22-12_Attachment C_Drawings.pdf

PDF 2 MB Posted

Attached to
22-12 Tech Tower Elevator Modernization
Solicitation number
BD-22-1064-1064-02481-73393
Issued by
Norfolk County, Massachusetts

About this file

This document contains attachments and drawings for a state and local contract opportunity for the Tech Tower Elevator Modernization project for the Massachusetts Bay Community College in Wellesley, Massachusetts. The project scope includes the modernization of the elevators in the Tech Tower building, including new elevator cabs, control systems, and supporting mechanical, electrical, and fire alarm work. The project drawings and specifications provide detailed requirements for the elevator work, as well as supporting building systems. The project is being bid as a 100% bid set, with a due date to be determined. The contract term is not specified, but it is presumed to be for the duration of the elevator modernization project.

The pricing terms and funding sources are not detailed in this document. There are no indications of any set-asides or incumbent contractors. The overall project appears to be funded by the Commonwealth of Massachusetts and Massachusetts Bay Community College. Additional salient information, such as bonding requirements, prevailing wage compliance, or small business participation, is not included in this set of attachments.

View the file

Other files

File Type Posted
Commonwealth_StandardContract2019.pdf PDF
Commonwealth_TermsConditions2019.pdf PDF
eft-form.pdf PDF
22-12 BID TAB.xlsx XLSX spreadsheet
22-12_Attachment B_Specifications.pdf PDF
Vendor_W9.pdf PDF
22-12_Attachment A_Prevailing Wage.pdf PDF
22-12_IFB_TechTowerElevatorModernization~1.doc DOC document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G0-00 COVER SHEET

G0-01 ABBREVIATIONS, SYMBOLS & MOUNTING HEIGHTS

A1-00 ATTIC & 5TH FLOOR ROOF PLAN

A1-01 TYPICAL ELEVATOR PLAN & ELEVATIONS

A1-02 ELEVATOR MACHINE ROOM PLANS & ELEVATIONS

A2-01 MACHINE ROOM STAIR DETAILS

A2-02 DOOR & HARDWARE SCHEDULE, MISC. DETAILS

H0-01 LEGEND AND SPECIFICATIONS

H0-02 MECHANICAL SCHEDULES, DETAILS & SEQUENCE OF CONTROLS

H1-01 MECHANICAL PLANS

E0-01 ELECTRICAL LEGEND AND SPECIFICATIONS

E0-02 ELECTRICAL DETAILS

E1-01 ELECTRICAL PLANS

FA0-01 FIRE ALARM LEGEND AND SPECIFIFCATIONS

FA1-01 FIRE ALARM PLANS

SHEET LIST

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

ARCHITECT: MEP ENGINEER:

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

BLW ENGINEERS INC.

G0-00 11/29/2021

100% BID SET

MASSBAY COMMUNITY COLLEGE TECH TOWER 1919 ELEVATOR MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

THE COMMONWEALTH OF MASSACHUSETTS

MASSACHUSETTS BAY COMMUNITY COLLEGE

WELLESLY HILLS, MASSACHUSETTS

LOCUS PLAN

1/32" = 1'-0"1 PROJECT SCOPE PLAN

KEYNOTE

BUILDING ELEVATION

INTERIOR ELEVATIONS

BUILDING SECTION

WALL SECTION CALLOUT

DETAIL CALLOUT

DOOR TAG

SPOT ELEVATION

WALL/PARTITION TAG

WINDOW TAG

ROOM TAG

LEVEL IDENTIFICATION

VIEW TITLE

STRUCT. GRID REFERENCE

A0.00

00 VIEW TITLE

SCALE: 1/2" = 1'-0"

0.00

A0.00

A0.00

101A

A0.00

NAME

ELEVATION

A0.00

PLAN DETAIL CALLOUT

A0.00

A

ROOM NAME

ROOM NO.

FLR FINISH

AREA

A

MATERIAL/FINISH TAG

BREAK LINE

CL CENTERLINE

REVISION CLOUD

FLOOR

ROOM #

A-Z FOR NUMBER OF

DOORS IN A ROOM

EARTH

GRANULAR FILL

BRICK OR C.S.M.U.

CONCRETE

CONCRETE MASONRY UNITS

GYPSUM WALL BOARD OR GROUT

NOM. LUMBER

FINISH WOOD

PLYWOOD

RIGID INSULATION

BATT INSULATION & MINERAL WOOL

STEEL

STONE (CUT OR CAST)

EPOXY RESIN

SPRAY FOAM INSULATION

SOLID SURFACE

BLOCKING/SHIM

AVB MEMBRANE

WATER PROOFING

FLASHING

ALUMINUM

ACCESSIBLE FIXTURES & ACCESSORIES

FEMININE NAPKIN DISPOSAL

(WOMENS TOILET ROOM STALLS, TYP.)

TOILET TISSUE DISPENSER

STANDARD TOILET STALL FIXTURES & ACCESSORIES

CL

" A

FF

CL

CL

RECESSED TOILET TISSUE

DISPENSER

1-1/2" DIA. GRAB BAR, 1-1/2"

FROM WALL

ACCESSIBLE TOILET STALL FIXTURES & ACCESSORIES

32"

CL

CL

" M

AX

FO

RW

AR

D R

EA

CH

FIRE ANNUNCIATOR

ANNUNCIATOR, THERMOSTAT, INTERCOM & CLOCK

CL

CL CL

EXIT SIGNCUSTODIAL CLOSET

SERVICE SINK W/ VINYL

RIMGUARD

" M

IN.

AF

F.

" M

AX

CL

PAPER TOWEL DISPENSER

SOAP DISPENSER

TO

CO

NT

RO

LS

" M

IN.

" M

AX

CL

CL

34"

" M

IN.

CL

" M

AX

12" MIN.24" MIN.

CL

FLUSH CONTROL (ON

WIDE SIDE OF TOILET

AREA)

18"

" M

AX

" M

AX

" 30

PHONE JACK, ELEC. OUTLET, SWITCH, FIRE ALARM HORN

& PULL STATION

" M

IN.TELEPHONE/ DATA

CONNECTION

ELEC. OUTLET

LIGHT SWITCH

PULL STATION

FIRE ALARM

AUDIO/ VISUAL DEVICE

SID

E R

EA

CH

THERMOSTAT

INTERCOM

CLOCK

ALIGN W/ DOOR

HEAD

EQ EQ

3"

4"

3"

EXIT EXIT

TACTILE EXIT SIGN

CEILING MOUNT RECESSED OR WALL

MOUNTED

NOTE: PROVIDE TACTILE EXIT SIGNAGE WHERE ILLUMINATED EXIT SIGNS ARE REQUIRED OR

WHERE REQUIRED BY CBC 1011.3

EQ EQ

CL

EXIT

4"

6" -8

EXIT

FLOOR LEVEL EXIT SIGN

BACKSPLASH, TYP.

5, 3'-0"x10" x3/4" ADJT. SHELVES ON 3 RECESSED

METAL STANDARDS. PROVIDE BLOCKING BEHIND

STANDARDS.

8"

36" MIN.

PROVIDE TWO DUPLEX OUTLETS, MIN.

" M

IN.

36" MAX.

12" MAX.

42" MIN.

54" MIN.

36" GRAB BAR

" 54

SE

E E

LE

C D

WG

S

18"

C.L. OF SINK TO WALL, MIN.

1-1/2" DIA. GRAB BAR,

1-1/2" FROM WALL

LA

TC

H S

IDE

ROOM SIGNAGE

WALL MTD. SIGNAGE

CL

3"

ACCESSIBLE DRINKING FOUNTAIN/BOTTLE FILLER

MI

N.27

" MA

X.

12" MAX

PROVIDE EQUIPMENT SHOWN

SEE SCHEDULES FOR FIXTURES AND ACCESSORES MAKE/MODEL SEE SCHEDULES FOR FIXTURES AND ACCESSORES MAKE/MODEL

OF BRAIL

SEE SCHEDULES FOR FIXTURES AND ACCESSORES MAKE/MODEL

ACCESSIBLE SHOWER STALL

FOLDING SEAT

30" X 60" STALL

CL

CL

SINGLE LEVER

CONTROL

FLEX HAND SPRAYER UNIT

CL27" MAX.

FLOOR SLOPE 2%

MAX.

RECESSED SOAP DISH

TO

TO

P O F M

NT

BR

AC

KE

T

27"

MAX.

19" MIN.

