26-0814 Project Manual Volume 2v1.pdf

PDF 2 MB Posted

Attached to
RACSB Crisis Receiving and Stabilization Center
Solicitation number
IFB-126662
Issued by
Stafford County, Virginia

About this file

This is a Project Manual Volume 2 document for the RACSB Crisis Receiving and Stabilization Center, a construction renovation project in Spotsylvania County, Virginia. The project involves the renovation of most of the first floor of an 80,000 square foot, two-story building. The manual provides comprehensive technical specifications, construction standards, and detailed requirements for bidders submitting proposals for the professional construction services needed to complete this renovation work. The document serves as a critical reference guide for contractors preparing bids, establishing the scope of work, performance standards, and construction methodologies required for project execution.

The Project Manual Volume 2 contains detailed specifications organized by construction trade and system type, outlining material standards, installation procedures, quality requirements, and testing protocols. This volume establishes the technical baseline against which all construction work will be evaluated and includes specifications for mechanical, electrical, plumbing, and other building systems relevant to the first-floor renovation scope. The manual ensures uniformity in bidding by providing all prospective contractors with identical technical requirements, allowing for competitive and equitable comparison of proposals based on price and contractor qualifications rather than varying interpretations of project needs.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

908 north thompson street richmond, virginia 23230 804-353-2635

09 JULY 2026

P R O J E C T M A N U A L

CRISIS RECEIVING &

STABILIZATION CENTER

Volume 1 of 2

VALLEY COMMUNITY SERVICES BOARD RAPPAHANNOCK AREA

COMMUNITY SERVICES BOARD

CRISIS RECEIVING &

STABILIZATION CENTER

Volume 2 of 2 14 August 2026

RACSB Crisis Receiving and Stabilization Center WA-2420c

TABLE OF CONTENTS 00 01 10 - 1

DOCUMENT 00 01 10

TABLE OF CONTENTS

VOLUME 1

Section Title 00 01 10 Table of Contents

PROCUREMENT REQUIREMENTS

00 00 05 Bid Form 00 11 16 Invitation To Bid

00 21 00 Instructions To Bidders

CONTRACT DOCUMENTS

00 52 00 Form of Agreement 00 52 01 Insurance Checklist 00 73 13 General Conditions 00 73 14 Supplementary Conditions

TECHNICAL SPECIFICATIONS

DIVISION 01 - GENERAL REQUIREMENTS

01 10 00 Summary 01 20 00 Price and Payment Procedures 01 25 00 Substitution Procedures 01 30 00 Administrative Requirements 01 32 16 Construction Progress Schedule 01 33 00 Submittal Procedures 01 40 00 Quality Requirements 01 50 00 Temporary Facilities and Controls 01 60 00 Product Requirements 01 70 00 Execution and Closeout Requirements

DIVISION 02 - EXISTING CONDITIONS

02 41 19.13 Selective Building Demolition

DIVISION 03 - CONCRETE

03 10 00 Concrete Forming and Accessories 03 20 00 Concrete Reinforcing 03 30 00 Cast-In-Place Concrete 03 30 01 Cast-In-Place Concrete for Sitework

DIVISION 04 – NOT USED

DIVISION 05 - METALS

TABLE OF CONTENTS 00 01 10 - 2

05 12 00 Structural Steel Framing 05 31 00 Steel Decking 05 40 00 Cold-Formed Metal Framing 05 50 00 Metal Fabrications 05 52 00 Metal Railings 05 58 00 Architectural Column Covers

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

06 10 53 Miscellaneous Rough Carpentry 06 16 00 Sheathing 06 41 00 Architectural Woodwork

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 21 13 Board Insulation 07 21 16 Blanket Insulation 07 27 26 Weather Barriers 07 42 16 Insulated Metal Panels 07 62 00 Sheet Metal Flashing and Trim 07 71 00 Roof Specialties 07 81 00 Applied Fireproofing 07 84 00 Firestopping 07 90 00 Joint Protection 07 95 00 Expansion Control

DIVISION 08 - OPENINGS

08 12 14 Standard Steel Frames 08 13 14 Standard Steel Doors 08 14 16 Flush Wood Doors 08 31 13 Access Doors and Frames 08 34 00 Special Function Doors 08 41 13 Aluminum-Framed Entrances and Storefronts 08 51 13 Aluminum Windows 08 58 00 Sliding Security Transaction Windows 08 71 00 Door Hardware 08 80 00 Glazing 08 88 53 Security Glazing

DIVISION 09 - FINISHES

09 21 16 Gypsum Board Assemblies 09 31 13 Ceramic Tile 09 51 13 Acoustical Panel Ceilings 09 65 00 Resilient Flooring 09 68 13 Tile Carpeting 09 72 00 Wall Coverings 09 84 33 Sound Absorbing Wall Units 09 90 00 Painting

DIVISION 10 - SPECIALTIES

TABLE OF CONTENTS 00 01 10 - 3

10 26 00 Wall and Door Protection 10 28 00 Toilet, Bath, and Laundry Accessories 10 43 10 Interior Signage 10 44 00 Fire Protection Specialties 10 51 16 Plastic Lockers 10 73 00 Prefabricated Metal Canopies

DIVISION 11 - EQUIPMENT

11 10 00 Miscellaneous Equipment

DIVISIONS 12 TO 20 - NOT USED

VOLUME 2

TECHNICAL SPECIFICATIONS (Continued)

DIVISION 21 - FIRE SUPPRESSION

21 05 00 Common Work Results for Fire Suppression 21 05 53 Identification for Fire Suppression Piping and Equipment 21 13 00 Fire-Suppression Sprinkler Systems

DIVISION 22 - PLUMBING

22 05 13 Common Motor Requirements for Plumbing Equipment 22 05 17 Sleeves and Sleeve Seals for Plumbing Piping 22 05 19 Meters and Gauges for Plumbing Piping 22 05 23 General-Duty Valves for Plumbing Piping 22 05 29 Hangers and Supports for Plumbing Piping and Equipment 22 05 48 Vibration and Seismic Controls for Plumbing Piping and Equipment 22 05 53 Identification for Plumbing Piping and Equipment 22 07 19 Plumbing Piping Insulation 22 10 05 Plumbing Piping 22 15 00 General-Service Compressed-Air Systems 22 30 00 Plumbing Equipment 22 31 00 Sanitary Waste Vacuum System 22 40 00 Plumbing Fixtures

DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)

