOINING "J"
BOXES IN SEPARATE
STUD CAVITIES
FIRE RATED SEALANT
EA SIDE OF PARTN W/
BACKER ROD
MET DUCT
UL COMPLYING STL BENT PLATE
RETAINING ANGLES, BOTH SIDES
OF PARTN, ATTACH TO DUCT W/
UL COMPLYING SM SCREWS,
OVERLAP PARTN OPNG 1" MIN
RATING NO:
MAX 2 HR, UL W-L-7008,
OR EQ
RATED GYP BD
PARTN, AS SCHED
DBL STUD FRAMED
OPNG, TYP
STOP DUCT INSUL @ FO
PARTN, SEAL VAPOR
BARRIER TO GYP BD
WHERE OCCURS
METAL SLEEVE WHERE
REQUIRED BY CONTRACT
DOCUMENTS
FIRE RATED SEALANT AND
PACKING - DEPTH AS REQ'D
BY RATED ASSEMBLY
ANNULAR SPACE PER
RATED ASSEMBLY
METAL PIPE
FILL AROUND SLEEVE IN
MASONRY CONSTRUCTION
W/ CEMENT MORTAR
RATING NO:
MAX 3 HR, UL C-AJ-1017,
OR EQ
CONCRETE
MASONRY
PARTN TYPE WIDTH
FIRESTOP
DEVICE
1 TO 7 GANG
CABLES
CMU/CONC PARTN
TYPE AS
SCHEDULED
RATING NO:
MAX 4 HR, UL W-J-3098
OR EQ
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
/4
/2
:0
:0
P M
PENETRATION
DETAILS
MD
DW
JO
08/05/2026
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
E N
O V
A T
E
R D
F L
O O
R
LA
B #2
-B
-0
/L
N V
N V
C C
A
N N
A N
D A
LE
C
A M
P U
S
IS
S
U E
D F
O R
B
ID
S E
T
L
IT
T
LE
R
IV
E R
T U
R N
P
IK
E
A N
N A
N D
A
LE
V
A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
G-004 Scale: 3" = 1'-0"9
TYP CABLE FIRESTOP DEVICE
THRU GYP BD
Scale: 3" = 1'-0"8
TYP CABLE TRAY
THRU CONC/CMU RATED WALL
Scale: 3" = 1'-0"7
TYP CABLE TRAY
THRU RATED GYP BD PARTN
Scale: 1 1/2" = 1'-0"6 TYP J BOX @ CMU PARTN Scale: 3" = 1'-0"5
TYP "J" BOX @ RATED
GYP BD PARTN
Scale: 3" = 1'-0"4
TYP "J" BOX @ GYP BD
PARTN W/ ACOUS INSUL
Scale: 3" = 1'-0"2
TYP MET DUCT
THRU RATED GYP BD PARTN
Scale: 3" = 1'-0"1
TYP PIPE/CONDUIT THRU
CONC/CMU RATED WALL
Scale: 3" = 1'-0"3
TYP. CABLE FIRESTOP DEVICE
THRU CONC/CMU
FIRE RATING:
STC RATING:
SOUND TEST:
SYSTEM THICKNESS:
LOCATION:
FRAMING TYPE:
1 HOUR
USG-150919
4-7/8" [124 MM]
INTERIOR
STEEL STUD (NON-LOAD-BEARING)
GYPSUM PANELS:
STEEL STUDS:
INSULATION:
GYPSUM PANELS:
ASSEMBLY REQUIREMENTS:
DESIGN NO. UL U419 - 1 HR FIRE RATING ASSEMBLY - FOR PATCHING ONLY
ONE LAYER 5/8" [15.9 MM] GYPSUM PANEL TYPE X
3-5/8" [92 MM] STEEL STUDS, 16" [406 MM] O.C.
3" [76 MM] FIBERGLASS INSULATION
ONE LAYER 5/8" [15.9 MM] GYPSUM PANEL TYPE X
/8
16" 16" 16"
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
/4
/2
:0
:1
P M
UL DESIGN
ASSEMBLY &
PARTITION WALL
MD
DW
JO
08/05/2026
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
E N
O V
A T
E
R D
F L
O O
R
LA
B #2
-B
-0
/L
N V
N V
C C
A
N N
A N
D A
LE
C
A M
P U
S
IS
S
U E
D F
O R
B
ID
S E
T
L
IT
T
LE
R
IV
E R
T U
R N
P
IK
E
A N
N A
N D
A
LE
V
A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
G-005
239 SF
CONF. RM.
111 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
138 SF
FACULTY
OFFICE
126 SF
VESTIBULE
138 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
239 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
310 206 SF
STAIR
301B
122 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
206 SF
STAIR
301A
122 SF
FACULTY
OFFICE
616 SF
CORRIDOR
300A
239 SF
CONF. RM.
111 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
138 SF
FACULTY
OFFICE
126 SF
VESTIBULE
138 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
239 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
310 206 SF
STAIR
301B
122 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
206 SF
STAIR
301A
122 SF
FACULTY
OFFICE
616 SF
CORRIDOR
300A
S
S
J
J
REMOVE EXISTING FLOOR FINISH
CARPET AND WALL BASE
DEMOLISH THE EXISTING PARTITION
WALL, FULL HEIGHT. REUSE WALL
MOUNTED PROJECTOR SCREENS
E
E 6' - 2" 11' - 0" 10' - 0" 10' - 6" 12' - 0"
D
D
C
C
B1
B1
B
B
A
A
1 1
0'
9'
1'
8'
1'
9'
0'
CUT EXISTING GYP BOARD AT EACH
NEW POWER OUTLET LOCATION TO
ROUTE THE WIRE. COORDINATE
LOCATION WITH ELECTRICAL
DRAWING - TYP.
DEMOLISH EXISTING FIXED
CABINETRY IN ITS ENTIRETY
GROUP
STUDY
787 SF
ORAL
COMMUNICATION
CENTER
544 SF
SELECTIVE EXISTING GYP BOARD
DEMO AT EACH PROJECTION
SCREEN TO INSTALL BLOCKING.
SPECIFIC LOCATION TO BE
COORDINATED WITH OWNER.
REMOVE EXISTING DOOR/
FRAMES & HARDWARS,
COORDINATE W/ NEW
WORK.
REMOVE EXISTING DOOR/
FRAMES & HARDWARS,
COORDINATE W/ NEW
WORK.
SELECTIVE EXISTING GYP BOARD
DEMO AT NEW WHITE BOARD
LOCATION TO INSTALL BLOCKING.
SPECIFIC LOCATION TO BE
COORDINATED WITH OWNER.
DEMOLITION PLAN GENERAL NOTES
1. VISIT SITE AND VERIFY EXISTING CONDITIONS PRIOR TO BID SUBMISSION.
DISCREPANCIES BETWEEN CONSTRUCTION INDICATED ON DRAWINGS AND
ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO ARCHITECT’S ATTENTION
IMMEDIATELY IN WRITING.
2. DEMOLISHED ITEMS NOT INDICATED TO BE “DELIVERED TO OWNER” OR “TO BE
RELOCATED” SHALL BE REMOVED FROM SITE AS SOON AS POSSIBLE UNLESS
THEY ARE TO BE USED FOR REQUIRED PATCHING AND INFILLING OF EXISTING
CONSTRUCTION THAT IS TO REMAIN. NO OTHER DEMOLISHED ITEMS SHALL BE
STORED ON SITE.