SEE SCHEDULES FOR FIXTURES AND ACCESSORES MAKE/MODEL

CENTERLINE

DEMOLISHED

HIDDEN

OVERHEAD/BEYOND

GRID LINE

PROPERTY LINE / PROJECT SCOPE

MATCH LINE

SUPPLY DIFFUSER

EXHAUST DIFFUSER

RECESSED LIGHT FIXTURE

SURFACE MOUNTED LIGHT FIXTURE

WALL MOUNTED LIGHT FIXTURE

DUPLEX

DUPLEX WITH GROUND FAULT

QUADPLEX

QUADPLEX WITH GROUND FAULT

TEL/DATA OUTLET

LINEAR DIFFUSER

PROJ SCR PROJECTION SCREEN

PROP PROPOSED

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT(ED)

PT PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTDR PAPER TOWEL DISPENSER & RECEPTOR

PTN PARTITION

PTR PAPER TOWEL RECEPTOR

PVC POLYVINYL CHLORIDE

PVMT PAVEMENT

PWD PLYWOOD

QT QUARRY TILE

QTY QUANTITY

R RISER

RA RETURN AIR

RAD RADIUS

RB RUBBER BASE

RBH ROBE HOOK

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RE REINFORCE(D), (ING)

REF REFERENCE

REFR REFRIGERATOR

REM REMOVE

REQD REQUIRED

RES RESILIENT

REV REVISION

RFL REFLECT(ED), (IVE), (OR)

RH RIGHT HAND

RM ROOM

RO ROUGH OPENING

RSF RESILIENT SHEET FLOORING

RT RESILIENT TILE

RWL RAINWATER LEADER

S SOUTH

SA SPRAY ACOUSTIC

SB SINK BASE

SC SEALED CONCRETE

SCH SCHEDULE

SD SOAP DISPENSER

SEC SECTION

SH SHELF, SHEVLING

SHT SHEET

SHTH SHEATHING

SHWR SHOWER

SIM SIMILAR

SJT SEISMIC EXPANSION JOINT

SM SHEET METAL

SND SANITARY NAPKIN DISPENSER

SNR SANITARY NAPKIN RECEPTOR

SNT SEALANT

SOG SLAB ON GRADE

SPEC SPECIFICATION(s)

SQ SQUARE

SST STAINLESS STEEL

ST STAIR

STA STATION

STC SOUND TAMISSION CLASS

STD STANDARD

STL STEEL

STOR STORAGE

STR STRUCTUR(E), (AL)

SUSP SUSPENDED

T TREAD

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

TB TOWEL BAR

TC TERRA COTTA

TC TOP OF CONCRETE

TEL TELEPHONE

TEMP TEMPORARY

TF TOP OF FOOTING

THK THICK(NESS)

TJ TOP OF JOIST

TKBD TACKBOARD

TPD TOILET PAPER DISPENSER

TSL TOP OF SLAB

TST TOP OF STEEL

TW TOP OF WALL

TYP TYPICAL

TZ TERRAZZO

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF, V.I.F. VERIFY IN FIELD

VIN VINYL

VP VENEER PLASTER

VPWD VENEER PLYWOOD

VWC VINYL WALL COVERING

W WEST, WIDE, WIDTH

W/ WITH

WC WATER CLOSET

WD WOOD

WH WATER HEATER

WI WROUGHT IRON

WIN WINDOW

WM WIRE MESH

WO WITHOUT

WP WORK POINT

WT WEIGHT

WWF WELDED WIRE FABRIC

ZTC ZINC-TIN COATED

ZTCC ZINC-TIN COATED COPPER

FF FINISHED FLOOR

FFE FURNITURE, FIXTURES & EQUIPMENT

FFO FLUSH FLOOR OUTLET

FHC FIRE HOSE CABINET

FHWS FLATHEAD WOOD SCREW

FIN FINISH(ED)

FIXT FIXTURE

FLG FLASHING

FLR FLOOR(ING)

FLUOR FLUORESCENT

FOC FACE OF CONCRETE

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF STUD

FPRF FIREPROOF

FR FIRE RATING, FRAME

FS FULL SIZE

FSS FOLDING SHOWER SEAT

FT FIRE TREATED

FTG FOOTING

FUR FURRED(ING)

GA GAGE, GAUGE

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GD GRADE, GRADING

GF GROUND FACE

GL GLASS, GLAZING

GLB GLASS BLOCK

GMU GLASS MASONRY UNIT

GR GRILLE

GT GROUT

GWB GYPSUM WALLBOARD

HB HOSE BIB

HC HOLLOW CORE

HD HAND DRYER

HDB HARDBOARD

HDW HARDWARE

HM HOLLOW METAL

HORZ HORIZONTAL

HP HIGH PERFORMANCE

HPT HIGH PAINT

HR HOUR

HT HEIGHT

HVAC HEATING/VENTILATING/AIR CONDITIONING

ID INSIDE DIAMETER

IDF INTERMEDIATE DISTRIBUTION FACILITY

IN INCH

INCL INCLUDE(D), (ING)

INSUL INSULATE(D), (ION)

INT INTERIOR

INV INVERT

J JOIST

JAN JANITOR

JT JOINT

KIT KITCHEN

LAM LAMINATE(D)

LAV LAVATORY

LCC LEAD-COATED COPPER

LCKR LOCKER

LH LEFT HAND

LNDG LANDING

LPT LOW POINT

LS LIGHT SWITCH

LT LIGHT

LTWT LIGHT WEIGHT

LVR LOUVER

M MIRROR

M.A.S. MASONRY ANCHORING SYSTEM

MACH MACHINE

MAS MASONRY

MAT MATERIAL(S)

MAX MAXIMUM

MBH MOP & BROOM HOLDER

MBRD MACHINE BOARD

MBRD MARKER BOARD

MC MEDICINE CABINET

MECH MECHANICAL

MFR MANUFACTURE(R)

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLDG MOLDING, MOULDING

MN MANUAL

MO MASONRY OPENING

MOD MODULAR

MR MOISTURE RESISTANT

MTD MOUNTED

MTL METAL

MWRK MILLWORK

N NORTH

NA NOT APPLICABLE

NC NONCORROSIVE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NPS NOMINAL PIPE SIZE

NTS NOT TO SCALE

OA OVERALL

OC, O.C. ON CENTER(S)

OD OUTSIDE DIAMTER

OFOI OWNER FURNISHED, OWNER INSTALLED

OH OVERHEAD

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OTA OPEN TO ABOVE

OTB OPEN TO BELOW

OZ OUNCE

P.L. E.L. PRECAST LINTEL ELEVATION

PBD PARTICLE BOARD

PERF PERFORATE(D)

PFB PREFABRICATE(D)

PL PLASTER

PLAM PLASTIC LAMINATE

PLN PLAN

PM PRESSED METAL

PNL PANEL

PR PAIR

PRL PICTURE RAIL

A/C AIR CONDITIONING

AB ANCHOR BOLT

ABV ABOVE

ACOUS ACOUSTICAL

ACT ACOUSTICAL TILE

ADA AMERICANS W/ DISABILITIES ACT

ADD ADDENDUM

ADH ADHESIVE

ADJ ADJACENT

ADJT ADJUSTABLE

AESS ARCHITECTURALLY EXPOSED STRUCTURAL

STEEL

AF ATHLETIC FLOOR(ING)

AFF ABOVE FINISHED FLOOR

AGG AGGREGATE

AL ALUMINUM

ALRM ALARM

ALT ALTERNATE

AMT AMOUNT

ANC ANCHOR, ANCHORAGE

ANOD ANODIZED

AP ACCESS PANEL, ACOUSTIC PANEL

APPROX APPROXIMATE

ARCH ARCHITECT(URAL)

AUTO AUTOMATIC

AVG AVERAGE

AWP ACOUSTIC WALL PANEL

BBRD BULLETIN BOARD

BD BOARD

BD BODY DRYER

BDF BLDG DISTRIBUTION FACILITY

BEL BELOW

BIT BITUMINOUS

BKT BRACKET

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BM BEAM

BOT BOTTOM

BRG BEARING

BRK BRICK

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT-UP ROOFING

BW BOTTOM OF WALL

CAB CABINET

CB CEMENT BOARD

CBRD CHALK BOARD

CD COMBINATION DISPENSER

CEM CEMENT

CG CORNER GUARD

CI CAST IRON

CJT CONTROL JOINT

CLNG CEILING

CLO CLOSET

CLR CLEAR(ANCE)

CMU CONCRETE MASONRY UNIT

CO CLEANOUT

COL COLUMN

COMP COMPRESS(ED), (ION), (IBLE)

CONC CONCRETE

CONST CONSTRUCTION

CONT CONTINUOUS, CONTINUE(D)

CONTR CONTRACTOR

CORR CORRIDOR

CPT CARPET(ED)

CRS COURSE

CSFH COUNTERSUNK FLAT HEAD

CT CERAMIC TILE

CTR CENTER

CTSK COUNTERSINK

CUH CABINET UNIT HEATER

DA DOUBLE ACTING

DBL DOUBLE

DCS DIAPER CHANGING STATION

DEMO DEMOLISH, DEMOLITION

DEPR DEPRESS(ED), (ION)

DEPT DEPARTMENT

DF DRINKING FOUNTAIN

DIAM DIAMETER

DIM DIMENSION

DISP DISPOSAL

DN DOWN

DO DOOR OPENING

DP DISABLED PERSONS

DPR DISPENSER

DR DOOR

DTL DETAIL

DW DISHWASHER

DWG DRAWING

DWR DRAWER

E EAST

EA EACH

EJT EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC(AL)

ELEV ELEVATOR

EM ENTRY MAT

EMER EMERGENCY

ENC ENCLOSE(URE)

EQ EQUAL

EQP EQUIPMENT

ERA EXTERIOR ROOF ASSEMBLY

ETR EXISTING TO REMAIN

EWA EXTERIOR WALL ASSEMBLY

EWC ELECTRIC WATER COOLER

EXG EXISTING

EXH EXHAUST

EXP EXPANSION, EXPOSED

EXP EXPOSED

EXT EXTERIOR

EXTD EXTRUDED

FA FIRE ALARM, FLOOR ASSEMBLY

FAB FABRICATED

FB FIBER BOARD

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

ARCHITECTURAL ABBREVIATIONS ARCHITECTURAL SYMBOLS

MATERIAL PATTERNS

STANDARD MOUNTING HEIGHTS

ARCHITECT

MECHANICAL ELECTRICAL

PLUMBING ENGINEERING

STAMP

REVISIONS

NUMBER DATE DESCRIPTION

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

BLW ENGINEERS INC.