23 05 13 Common Motor Requirements for HVAC Equipment 23 05 16 Expansion Fittings and Loops for HVAC Piping 23 05 17 Sleeves and Sleeve Seals for HVAC Piping 23 05 19 Meters and Gauges for HVAC Piping 23 05 29 Hangers and Supports for HVAC Piping and Equipment 23 05 33 Heat Tracing for HVAC Piping 23 05 48 Vibration and Seismic Controls for HVAC 23 05 53 Identification for HVAC Piping and Equipment 23 05 93 Testing, Adjusting, and Balancing for HVAC 23 07 13 Duct Insulation

TABLE OF CONTENTS 00 01 10 - 4

23 07 19 HVAC Piping Insulation 23 08 00 Commissioning of HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 23 Direct-Digital Control System for HVAC 23 23 00 Refrigerant Piping 23 31 00 HVAC Ducts and Casings 23 33 00 Air Duct Accessories 23 34 16 Centrifugal HVAC Fans 23 36 00 Air Terminal Units 23 37 00 Air Outlets and Inlets 23 74 16 Packaged Rooftop Air-Conditioning Units 23 81 26.13 Small-Capacity Split-System Air Conditioners

DIVISIONS 24 TO 25 - NOT USED

DIVISION 26 - ELECTRICAL

26 05 05 Selective Demolition for Electrical 26 05 19 Low-Voltage Electrical Power Conductors and Cables 26 05 26 Grounding and Bonding for Electrical Systems 26 05 29 Hangers and Supports for Electrical Systems 26 05 33.13 Conduit for Electrical Systems 26 05 33.16 Boxes for Electrical Systems 26 05 48 Vibration and Seismic Controls for Electrical Systems 26 05 53 Identification for Electrical Systems 26 05 73 Power System Studies 26 09 23 Lighting Control Devices262100 - Low-Voltage Electrical Service Entrance 26 2200 Low-Voltage Transformers 26 24 13 Switchboards 26 24 16 Panelboards 26 27 26 Wiring Devices 26 28 13 Fuses 26 2816.13 Enclosed Circuit Breakers 26 32 13 Engine Generators 26 28 16.16 Enclosed Switches 26 36 00 Transfer Switches 26 41 13 Lightning Protection for Structures 26 43 00 Surge Protective Devices 26 51 00 Interior Lighting 26 56 00 Exterior Lighting

DIVISION 27 – NOT USED

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28 46 00 Fire Detection and Alarm

DIVISION 29 TO 31 - NOT USED

DIVISION 32 - EXTERIOR IMPROVEMENTS

32 31 13 Privacy Fences and Gates

TABLE OF CONTENTS 00 01 10 - 5

32 31 19 Security Fences and Gates

DIVISIONS 33 TO 49 - NOT USED

END OF SECTION

Common Work Results for Fire Suppression 210500

SECTION 210500 - COMMON WORK RESULTS FOR FIRE SUPPRESSION

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Above ground piping.

B. Escutcheons.

C. Expansions - hose and braid.

D. Mechanical couplings.

E. Pipe hangers and supports.

F. Pipe sleeves.

G. Pipe sleeve-seal systems.

H. Piping specialties.

I. Pressure gauges.

1.02 RELATED REQUIREMENTS

A. Section 078400 - Firestopping.

1.03 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide manufacturer's catalog information. Indicate valve data and ratings.

C. Shop Drawings: Indicate pipe materials used, jointing methods, supports, and floor and wall penetration seals. Indicate installation, layout, weights, mounting and support details, and piping connections.

1.04 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section with minimum three years documented experience.

B. Installer Qualifications: Company specializing in performing work of the type specified in this section.

1. Minimum three years experience.

2. Approved by manufacturer.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Deliver and store valves in shipping containers, with labeling in place.

B. Provide temporary end caps and closures on piping and fittings. Maintain in place until installation.

1.06 WARRANTY

A. See Section 017800 - Closeout Submittals for additional warranty requirements.

B. Correct defective Work within a five year period after Date of Substantial Completion.

PART 2 PRODUCTS

2.01 GENERAL REQUIREMENTS

A. Welding Materials and Procedures: Comply with ASME BPVC-IX.

B. Provide system pipes, fittings, sleeves, escutcheons, seals, and other related accessories.

2.02 ABOVE GROUND PIPING

A. Steel Pipe: ASTM A795 Schedule 40, black.

1. Steel Fittings: ASME B16.5 steel flanges and fittings.

Suppression 210500

2. Mechanical Grooved Couplings: Malleable iron housing clamps to engage and lock, "C" shaped elastomeric sealing gasket, steel bolts, nuts, and washers; galvanized for galvanized pipe.

2.03 PIPE SLEEVES

A. Vertical Piping:

1. Sleeve Length: 1 inch above finished floor.

2. Provide sealant for watertight joint.

3. Blocked Out Floor Openings: Provide 1-1/2 inch angle set in silicon adhesive around opening.

4. Drilled Penetrations: Provide 1-1/2 inch angle ring or square set in silicone adhesive around penetration.

B. Clearances:

1. Provide allowance for insulated piping.

2. Wall, Floor, Floor, Partitions, and Beam Flanges: 1 inch greater than external; pipe diameter.

3. Rated Openings: Caulked tight with firestopping material complying with ASTM E814 in accordance with Section 078400 to prevent the spread of fire, smoke, and gases.

2.04 PIPE SLEEVE-SEAL SYSTEMS

A. Manufacturers:

1. Advance Products & Systems, Inc: www.apsonline.com/#sle.

2. GPT, a company of Enpro Industries, Inc: www.gptindustries.com/#sle.

B. Modular Mechanical Seals:

1. Elastomer-based interlocking links to continuously fill annular space between pipe and wall-sleeve, wall or casing opening.

2. Watertight seal between pipe and wall-sleeve, wall or casing opening.

3. Size and select seal component materials in accordance with service requirements.

4. Service Requirements:

a. Underground, buried, and wet conditions.

5. Glass-reinforced plastic pressure end plates.

C. Wall Sleeve: PVC material with waterstop collar, and nailer end caps.

D. Sleeve-Forming Disk: Nonconductive plastic-based material, 3 inch thick.

E. Pipeline-Casing Seals:

1. End Seals: 1/8 inch, pull-on type, rubber or synthetic rubber based.

2.05 ESCUTCHEONS

A. Manufacturers:

1. Fire Protection Products, Inc: www.fppi.com/#sle.com/#sle.

2. Tyco Fire Protection Products : www.tyco-fire.com/#sle.

3. Viking Group Inc: www.vikinggroupinc.com/#sle.

B. Material:

1. Fabricate from nonferrous metal.

2. Metals and Finish: Comply with ASME A112.18.1.

C. Construction:

1. One-piece for mounting on chrome-plated tubing or pipe and one-piece or split-pattern type elsewhere.

2. Internal spring tension devices or setscrews to maintain a fixed position against a surface.

2.06 PIPE HANGERS AND SUPPORTS

A. Hangers for Pipe Sizes 1/2 to 1-1/2 inch: Malleable iron, adjustable swivel, split ring.

1. Manufacturers:

a. AFCON, a brand of Anvil International : www.anvilintl.com/#sle.