3. DEMOLISHED ITEMS NOTED AS “DELIVER TO OWNER” OR “TO BE RELOCATED”
SHALL BE REMOVED OR DISASSEMBLED IN SUCH A MANNER THAT WILL NOT
DAMAGE THE ITEM AND PREVENT IT FROM BEING RELOCATED. REPAIR OR
REPLACE SUCH ITEMS, IF DAMAGED. NOTIFY OWNER’S REPRESENTATIVE
IMMEDIATELY IF DAMAGE HAS OCCURRED, AND SUBMIT A REPAIR SOLUTION TO
ARCHITECT FOR REVIEW.
4. TEMPORARILY STORE ITEMS INDICATED AS “DELIVER TO THE OWNER” IN ONSITE
LOCATION, DESIGNATED BY THE OWNER. OWNER SHALL MOVE ITEM(S), AS
NECESSARY, TO NOT HINDER OR DELAY PERFORMANCE OF WORK IN AREA.
5. TEMPORARILY STORE ITEMS INDICATED AS “TO BE RELOCATED” IN LOCATION
ONSITE AND PROTECT ITEMS FROM DAMAGE PRIOR TO INSTALLATION IN NEW
LOCATION.
6. ITEMS INDICATED “TO REMAIN” THAT ARE DAMAGED DURING THE PERFORMANCE
OF THE DEMOLITION WORK. SUCH DAMAGE SHALL BE REPORTED TO OWNER’S
REPRESENTATIVE IMMEDIATELY, AND SUBMIT A REPAIR SOLUTION TO ARCHITECT
FOR REVIEW.
7. COORDINATE DEMOLITION WORK WITH NEW CONSTRUCTION WORK IN EACH
AREA OF DEMOLITION. EXISTING CONSTRUCTION IN AREAS ADJACENT TO
DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO MATCH ORIGINAL
EXISTING CONDITION AS REQUIRED TO PROVIDE FOR NEW CONSTRUCTION
WORK IN AREA OF DEMOLITION.
8. ITEMS INDICATED TO BE REMOVED BY OWNER SHALL BE COMPLETED PRIOR TO
COMMENCEMENT OF WORK.
9. AT LOCATIONS WHERE A PORTION OF EXISTING CONSTRUCTION IS TO BE
REMOVED AND PREPARED FOR NEW INFILL CONSTRUCTION, OR AN OPENING IN A
WALL, ROOF, OR FLOOR IS CREATED BY DEMOLITION WORK, CONSTRUCT INFILL
WITH SAME MATERIALS AND METHOD OF CONSTRUCTION AS EXISTING ADJACENT
CONSTRUCTION, UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL DRAWINGS
FOR INFILL CONSTRUCTION. INFILL CONSTRUCTION SHALL SMOOTHLY BUTT
ADJACENT SURFACES AND MATCH THE FINISH, U.N.O.
10. AT LOCATIONS WHERE AN ITEM IS TO BE REMOVED FROM A SURFACE THAT IS TO
REMAIN, PATCH AND REPAIR EXISTING SURFACE TO MATCH EXISTING ADJACENT
SURFACE, UNLESS INDICATED OTHERWISE.
11. EXISTING ITEMS ANCHORED TO CONSTRUCTION THAT IS INDICATED TO BE
DEMOLISHED SHALL BE CONSIDERED A PART OF DEMOLISHED CONSTRUCTION
AND SHALL BE DEMOLISHED WITH THE INDICATED CONSTRUCTION, UNLESS
NOTED OTHERWISE.
12. IN CONDITIONS WHERE A WALL OR FLOOR FINISH IS DEMOLISHED CREATING A
DISSIMILAR ELEVATION IN ADJACENT FLOOR FINISHES, INSTALL AN APPROVED
LEVELING MATERIAL TO BRING LOWER FLOOR FINISH ELEVATION UP TO AN
ELEVATION FLUSH WITH ADJACENT FLOOR.
13. CONSTRUCT TEMPORARY DUST PARTITIONS TO CONTAIN DEMOLITION WORK
AND PREVENT CONSTRUCTION DUST FROM ENTERING ADJACENT EXISTING
CONSTRUCTION. SUBMIT LOCATIONS OF THESE PARTITIONS FOR APPROVAL BY
OWNER’S REPRESENTATIVE. PARTITION LOCATIONS SHALL NOT IMPEDE OR
HINDER EMERGENCY EGRESS FROM BUILDING. REFER TO SPECIFICATIONS FOR
CONSTRUCTION OF DUST PARTITIONS.
14. RETAIN DEMOLISHED MATERIALS AS NEEDED FOR INFILLING OPENINGS IN
EXISTING CONSTRUCTION SO THAT FINISH MATERIALS WILL PROPERLY ALIGN
WITH EXISTING AND MATCH THE EXISTING FINISH. IF DEMOLISHED MATERIALS
ARE NOT SALVAGEABLE, NOTIFY OWNER’S REPRESENTATIVE, SO THAT
ALTERNATE SOLUTIONS MAY BE DETERMINED.
15. IF EXISTING CONSTRUCTION IS REVEALED NOT CONSTRUCTED OR FINISHED IN A
MANNER THAT MATCHES ADJACENT SURFACES, PATCH AREA AS NECESSARY
WITH APPROPRIATE MATERIALS AND METHODS OF CONSTRUCTION TO MATCH
EXISTING ADJACENT FINISH, OR PREPARE SURFACE FOR INSTALLATION OF NEW
FINISH. CONTACT OWNER’S REPRESENTATIVE AS SOON AS POSSIBLE SO THAT
CONCEALED CONSTRUCTION MAY BE IDENTIFIED AND SCOPE OF POSSIBLE
ADDITIONAL WORK DETERMINED.
16. WHEN EXISTING SURFACE IS INDICATED TO BE “PATCHED AND REPAIRED” OR
“PREPARED” TO RECEIVE NEW FINISH MATERIAL, PROVIDE A CONSTRUCTION
SURFACE THAT IS CAPABLE OF RECEIVING NEW FINISH MATERIAL.
17. WHEN THE TERM ‘ENTIRETY’ IS DIRECTED TO A SPECIFIC ITEM OR ASSEMBLY,
DEMOLISH AND REMOVE IDENTIFIED ITEM AND ASSOCIATED CONSTRUCTION
PERTINENT TO THE ITEM, INCLUDING, BUT NOT LIMITED TO UNDERGROUND AND
CONCEALED CONSTRUCTION, SUCH AS FOOTINGS AND FOUNDATIONS, SEWER,
PLUMBING, AND ELECTRICAL WORK. THIS DEMOLITION WORK SHALL BE
COORDINATED WITH THE CIVIL, STRUCTURAL, PLUMBING, MECHANICAL,
ELECTRICAL, AND TECHNOLOGY DRAWINGS.
18. CONTRACTOR TO PROVIDE HOURLY FIRE WATCH FOR ANY FIRE ALARM OR
SPRINKLER IMPAIRMENTS 1-HOUR OR LONGER. FIRE WATCH TO INCLUDE
WALKING THE ENTIRE BUILDING HOURS. FIRE WATCH TO BE DOCUMENTED ON A
FIRE WATCH LOG. PROVIDE THE FIRE WATCH LOG TO THE PROJECT MANAGER.