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

KEY PLAN

ABBREVIATIONS,

SYMBOLS &

MOUNTING HEIGHTS

03/21/2022

MASSBAY

COMMUNITY COLLEGE

TECH TOWER 1919

ELEVATOR

MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

G0-01

100% BID SET

0 42

NORTHMEP COORDINATION

LINETYPES

ARCHITECT

MECHANICAL ELECTRICAL

PLUMBING ENGINEERING

STAMP

REVISIONS

NUMBER DATE DESCRIPTION

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

BLW ENGINEERS INC.

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

KEY PLAN

ATTIC & 5TH FLOOR

ROOF PLAN

03/21/2022

MASSBAY

COMMUNITY COLLEGE

TECH TOWER 1919

ELEVATOR

MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

A1-00

100% BID SET

1/16" = 1'-0"1 ATTIC LEVEL PLAN

NEW HEAT PUMP, SEE ELECTRICAL &

MECHANICAL DRAWINGS FOR DETAILS

ETR ROOFTOP UNITS

ELEVATOR

MACHINE

ROOM

SHAFT V.I.F.

5'-7 1/2"

2'- 1 1

/2" 3'-

4" 2'-

1 1 /2"

SH

AF

T V .I.F

8'-

6 1 /4"

PL

AT

F O

RM

6'- 3"

CA

B

5'-

SHAFT

5'-7 1/2"

V.I .F.

2'- 1 1

/2" V.I

.F.

3'-

4" V.I

.F.

2'-

1 1 /2"

V.I .F.

8'- 6 1

/4" A1-01 6

A1-01 9

PL

AT

F O

RM

6'- 3"

EL

EV

AT

OR

SH

AF

T 7'-

7"

PLATFORM

4'-11 1/2"

EQEQ

8" 2'-

6" 4"

EQ EQ EQ

V.I .F.

3'- 6"

3'- 2"

4"

EQ EQ

V.I.F.

4'-1 1/2"

A1-01

4" 2'-

6" 8"

V.I.F.

5'-11"

2'- 2"

4"

CL

3'- 6"

3'- 6"

A1-01 6

CA

B

5'-

CAB

4'-1 1/2"

A1-01

EQ

EQ

EQ

EQ EQ

PLAM PLAM

#4 SATIN SS

A1-01

1" 1/8"

1" 1/8

1/8" 1/4" 1/8"

1/4

ARCHITECT

MECHANICAL ELECTRICAL

PLUMBING ENGINEERING

STAMP

REVISIONS

NUMBER DATE DESCRIPTION

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

BLW ENGINEERS INC.

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

KEY PLAN

TYPICAL ELEVATOR

PLAN & ELEVATIONS

03/21/2022

MASSBAY

COMMUNITY COLLEGE

TECH TOWER 1919

ELEVATOR

MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

A1-01

100% BID SET

1/2" = 1'-0"1 EXISTING TYPICAL ELEVATOR FLOOR PLAN

1/2" = 1'-0"2 TYPICAL ELEVATOR FLOOR CONSTRUCTION PLAN

1/2" = 1'-0"5 INTERIOR ELEVATION - ELEVATOR CAB - NORTH

1/2" = 1'-0"6 INTERIOR ELEVATION - ELEVATOR CAB - EAST

1/2" = 1'-0"7 INTERIOR ELEVATION - ELEVATOR CAB - SOUTH

1/2" = 1'-0"8 INTERIOR ELEVATION - ELEVATOR CAB - WEST

1/2" = 1'-0"9 INTERIOR ELEVATION - TYPICAL ELEVATOR ENTRY (APPLY TO ALL 5 FLOORS)

1/2" = 1'-0"3 ELEVATOR CAB PLAN

1/2" = 1'-0"4 ELEVATOR CAB REFLECTED CEILING PLAN

HIGH IMPACT PLASTIC LAMINATE

1/2" STAINLESS STEEL TRIM

BETWEEN PLASTIC LAMINATE

PANELS

#4 SATIN STAINLESS STEEL PANEL

#4 SATIN STAINLESS STEEL BASE

#4 SATIN STAINLESS STEEL BASE

HIGH IMPACT PLASTIC LAMINATE

1" STAINLESS STEEL TRIM AROUND

ELEVATOR DOOR, VERIFY EXACT DOOR

LOCATION WITH EXISTING OPENING

#4 SATIN STAINLESS STEEL PANELS

1/2" STAINLESS STEEL TRIM

BETWEEN PLASTIC LAMINATE &

STAINLESS STEEL PANELS

SATIN STAINLESS STEEL CEILING

LED DOWNLIGHT, TYP.

NEW 12" TILE, FINISH SELECTION

WILL

BE MADE IN THE SUBMITTAL

PROCESS

TILE SETTING OUT POINT

NEW CALL BUTTION W/ LANTERN

TO MATCH EXISTING

EXISTING OPENING

NEW 2" STAINLESS STEEL WRAP

OVER ETR METAL FRAME

#4 SATIN STAINLESS STEEL

ELEVATOR DOOR

ELEVATOR CONTROL PANEL

ACCESS HATCH LOCATION

2"x1/4" SATIN STAINLESS

STEEL HANDRAIL

HIGH IMPACT PLASTIC

LAMINATE

1/2" STAINLESS STEEL TRIM

BETWEEN PLASTIC LAMINATE

PANELS

#4 SATIN STAINLESS

STEEL PANEL

#4 SATIN STAINLESS

STEEL BASE

#4 SATIN STAINLESS STEEL

PANELS

HIGH IMPACT PLASTIC LAMINATE

1/2" STAINLESS STEEL TRIM

BETWEEN PLASTIC LAMINATE

PANELS

#4 SATIN STAINLESS

STEEL PANELS

#4 SATIN STAINLESS STEEL BASE

HANDRAIL MOUNT (3)

CENTERED ON EACH PANEL

3" = 1'-0"10 ELEVATION DETAIL - ELEVATOR PANEL TRIM

3" = 1'-0"11 PLAN DETAIL - ELEVATOR CORNER TRIM

3" = 1'-0"12 PLAN DETAIL - ELEVATOR PANEL TRIM

1/8" STAINLESS

STEEL TRIM

1/8" STAINLESS

STEEL TRIM

2"x1/4" SATIN STAINLESS

STEEL HANDRAIL

1/8" STAINLESS

STEEL TRIM

NEW STAINLESS STEEL CORNER

GUARDS

ALUMINUM PAD BUTTONS,

TYP.

ALUMINUM PAD BUTTONS,

TYP.

ALUMINUM PAD BUTTONS,

TYP.

1/4" REVEAL, PAINTED. PAINT

COLOR SELECTION TO BE MADE IN

SUBMITTAL PROCESS

HANDRAIL MOUNT (2)

CENTERED ON EACH PLAM

PANEL

2"x1/4" SATIN STAINLESS

STEEL HANDRAIL

HANDRAIL MOUNT (2) CENTERED

ON EACH PLAM PANEL

2"x1/4" SATIN STAINLESS

STEEL HANDRAIL

HANDRAIL MOUNT (2)

CENTERED ON EACH PLAM

PANEL ABOVE

2"x1/4" SATIN STAINLESS

STEEL HANDRAIL

HANDRAIL MOUNT (2)

CENTERED ON EACH PLAM

PANEL ABOVE

UP

V.I.F.

8'-0"

V.I .F.

9'-

9"EXISTING

POWER

UNIT TO BE

REMOVED

V.I.F.

8'-0"

V.I .F.

9'- 9"A1-02 4

A1-02

A1-02

7 A1-029

NEW

POWER

UNIT

A2-01

NEW POWER UNIT

NEW POWER UNIT

NEW POWER UNIT

ARCHITECT

MECHANICAL ELECTRICAL

PLUMBING ENGINEERING

STAMP

REVISIONS

NUMBER DATE DESCRIPTION

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

BLW ENGINEERS INC.

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

KEY PLAN

ELEVATOR MACHINE

ROOM PLANS &

ELEVATIONS

03/21/2022

MASSBAY

COMMUNITY COLLEGE

TECH TOWER 1919

ELEVATOR

MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

A1-02

100% BID SET

1/2" = 1'-0"1 ELEVATOR MACHINE ROOM DEMOLITION PLAN

1/2" = 1'-0"2 ELEVATOR MACHINE ROOM CONSTRUCTION PLAN

1/2" = 1'-0"3 INTERIOR ELEVATION - ELEVATOR MACHINE ROOM - NORTH

1/2" = 1'-0"4 INTERIOR ELEVATION - ELEVATOR MACHINE ROOM - EAST

1/2" = 1'-0"5 INTERIOR ELEVATION - ELEVATOR MACHINE ROOM - SOUTH

1/2" = 1'-0"7 INTERIOR ELEVATION - OUTSIDE ELEVATOR MACHINE ROOM - WEST

1/2" = 1'-0"8 INTERIOR ELEVATION - OUTSIDE ELEVATOR MACHINE ROOM - SOUTH

1/2" = 1'-0"9 INTERIOR ELEVATION - OUTSIDE ELEVATOR MACHINE ROOM - EAST

DEMO 12"x12" (1sf)

FLOOR GRILLE

ETR 24"x24" LOUVER

EXTENT OF ELEVATOR

SHAFT BELOW

EXISTING OIL LINE

NEW 12"x36" (3sf)

FLOOR GRILLE

1/2" = 1'-0"6 INTERIOR ELEVATION - ELEVATOR MACHINE ROOM - WEST

ETR 24"X24" LOUVER

EXTENT OF ELEVATOR

SHAFT BELOW

ETR OIL LINE

DEMO STAIRS

DEMO DOOR

ETR 24"x24" LOUVER

ETR UNDERSIDE OF ROOF

NEW 1 1/2-HR RATED

DOOR IN EXISTING

MASONRY OPENING,

VERIFY EXISTING

OPENING IN FIELD

NEW OPEN METAL

GRATE STAIR

DEMO STAIR, LANDING

& RAILINGS

ETR 24"X24" LOUVER

NEW OPEN METAL

GRATE STAIR, REFER

TO A2-01 FOR DETAILS

NEW OPEN METAL

GRATE STAIR, REFER

TO A2-01 FOR DETAILS

A2-01

A2-01

A2-01

ELEVATOR MACHINE ROOM

1 1 /2"

2'- 2"

2'- 2"

2 1 /2"

A2-02

A2-02

6R @ 11"EA

5'-6" 3'-8 3/8" 3"

3/4" 2'-9" 2'-9"

4' -8

A2-01

C12X20.7 STRINGER

HS

S 4

X4 X1

/4

1'- 6"

1'- 6"

3'-

2'-2" 2'-2"

A2-01

A2-01

A2-01

7-

RIS

ER

V.I

.F.