Suppression 210500

b. FNW: www.fnw.com/#sle.

B. Hangers for Pipe Sizes 2 inches and Over: Carbon steel, adjustable, clevis.

1. Manufacturers:

a. AFCON, a brand of Anvil International : www.anvilintl.com/#sle.

b. FNW: www.fnw.com/#sle.

C. Vertical Support: Steel riser clamp.

1. Manufacturers:

a. Anvil International : www.anvilintl.com/#sle.

b. Substitutions: See Section 016000 - Product Requirements.

2.07 EXPANSION JOINTS AND LOOPS - HOSE AND BRAID

A. Manufacturers:

1. The Metraflex Company : www.metrafire.com/#sle.

2. Flex-Hose Co. Inc: www.flexhose.com/#sle.

3. Flex-Weld, Inc: www.kelcoind.com/#sle.

4. Substitutions: See Section 016000 - Product Requirements.

B. Provide flexible loops with two flexible sections of hose and braid, two 90-degree elbows, and 180-degree return with support bracket and air release or drain plug.

2.08 MECHANICAL COUPLINGS

A. Manufacturers:

1. Anvil International : www.anvilintl.com/#sle.

2. Shurjoint Piping Products, Inc: www.shurjoint.com/#sle.

3. Tyco Fire Protection Products : www.tyco-fire.com/#sle.

B. Rigid Mechanical Couplings for Grooved Joints:

1. Dimensions and Testing: Comply with AWWA C606.

2. Minimum Working Pressure: 300 psig.

3. Housing Material: Fabricate of ductile iron complying with ASTM A536.

4. Housing Coating: Factory applied orange enamel.

5. Gasket Material: EPDM suitable for operating temperature range from minus 30 degrees

F to 230 degrees F.

6. Bolts and Nuts: Hot-dipped-galvanized or zinc-electroplated steel.

2.09 PIPING SPECIALTIES

A. Wet Pipe Sprinkler Alarm Valve: Check type valve with divided seat ring, rubber-faced clapper to automatically actuate water motor alarm, pressure retard chamber and variable pressure trim with the following additional capabilities and features:

1. Activate electric alarm.

2. Test and drain valve.

3. Replaceable internal components without removing valve from installed position.

4. Manufacturers:

a. Victaulic Company : www.victaulic.com/#sle.

b. Tyco Fire Protection Products[<>]: www.tyco-fire.com/#sle.

B. Auxiliary Drains: Condensate collection drain for each section of trapped pipe in preaction or dry fire protection system.

1. Manufacturers:

a. AGF Manufacturing : www.agfmfg.com/#sle.

C. Air Venting Valves:

1. Manufacturers:

a. AGF Manufacturing : www.agfmfg.com/#sle.

D. Backflow Preventer: Reduced-pressure principle valve assembly backflow preventer with drain and OS & Y gate valve on each end.

Suppression 210500

1. Manufacturers:

a. Watts: www.watts.com/#sle.

2.10 PRESSURE GAUGES

A. Manufacturers:

1. AGF Manufacturing : www.agfmfg.com/#sle.

2. Dwyer Instruments, Inc: www.dwyer-inst.com/#sle.

3. Moeller Instrument Company, Inc: www.moellerinstrument.com/#sle.

4. Omega Engineering, Inc: www.omega.com/#sle.

PART 3 EXECUTION

3.01 PREPARATION

A. Ream pipe and tube ends. Remove burrs. Bevel plain end ferrous pipe.

B. Remove scale and foreign material, from inside and outside, before assembly.

C. Prepare piping connections to equipment with flanges or unions.

3.02 INSTALLATION

A. Install sprinkler system and service main piping, hangers, and supports in accordance with

NFPA 13.

B. Route piping in orderly manner, plumb and parallel to building structure. Maintain gradient.

C. Install piping to conserve building space, to not interfere with use of space and other work.

D. Group piping whenever practical at common elevations.

E. Install piping to allow for expansion and contraction without stressing pipe, joints, or connected equipment.

F. Pipe Hangers and Supports:

1. Install hangers to provide minimum 1/2 inch space between finished covering and adjacent work.

2. Place hangers within 12 inches of each horizontal elbow.

3. Use hangers with 1-1/2 inch minimum vertical adjustment. Design hangers for pipe movement without disengagement of supported pipe.

4. Support vertical piping at every other floor. Support riser piping independently of connected horizontal piping.

5. Where several pipes can be installed in parallel and at same elevation, provide multiple or trapeze hangers.

G. Slope piping and arrange systems to drain at low points. Use eccentric reducers to maintain top of pipe level.

H. Prepare pipe, fittings, supports, and accessories for finish painting. Where pipe support members are welded to structural building framing, scrape, brush clean, and apply one coat of zinc-rich primer to welding.

I. Provide sleeves when penetrating footings, floors, walls, and partitions. Seal pipe including sleeve penetrations to achieve fire resistance equivalent to fire separation required.

J. Manufactured Sleeve-Seal Systems:

1. Install manufactured sleeve-seal systems in sleeves located in grade slabs and exterior concrete walls at piping entrances into building.

2. Provide sealing elements of the size, quantity, and type required for the piping and sleeve inner diameter or penetration diameter.

3. Locate piping in center of sleeve or penetration.

4. Install field assembled sleeve-seal system components in annular space between sleeve and piping.

5. Tighten bolting for a watertight seal.

6. Install in accordance with manufacturer's recommendations.

Suppression 210500

K. Escutcheons:

1. Install and firmly attach escutcheons at piping penetrations into finished spaces.

2. Provide escutcheons on both sides of partitions separating finished areas through which piping passes.

3. Use chrome plated escutcheons in occupied spaces and to conceal openings in construction.

L. When installing more than one piping system material, ensure system components are compatible and joined to ensure the integrity of the system. Provide necessary joining fittings.

Ensure flanges, unions, and couplings for servicing are consistently provided.

3.03 CLEANING

A. Upon completion of work, clean all parts of the installation.

B. Clean equipment, pipes, valves, and fittings of grease, metal cuttings, and sludge that may have accumulated from the installation and testing of the system.

Identification for Fire Suppression Piping and Equipment 210553

SECTION 210553 - IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Nameplates.