E
E
D
D
C
C
B1
B1
B
B
A
A
REMOVE CEILING TILES
AND GRIDS AFFECTED
BY THE DEMOLITION
EX. ACP
10' - 0"
COMPUTER
CLASS RM
MOVE EXISTING CEILING
PROJECTOR TO THE NEW
LOCATION - COORDINATE
WITH THE OWNER FOR
THE EXACT LOCATION
MOVE EXISTING CEILING
PROJECTOR TO THE NEW
LOCATION - COORDINATE
WITH THE OWNER FOR
THE EXACT LOCATION
EXISTING SPRINKLER
HEAD TO REMINA - TYP.
LEGEND - DEMOLITION PLAN
EXISTING WALL TO REMAIN
EXISTING DOOR AND FRAME TO DEMOLISH
EXISTING WALL TO DEMOLISH
EXISTING DOOR TO NOT IN THE SCOPE
WORK NOT INCLUDED IN THE SCOPE
EXISTING CEILING PANEL TO DEMOLISH
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
/4
/2
:0
:1
P M
THIRD FLOOR
DEMO WORK
PLAN
MD
MD
JO
08/05/2026
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
E N
O V
A T
E
R D
F L
O O
R
LA
B #2
-B
-0
/L
N V
N V
C C
A
N N
A N
D A
LE
C
A M
P U
S
IS
S
U E
D F
O R
B
ID
S E
T
L
IT
T
LE
R
IV
E R
T U
R N
P
IK
E
A N
N A
N D
A
LE
V
A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
A-1110' 4' 8'2'
SCALE: 1/4" = 1' - 0"
NORTH
Scale: 1/8" = 1'-0"1 THIRD FLOOR - DEMO WORK PLAN
NO. DESCRIPTION DATE
Scale: 1/8" = 1'-0"2 3RD FLOOR - DEMO WORK RCP
111 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
138 SF
FACULTY
OFFICE
126 SF
VESTIBULE
138 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
239 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
310 206 SF
STAIR
301B
122 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
206 SF
STAIR
301A
122 SF
FACULTY
OFFICE
616 SF
CORRIDOR
300A
S
S
239 SF
CONF. RM.
111 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
138 SF
FACULTY
OFFICE
126 SF
VESTIBULE
138 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
239 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
310 206 SF
STAIR
301B
122 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
206 SF
STAIR
301A
122 SF
FACULTY
OFFICE
616 SF
CORRIDOR
300A
REPLACE CEILING TILES AND
GRIDS AFFECTED BY THE
PARTITION WALL DEMOLITION -
COLOR & MATERIAL TO MATCH
EXISTING CEILING
E
E
D
D
C
C
B1
B1
B
B
A
A
EX. ACP
10' - 0"
RELOCATE EXISTING CEILING
MOUNTED POWER OUTLET AND
PROJECTOR. COORDINATE W/
OWNER FOR EXACT LOCATION
RELOCATE EXISTING CEILING
MOUNTED POWER OUTLET AND
PROJECTOR. COORDINATE W/
OWNER FOR EXACT LOCATION
PROVIDE CEILING MOUTED
RECEPTACLE - SEE ELECTRICAL
DWGS. COORDINATE W/ OWNER
FOR EXACT LOCATION - TYP
PROVIDE CEILING MOUTED
RECEPTACLE - SEE ELECTRICAL
DWGS. COORDINATE W/ OWNER
FOR EXACT LOCATION - TYP
RECESSED LIGHT
FIXTURE
PENDANT FIXTURE
SUPPLY DIFFUSER
RETURN DIFFUSER
EXIT SIGN
S SPEAKER
A FIRE ALARM
HEAT DETECTOR
SMOKE DETECTOR
LINEAR SLOT DIFFUSER
EXISTING SPRINKLER
HEAD
EMERGENCY LIGHT
RECESSED LIGHT
FIXTURE
CEILING LEGEND
EXISTING SUSPENDED
ACOUSTICAL PANEL
CEILING TO REMAIN
CEILING MOUNTED PROJECTOR
CEILING OR WALL MOUNTED
MOTORIZED PROJECTION
SCREEN
SURFACE MOUNTED
LIGHT FIXTURE
STRIP FIXTURE
TRACK LIGHTING
HORN/STROBE DEVICE
EXHAUST AIR DEVICE
OCCUPANCY SENSOR
CELING MOUNTED
POWER OUTLET -
DUPLEX
s SPEAKER/STROBE
STROBE
NOTE: FOR MEPFP DEVICES, REFER TO MEPFP DRAWINGS.
APC-X
8' - 0"
CEILING TYPE
CEILING HEIGHT
NEW SUSPENDED ACOUSTICAL
PANEL CEILING
CELING MOUNTED
POWER OUTLET -
QUADRUPLEX
GENERAL NOTES - NEW WORK PLAN
1. DIMENSIONS ARE SHOWN AS FOLLOWS, U.N.O.
A. ALL DIMENSIONS ARE SHOWN TO THE FINISHED FACE, U.N.O.
B. DIMENSIONS NOTED AS "CLEAR" (CLR.) ARE TO THE FACE OF FINISHED
SURFACE AND TAKE PRECEDENT OVER ALL OTHER DIMENSIONS.
C. DISCREPANCIES IN DIMENSIONS SHALL BE IMMEDIATELY BROUGHT TO THE
ATTENTION OF THE ARCHITECT, WHO WILL ISSUE WRITTEN CLARIFICATION.
2. FINAL WALL PREP REQUIREMENTS ARE BASED ON OWNER SELECTION FINISH
AND WITH THE SPECIFICATIONS.
3. BACK-TO-BACK OUTLETS CANNOT OCCUPY SAME STUD CAVITY SPACE. IN
ACOUSTICALLY TREATED WALLS, PROVIDE ACOUSTIC PUTTY PADS AROUND
OUTLET BOXES.
4. REFER TO G-003 LIFE SAFETY & CODE PLANS ANALYSIS AND LOCATION OF
FIRE RATED WALLS .
5. REFER TO SHEET G-004 FOR FIRE-RATED UL WALL PENETRATIONS AND
ASSEMBLY NUMBERS.
E
E
D
D
C
C
B1
B1
B
B
A
A
USE TYPE X, FIRE RATED
GYP BOARD TO PATCH &
FINISH ALL WALL
PENETRATIONS AND GAP
W/ FIRE SEAL INCLUDING
TOP AND BOTTOM OF
THE WALL JOINTS.
6' - 2" 11' - 0" 10' - 0" 10' - 6" 12' - 0"
0'
9'
1'
8'
1'
9'
0'
COMPUTER
CLASS RM
INSTALL NEW DOOR/ FRAME W/
ELECTRONIC DOOR ACCESS
(EDA). SEE A-201 FOR DOOR
SCHEDULE AND SPEC 08 71 00
INSTALL NEW DOOR/ FRAME W/
ELECTRONIC DOOR ACCESS
(EDA). SEE A-201 FOR DOOR
SCHEDULE AND SPEC 08 71 00
PROVIDE BLOCKING AS
REQUIRED TO RELOCATE
EXISTING WALL
MOUNTED PROJECTOR.