1'-

6" 1'-

6"

2'-9"2'-9"1'-11 3/8"1'-11 3/8"

C12X20.7 STRINGER

HS

S 4

X4 X1

/4

1'-0"

9'-4 3/4"

A2-01

A2-01

4" 1/4" 1'-2" 1/4" 4 3/4" 1/8"

1'-1 1/2" 1/4"

6"

4"

1'-0"

1'- 6"

1'- 6"

7-

RIS

ER

S

" V

.I.F

A2-022'-9"2'-9"

2 1 /2"

4" 1/2

2"

2"

6"

6"

ARCHITECT

MECHANICAL ELECTRICAL

PLUMBING ENGINEERING

STAMP

REVISIONS

NUMBER DATE DESCRIPTION

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

BLW ENGINEERS INC.

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

KEY PLAN

MACHINE ROOM

STAIR DETAILS

03/21/2022

MASSBAY

COMMUNITY COLLEGE

TECH TOWER 1919

ELEVATOR

MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

A2-01

100% BID SET

1" = 1'-0"1 ENLARGED PLAN - MACHINE ROOM STAIR

1" = 1'-0"3 CROSS SECTION - ELEVATOR MACHINE ROOM STAIR - EAST

1" = 1'-0"2 CROSS SECTION - ELEVATOR MACHINE ROOM STAIR - SOUTH

GALVINIZED HANDRAIL @ 18"

& 36", 1 1/2" DIA.

SCHEDULE 40 STEEL TUBE

C12X20.7 STRINGER

HSS4X4X1/4 CORNER POST,

WELDED TO C12 STRINGERS

HSS4"x4"x1/4" CORNER

POST, WELDED TO C12

STRINGERS

C12X20.7 STRINGER

1" = 1'-0"4 CROSS SECTION - ELEVATOR MACHINE ROOM STAIR - NORTH

2"x3/16"x1 1/2"D GALVI

GRATING STAIR TREAD W/

CHECKER PLATED GALVI NOSING

GALVINIZED STEEL BALUSTER,

WELD TO C12 STRINGER

GALVINIZED HANDRAIL @ 18"

& 36", 1 1/2" DIA.

SCHEDULE 40 STEEL TUBE

GALVINIZED HANDRAIL @ 18"

& 36", 1 1/2" DIA.

SCHEDULE 40 STEEL TUBE

2X2 GALVI STEEL ANGLE TREAD

SUPPORT SHOP WELDED TO

STRINGER

2"x2"x1/4" GALVI STEEL ANGLE SHOP WELDED TO STRINGER W/ 1/2"x 4 1/2"

EPOXY INJECTED GALVI ANCHOR BOLTS

INTO EXISTING CONCRETE SLAB

CONTINUOUS 2X2 GALVI STL SUPPORT

ANGLE, SHOP WELD ANGLES ONTO

STRINGER PRIOR TO DELIVERING ON SITE

CONTINUOUS 2"x2"x1/4" GALVI STL

SUPPORT ANGLE, SHOP WELD ANGLES

ONTO STRINGER PRIOR TO DELIVERING

ON SITE

2X2 GALVI STEEL ANGLE TREAD

SUPPORT SHOP WELDED TO TO

STRINGER

2"x 3/16" x1 1/2" GALVI

GRATING STAIR TREAD W/

CHECKER PLATED GALVI NOSING

HSS4X4X1/4 CORNER POST,

WELDED TO C12 STRINGERS

3" = 1'-0"5 METAL GRATE WALKWAY - ANCHOR DETAIL

2"X1/4" GALVI GRATING

2"x2"x1/4" GALVI STL SUPPORT ANGLE, SHOP WELD ANGLES ONTO STRINGER

PRIOR TO DELIVERING ON SITE

GALVI STL GRATING CLIP FASTENED TO

STL SUPPORT ANGLE

STL GRATE CLIP FASTENER

3" = 1'-0"6 TYPICAL METAL GRATE STAIR TREAD

2X2 GALVI STEEL ANGLE TREAD

SUPPORT SHOP WELDED TO

STRINGER

2"L x 3/16"W x 1 1/2"D GALVI

GRATING STAIR TREAD W/

CHECKER PLATED GALVI NOSING

GALVI STL GRATING CLIP

FASTENED TO STL

SUPPORT ANGLE

STL GRATE CLIP FASTENER

C12X20.7 STRINGER

3" = 1'-0"7 STAIR CONNECTION DETAIL

2"x3/16"x1 1/2"D GALVI

GRATING

2"L x 3/16"W x 1 1/2"D GALVI

GRATING

ETR STEEL CHANNEL, VERIFY

EXACT SIZE OF CHANNEL IN

FIELD PRIOR TO FABRICATING

STEEL ATTACHMENTS

2X2 GALVI STL SUPPORT ANGLE, SHOP

WELD ANGLES ONTO STRINGER PRIOR TO

DELIVERING ON SITE

CHECKER PLATED GALVI

STEEL NOSING

2"L x 3/16"W x 1 1/2"D GALVI

GRATING

C9X20 INTERMEDIATE

STEEL CHANNEL SUPPORT

L6"x6"x1/4" THICK STEEL ANGLE SHOP

WELDED TO C12 STRINGER PRIOR TO

BEING DELIVERED ON SITE ON ONE SIDE.

OTHER SIDE BOLTED TO ETR STEEL

CHANNEL

FASTEN STEEL PLATE TO EXISTING STEEL

CHANNEL. DRILL HOLES INTO EXISTING

CHANNEL

1/2"Dx4 1/2"L GALVI ANCHOR

BOLT EPOXY INJECTED INTO

ETR CONCRETE SLAB

2X2 GALVI STL SUPPORT ANGLE

BOLTED TO ETR STEEL CHANNEL

2"x3/16"x1 1/2"D GALVI

GRATING STAIR TREAD W/

CHECKER PLATED GALVI NOSING

4"x2"x1/4" GALVI STL SUPPORT ANGLE, SHOP WELD ANGLES ONTO STRINGER

PRIOR TO DELIVERING ON SITE

C9X20 INTERMEDIATE STEEL CHANNEL

SUPPORT

C9X20 STEEL CHANNEL

SUPPORTS

4"x2"x1/4" GALVI STL SUPPORT

ANGLE, SHOP WELD ANGLES ONTO

STRINGER PRIOR TO DELIVERING

ON SITE

1/2"Dx4 1/2"L GALVI ANCHOR

BOLT FASTENED TO ETR STEEL

CHANNEL

6"x6"x1/4" GALVI STEEL PLATE W/ 1/2"x 4 1/2" EPOXY INJECTED GALVI ANCHOR

BOLTS INTO EXISTING CONCRETE SLAB

2"x2"x1/4" GALVI STEEL ANGLE SHOP WELDED TO STRINGER W/ 1/2"x 4 1/2"

EPOXY INJECTED GALVI ANCHOR BOLTS

INTO EXISTING CONCRETE SLAB

ITEM DESCRIPTION / FUNCTION HARDWARE SET

BUTTS AND HINGES / PIVOT SET01

DOOR STOP: FLOOR OR WALL AS NEEDED

CLOSER (ANSI A156.4)

KICK PROTECTION PLATE (34" WIDE X 8" HIGH, BOTH SIDES OF DOOR)

DOOR HARDWARE SCHEDULE

KICK-DOWN HOLD OPEN

LOCATIONS:

NEW

DOOR

NOTE: SEE SPEC SECTION 087100 DOOR HARDWARE

ALL FINISHES SHALL BE US32D SATIN STAINLESS STEEL UNLESS NOTED OTHERWISE

PERIMETER FIRE + SMOKE SEAL (NFPA 80 + 285, UL10B, UL10C)

MORTISE LOCKSET (ANSI A156.13, F07 STOREROOM)

DOOR SWEEP (UL10B, UL10C)

HMF = HOLLOW METAL FRAME

DOOR + HW NOMENCLATURE

SSFP = STEEL SHEET, FACTORY PRIME, FIELD PAINT

SF = SINGLE FLUSH

SIC = STEEL INSULATED CORE

6 1/8" 1 3/4" 2 5/8" 1 3/4"

1/4"

A2-02

1 3/4" 3'-0" 2"

V.I.F.