B. Tags.

C. Pipe markers.

D. ASME A13.1 - Scheme for the Identification of Piping Systems.

1.02 SUBMITTALS

A. See Section 013000 - Administrative Requirements, for submittal procedures.

B. Manufacturer's Installation Instructions: Indicate special procedures, and installation instructions.

PART 2 PRODUCTS

2.01 IDENTIFICATION APPLICATIONS

A. Piping: Tags.

2.02 TAGS

A. Manufacturers:

1. Brady Corporation : www.bradycorp.com/#sle.

2. Craftmark Pipe Markers : www.craftmarkid.com/#sle.

3. Seton Identification Products, a Tricor Direct Company : www.seton.com/#sle.

B. Metal Tags: Brass with stamped letters; tag size minimum 1-1/2 inch diameter with smooth edges.

2.03 PIPE MARKERS

A. Manufacturers:

1. Brady Corporation : www.bradycorp.com/#sle.

2. Craftmark Pipe Markers : www.craftmarkid.com/#sle.

3. Seton Identification Products, a Tricor Company : www.seton.com/#sle.

B. Color: Comply with ASME A13.1.

C. Plastic Tape Pipe Markers: Flexible, vinyl film tape with pressure-sensitive adhesive backing and printed markings.

PART 3 EXECUTION

3.01 PREPARATION

A. Degrease and clean surfaces to receive adhesive for identification materials.

3.02 INSTALLATION

A. Install nameplates with corrosive-resistant mechanical fasteners, or adhesive. Apply with sufficient adhesive to ensure permanent adhesion and seal with clear lacquer.

B. Install tags with corrosion resistant chain.

C. Install plastic pipe markers in accordance with manufacturer's instructions.

D. Install plastic tape pipe markers complete around pipe in accordance with manufacturer's instructions.

E. Use tags on piping 3/4 inch diameter and smaller.

1. Install in clear view and align with axis of piping.

Fire-Suppression Sprinkler Systems 211300

SECTION 211300 - FIRE-SUPPRESSION SPRINKLER SYSTEMS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Wet-pipe sprinkler system.

B. System design, installation, and certification.

1.02 RELATED REQUIREMENTS

A. Section 213000 - Fire Pumps.

1.03 REFERENCE STANDARDS

A. ICC-ES AC193 - Acceptance Criteria for Mechanical Anchors in Concrete Elements.

B. NFPA 13 - Standard for the Installation of Sprinkler Systems.

C. UL (DIR) - Online Certifications Directory.

1.04 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide data on sprinklers, valves, and specialties, including manufacturers catalog information. Submit performance ratings, rough-in details, weights, support requirements, and piping connections.

C. Shop Drawings:

1. Indicate hydraulic calculations, detailed pipe layout, hangers and supports, sprinklers, components, and accessories. Indicate system controls.

D. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.

1. See Section 016000 - Product Requirements for additional provisions.

2. Extra Sprinklers: Type and size matching those installed in quantity required by referenced NFPA design and installation standard.

3. Sprinkler Wrenches: For each sprinkler type.

1.05 QUALITY ASSURANCE

A. Comply with FM (AG) requirements.

B. Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section with minimum three years documented experience.

C. Products Requiring Electrical Connection: Listed and classified by UL (DIR) as suitable for the purpose specified and indicated.

1.06 DELIVERY, STORAGE, AND HANDLING

A. Store products in shipping containers and maintain in place until installation. Provide temporary inlet and outlet caps. Maintain caps in place until installation.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Sprinklers, Valves, and Equipment:

1. Anvil International : www.anvilintl.com/#sle.

2. Tyco Fire Protection Products : www.tyco-fire.com/#sle.

3. Viking Corporation : www.vikinggroupinc.com/#sle.

2.02 SPRINKLER SYSTEM

A. Sprinkler System: Provide coverage for entire building.

B. Occupancy: Light hazard; comply with NFPA 13.

C. Water Supply: Determine volume and pressure from water flow test data.

D. Storage Cabinet for Spare Sprinklers and Tools: Steel, located adjacent to alarm valve.

Systems 211300

E. Pipe Hanger Fasteners: Attach hangers to structure using appropriate fasteners, as follows:

1. Concrete Wedge Expansion Anchors: Complying with ICC-ES AC193.

2. Other Types: As required.

2.03 SPRINKLERS

A. Suspended Ceiling Type: Concealed pendant type with matching push on escutcheon plate.

1. Response Type: Quick.

2. Coverage Type: Standard.

3. Finish: Enamel, color as selected.

4. Fusible Link: Fusible solder link type temperature rated for specific area hazard.

B. Exposed Area Type: Pendant type with guard.

1. Response Type: Quick.

2. Coverage Type: Standard.

3. Fusible Link: Fusible solder link type temperature rated for specific area hazard.

C. Sidewall Type: Semi-recessed horizontal sidewall type with matching push on escutcheon plate.

1. Response Type: Quick.

2. Coverage Type: Standard.

3. Fusible Link: Fusible solder link type temperature rated for specific area hazard.

D. Storage Sprinklers: Pendant type with guard.

1. Response Type: Standard.

2. Coverage Type: Standard.

3. Fusible Link: Fusible solder link type temperature rated for specific area hazard.

2.04 PIPING SPECIALTIES

A. Wet Pipe Sprinkler Alarm Valve: Check type valve with divided seat ring, rubber-faced clapper to automatically actuate water motor alarm, pressure retard chamber and variable pressure trim with the following additional capabilities and features:

1. Activate electric alarm.

2. Test and drain valve.

B. Electric Alarm: Electrically operated chrome plated gong with pressure alarm switch.

PART 3 EXECUTION

3.01 INSTALLATION

A. Install in accordance with referenced NFPA design and installation standard.

B. Install equipment in accordance with manufacturer's instructions.

C. Install buried shut-off valves in valve box. Provide post indicator.

D. Locate fire department connection with sufficient clearance from walls, obstructions, or adjacent siamese connectors to allow full swing of fire department wrench handle.

E. Locate outside alarm gong on building wall as indicated.

F. Place pipe runs to minimize obstruction to other work.

G. Place piping in concealed spaces above finished ceilings.

H. Apply masking tape or paper cover to ensure concealed sprinklers, cover plates, and sprinkler escutcheons do not receive field paint finish. Remove after painting. Replace painted sprinklers.

I. Install and connect to fire pump system in accordance with Section 213000.

J. Flush entire piping system of foreign matter.

K. Hydrostatically test entire system.

L. Require test be witnessed by Fire Marshal.

Systems 211300

3.02 SCHEDULES

A. System Hazard Areas:

1. Light Hazard.

Common Motor Requirements for Plumbing Equipment 220513

SECTION 220513 - COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

PART 1 GENERAL

1.01 SECTION INCLUDES

A. General construction and requirements.

B. Applications.

C. Single phase electric motors.

1.02 RELATED REQUIREMENTS

A. Section 260583 - Wiring Connections: Electrical characteristics and wiring connections.

1.03 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide wiring diagrams with electrical characteristics and connection requirements.