EXACT LOCATION TO BE
COORDINATED WITH
OWNER.
PROVIDE WHIEBOARD - SIZE
TO BE SELECTED BY OWNER.
PROVIDE BLOCKING AS
REQUIRED.
PROVIDE BLOCKING AS
REQUIRED TO RELOCATE
EXISTING WALL
MOUNTED PROJECTOR.
EXACT LOCATION TO BE
COORDINATED WITH
OWNER.
USE SIMILAR GYP BOARD
AS THE EXISTING WALL
TO PATCH & FINISH ALL
WALL PENETRATIONS
AND GAP W/ ACOUSTICAL
SEAL INCLUDING TOP
AND BOTTOM OF THE
WALL JOINTS.
311B
311A
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
/4
/2
:0
:1
P M
THIRD FLOOR
NEW WORK PLAN
MD
MD
JO
08/05/2026
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
E N
O V
A T
E
R D
F L
O O
R
LA
B #2
-B
-0
/L
N V
N V
C C
A
N N
A N
D A
LE
C
A M
P U
S
IS
S
U E
D F
O R
B
ID
S E
T
L
IT
T
LE
R
IV
E R
T U
R N
P
IK
E
A N
N A
N D
A
LE
V
A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
A-112Scale: 1/8" = 1'-0"2 3RD FLOOR - NEW WORK RCP
0' 4' 8'2'
SCALE: 1/4" = 1' - 0"
NORTH
NO. DESCRIPTION DATE
Scale: 1/8" = 1'-0"1 THIRD FLOOR - NEW WORK PLAN
111 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
138 SF
FACULTY
OFFICE
126 SF
VESTIBULE
138 SF
FACULTY
OFFICE
106 SF
FACULTY
OFFICE
111 SF
FACULTY
OFFICE
239 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
310 206 SF
STAIR
301B
122 SF
FACULTY
OFFICE
122 SF
FACULTY
OFFICE
206 SF
STAIR
301A
122 SF
FACULTY
OFFICE
616 SF
CORRIDOR
300A
E
E
D
D
C
C
B1
B1
B
B
A
A
6' - 2" 11' - 0" 10' - 0" 10' - 6" 12' - 0"
0'
9'
1'
8'
1'
9'
0'
PNT-1
VCB
CPT
COMPUTER
CLASS RM
SH-1 TA-1
SH-1
CH-1 (TYP)
(TYP)
N
H E
IG
H
T
WIDTH
* 6" 6"
D O
O R
H E
IG
H
T
WIDTH
DOOR
5/16" THICK CLEAR,
45 MINUTES FIRE RATED,
SAFETY RATED GLASS
PT-X
RB-X
CPT-X
NOTES: 22
ROOM NAME
INTERIOR FINISH LEGEND
ROOM FINISH TAG
WALL FINISH
BASE FINISH
FLOOR FINISH
NOTES
(IF APPLICABLE)
ACCENT WALL MATERIAL / COLOR
XXX
FINISH AND FURNITURE PLAN GENERAL NOTES
1. FINISH INDICATES ENTIRE SURFACE, U.N.O.
2. SEE FINISH SCHEDULE FOR FINISH DETAILS.
3. ALL FURNITURE (CHAIRS & TABLES) ARE OWNER FURNISHER / OWNER
INSTALLED
1/2"1/2"
2"
VARIES
SEALANT ALL AROUND,
BOTH SIDES
HOLLOW METAL FRAME
PARTITION AS SCHEDULED
DOOR AS SCHEDULED
/2
/2
2"
V A
R
IE
S
PARTITION AS SCHEDULED
HOLLOW METAL FRAME
JAMB ANCHOR CLIP
DOOR AS SCHEDULED
SEALANT ALL AROUND,
BOTH SIDES
DOOR
CONCRETE SLAB
MAT-1
EXISTING LVT-1
SCHLUTER SCHIENE,
BRUSHED STAINLESS STEEL
V2A, 3MM (1/8")
M A
X
/2
HOLLOW METAL DOOR & GLAZING GENERAL NOTES:
1. DOOR ASSEMBLY TO BE A 45-MINUTE FIRE-PROTECTION-RATED, MINIMUM 18-
GAUGE HOLLOW METAL DOOR INSTALLED IN A 1-HOUR FIRE-RATED CORRIDOR
WALL ASSEMBLY. DOOR AND FRAME TO BEAR COMPLIANT UL/WHI IDENTIFICATION
LABELS PER VCC TABLE 716.1(2).
2. PROVIDE 45-MINUTE FIRE-PROTECTION AND IMPACT SAFETY-RATED GLAZING (5/16"
NOMINAL THICKNESS, 6" X 36" VISIBLE AREA) FIELD-INSTALLED IN THE FACTORY-
PREPARED CUTOUT.
3. GLAZING TO BE ETCHED WITH PERMANENT CERTIFICATION MARKINGS COMPLYING
WITH VCC CHAPTERS 7 & 24, INCLUDING "D-H-45" (VCC TABLE 716.1(1)) AND CPSC 16
CFR 1201 CAT. II / ANSI Z97.1 FOR HAZARDOUS DOOR LOCATIONS.
4. GLAZING ENCLOSURE KIT MUST BE A LISTED 18-GAUGE STEEL, SELF-CORING/BOLT-
THROUGH VISION FRAME KIT IN ACCORDANCE WITH NFPA 80 WITH APPROVED
INTUMESCENT GLAZING TAPE.
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
/4
/2
:0
:1
P M
FINISH/
FURNITURE PLAN
& DOOR
SCHEDULE
MD
MD
JO
08/05/2026
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
E N
O V
A T
E
R D
F L
O O
R
LA
B #2
-B
-0
/L
N V
N V
C C
A
N N
A N
D A
LE
C
A M
P U
S
IS
S
U E
D F
O R
B
ID
S E
T
L
IT
T
LE
R
IV
E R
T U
R N
P
IK
E
A N
N A
N D
A
LE
V
A
Dewberry Engineering Inc.