3'-4" MASONRY OPENING

ARCHITECT

MECHANICAL ELECTRICAL

PLUMBING ENGINEERING

STAMP

REVISIONS

NUMBER DATE DESCRIPTION

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

BLW ENGINEERS INC.

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

KEY PLAN

DOOR & HARDWARE

SCHEDULE, MISC.

DETAILS

03/21/2022

MASSBAY

COMMUNITY COLLEGE

TECH TOWER 1919

ELEVATOR

MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

A2-02

100% BID SET

DOOR SCHEDULE

Ty pe

M ar k

W idt h

He igh t

Fr am e T yp e

Ha rd wa re

Fir e R at ing

Comments

1 3'-0" 7'-0" HMF 1 1 1/2-HR SF, SIC, SSFP

3" = 1'-0"1 SECTION DETAIL - ELEVATOR MACHINE ROOM DOOR

3" = 1'-0"2 PLAN DETAIL - ELEVATOR MACHINE ROOM DOOR

ETR 6" CMU

NEW MASONRY ANCHORS

NEW HOLLOW METAL FRAME

NEW HOLLOW METAL FRAME

CONCRETE BEAM OVER

MASONRY OPENING

SEALANT W/ BACKER ROD

SINGLE FLUSH, STEEL

INSULATED CORE, 1 1/2 HR-

RATED

SINGLE FLUSH, STEEL

INSULATED CORE, 1 1/2 HR-

RATED

NEW MASONRY ANCHORS

ETR CONCRETE SLAB

ETR STEEL CHANNEL

THRESHOLD, FASTENED INTO

ETR CONCRETE SLAB

*VERIFY EXISTING OPENING IN FIELD PRIOR TO ORDERING NEW DOOR

1. MECHANICAL WORK INDICATED (PIPING, DUCT, ETC.) IS DIAGRAMMATIC. EXACT LOCATIONS OF ALL COMPONENTS ARE TO BE DETERMINED IN THE FIELD (SPACING SUBJECT TO ARCHITECT'S REVIEW AND APPROVAL) TO AVOID CONFLICT WITH OTHER TRADES

AND EXISTING SITE CONDITIONS.

2. THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THE SITE TO IDENTIFY EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE WORK OF THIS SECTION. REPORT IN WRITING (THROUGH THE GENERAL CONTRACTOR) TO THE OWNER AND ARCHITECT ANY CONDITIONS WHICH MIGHT ADVERSELY AFFECT WORK. NO EXTRA PAYMENT WILL BE PROVIDED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY AN EXPERIENCED OBSERVER.

3. WORK REQUIRING INTERRUPTION OF BUILDING SERVICES SHALL BE CAREFULLY REVIEWED AND COORDINATED WITH THE OWNER TO

MINIMIZE FREQUENCY AND DURATION OF SERVICE INTERRUPTIONS.

4. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION OF CEILING GRID, DIFFUSERS, AND GRILLES.

5. ALL INSTALLATIONS SHALL PERMIT AND PROVIDE ACCESSIBILITY FOR SERVICE AND REPLACEMENT OF ALL NEW EQUIPMENT AND

EXISTING EQUIPMENT IMPACTED BY THIS WORK.

6. COORDINATE ALL OPENINGS IN FLOORS WITH STRUCTURAL DRAWINGS AND GENERAL CONTRACTOR.

7. COORDINATE ALL ROOF OPENINGS WITH ARCHITECT AND STRUCTURAL ENGINEER.

8. REFER TO STRUCTURAL FRAMING PLANS FOR EXACT LOCATION OF ALL ROOF MOUNTED EQUIPMENT.

9. ALL MECHANICAL EQUIPMENT, PIPING, AND DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF GOVERNING LOCAL, STATE, AND FEDERAL SEISMIC CODES. PARTICULAR ATTENTION SHALL BE MADE TO VIBRATION ISOLATION, ANCHORING, AND BALANCING REQUIREMENTS.

10. ALL DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH CODES AND STANDARDS SET FORTH IN NFPA, SMACNA, AND ASHRAE

FOR MEDIUM AND LOW PRESSURE DUCTWORK SYSTEMS.

11. ALL EXPOSED DUCTWORK SHALL BE PAINTED TO MATCH CEILING. REFER TO ARCHITECTURAL DRAWINGS.

12. PROVIDE MANUAL VOLUME DAMPERS AT ALL BRANCH DUCTS FOR AIR BALANCING. ALL VOLUME DAMPERS LOCATED ABOVE INACCESSIBLE CEILING OR BEHIND INACCESSIBLE WALL SHALL BE PROVIDED WITH REMOTE WIRE DAMPER AT THE AIR OUTLETS.

13. ALL SHEET METAL PLENUMS AT OUTSIDE AIR LOUVERS SHALL BE INSULATED WITH RIGID INSULATION, AS PER SPECIFICATION.

14. RUN-OUTS TO RETURN AND EXHAUST REGISTERS, OR GRILLES ABOVE GYP BOARD CEILINGS, SHALL BE RIGID DUCTED. NO FLEXIBLE

DUCT WORK SHALL BE ALLOWED ON RETURN OR EXHAUST REGISTERS.

15. ALL DUCTS, PIPES, AND EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED FROM THE BUILDING STRUCTURE WITH PROPER

ALLOWANCES FOR CONTRACTION, EXPANSION, AND VIBRATION ELIMINATION.

16. PROVIDE COPPER 1" RUN-OUTS TO HOT WATER REHEAT COILS, CABINET HEATERS AND UNIT HEATERS UNLESS NOTED OTHERWISE.

17. PROVIDE SWING JOINTS AT ALL BRANCH CONNECTIONS TO HYDRONIC EQUIPMENT.

18. ROOM THERMOSTATS SHALL BE MOUNTED 4'-0" ABOVE FINISHED FLOOR UNLESS OTHERWISE SHOWN OR DIRECTED.

19. COORDINATE EXACT LOCATION OF UNIT HEATERS WITHIN ELECTRIC ROOMS WITH ELECTRICAL CONTRACTOR.

20. REFER TO SPECIFICATIONS FOR TYPE OF VALVE TO BE USED. VALVES ARE SHOWN ON PLANS FOR PLACEMENT ONLY.

21. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR FREE AREA REQUIRED.

22. ALL DIFFUSER, REGISTER, AND GRILLE SIZES INDICATED ON FLOOR PLANS ARE NECK SIZE REQUIRED.

23. ALL PIPING IS TO BE SLOPED A MINIMUM OF 1/4" PER HUNDRED FEET IN THE DIRECTION OF DRAINAGE.

24. NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED ON THIS PROJECT.

25. COORDINATE ENTIRE INSTALLATION WITH THE WORK OF ALL OTHER TRADES PRIOR TO ANY FABRICATION OR INSTALLATIONS.

26. OBTAIN ALL REQUIRED PERMITS AND PAY ALL FEES RELATED TO SAME.

27. REVIEW ALL ARCHITECTURAL, STRUCTURAL, PLUMBING, ELECTRICAL, FIRE PROTECTION AND SITE DRAWINGS BEFORE STARTING ANY WORK TO BECOME FAMILIAR WITH THE DETAILS OF CONSTRUCTION, AND COORDINATE WITH OTHER TRADES.

28. PROVIDE ALL NECESSARY PIPING, EQUIPMENT AND SUPPORTS AS WELL AS ANY ADDITIONAL EQUIPMENT, ETC. NOT SHOWN ON THE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS BUT NECESSARY TO PROVIDE COMPLETE AND WORKABLE SYSTEMS.

29. PROVIDE ACCESS TO ALL EQUIPMENT REQUIRING PERIODIC SERVICE AND MAINTENANCE.

30. DO NOT SCALE THESE DRAWINGS. TAKE ALL MEASUREMENTS IN THE FIELD IN COORDINATION WITH ALL EQUIPMENT AS APPROVED

AND WITH ALL OTHER TRADES.

31. FOR EQUIPMENT SCHEDULES, SEE DRAWING H0.2

32. ALL DUCTWORK SHALL BE INSTALLED ON ACCORDANCE WITH THE LATEST EDITION OF SMACNA

33. ALL HOT WATER, REFRIGERANT AND CONDENSATE PIPING SHALL BE INSULATED IN ACCORDANCE WITH THE MASSACHUSETTS STATE

BUILDING CODE.

34. ALL PIPING HIGH POINTS SHALL HAVE 3/4 INCH VENTS AND LOW POINTS SHALL HAVE 3/4" DRAINS.

35. ALL ROTATING EQUIPMENT SHALL HAVE FLEXIBLE PIPE ON DUCT CONNECTIONS AND APPROVED VIBRATION ISOLATORS.

36. DETAILS SHOWN ON SHEET H0.3 AND H0.4 ARE APPLICABLE TO ALL EQUIPMENT, EXCEPT WHERE INDICATED.

37. PROVIDE AIRTIGHT ACCESS DOOR FOR INSPECTION OF FIRE DAMPERS, FILTERS, AND COILS.

38. CONTRACTOR SHALL VERIFY DUCT, PIPING AND EQUIPMENT LOCATIONS FOR INTERFERENCES BEFORE INSTALLATION.

39. PROVIDE VERTICAL SUPPORTS FOR HOT WATER, REFRIGERANT AND CONDENSATE PIPING AT THE FOLLOWING MAXIMUM INTERVALS;

15' FOR 6"& 5" DIAMETER PIPE; 12' FOR 4" DIAMETER PIPE; 10' FOR 3" & 2-1/2" DIAMETER PIPE; 8' FOR 2" DIAMETER PIPE; 7' FOR 1-1/2 &

1-1/4" DIAMETER PIPE; 5' FOR 1" & 3/4" DIAMETER PIPE.