1.04 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacture of electric motors for _______________ use, and their accessories, with minimum three years documented product development, testing, and manufacturing experience.

B. Comply with NFPA 70.

C. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories

Inc. as suitable for the purpose specified and indicated.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Protect motors stored on site from weather and moisture by maintaining factory covers and suitable weather-proof covering. For extended outdoor storage, remove motors from equipment and store separately.

1.06 WARRANTY

PART 2 PRODUCTS

2.01 GENERAL CONSTRUCTION AND REQUIREMENTS

A. Electrical Service: Refer to Section 260583 for required electrical characteristics.

B. Electrical Service:

1. Motors 1/2 HP and Smaller: 115 volts, single phase, 60 Hz.

2. Motors Larger than 1/2 Horsepower: 480 volts, three phase, 60 Hz.

C. Construction:

1. Open drip-proof type except where specifically noted otherwise.

2. Design for continuous operation in 104 degrees F environment.

3. Design for temperature rise in accordance with NEMA MG 00001 limits for insulation class, service factor, and motor enclosure type.

D. Visible Nameplate: Indicating motor horsepower, voltage, phase, cycles, RPM, full load amps, locked rotor amps, frame size, manufacturer's name and model number, service factor, power factor, efficiency.

E. Wiring Terminations:

1. Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70, threaded for conduit.

2. For fractional horsepower motors where connection is made directly, provide threaded conduit connection in end frame.

2.02 APPLICATIONS

A. Single phase motors for fans, pumps, blowers, and air compressors: Capacitor start type.

Common Motor Requirements for Plumbing Equipment 220513

2.03 SINGLE PHASE POWER - CAPACITOR START MOTORS

A. Starting Torque: Three times full load torque.

B. Starting Current: Less than five times full load current.

C. Pull-up Torque: Up to 350 percent of full load torque.

D. Breakdown Torque: Approximately 250 percent of full load torque.

PART 3 EXECUTION

3.01 INSTALLATION

A. Install in accordance with manufacturer's instructions.

B. Install securely on firm foundation. Mount ball bearing motors with shaft in any position.

C. Check line voltage and phase and ensure agreement with nameplate.

Sleeves and Sleeve Seals for Plumbing Piping 220517

SECTION 220517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Pipe sleeves.

B. Pipe sleeve-seals.

C. Section 078400 - Firestopping.

D. Section 099123 - Interior Painting: Preparation and painting of interior piping systems.

1.02 REFERENCE STANDARDS

A. ASTM C592 - Standard Specification for Mineral Fiber Blanket Insulation and Blanket-Type

Pipe Insulation (Metal-Mesh Covered) (Industrial Type).

B. ASTM E814 - Standard Test Method for Fire Tests of Penetration Firestop Systems.

C. UL (DIR) - Online Certifications Directory.

1.03 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.

1. See Section 016000 - Product Requirements, for additional provisions.

1.04 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section with minimum three years documented experience.

B. Installer Qualifications: Company specializing in performing work of the type specified this section.

1. Minimum three years experience.

2. Approved by manufacturer.

C. Clean equipment, pipes, valves, and fittings of grease, metal cuttings, and sludge that may have accumulated from the installation and testing of the system.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Deliver and store sleeve and sleeve seals in shipping containers, with labeling in place.

B. Provide temporary protective coating on cast iron and steel sleeves if shipped loose.

1.06 WARRANTY

A. See Section 017800 - Closeout Submittals, for additional warranty requirements.

PART 2 PRODUCTS

2.01 PIPE SLEEVES

A. Manufacturers:

1. Flexicraft Industries; Pipe Wall Sleeve: www.flexicraft.com/#sle.

B. Vertical Piping:

1. Sleeve Length: 1 inch above finished floor.

2. Provide sealant for watertight joint.

3. Blocked Out Floor Openings: Provide 1-1/2 inch angle set in silicon adhesive around opening.

4. Drilled Penetrations: Provide 1-1/2 inch angle ring or square set in silicone adhesive around penetration.

C. Plastic or Sheet Metal: Pipe passing through interior walls, partitions, and floors, unless steel or brass sleeves are specified below.

D. Clearances:

Plumbing Piping 220517

1. Provide allowance for insulated piping.

2. Wall, Floor, Partitions, and Beam Flanges: 1 inch greater than external pipe diameter.

3. All Rated Openings: Caulked tight with fire stopping material complying with ASTM E814 in accordance with Section 078400 to prevent the spread of fire, smoke, and gases.

2.02 PIPE-SLEEVE SEALS

A. Manufacturers:

1. Advance Products & Systems, LLC : www.apsonline.com/#sle.

2. Flexicraft Industries; PipeSeal: www.flexicraft.com/#sle.

B. Modular Mechanical Sleeve-Seal:

1. Elastomer-based interlocking links continuously fill annular space between pipe and wall-sleeve, wall or casing opening.

2. Watertight seal between pipe and wall-sleeve, wall or casing opening.

3. Size and select seal component materials in accordance with service requirements.

4. Service Requirements:

a. Corrosion resistant.

b. Underground, buried, and wet conditions.

c. Fire Resistant: 1 hour, UL (DIR) approved.

5. Glass-reinforced plastic pressure end plates.

C. Sealing Compounds:

1. Provide packing and sealing compound to fill pipe to sleeve thickness.

2. Combined packing and sealing compounding to match partition fire-resistance hourly rating.

D. Pipe Sleeve Material:

1. Bearing Walls: Steel, cast iron, or terra-cotta pipe.

2. Masonry Structures: Sheet metal or fiber.

PART 3 EXECUTION

3.01 PREPARATION

A. Ream pipe and tube ends. Remove burrs. Bevel plain end ferrous pipe.

B. Remove scale and foreign material, from inside and outside, before assembly.

3.02 INSTALLATION

A. Route piping in orderly manner, plumb and parallel to building structure. Maintain gradient.

B. Install piping to conserve building space, to not interfere with use of space and other work.

C. Install piping and pipe sleeves to allow for expansion and contraction without stressing pipe, joints, or connected equipment.

D. Provide sleeves when penetrating footings, floors, walls, and partitions. Seal pipe including sleeve penetrations to achieve fire resistance equivalent to fire separation required.

1. Underground Piping: Caulk pipe sleeve watertight with lead and oakum or mechanically expandable chloroprene inserts with bitumen sealed metal components.

2. Aboveground Piping:

a. Pack solid using mineral fiber complying with ASTM C592.

b. Fill space with an elastomer caulk to a depth of 0.50 inch where penetrations occur between conditioned and unconditioned spaces.