8401 ARLINGTON BOULEVARD
FAIRFAX, VA 22031 -4666
703.849.0100
A-201Scale: 1/8" = 1'-0"1 THIRD FLOOR - NEW FINISH & FURNITURE PLAN
NO. DESCRIPTION DATE
DOOR SCHEDULE
D O
O R
N U
M B
E
R DOOR FRAME DETAILS
F
IR
E L
A B
E L
H A
R D
W A
R E
R E
M A
R K
S
D O
O R
N U
M B
E R
LE
A
F Q
T Y
SIZE
T Y
P E
M A
T E
R
IA
L
G
LA
Z
IN
G
T Y
P E
M A
T E
R
IA
L
G
LA
Z
IN
G
SIDELIGHT
WIDTH
TRANSOM
HEIGHT HEAD JAMB SILLWIDTH
WIDTH
(IF
UNEVEN) HEIGHT THICKNESS
311A 1 3' - 0" 7' - 0" 1 3/4" N HM 01 HM H-1 J-1 S-1 45 minutes 01 311A 311B 1 3' - 0" 7' - 0" 1 3/4" N HM 01 HM H-1 J-1 S-1 45 minutes 01 311B
Scale: 1/4" = 1'-0"3 DOOR PANEL & FRAME TYPES
COMUPTER CLASS ROOM - 311 - FINISH SCHEDULE
MATERIAL TYPE FINISH DESCRIPTIONS
BASE FINISHES
VINYLE BASES VCB JOHNSONITE - JOHNSONITE - 38 PEWTER CG
CEILING FINISHES
ACOUSTIC CEILING TILE (ACT) ACT-1 MATCH EXISTING CEILING TILES SIZE, COLOR AND TEXTURE
FLOOR FINISHES
CARPET TILE (CPT) CPT-1 J&J FLOORING JOURNEY - 3352 GREEN LEAD - 18" x 32" MODULAR TILE
WALL FINISHES
PAINT (PNT) PNT-1 SHERWIN WILLIAMS - SW 7035 - AESTHETIC WHITE EGG SHELL FINISH
PAINT (PNT) PNT-2 (ACCENT WALL) SHERWIN WILLIAMS - SW 6460 - KALE GREEN EGGE SHELL FINISH PAINT (PNT) PNT-3 (DOOR FRAME PAINTS) SHERWIN WILLIAMS - SW 9162 AFRICAN GRAY - SEMI GLSOSS FINISH
FURNITURE SCHEDULE & RESPONSIBILITY MATRIX
FURNITURE
TAG DESCRIPTION RESPONSIBILITY
CH-1 CHAIR OWNER FURNISHED - OWNER INSTALLED
SH-1 SHELF OWNER FURNISHED - OWNER INSTALLED
TA-1 TABLE OWNER FURNISHED - OWNER INSTALLED
Scale: 1 1/2" = 1'-0"4 H-1 DOOR HEAD
Scale: 1 1/2" = 1'-0"5 J-1 DOOR JAMB
Scale: 6" = 1'-0"6 S-1 - CARPET TO VCT
HARDWARE NOTE: THE HARDWARE MUST PROVIDE FREE MECHANICAL EGRESS AT ALL TIMES.
A101
SIM
A
FIRST FLOOR
100' - 0"
A101
SIM
Scale:1 View Name 1/8" = 1'-0"
CALLOUT
BUILDING/WALL
SECTION
ROOM TAG
REVISION TAG
KEYNOTE TAG
(PER SHEET NUMBERS)
AREA TO BE
ENLARGED SHEET REF.
PLAN / DETAIL
REF.
SECTION REF.
SHEET REF.
LEVEL LINE
ROOM NUMBER
VIEW NAME
VIEW SCALE
VIEW DESIGNATION VIEW TITLE
LEVEL NAME
LEVEL
ELEVATION
GRID LINE
NORTH INDICATOR
GRID NUMBER OR
LETTER
INDICATES
PLAN NORTH
INDICATES
TRUE NORTH
SPOT ELEVATION
SYMBOL
?1
REVISION NUMBER
REVISION CLOUD
POINT OF
CONNECTION
1' - 0"ELEVATION AT
POINT INDICATED
POINT OF
DISCONNECTION
STANDARD DETAILING SYMBOLS
EXISTING
DEMOLITION
NEW
FUTURE
BACKGROUND
HIDDEN/UNDER
OBSTRUCTION
Space Name
SYMBOL DESCRIPTION
LINETYPES
R
D
FLEXIBLE CONNECTOR
SUPPLY SQUARE CEILING DIFFUSER
(4-WAY DISCHARGE UNLESS INDICATED OTHERWISE)
RETURN SQUARE CEILING DIFFUSER
RETURN DUCT VIEW INTO DUCT
DUCTWORK TO DROP IN ELEVATION
DUCTWORK TO RISE IN ELEVATION
RETURN DUCT VIEW HEEL OF ELBOW
SUPPLY DUCT VIEW HEEL OF ELBOW
FLEXIBLE DUCTWORK
SYMBOL
SUPPLY DUCT VIEW INTO DUCT
DUCTWORK & SIZE
EXTRACTOR WITH ADJUSTABLE OPERATOR
SPLITTER DAMPER
TURNING VANES AT MITERED ELBOW
AUTOMATIC DAMPER (MOTORIZED)
FIRE & SMOKE DAMPER (MOTORIZED)
DESCRIPTION
AUTOMATIC FIRE DAMPER (MOTORIZED)
MANUAL DAMPER
LINEAR DIFFUSER WITH PLENUM ON TOP
FIRE DAMPER FD
AD
AF
MD
SMOKE DAMPER (MOTORIZED)
BACKDRAFT DAMPER
FS
SD
BD
DAMPER
EXHAUST DUCT VIEW INTO DUCT
EXHAUST DUCT VIEW HEEL OF ELBOW
EXHAUST SQUARE CEILING DIFFUSER
PLENUM SLOT DIFFUSER
SYMBOL DESCRIPTION
PRESSURE RELIEF VALVE
AUTOMATIC AIR VENT
PIPE ELBOW DOWN
DIRECTION OF FLOW
PIPE ELBOW UP
GAUGE COCK
2-WAY AUTOMATIC CONTROL VALVE (MOTORIZED)
HOSE END DRAIN VALVE WITH CAP
BALANCING VALVE
THERMOMETER AND WELL
PIPE TOP TAKE OFF
PIPE BOTTOM TAKE OFF
UNION
CHECK VALVE (DIRECTION OF FLOW INDICATED)
PIPE CONTINUES
PIPE SLEEVE
PIPE CAP OR PLUG
FLANGE
PRESSURE & TEMPERATURE TEST PLUG
PRESSURE GAUGE
STOP VALVE
BACKFLOW PREVENTER
3-WAY AUTOMATIC CONTROL VALVE (MOTORIZED)
VENTURI FLOW TUBE
Y-TYPE STRAINER
BASKET TYPE STRAINER
FLEXIBLE CONNECTION
SOLENOID VALVE
PRESSURE REGULATING VALVE
REDUCER (CONCENTRIC)
REDUCER (ECCENTRIC)
PRESSURE REDUCING VALVE
S
WATER METER
SUPPLY ROUND CEILING DIFFUSER
HVAC SYMBOLS MECHANICAL PIPING SYMBOLS
T
H
CD
CM
ND
THERMOSTAT
HUMIDISTAT
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
NITROGEN DIOXIDE SENSOR
SIDEWALL SUPPLY REGISTER OR GRILLE
SIDEWALL RETURN/EXHAUST REGISTER OR GRILLE
THE FOLLOWING SCHEDULE SHALL BE USED BY THE
CONTRACTOR FOR ROUND TO FLAT OVAL DUCTWORK SIZE
EQUIVALENTS UNLESS NOTED OTHERWISE.
ROUND DIAMETER (IN) EQUIVALENT FLAT OVAL (IN - H x W)
3 x 11, 4 x 9, 5 x 8
4 x 15, 5 x 12, 6 x 11
6 x 15, 7 x 13, 8 x 11, 9 x 12
7 x 20, 8 x 17, 9 x 15, 10 x 13
9 x 20, 10 x 18, 11 x 17, 12 x 15
FLAT OVAL DUCTWORK SCHEDULE
FLEXIBLE AND RIGID ROUND BRANCH DUCTWORK FOR DIFFUSER TAKE-OFFS
OR RUNOUTS SHALL BE SIZED IN ACCORDANCE WITH THE FOLLOWING
SCHEDULE UNLESS NOTED OTHERWISE ON FLOOR PLANS.