40. REFERENCE DRAWING H0.5 & H0.6 FOR SEQUENCE OF OPERATION OF NEW EQUIPMENT.

41. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.

GENERAL NOTES

DEMOLITION NOTES

1. PRIOR TO COMMENCING WORK OF THIS SECTION, EXAMINE SITE AND CONDITIONS UNDER WHICH WORK WILL BE PERFORMED.

DETERMINE EXACT LOCATIONS OF EXISTING EQUIPMENT, PIPING AND CONTROLS. REPORT TO OWNER ANY CONDITIONS THAT MIGHT ADVERSELY AFFECT WORK. COMMENCEMENT OF WORK SHALL BE CONSTRUED AS COMPLETE ACCEPTANCE OF EXISTING CONDITIONS

AND PREPARATORY WORK.

2. ABANDONING OF DUCTWORK, PIPING OR EQUIPMENT IN PLACE SHALL NOT BE ALLOWED. COMPLETE REMOVAL REQUIRED UNLESS NOTED

OTHERWISE.

3. DUCTS TO BE REMOVED: REMOVE PORTION OF DUCTS INDICATED TO BE REMOVED & CAP REMAINING DUCTS WITH SAME OR

COMPATIBLE DUCTWORK MATERIAL.

4. EQUIPMENT TO BE REMOVED: DISCONNECT AND CAP SERVICES AND REMOVE EQUIPMENT.

5. EQUIPMENT TO BE SALVAGED: DISCONNECT, CAP SERVICES, REMOVE EQUIPMENT, DELIVER TO OWNER.

6. COMPLY WITH ALL STATE & LOCAL CODES AS TO REMOVAL & DISPOSAL OF EQUIPMENT FROM SITE.

7. COMPLY WITH GOVERNING EPA NOTIFICATION REGULATIONS BEFORE BEGINNING SELECTIVE DEMOLITION.

8. REMOVE PREVIOUSLY ABANDONED WORK IN THE WAY OF EXISTING CONSTRUCTION, OR AS NOTED.

9. COMPLY WITH HAULING AND DISPOSAL REGULATIONS OF AUTHORITIES HAVING JURISDICTION.

10. PERMITS: GIVE ALL REQUIRED NOTICES, FILE ALL REQUIRED PLANS AND SPECIFICATIONS RELATING TO THE WORK OF THIS SECTION

WITH THE PROPER AUTHORITIES AND PAY FOR ANY REQUIRED PERMITS.

11. ALL AIR-CONDITIONING EQUIPMENT AND SYSTEMS SHALL BE REMOVED OR DEMOLISHED WITHOUT RELEASING REFRIGERANTS.

REFRIGERANT RECOVERY IS TO BE PERFORMED BY A REFRIGERANT RECOVERY TECHNICAL CERTIFIED BY AN EPA-APPROVED

CERTIFICATION PROGRAM.

12. ALL EQUIPMENT AND SYSTEMS TO BE REMOVED OR DEMOLISHED UNDER THIS SECTION AND NOT DESIRED BY OWNER SHALL BECOME THE PROPERTY OF THE CONTRACTOR. THE CONTRACTOR SHALL REMOVE ALL SUCH EQUIPMENT FROM THE SITE PROMPTLY AFTER

DETACHMENT FROM BUILDING STRUCTURE.

13. EXISTING PIPING SHOWN ON DRAWINGS DOES NOT INDICATE FULL EXTENT OF PIPING DEMOLITION. FIELD VERIFICATIONS REQUIRED.

REVISION CLOUD

CAP EXISTING

CONNECT TO EXISTING

DRAWING REVISION NOTE

NEW WORK NOTE

EQUIPMENT DESIGNATIONACCU-1

DRAWING NOTES

LIMIT OF DEMOLITION

QUANTITY

NECK SIZE OR LENGTH IF LINEAR DIFFUSER

AIR VOLUME (CFM)

SUPPLY/RETURN/EXHAUST REGISTER OR GRILLE

QUANTITY

NECK SIZE OR LENGTH IF LINEAR DIFFUSER

AIR VOLUME (CFM)

SUPPLY DIFFUSER DESIGNATION

DEMOLITION SCOPE

DEMOLITION WORK NOTE

CONTROL SCHEMATIC LEGEND

DUCT SMOKE DETECTOR

TEMPERATURE SENSOR

HUMIDITY SENSOR

TIME CLOCK CONTROLLER

SWITCH CONTROLLER

HEAT/COOL THERMOSTAT

CONTROL LINE

REVERSE ACTING THERMOSTAT

FILTER GAUGE

VARIABLE FREQUENCY DRIVE

AIR FLOW MEASURING STATION

ENTHALPY CONTROL

FLOW RATE SENSOR

DIFFERENTIAL PRESSURE SENSOR

FREEZESTAT

CAPILLARY TUBE

CO SENSOR

CO2 SENSOR

FLOW SWITCH

HIGH LIMIT THERMOSTAT

STATIC PRESSURE SENSOR

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

COIL

DIFFERENTIAL PRESSURE SENSOR

PIPING LEGEND

VV

STUB UP TO TERMINAL

PIPE DOWN

PIPE UP

BRANCH CONNECTION

RUN-OUT OFF BOTTOM

RUN-OUT OFF TOP

PIPE OFF TOP

PIPE OFF BOTTOM

DIRECTION OF FLOW

PIPING TO BE REMOVED

EXISTING PIPING TO REMAIN

PIPE BREAK

PC PUMPED CONDENSATE

VENT

LPS LOW PRESSURE STEAMLPS

LPC LPC LOW PRESSURE STEAM CONDENSATE

HWS HWS HOT WATER SUPPLY

MUW MAKE UP WATER

D CD A.C. CONDENSATE DRAIN

RHG RHG REFRIGERANT HOT GAS

RL RL REFRIGERANT LIQUID

RS RS REFRIGERANT SUCTION

CWR CWR CONDENSER WATER RETURN

CWS CWS CONDENSER WATER SUPPLY

CHR CHR CHILLED WATER RETURN

CHS CHS CHILLED WATER SUPPLY

HWR HWR HOT WATER RETURN

DRAIN PIPE PITCH AND FLOW

(DIRECTION TO BE FIELD DETERMINED)

GV GATE VALVE

GLV GLOBE VALVE

BLV BALL VALVE

BFV BUTTERFLY VALVE

DV DRAIN VALVE

SCV SWING CHECK VALVE

LCV LIFT CHECK VALVE

BALANCE COCKBC

BV BALANCE VALVE

PRV PRESSURE REDUCING VALVE

TWO WAY AUTOMATIC CONTROL VALVEACV

ACV THREE WAY AUTOMATIC CONTROL VALVE

SC SELF CONTAINED CONTROL VALVE

UNION

FLG FLANGE

PLS PIPE LINE STRAINER

BASKET STRAINERBKS

CONCENTRIC REDUCER (ENLARGER)CRD

ECCENTRIC REDUCER (ENLARGER)ERD

PRESSURE GAUGEPG

FLOW SWITCHFSW

AUTOMATIC AIR VENTAAV

MANUAL AIR VENTMAV

FLOW MEASURE STATIONFMS

PIPE ANCHORAN

PIPE GUIDEGD

EXPANSION COMPENSATOREC

PIPE FLEXIBLE CONNECTIONPFC

RV RELIEF VALVE

TRM THERMOMETER

VALVE LEGEND

PRESSURE/TEMPERATURE PLUGPT

PIPE CAP

STRAINER WITH DRAIN VALVE AND CAP

IS ISOLATION VALVE REFER TO DETAILS AND SPEC.

MANUAL AIR VENT

MULTI-PURPOSE VALVE

FD FIRE DAMPER

S

M

SMOKE DAMPER

MOTORIZED OR AUTOMATIC CONTROL DAMPER

BACK DRAFT DAMPER

VOLUME DAMPER

DAMPER LEGEND

ACD

SD

BD

VD

FD

BD

FS FIRE & SMOKE DAMPERFS

ZONE DAMPERZD

RADIATION DAMPERRD

VB VACUUM BREAKER

UNIT VENTILATORUV

UH UNIT HEATER (WATER OR STEAM)

VI VIBRATION ISOLATION

PUMPP

LOUVERLU

HEAT EXCHANGERHX

H HUMIDIFIER

FIN TUBE RADIATIONFTR

FCU FAN COIL UNIT

EB ELECTRIC BASEBOARD

BOILER

AIR HANDLING UNITAHU

B

CONVECTORCV

CUH CABINET UNIT HEATER

AIR FLOW STATION

AIR COOLED CONDENSING UNITACCU

AFS

EQUIPMENT TAGS

AIR CONDITIONING UNITAC

CP CONDENSATE PUMP

EXHAUST GRILLEEG

RG RETURN GRILLE

SD SUPPLY DIFFUSER

SR SUPPLY REGISTER

EXHAUST REGISTERER

RR RETURN REGISTER

SG SUPPLY GRILLE

EXHAUST FANEF

SF SUPPLY FAN

RF RETURN FAN

EDH ELECTRIC DUCT HEATER

AIR SEPARATORAS

EXPANSION TANKET

ELECTRIC UNIT HEATEREUH

TRANSFER AIR GRILLETG

TOILET EXHAUST FANTF

HOT WATER PUMPHWP

KITCHEN EXHAUST FANKF

HEAT PUMPHP

HYDRAULIC SEPARATORHS

COMBUSTION AIRCA

CAP CAPACITY

BRITISH THERMAL UNIT PER HOUR

BRITISH THERMAL UNIT

BOTTOM OF DUCTBOD

BTUH

BTU

C CLOSED

AUTOMATIC TEMPERATURE CONTROLATC

AP

ARCH.