3. All Rated Openings: Caulk tight with fire stopping material complying with ASTM E814 in accordance with Section 078400 to prevent the spread of fire, smoke, and gases.

E. Manufactured Sleeve-Seal Systems:

1. Install manufactured sleeve-seal systems in sleeves located in grade slabs and exterior concrete walls at piping entrances into building.

2. Provide sealing elements of the size, quantity, and type required for the piping and sleeve inner diameter or penetration diameter.

Plumbing Piping 220517

3. Locate piping in center of sleeve or penetration.

4. Install field assembled sleeve-seal system components in annular space between sleeve and piping.

5. Tighten bolting for a water-tight seal.

6. Install in accordance with manufacturer's recommendations.

F. When installing more than one piping system material, ensure system components are compatible and joined to ensure the integrity of the system. Provide necessary joining fittings.

Ensure flanges, union, and couplings for servicing are consistently provided.

3.03 CLEANING

A. Upon completion of work, clean all parts of the installation.

B. Clean equipment, pipes, valves, and fittings of grease, metal cuttings, and sludge that may have accumulated from the installation and testing of the system.

Meters and Gauges for Plumbing Piping 220519

SECTION 220519 - METERS AND GAUGES FOR PLUMBING PIPING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Pressure gauges.

B. Thermometers.

1.02 RELATED REQUIREMENTS

1.03 REFERENCE STANDARDS

A. ASME B40.100 - Pressure Gauges and Gauge Attachments.

B. ASTM E1 - Standard Specification for ASTM Liquid-in-Glass Thermometers.

C. ASTM E77 - Standard Test Method for Inspection and Verification of Thermometers.

D. UL 393 - Indicating Pressure Gauges for Fire-Protection Service.

E. UL 404 - Gauges, Indicating Pressure, for Compressed Gas Service.

1.04 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide red-marked product data sheets for each furnished item with associated components and accessories.

PART 2 PRODUCTS

2.01 PRESSURE GAUGES

A. Manufacturers:

1. Ashcroft, Inc: www.ashcroft.com/#sle.

2. DwyerOmega: www.dwyeromega.com/#sle.

B. Bourdon Tube for Liquids and Gases:

1. Accuracy: ASME B40.100, adjustable commercial grade (D) with 5 percent of span.

2. Process Connection: Lower-back, 1/4 inch NPT male except where noted.

3. Comply with UL 393 when used for fire protection service or UL 404 when used for compressed gas service.

C. Diaphragm Actuated for Gases:

1. Dial Size and Cover: 3-1/2 inch diameter scale with polycarbonate window.

2. Accuracy: ASME B40.100, adjustable commercial grade (B) with 2 percent at mid-range of span.

3. Process Connection: Lower-back, 1/4 inch NPT male except where noted.

4. Comply with UL 404 when used for compressed gas service.

2.02 THERMOMETERS

A. Manufacturers:

1. DwyerOmega: www.dwyeromega.com/#sle.

2. Watts Water Technologies, Inc: www.watts.com/#sle.

3. Weiss Instruments, LLC : www.weissinstruments.com/#sle.

B. General:

1. Product Compliance: ASTM E1.

2. Lens: Clear glass, except where stated.

3. Accuracy: One percent, when tested in accordance with ASTM E77, except where stated.

4. Scale: Black markings depicting single scale in degrees F where expected process value falls half-span of standard temperature range.

C. Thermometers - Adjustable Angle: 7 inch v-shape aluminum case with clear glass window scale, 6 inch NPT stem, red or blue organic non-toxic liquid filled glass tube, and adjustable

Meters and Gauges for Plumbing Piping 220519 joint with positive locking device allowing 360 degrees in horizontal plane or 180 degrees in vertical plane adjustments.

D. Thermometers - Dial Type:

1. Adjustable Angle : 5 inch diameter dial with black pointer, lead-free brass case, silicone damping bimetal element, hermetically sealed lens, recalibrating screw, and 2-1/2 inch NPT stem.

PART 3 EXECUTION

3.01 EXAMINATION

A. Do not install instrumentation when areas are under construction, except for required rough-in, taps, supports, and test plugs.

3.02 INSTALLATION

A. Install metering products in accordance with manufacturer's instructions for intended fluid type and service.

B. Install pressure gauges as follows:

1. At Pumps: Place single gauge before strainer, suction side and discharge side.

2. Include siphons on high temperature systems and select type according to service rating.

3. Adjust gauges to selected viewing angle, clean thoroughly, and calibrate to zero.

C. Install thermometers as follows:

1. Hot Water Heaters: Place upstream and downstream of heater. Add one on the inlet end when using steam as the water heating medium.

2. Piping: Install thermometers in branch butt weld connection fitting or socket-weld thermowell. Enlarge pipes smaller than 2-1/2 inch to accommodate sockets. Ensure sockets are above insulation clearance.

3.03 SCHEDULES

A. Pressure Gauge Tappings, Location:

1. Control valves 3/4 inch & larger - inlets and outlets.

2. Wye strainers 1/2 inch & larger - inlets and outlets.

B. Stem Type Thermometers, Location and Scale Range:

1. Domestic hot water supply and recirculation, 0 to 180 degrees F.

General-Duty Valves for Plumbing Piping 220523

SECTION 220523 - GENERAL-DUTY VALVES FOR PLUMBING PIPING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Ball valves.

B. Check valves.

1.02 RELATED REQUIREMENTS

A. Section 220548 - Vibration and Seismic Controls for Plumbing Piping and Equipment.

B. Section 220553 - Identification for Plumbing Piping and Equipment.

C. Section 221005 - Plumbing Piping.

1.03 REFERENCE STANDARDS

A. ASME B16.18 - Cast Copper Alloy Solder Joint Pressure Fittings.

B. MSS SP-110 - Ball Valves Threaded, Socket-Welding, Solder Joint, Grooved and Flared Ends.

C. NSF 61 - Drinking Water System Components - Health Effects.

D. NSF 372 - Drinking Water System Components - Lead Content.

1.04 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide data on valves including manufacturers catalog information. Submit performance ratings, rough-in details, weights, support requirements, and piping connections.

1.05 QUALITY ASSURANCE

A. Manufacturer:

1. Obtain valves for each valve type from single manufacturer.

2. Company must specialize in manufacturing products specified in this section, with not less than three years of documented experience.

1.06 DELIVERY, STORAGE, AND HANDLING

A. Prepare valves for shipping as follows:

1. Minimize exposure of operable surfaces by setting plug and ball valves to open position.

2. Protect valve parts exposed to piped medium against rust and corrosion.

3. Protect valve piping connections such as grooves, weld ends, threads, and flange faces.

4. Secure check valves in either the closed position or open position.

B. Use the following precautions during storage:

1. Maintain valve end protection and protect flanges and specialties from dirt.

a. Provide temporary inlet and outlet caps.

b. Maintain caps in place until installation.