WHERE THE DEPTH OF THE DUCTWORK WILL NOT PERMIT A ROUND SPIN
COLLAR FITTING, PROVIDE AN EQUIVALENT FLAT OVAL CONNECTION WITH
MANUAL VOLUME DAMPER AND AN OVAL TO ROUND TRANSITION FOR EACH
TAP. SEE FLAT OVAL DUCTWORK SCHEDULE FOR EQUIVALENT FLAT OVAL
SIZES. THIS SCHEDULE DOES NOT APPLY FOR DUCTWORK SERVING
PERIMETER SLOT DIFFUSERS SD-A AND SD-B. REFER TO FLOOR PLANS FOR
ADDITIONAL INFORMATION.
0 - 150
151 - 250
251 - 350
351 - 550
551 - 700
AIRFLOW (CFM) ROUND DIAMETER (IN)
ROUND BRANCH DUCTWORK SCHEDULE
12x12
DUCT ACCESS DOOR (ON BOTTOM)
DUCT ACCESS DOOR (ON SIDE)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
REFER TO RISER AND SCHEMATIC DIAGRAMS FOR PIPE SIZES, DUCT
SIZES, AND AIRFLOWS NOT INDICATED ON THE FLOOR PLANS.
THROUGH-PENETRATION FIRESTOP MATERIAL SHALL BE TESTED,
MANUFACTURED AND INSTALLED IN ACCORDANCE WITH UL 1479.
IN ACCORDANCE WITH MECHANICAL CODE, ALL PRODUCTS,
COMPONENTS, MATERIALS AND COMPOSITE MATERIALS WITHIN
SUPPLY, RETURN, EXHAUST, RELIEF AND VENTILATION AIR PLENUMS
SHALL BE NON-COMBUSTIBLE OR SHALL BE LISTED/CLASSIFIED AND
LABELED AS HAVING A FLAME SPREAD INDEX OF NOT MORE THAN 25
AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.
ALL DUCT DIMENSIONS SHOWN ARE INSIDE DIMENSIONS. REFER TO
SPECIFICATIONS FOR INTERNALLY INSULATED/LINED DUCTWORK
REQUIREMENTS.
ALL DUCTWORK AND PIPING SHALL BE TIGHT TO BOTTOM OF
STRUCTURE UNLESS OTHERWISE INDICATED.
REFER TO THE ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATION
AND SIZE OF ALL WALL OR FLOOR OPENINGS.
VALVES, JUNCTION BOXES, CLEAN-OUTS, FUTURE CONNECTIONS AND
OTHER ITEMS THAT WILL REQUIRE ACCESS PANELS IN DRYWALL
CEILINGS SHALL NOT BE LOCATED WITHIN THE MAIN LOBBY AND
ELEVATOR LOBBIES. DUCTWORK, PIPING, WIRING AND ETC. SHALL NOT
BLOCK ACCESS TO JUNCTION BOXES, VALVES AND CLEAN-OUTS.
REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION OF ALL VISIBLE
CEILING AND WALL MOUNTED DEVICES.
THE EXISTING MECHANICAL, ELECTRICAL, AND PLUMBING SYSTEMS
AND ASSOCIATED MATERIALS OF CONSTRUCTION HAVE BEEN
PREVIOUSLY APPROVED BY THE MECHANICAL, ELECTRICAL, PLUMBING
DIVISIONS AND FIRE MARSHAL'S OFFICE OF THE LOCAL CODE
AUTHORITIES HAVING JURISDICTION. EXISTING SPECIFICATIONS AND
MATERIALS OF CONSTRUCTION APPLY TO ALL WORK SHOWN ON THE
DRAWINGS UNLESS OTHERWISE NOTED.
RETURN AIR SYSTEM: THE RETURN AIR SYSTEM CONSISTS OF A
CONTINUOUS PLENUM COMMON TO ALL AREAS WITHIN THE LEASE
SPACE. AIR IS RETURNED FROM THE SPACE INTO THE PLENUM
THROUGH RETURN AIR GRILLES AND HEAT EXTRACT LIGHT FIXTURES
DESIGNED FOR RETURN AIR APPLICATION.
RETURN AIR SYSTEM: THE RETURN AIR SYSTEM CONSISTS OF A
DUCTED SYSTEM TO ALL AREAS WITHIN THE LEASE SPACE. AIR IS
RETURNED FROM THE SPACE INTO THE DUCTWORK THROUGH RETURN
AIR GRILLES.
OUTDOOR AIR SYSTEM: OUTDOOR AIR IS PROVIDED TO EACH
FLOOR/SYSTEM THROUGH A SUPPLY TAP LOCATED WITHIN THE AIR
HANDLING UNIT ROOM. FROM THIS POINT, THE OUTDOOR AIR IS
EQUITABLY DISTRIBUTED THROUGHOUT THE SPACE THROUGH THE
SUPPLY DUCTWORK SYSTEM. REFER TO DRAWINGS FOR VENTILATION
CALCULATIONS AND OUTDOOR AIR PROVIDED FOR EACH SYSTEM.
FLOW METER
ABBREVIATIONS GENERAL NOTES
FLOW SWITCHFS
TEMPERATURE SENSORTS
MECHANICAL SYSTEMS SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE FOLLOWING CODES.