AFF

AD ACCESS DOOR

ABOVE FINISHED FLOOR

ACCESS PANEL

ARCHITECT

AAV AUTOMATIC AIR VENT

VARIABLE FREQUENCY DRIVEVFD

WB WET BULB TEMPERATURE (°F)

TA

TD

SST SATURATED SUCTION TEMPERATURE

TRANSFER AIR

TRANSFER AIR DUCT

UC UNDERCUT DOOR

ETBR

ETR

EXISTING TO BE REMOVED

EXISTING TO REMAIN

FINS PER INCHFPI

FULL LOAD AMPSFLA

FA

EXH

EX. EXISTING

EXHAUST

FREE AREA

GALLONS PER MINUTE

GENERAL EXHAUST

GENERAL CONTRACTORGC

GE

GPM

HP HORSE POWER

KILOWATTSKW

ID

KF

IN

HVAC HEATING, VENTILATION AND AIR CONDITIONING

INCHES

INSIDE DIAMETER

KITCHEN EXHAUST FAN

MECHANICALMECH

LD

MBH

LWT

LAT LEAVING AIR TEMPERATURE

LEAVING WATER TEMPERATURE

LOUVERED DOOR

THOUSANDS OF BRITISH THERMAL UNITS PER HOUR

FEET

COMBINATION FIRE AND SMOKE DAMPER

FEET PER MINUTEFPM

FT

FSD

GAL GALLONS

POUNDS PER SQUARE INCH

PRESSURE DROP

PSI

PD

RA RETURN AIR

RM ROOM

PLUMBING CONTRACTOR

OUTSIDE DIAMETER

OPPOSED BLADE DAMPEROBD

OD

PC

NC NORMALLY CLOSED

OUTSIDE AIR TEMPERATUREOAT

NTS

OAI

NO

NIC NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

OUTSIDE AIR INTAKE

STATIC PRESSURE

STAND ALONE DIGITAL CONTROLLERSDC

SP

SPD SPEED

SS STAINLESS STEEL

SUPPLY AIRSA

SAT SUPPLY AIR TEMPERATURE

EACHEA.

DRAWINGDWG

ENERGY MANAGEMENT SYSTEMEMS

ENTERING AIR TEMPERATURE

EXHAUST AIREA

EAT

DIGITAL OUTPUTDO

DIA.

DN

DDC

DB DRY BULB TEMPERATURE (°F)

DIRECT DIGITAL CONTROL

DIAMETER

DOWN

CONTROL VALVE

CURRENT TRANSFORMERCT

CV

CONTR CONTRACTOR

CONNECTCONN.

ABBREVIATIONS

DRAINDR

FLOOR DRAINFLD

ELECTRICAL CONTRACTOREC

EXTERNAL STATIC PRESSUREESP

ENTERING WATER TEMPERATUREEWT

HEATING COILHC

SQUARE FEETSF

WMS WIRE MESH SCREEN

EL EXPANSION LOOP

THERMOSTAT

TYPICALTYP

TSTAT

OA OUTSIDE AIR

EXHAUST FANEF

OPEN END DUCTOED

TF TOILET EXHAUST FAN

CLEAN OUT

CUBIC FEET PER MINUTECFM

CO

CAS

CAR COMBUSTION AIR RELIEF

COMBUSTION AIR SUPPLY

COOLING COILCC

CONDENSATE DRAINCD

ABBREVIATIONS

ARCHITECT

MECHANICAL ELECTRICAL

PLUMBING ENGINEERING

STAMP

REVISIONS

NUMBER DATE DESCRIPTION

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

BLW ENGINEERS INC.

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

KEY PLAN

3/21/2022

MASSBAY

COMMUNITY COLLEGE

TECH TOWER 1919

ELEVATOR

MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

100% BID SET

MECHANICAL

LEGEND

H0-01

AutoCAD SHX Text 10"%%C, 12"x12" SG-A, RG-A or EG-A

AutoCAD SHX Text

200 CFM

AutoCAD SHX Text

(TYP. OF 3)

AutoCAD SHX Text 12"x12", SD

AutoCAD SHX Text

200 CFM

AutoCAD SHX Text

(TYP. OF 3)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TS

AutoCAD SHX Text H

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text

DSD

AutoCAD SHX Text E1

AutoCAD SHX Text F

AutoCAD SHX Text

DPS

AutoCAD SHX Text

VFD

AutoCAD SHX Text

%%UAFS-

AutoCAD SHX Text

FZ

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO2

AutoCAD SHX Text

FS1

AutoCAD SHX Text

HLT

AutoCAD SHX Text

SP1

AutoCAD SHX Text

DPS

AutoCAD SHX Text

AV

TAG NO.

MANUFACTURER

(AS STANDARD)

MODEL NO.

(AS STANDARD) TYPE

WALL MOUNTED

FAN DATA

MAX ESP

(CFM) (IN.WC.)

FANS

MIN

(CFM)

ELECTRICAL DATA

PHASE HZ

MCA

(A)

VOLTS

MOCP

(A)

REMARKS

NOTES:

1) PROVIDE WIRED THERMOSTAT MOUNTED TO WALL.

FCU-1 MITSUBISHI PKA-A30KA7 775 570 - - 208 1 60 1 -

SPLIT DX FAN COIL UNIT SCHEDULE

PROVIDE UNIT WITH DISCONNECT SWITCH, CONDENSATE PUMP (LITTLE GIANT MODEL VCC-20ULS or

SIMILAR), CONDENSATE OVERFLOW SENSOR, THERMOSTAT AND ALL CONTROLS

OA

(CFM)

MOTOR

(W)

COOLING HTG-NOM

(MBH) (MBH)

DX COIL DATA

HTG-AUX

(KW)

EER

30 34 21 - 9.5

HTG-17°F

(MBH)

TAG NO.

MANUFACTURER

(AS STANDARD)

MODEL NO.

(AS STANDARD) TYPE

SINGLE ZONE

COOLING HTG-NOM

(MBH) (MBH)

CAPACITY DATA

REFRIG. EER

FAN DATA

ESP

(IN.WC.)

FANS

MAX

(CFM)

ELECTRICAL DATA

PHASE HZ

MCA

(A)

VOLTS

MOCP

(A)

REMARKS

NOTES:

1) UNIT SHALL BE CAPABLE OF INDICATED HEATING CAPACITY AT 17°F AND OF OPERATION IN HEATING MODE WITH AMBIENT TEMPERATURES AT OR BELOW 17°F.

HP-1 MITSUBISHI PUZ-A30NHA7 30 34 21 R-410A 9.5 1940 xx xx 208 1 60 19 26

AIR SOURCE HEAT PUMP UNIT SCHEDULE

PROVIDE WITH BREAKER, DISCONNECT SWITCH, LOW AMBIENT OPERATION, EQUIPMENT PAD AND/OR 24"

(MIN) EQUIPMENT STAND AS REQUIRED.

MOTOR

(FLA)

HTG-17°F

(MBH)

xx

WEIGHT

(LBS)

153-

MOD

(NO.)

LOCATION

SERVED

ELEV. MACH. RM

LOCATION

SERVED

ELEV. MACH. RM

TAG NO.

MANUFACTURER

(AS STANDARD)

MODEL NO.

(AS STANDARD) FINISH REMARKS

TR TITUS 33RL

REGISTER, GRILLE & DIFFUSER SCHEDULE

SYSTEM

SERVED

NOTES:

1) COORDINATE FINISH & COLOR WITH ARCHITECT.

2) PROVIDE FRAME SUITABLE FOR SURFACE MOUNTING ON FLOOR.

3) REFER TO DRAWINGS FOR CFM UNLESS NOTED ABOVE.

4) PROVIDE OPPOSED BLADE DAMPER.

[1][2][3][4]TBD

DAMPER

NO

MATERIAL

ST

MAX

NC LEVEL

MAX

VELOCITY

(FPM)

~500

CFM RANGE

FRAME

TYPE

RECTANG.

MOUNTING

FLOOR

NECK

SIZE

--ELEV. SHAFT

HVAC SCHEDULES

HVAC DETAILS

HVAC SEQUENCE OF CONTROLS

THE INDIVIDUAL FAN COIL UNITS SHALL BE CONTROLLED THROUGH THE CORRESPONDING SPACE THERMOSTAT AND THE MASTER CONTROL UNIT. THE SEQUENCE LISTED BELOW IS REVERSIBLE UNLESS NOTED OTHERWISE.

THE SYSTEM SHALL BE IN HEATING MODE WHEN THE OUTDOOR AIR TEMP IS BELOW 60° (ADJ.) THE SYSTEM SHALL BE IN

COOLING MODE WHEN THE OUTDOOR AIR TEMPERATURE IS ABOVE 70° (ADJ.)

THE HEAT PUMP UNIT SHALL ENERGIZE AND OPERATE PER THE MANUFACTURE'S SEQUENCES. THE FAN COIL UNIT

SUPPLY FAN SHALL ENERGIZE TO LOW SPEED AND OPERATE CONTINUOUSLY.