2. Store valves in shipping containers and maintain in place until installation.

PART 2 PRODUCTS

2.01 APPLICATIONS

A. Listed pipe sizes shown using nominal pipe sizes (NPS) and nominal diameter (DN).

B. Provide the following valves for the applications if not indicated on drawings:

1. Shutoff: Ball

2. Swing Check (Pump Outlet):

a. 2 inch and Smaller: Bronze swing check valves with bronze or nonmetallic disc.

C. Domestic, Hot and Cold Water Valves:

1. 2 inch and Smaller:

a. Brass: Provide with solder or Push-to-fit ends.

b. Ball: One piece, full port, brass with stainless-steel trim.

Piping 220523

c. Bronze Swing Check: Class 125, bronze disc.

2. 2-1/2 inch and Larger:

a. Iron, 2-1/2 inch to 4 inch : Provide with threaded or flanged ends.

b. Iron Single-Flange Butterfly: 200 CWP, EPDM seat, aluminum-bronze disc.

2.02 GENERAL REQUIREMENTS

A. Valve Pressure and Temperature Ratings: No less than rating indicated; as required for system pressures and temperatures.

B. Valve Sizes: Match upstream piping unless otherwise indicated.

C. Valve Actuator Types:

1. Hand Lever: Quarter-turn valves 6 inch and smaller except plug valves.

D. Valve-End Connections:

1. Solder Joint Connections: ASME B16.18.

E. General ASME Compliance:

F. Potable Water Use:

1. Certified: Approved for use in compliance with NSF 61 and NSF 372.

2. Lead-Free Certified: Wetted surface material includes less than 0.25 percent lead content.

2.03 BRASS, BALL VALVES

A. One Piece, Full Port with Brass Trim and Push-to-fit or Soldered Connections:

1. Comply with MSS SP-110.

2. CWP Rating: 200 psi.

3. Body: Forged brass.

4. Seats: PTFE.

5. Stem: Brass.

6. Ball: Chrome-plated brass.

7. Operator: Handle.

8. Manufacturers:

a. FNW; X485A : www.fnw.com/#sle.

b. Apollo Valves

B. Two Piece, Full Port with Brass Trim and Female Thread, Male thread, or Solder Connections:

1. Comply with MSS SP-110.

2. WSP Rating: 150 psi.

3. WOG Rating: 600 psi.

4. Body: Forged brass.

5. Seats: PTFE.

6. Ball: Chrome-plated brass.

7. Operator: Lockable handle and memory stop.

8. Manufacturers:

a. Apollo Valves : www.apollovalves.com/#sle.

b. FNW; 410A: www.fnw.com/#sle.

C. Two Piece, Full Port with Press Connections:

1. WOG Rating: 250 psi.

2. Body: Forged brass.

3. Seats: EPDM.

4. Ball: Chrome-plated brass.

5. Blow-out Proof Stem: Forged brass.

6. Operator: Provide lockable handle.

7. Maximum Service Temperature: 250 degrees F.

8. Manufacturers:

Piping 220523

a. FNW; 430: www.fnw.com/#sle.

b. Jomar Valves, a division of Jomar Group : www.jomarvalve.com/#sle.

2.04 BRASS, INLINE CHECK VALVES

A. Class 150:

1. Maximum Service Temperature: 250 degrees F.

2. Body: Forged brass.

3. Disc: Forged brass.

4. Seal: PTFE, bubble-tight.

5. End Connections: Press .

6. Manufacturers:

a. Jomar Valves, a division of Jomar Group : www.jomarvalve.com/#sle.

b. FNW: www.fnw.com/#sle.

PART 3 EXECUTION

3.01 EXAMINATION

A. Discard all packing materials and verify that valve interior, including threads and flanges are completely clean without signs of damage or degradation that could result in leakage.

B. Verify valve parts to be fully operational in all positions from closed to fully open.

C. Confirm gasket material to be suitable for the service, to be of correct size, and without defects that could compromise effectiveness.

D. Should valve is determined to be defective, replace with new valve.

3.02 INSTALLATION

A. Provide unions or flanges with valves to facilitate equipment removal and maintenance while maintaining system operation and full accessibility for servicing.

B. Provide separate valve support as required and locate valve with stem at or above center of piping, maintaining unimpeded stem movement.

C. Install check valves where necessary to maintain direction of flow as follows:

1. Lift Check: Install with stem plumb and vertical.

2. Swing Check: Install horizontal maintaining hinge pin level.

Hangers and Supports for Plumbing Piping and Equipment 220529

SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Prefabricated trapeze-framed systems.

B. Strut systems for pipe or equipment support.

C. Beam clamps.

D. Pipe hangers.

E. Pipe supports, guides, shields, and saddles.

F. Anchors and fasteners.

G. Section 033000 - Cast-in-Place Concrete: Concrete equipment pads.

H. Section 055000 - Metal Fabrications.

1.02 REFERENCE STANDARDS

A. ASTM A36/A36M - Standard Specification for Carbon Structural Steel.

B. ASTM A47/A47M - Standard Specification for Ferritic Malleable Iron Castings.

C. ASTM A123/A123M - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products.

D. ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel

Hardware.

E. ASTM A181/A181M - Standard Specification for Carbon Steel Forgings, for General-Purpose

Piping.

F. ASTM A283/A283M - Standard Specification for Low and Intermediate Tensile Strength Carbon

Steel Plates.

G. ASTM A395/A395M - Standard Specification for Ferritic Ductile Iron Pressure-Retaining

Castings for Use at Elevated Temperatures.

H. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-

Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.

I. ASTM A1011/A1011M - Standard Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength.

J. ASTM B633 - Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel.

K. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials.

L. ASTM E96/E96M - Standard Test Methods for Gravimetric Determination of Water Vapor

Transmission Rate of Materials.

M. FM (AG) - FM Approval Guide.

N. MSS SP-58 - Pipe Hangers and Supports - Materials, Design, Manufacture, Selection, Application, and Installation.

O. UL (DIR) - Online Certifications Directory.

P. UL 723 - Standard for Test for Surface Burning Characteristics of Building Materials.

1.03 ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1. Coordinate sizes and arrangement of supports and bases with the actual equipment and components to be installed.

2. Coordinate the work with other trades to provide additional framing and materials required for installation.

Plumbing Piping and Equipment 220529

3. Coordinate compatibility of support and attachment components with mounting surfaces at the installed locations.

4. Coordinate the arrangement of supports with ductwork, piping, equipment and other potential conflicts installed under other sections or by others.