2021 VIRGINIA MECHANICAL CODE
2021 VIRGINIA CONSTRUCTION CODE
2021 VIRGINIA ENERGY CONSERVATION CODE
2021 VIRGINIA FUEL GAS CODE
2021 VIRGINIA STATEWIDE FIRE PREVENTION CODE
2021 VIRGINIA FUEL GAS CODE
CODES
CARBON MONOXIDE AND NITROGEN DIOXIDE SENSORCN
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
8/ 5/
:1
0:
P M
MECHANICAL
SYMBOLS,
LEGEND, NOTES
JS/MN
MD
08/05/26
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
EN
O
VA
TE
R
D F
LO
O
R
LA
B
0- B4
0-
8/
L2 4N
V5
N
VC
C
AN
N
AN
D
AL
E
C
AM
PU
S
IS
SU
ED
F
O R
B
ID
S
ET
L
IT
TL
E
R
IV
ER
T
U R
N
PI
KE
AN
N
AN
D
AL
E, V
A
M-001
DRAWING LIST - MECHANICAL
M-001 MECHANICAL SYMBOLS, LEGEND, NOTES
M-111 MECHANICAL THIRD FLOOR NEW WORK PLAN
TOTAL: 2
AC AIR CONDITIONING
AD ACCESS DOOR
ADJ ADJUSTABLE
AF AIRFLOW
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AO ANALOG OUTPUT
ARCH ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATING, AND AIR-CONDITIONING
ENGINEERS
ATC AUTOMATIC TEMPERATURE CONTROL
ATV ATMOSPHERIC VENT
B BOILER
BAS BUILDING AUTOMATION SYSTEM
BBD BOILER BLOWDOWN
BHP BRAKE HORSEPOWER
BI BINARY INPUT
BMS BUILDING MANAGEMENT SYSTEM
BO BINARY OUTPUT
BT BUFFER TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CD CONDENSATE DRAIN
CF CHEMICAL FEEDER
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWP CHILLED WATER PUMP
CO2, CD CARBON DIOXIDE
CO, CM CARBON MONOXIDE
CONT CONTROLS, CONTINUED
CRU CONDENSATE RETURN UNIT
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
Cv VALVE COEFFICIENT
CWP CONDENSER WATER PUMP
DB DRY BULB
DBL DOUBLE
DEG DEGREE
DI DIGITAL INPUT
DIA DIAMETER
DMSS DUCTLESS MINI-SPLIT SYSTEM
DN DOWN
DO DIGITAL OUTPUT
DOAS DEDICATED OUTDOOR AIR SYSTEM
DP DIFFERENTIAL PRESSURE (SENSOR)
DP DEW POINT
DRE DRYER EXHAUST
DWG DRAWING
DWH DOMESTIC WATER HEATER
DX DIRECT EXPANSION
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECM ELECTRONICALLY COMMUTATED MOTOR
EF EXHAUST FAN
EHC ELECTRIC HEATING COIL
ELEC ELECTRICAL
EMCS ENVIRONMENTAL MANAGEMENT CONTROL
SYSTEM
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETC ETCETERA
EUH ELECTRIC UNIT HEATER
EWH ELECTRIC WATER HEATER
EWT ENTERING WATER TEMPERATURE
F DEGREES FAHRENHEIT
FD FIRE DAMPER OR FLOOR DRAIN
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FP FAN POWERED
FPM FEET PER MINUTE
FPTD FAN POWERED TERMINAL DEVICE
FS FLOW SWITCH
FT FOOT/FEET
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRAINS
GUH GAS FIRED UNIT HEATER
H HUMIDIFIER OR HEIGHT
H2O WATER
HD HEAD
HP HORSEPOWER
HVAC HEATING, VENTILATION, AND
AIR-CONDITIONING
HWT HEATING WATER TEMPERATURE
HX HEAT EXCHANGER
IN INCH
KEF KITCHEN EXHAUST FAN
KW KILOWATT
L LOUVER
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LF LINEAR FEET
LWT LEAVING WATER TEMPERATURE
M MOTOR OR MOTORIZED DAMPER OR METER
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKEUP AIR UNIT
MBH 1,000 BRITISH THERMAL UNITS PER HOUR
MCA MINIMUM CIRCUIT AMPS
MERV MINIMUM EFFICIENCY REPORTING VALUE
MFR MANUFACTURER
MOCP MAXIMUM OVERCURRENT PROTECTION
NC NORMALLY CLOSED OR NOISE CRITERIA
NO NORMALLY OPEN OR NUMBER
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTDOOR AIR
OAT OUTDOOR AIR TEMPERATURE
OD OUTSIDE DIAMETER
OS OCCUPANCY SENSOR
P PRESSURE OR PRESSURE SENSOR
PD PRESSURE DROP
PH PHASE
PHC PREHEAT COIL
PICV PRESSURE INDEPENDENT CONTROL VALVE
PPM PARTS PER MILLION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
PTAC PACKAGED TERMINAL AIR CONDITIONER
QTY QUANTITY
R RADIUS, RISE, OR REMOVE
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RCP REFLECTED CEILING PLAN
REF RELIEF AIR FAN
RF RETURN AIR FAN
RH RELATIVE HUMIDITY, REHEAT
RHC REHEAT COIL
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
SA SUPPLY AIR
SAT SUPPLY AIR TEMPERATURE
SCH SCHEDULE
SEC SECONDS
SF SUPPLY FAN OR SQUARE FOOT
SF SUPPLY AIR FAN
SP STATIC PRESSURE
SS SPLIT SYSTEM OR STAINLESS STEEL
T&P TEMPERATURE AND PRESSURE
T, TEMP TEMPERATURE
T-STAT THERMOSTAT
TON COOLING TONS (12,000 BTUH)
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UH UNIT HEATER
V, VOLT VOLTAGE
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VF VENTILATION FAN
VFD VARIABLE FREQUENCY DRIVE
W WIDTH OR WATTS
W/ WITH
WB WET BULB
WC WATER COLUMN
WG WATER GAUGE
WPD WATER PRESSURE DROP
WSHP WATER-SOURCE HEAT PUMP
NO. DESCRIPTION DATE
RT
EDC
14x8
14x8
10x8 6x6
6x6
10x8
22x6
12x8
22x6
18/12ø
20x10
14/8ø
18x10
20x10 20x12
26/14ø20/14ø
FPT-3-37 (E)
FPT-3-6 (E)
COMPUTER CLASS
RM
130 130
130130
130135
130135
T
T
3/4" HWR
3/4" HWS
3/4" HWS
3/4" HWR
14x6
1.
2.
3.
4.
NOTES:
THE TERMINAL UNIT DESIGNATION, FAN AIRFLOW SET POINTS, AND HOT WATER FLOW RATE (GPM) SHALL BE AS
INDICATED ON THE DRAWINGS.
REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS, INCLUDING BUT NOT LIMITED TO, REQUIREMENTS FOR SHOP DRAWING SUBMITTAL DATA. SUBMITTAL DATA MUST LIST EACH UNIT BY THE ZONE DESIGNATION
SHOWN ON THE DRAWINGS.
THE MAXIMUM PRIMARY AIR VOLUME SET POINT SHALL BE 88.1% OF THE FAN AIRFLOW SET POINT INDICATED ON THE FLOOR PLANS. THE MINIMUM PRIMARY AIRFLOW SET POINT SHALL BE 16% OF THE MAXIMUM PRIMARY
AIRFLOW SET POINT.
INLET SIZE INDICATED FOR TERMINAL UNITS IS FOR ROUND OR ROUND EQUIVALENT FLAT OVAL CONNECTION.
SIZE OF INLET DUCTWORK SHALL MATCH THE INLET SIZE OF THE TERMINAL UNIT UNLESS OTHERWISE INDICATED. TERMINAL UNIT MANUFACTURER SHALL MAKE RECOMMENDATIONS CONCERNING THE ADJUSTMENT OF INLET SIZES BASED ON OPTIMIZING AND IMPROVING THE COMBINATION OF PERFORMANCE FACTORS INCLUDING BUT NOT LIMITED TO CONTROLLABILITY OF MINIMUM AND MAXIMUM PRIMARY AIRFLOW SET POINTS AND ACOUSTICS. INLET SIZE ADJUSTMENTS BASED ON THESE RECOMMENDATIONS SHALL BE PROVIDED BY THE TERMINAL UNIT MANUFACTURER, AS APPROVED BY THE ENGINEER, WITHOUT ADDITIONAL COST. ADJUSTMENTS SHALL BE INDICATED IN THE SUBMITTAL DATA AND FORWARDED TO THE CONTRACTOR FOR COORDINATION WITH
OTHER TRADES.