5. Notify Architect of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.

B. Sequencing:

1. Do not install products on or provide attachment to concrete surfaces until concrete has fully cured in accordance with Section 033000.

1.04 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide manufacturer's standard catalog pages and data sheets for metal channel (strut) framing systems, nonpenetrating rooftop supports, post-installed concrete and masonry anchors, and thermal insulated pipe supports.

1.05 QUALITY ASSURANCE

A. Comply with applicable building code.

PART 2 PRODUCTS

2.01 GENERAL REQUIREMENTS

A. Provide required hardware to hang or support piping, equipment, or fixtures with related accessories as necessary to complete installation of plumbing work.

B. Provide hardware products listed, classified, and labeled as suitable for intended purpose.

C. Where support and attachment component types and sizes are not indicated, select in accordance with manufacturer's application criteria as required for the load to be supported .

Include consideration for vibration, equipment operation, and shock loads where applicable.

D. Do not use wire, chain, perforated pipe strap, or wood for permanent supports unless specifically indicated or permitted.

E. Fire Resistance: Provide hardware rated for 60 minutes resistance unless specifically indicated by the authority having jurisdiction.

F. Materials for Metal Fabricated Supports: Comply with Section 055000.

1. Zinc-Plated Steel: Electroplated in accordance with ASTM B633 unless stated otherwise.

2. Galvanized Steel: Hot-dip galvanized in accordance with ASTM A123/A123M or ASTM

A153/A153M unless stated otherwise.

G. Corrosion Resistance: Use corrosion-resistant metal-based materials fully compatible with exposed piping materials and suitable for the environment where installed.

1. Indoor Dry Locations: Use zinc-plated steel or approved equivalent unless otherwise indicated.

2.02 PREFABRICATED TRAPEZE-FRAMED SYSTEMS

A. Prefabricated Trapeze-Framed Metal Strut Systems:

1. Manufacturers:

a. Anvil International, LLC : www.asc-es.com/#sle.

b. Unistrut, a brand of Atkore International, Inc: www.unistrut.com/#sle.

2. Strut Channel or Bracket Material:

a. Indoor Dry Locations: Use zinc-plated steel or galvanized steel.

3. Accessories: Provide bracket covers, cable basket clips, cable tray clips, clamps, conduit clamps, fire-retarding brackets, j-hooks, protectors, and vibration dampeners.

2.03 STRUT SYSTEMS FOR PIPE OR EQUIPMENT SUPPORT

A. Strut Channels:

Plumbing Piping and Equipment 220529

a. ABB Installation Products : electrification.us.abb.com/#sle.

b. Unistrut, a brand of Atkore International Inc: www.unistrut.com/#sle.

2. ASTM A653/A653M galvanized steel bracket with clamps for surface mounting of piping or plumbing equipment support.

3. Channel or Bracket Kits: Include rods, brackets, end-fixed fittings, covers, clips, and other related hardware required to complete sectional trapeze section for piping or other support.

B. Hanger Rods:

1. Threaded zinc-plated steel unless otherwise indicated.

2. Minimum Size, Unless Otherwise Indicated or Required:

a. Piping up to 1 inch: 1/4 inch diameter.

b. Piping larger than 1 inch: 3/8 inch diameter.

C. Channel Nuts:

1. Manufacturers:

a. B-Line, a brand of Eaton Corporation : www.eaton.com/#sle.

b. Unistrut, a brand of Atkore International, Inc: www.unistrut.com/#sle.

2. Provide carbon steel channel nut with epoxy copper or zinc finish and long, regular, or short spring as indicated on drawings.

2.04 BEAM CLAMPS

A. Manufacturers:

1. B-Line, a brand of Eaton Corporation : www.eaton.com/#sle.

2. Unistrut, a brand of Atkore International, Inc: www.unistrut.com/#sle.

B. MSS SP-58 types 19 through 23, 25 or 27 through 30 based on required load.

C. C-Clamp: MSS SP-58 type 23, malleable iron and steel with plain, stainless steel, and zinc finish.

D. Small or Junior Beam Clamp: MSS SP-58 type 19, malleable iron with plain finish. For inverted usage provide manufacturer listed size(s).

E. Wide Mouth Beam Clamp: MSS SP-58 type 19, malleable iron with plain finish.

F. Centerload Beam Clamp with Extension Piece: MSS SP-58 type 30, malleable iron with plain finish.

G. Provide clamps with hardened steel cup-point set screws and lock-nuts for anchoring in place.

H. Material: ASTM A395/A395M ductile iron, ASTM A36/A36M carbon steel, ASTM A47/A47M malleable iron, ASTM A181/A181M forged steel, or ASTM A283/A283M steel.

2.05 PIPE HANGERS

A. Band Hangers, Adjustable:

1. Manufacturers:

a. B-Line, a brand of Eaton Corporation : www.eaton.com/#sle.

b. Gripple, Inc; Universal Clamp (Threaded): www.gripple.com/#sle.

c. Source Limitations: Furnish hardware, fittings, and accessories from single manufacturer.

2. MSS SP-58 type 7 or 9, zinc-plated ASTM A1011/A1011M steel or ASTM A653/A653M carbon steel.

B. J-Hangers, Adjustable:

1. Manufacturers:

a. B-Line, a brand of Eaton Corporation : www.eaton.com/#sle.

b. Unistrut, a brand of Atkore International, Inc: www.unistrut.com/#sle.

c. Source Limitations: Furnish hardware, fittings, and accessories from single manufacturer.

Plumbing Piping and Equipment 220529

2. MSS SP-58 type 5, zinc-plated ASTM A1011/A1011M steel or ASTM A653/A653M carbon steel.

C. Swivel Ring Hangers, Adjustable:

1. Manufacturers:

a. B-Line, a brand of Eaton Corporation : www.eaton.com/#sle.

b. FNW: www.fnw.com/#sle.

c. Source Limitations: Furnish hardware, fittings, and accessories from single manufacturer.

2. MSS SP-58 type 10, epoxy-painted, zinc-colored.

3. Material: ASTM A395/A395M ductile iron, ASTM A36/A36M carbon steel, ASTM

A47/A47M malleable iron, ASTM A181/A181M forged steel, or ASTM A283/A283M steel.

4. FM (AG) and UL (DIR) listed for specific pipe size runs and loads.

D. Clevis Hangers, Adjustable:

1. Manufacturers:

a. B-Line, a brand of Eaton Corporation : www.eaton.com/#sle.

b. FNW: www.fnw.com/#sle.

2. Copper Tube: MSS SP-58 type 1, epoxy-plated copper.

3.

This is the start of the file's text. The full file is on GovTribe.