FPT-3-6 (E)
FPT-3-37 (E)
EQUIPMENT
SET
AIRFLOW
(CFM)
PRIMARY
AIR INLET
SIZE
(IN)
0.40
0.40
FAN POWERED TERMINAL UNIT SCHEDULE (SERIES FLOW)
EWT
(°F)
LWT
(°F)
WATER
FLOW
(GPM)
1.4
1.4
AIRFLOW
(CFM)
CAPACITY
(BTU/H)
13,900
13,900
HEATING COIL
DISCHARGE
STATIC
PRESSURE
(IN WG)
MAX
AIRFLOW
(CFM)
MIN
AIRFLOW
(CFM)
PRIMARY AIR
MAX FAN
AIRFLOW
(CFM)
A
54321
B
C
D
E
KEY PLAN
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SEAL
REVISIONS
8/ 5/
:1
0:
P M
MECHANICAL
THIRD FLOOR
NEW WORK PLAN
JS/MN
MD
RT
08/05/26
50186890
C M
-M C
D
IA
R M
ID
B
U
IL
D
IN
G R
EN
O
VA
TE
R
D F
LO
O
R
LA
B
0- B4
0-
8/
L2 4N
V5
N
VC
C
AN
N
AN
D
AL
E
C
AM
PU
S
IS
SU
ED
F
O R
B
ID
S
ET
L
IT
TL
E
R
IV
ER
T
U R
N
PI
KE
AN
N
AN
D
AL
E, V
A
M-111
0' 8' 16'4'
1 EXISTING THERMOSTAT TO REMAIN.
2 RE-BALANCE EXISTING TERMINAL UNIT AND ASSOCIATED DIFFUSERS
TO THE VALUES INDICATED ON THE DRAWING.
1.
2.
DUCT SIZES INDICATED ARE INSIDE CLEAR DIMENSIONS.
EXISTING SUPPLY AND RETURN DIFFUSERS TO REMAIN IN EXISTING
CEILING. RE-BALANCE SUPPLY AIR DIFFUSERS TO AIRFLOW INDICATED
ON DRAWING.
Scale: 1/8" = 1'-0"1 MECHANICAL THIRD FLOOR NEW WORK PLAN
GENERAL NOTES
KEYNOTES
EDC
COMPUTER CLASS
RM
EXISTING SPRINKLER
HEAD, TYPICAL
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
TENANT FIRE PROTECTION NOTES
VERIFY IN THE FIELD EXACT SIZES AND LOCATIONS OF ALL EXISTING FIRE
PROTECTION SYSTEM PIPING PRIOR TO INSTALLATION OF ANY NEW FIRE
PROTECTION SYSTEM WORK. NEW FIRE PROTECTION SYSTEM WORK
SHALL BE COORDINATED WITH EXISTING CONDITIONS TO ASSURE
PROPER INSTALLATION.
ANY PIPING WHICH MUST REMAIN AS PART OF AN ACTIVE SYSTEM AND IS
IN CONFLICT WITH THE NEW LAYOUT SHALL BE RELOCATED AT NO
ADDITIONAL COST OVER THE CONTRACT AMOUNT.
THE DESIGN AND INSTALLATION OF THE TENANT WET SPRINKLER AND
STANDPIPE SYSTEMS SHALL CONFORM TO THE REQUIREMENTS OF
N.F.P.A. STANDARDS NO. 13 AND 14.
SPRINKLER HEAD LAYOUTS SHALL BE SYMMETRICAL. SPRINKLER HEADS,
VALVES, ALARMS, ETC. SHALL BE MANUFACTURED BY VIKING, GRINNELL,
CENTRAL, STAR OR RELIABLE.
THE CONTRACTOR SHALL PREPARE SPRINKLER SHOP DRAWINGS FOR
SUBMISSION AND APPROVAL BY THE LOCAL CODE AUTHORITY HAVING
JURISDICTION.
THE CONTRACTOR SHALL PROVIDE A HYDRAULICALLY CALCULATED WET
AND/OR DRY SPRINKLER SYSTEM SUFFICIENT TO PROVIDE THE DESIGN
DENSITIES, DEMAND AND HEAD SPACING AS REQUIRED BY N.F.P.A.
STANDARD NO. 13 IN THE TENANT AREAS TO BE MODIFIED. ALL
HYDRAULIC CALCULATIONS AND SPRINKLER SYSTEM DESIGN SHALL BE
BASED ON THE WATER PRESSURE.
THE NEW SPRINKLER AND STANDPIPE SYSTEMS SHALL ACCOUNT FOR
EXPECTED LOSSES OF EXISTING PIPING CONNECTIONS TO THE SYSTEM.
THE AUTOMATIC SUPPLY AND ALL SUPPLY PIPING SHALL BE CAPABLE OF
PROVIDING THE REQUIRED DEMAND IN ACCORDANCE WITH N.F.P.A.
STANDARDS NO. 13 AND 14.
SPRINKLER HEADS SHALL BE QUICK RESPONSE TYPE AND SHALL BE
RATED AND U.L. LISTED FOR THE INTENDED TEMPERATURE
CLASSIFICATION. SPRINKLERS IN AREAS REQUIRING TEMPERATURE
CLASSIFICATIONS OF INTERMEDIATE AND GREATER SHALL REQUIRE THE
USE OF A TEMPERATURE MEASURING DEVICE TO DETERMINE THE
APPROPRIATE TEMPERATURE CLASSIFICATION.
UNLESS OTHERWISE NOTED, ALL NEW SPRINKLER HEADS SHALL BE THE
SAME MANUFACTURER, MODEL, TYPE AND FINISH AS THE EXISTING
SPRINKLER HEADS IN THE AREAS TO BE MODIFIED.
THE CONTRACTOR SHALL REFER TO THE TENANT ARCHITECTURAL
DRAWINGS FOR PROPOSED SPRINKLER HEAD LOCATIONS WHERE
APPLICABLE.
ALL SPRINKLER HEADS MOUNTED IN REMOVABLE ACCESSIBLE CEILINGS
SHALL BE LOCATED AT THE CENTER (+1") OF THE CEILING TILE.
THE CONTRACTOR SHALL REMOVE ALL EXISTING TEMPORARY SPRINKLER
HEADS IN THE AREAS TO BE MODIFIED.
THE EXISTING RUN-OUTS AND DROPS SHALL BE MODIFIED AS REQUIRED
TO CONFORM TO THE FLOOR PLAN SHOWN.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE RELOCATION AND
COORDINATION OF THE EXISTING SPRINKLER SYSTEM WITH THE NEW
MEP SYSTEM REQUIREMENTS OF THIS PROJECT.
SUPPORT ALL PIPING FROM EXISTING OR NEW STRUCTURE WITH U.L.
LISTED HANGERS AND SUPPORTS SUITABLE FOR THE INTENDED
INSTALLATION. DESIGN, SELECTION, SPACING AND APPLICATION OF
HANGERS AND SUPPORTS SHALL COMPLY WITH N.F.P.A. STANDARDS,
ANSI B31.1 AND MSS SP-58.
ALL TRAPPED PIPING SHALL BE PROVIDED WITH DRAIN VALVES, NIPPLE
AND CAP.
ALL NEW FIRE PROTECTION PIPING SHALL BE EITHER ASTM-A135,-A795
OR -A53 SCHEDULE 40 BLACK STEEL OR TYPE L HARD DRAWN SEAMLESS
COPPER WATER TUBE. THE USE OF THE COPPER PIPING MATERIALS
SHALL BE LIMITED TO THE SPRINKLER SYSTEM PIPING DOWNSTREAM OF
THE FLOOR CONTROL VALVES.
ALL NEW FIRE PROTECTION PIPING SHALL HAVE THE OPTION TO BE U.L.
LISTED AND FACTORY MUTUAL…
This is the start of the file's text. The full file is on GovTribe.