DURING HEATING MODE. UPON A CALL FOR HEAT FROM THE SPACE THERMOSTAT, THE FAN COIL UNIT SHALL OPERATE PER MANUFACTURE'S SEQUENCES TO MAINTAIN THE SPACE TEMPERATURE SETPOINT (ADJ.) UPON A FURTHER CALL FOR HEAT, THE UNIT'S FAN SPEED SHALL BE INCREASED FROM LOW TO MEDIUM AND MEDIUM TO HIGH, AS REQUIRED TO

MAINTAIN THE SPACE TEMPERATURE SETPOINT.

DURING THE COOLING MODE, UPON A CALL FOR COOLING FROM THE SPACE THERMOSTAT, THE FAN COIL UNIT SHALL OPERATE PER THE MANUFACTURES SEQUENCES TO MAINTAIN THE SPACE TEMPERATURE SETPOINT (ADJ.). UPON A FURTHER CALL FOR COOLING, THE UNITS FAN SPEED SHALL BE INCREASED FROM LOW TO MEDIUM AND MEDIUM TO

HIGH, AS REQUIRED TO MAINTAIN THE SPACE TEMPERATURE SETPOINT.

UPON LOSS OF POWER TO THE UNIT OR FAN STATUS FAILURE, THE APPROPRIATE ALARM SIGNAL SHALL BE

TRANSMITTED TO THE MAIN SYSTEM CONTROLLER

SPACE

THERMOSTAT

COIL

FILTER

HEAT PUMP & FAN COIL UNITS

APPLICATION TABLE

TYPICAL OF ALL FCU'S AND HP

HP

FAN SPEED

SUPPLY AIR

H-C

DX

RETURN AIR

FCU S

T

N.T.S.1 ROOF PIPE SUPPORT DETAIL

ROOF

GALVANIZED

CHANNEL

7/8" Ø RODS

(TYPICAL)

CONTINUOUS VAPOR

BARRIER (TYPICAL)

LOCK NUT (TYPICAL)

FREE TO SLIDE

ON ROD

LOCK NUT (TYP)

INSULATE PER

SPECS

PIPE GUIDE (TYP)

1" SPACE EACH SIDE

FOR PIPE

EXPANSION.

(TYP)

PREFABRICATED

EQUIPMENT

SUPPORT REFER TO

DETAIL

1/2 SECTION X 10"L

LOAD BEARING.

INSULATE PER SPEC

(TYPICAL)

120°, 14 GA, 8"L

SHEETMETAL.

SADDLE (TYP)

10" MIN.

18" MIN.

N.T.S.2 VARIABLE REFRIGERANT FLOW PIPING DETAIL

THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR POWER WIRING TO THE FCU AND HP UNITS. THE ELECTRICAL CONTRACTOR SHALL PROVIDE POWER FEED TO THE HP UNIT, FUSED DISCONNECT AND WIRING TO THE HP UNIT. THE ELECTRICAL CONTRACTOR SHALL PROVIDE POWER FEED TO THE FCU, NON-FUSED DISCONNECT AND WIRING TO FCU. THE CONTROL WIRING BETWEEN FCU AND HP UNIT SHALL BE PROVIDED BY THE ATC CONTRACTOR.

THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR POWER WIRING TO THE HP UNIT, FUSED DISCONNECT AND WIRING TO THE HP UNIT. THE LOW OR LINE VOLTAGE CONTROL/FAN POWER WIRING BETWEEN THE HP UNIT AND

THE FCU SHALL BE PROVIDED BY THE ATC CONTRACTOR.

1. SIZE PIPING PER EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.

2. ALL INTERIOR PIPING SHALL BE CONCEALED IN CEILINGS AND WALLS..

3. FURNISH AND INSTALL ALL REFRIGERANT VALVES AND SPECIALTIES REQUIRED BY MANUFACTURER.

4. PROVIDE WEATHERTIGHT SEAL AT ALL PIPING PENETRATIONS. COORDINATE PENETRATIONS WITH G.C. AND

ALL ASSOCIATED TRADES AS REQUIRED.

5. SPLIT SYSTEM MANUFACTURERS UTILIZE DIFFERENT WIRING CONFIGURATIONS. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE THE WIRING REQUIREMENTS OF THE SHOP DRAWING

APPROVED EQUIPMENT WITH THE ELECTRICAL CONTRACTOR.

6" CONTRETE PAD BY G.C.

(FOR GROUND INSTALLATION)

FLEX

CONN. (TYP)

REFER TO PIPING

PENETRATION DETAIL

WHERE APPLICABLE

A.C. CONDENSATE DRAIN

WITH P-TRAP. PIPE TO DRAIN.

PROVIDE A.C. CONDENSATE PUMP

AS REQUIRED.

THERMAL EXPANSION VALVE AND

DISTRIBUTOR BY COIL MANUFACTURER

RUN REFRIG. PIPING THROUGH

WALL SLEEVE WHERE APPLICABLE

FILTER/DRIER

REFRIGERANT

VALVE (TYPICAL)

NOTES:

A. SINGLE FEED SYSTEM

B. DUAL FEED SYSTEM

FCU

(INDOOR UNIT)

RLL

RGL

HP

(OUTDOOR UNIT)

SEE NOTE 5

POWER WIRING TO ACCU

BY E.C SEE NOTE 5.

SEE NOTE 5

N.T.S.3 TYPICAL REFRIGERANT PIPING INSULATION DETAIL

REFRIGERANT PIPE

SCALE: N.T.S.1 Tech Tower Key Plan

ARCHITECT

MECHANICAL ELECTRICAL

PLUMBING ENGINEERING

STAMP

REVISIONS

NUMBER DATE DESCRIPTION

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

BLW ENGINEERS INC.

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

KEY PLAN

3/21/2022

MASSBAY

COMMUNITY COLLEGE

TECH TOWER 1919

ELEVATOR

MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

100% BID SET

MECHANICAL

SCHEDULES, DETAILS

& SEQUENCE OF

CONTROLS

H0-02

AREA OF NEW WORK

AutoCAD SHX Text ONE- PIECE CLOSED CELL, ELASTOMERIC OR PVC PIPE INSULATION (OVERLAP ALL JOINTS AND SEALS PER INSULATION MANUFACTURER'S RECOMMENDATIONS)

AutoCAD SHX Text

REFRIGERANT PIPE

AutoCAD SHX Text PROVIDE UV RESISTANT JACKET OR PIPE GUARD WHERE EXPOSED TO ATMOSPHERE (OVERLAP AND SEAL ALL JOINTS)

ELEVATOR

MACHINE

SCALE: 1/4"=1'-0"1 Elevator Machine Room Demo Plan

WALL MOUNT FAN COIL

E.T.B.R.

CD

HEAT PUMP

E.T.B.R.

MOTORIZED

FIRE/SMOKE

DAMPER

E.T.R.

PIPE

E.T.R.

FS

UP

ELEVATOR

MACHINE

SCALE: 1/4"=1'-0"2 Elevator Machine Room Plan

CD

FCU-1

TR-36x12

1 2

MOTORIZED

FIRE/SMOKE

DAMPER

E.T.R.

EXISTING PIPE

T

FS

HVAC DEMO NOTES

1. REPAIR AND PATCH WALL AS NEEDED AFTER UNIT REMOVAL.

2. REPAIR AND PATCH FLOOR AS NEEDED AFTER GRILLE REMOVAL.

3. REPAIR EXISTING PENETRATIONS FOR REFRIG. PIPING.

HVAC NEW WORK NOTES

1. PROVIDE 1' SEPARATION FROM EXISTING PIPE AND NEW FCU-1.

2. USE EXISTING WALL PENETRATIONS FOR NEW REFRIG. PIPING.

3. EXTEND PIPE TO EXTERIOR WALL AND APPROX. 40'-0" DOWN TO LOWER TECH

TOWER ROOF.

4. NEW 1" CONDENSATE PIPING SHALL BE PLACED IN EXISTING CONDENSATE

PENETRATION AND DRAIN LOCATION.

5. HP-1 TO BE MOUNTED TO 24" BIG-FOOT STAND, OR MANUFACTURER'S

EQUIVALENT.

6. HP-1 AND MOUNT TO BE SECURED TO TECH TOWER LOWER ROOF.

7. PROVIDE APPROX. 120'-0" TOTAL REFRIGERANT PIPING FROM HP-1 TO FCU-1.

HP-1

EXISTING ACCUs

TO REMAIN

APPROX. 40'-0" VERTICAL RISE

TO NEW WALL PENETRATION.

SCALE: 1/4"=1'-0"3 Tech Tower Lower Roof Plan

ARCHITECT

MECHANICAL ELECTRICAL

PLUMBING ENGINEERING

STAMP

REVISIONS

NUMBER DATE DESCRIPTION

58 WINTER STREET

BOSTON, MA 02108

Phone: 617-357-5335 Fax: 617-354-5654 www.TaylorBurns.com

BLW ENGINEERS INC.

311 GREAT ROAD

LITTLETON, MA 01460

Phone:978-486-4301 Fax:978-428-0067 www.blwengineers.com

KEY PLAN

3/21/2022

MASSBAY

COMMUNITY COLLEGE

TECH TOWER 1919

ELEVATOR

MODERNIZATION

MASSBAY COMMUNITY COLLEGE

50 OAKLAND STREET

WELLESLEY MA 02481

100% BID SET

MECHANICAL

PLANS

H1-01

GENERAL NOTES

1. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR MOUNTING HEIGHTS AND EXACT LOCATIONS OF ALL DEVICES.

2. PERFORM WORK AND PROVIDE MATERIALS AND EQUIPMENT TO MAKE INSTALLATION COMPLETE IN EVERY DETAIL UNDER THIS CONTRACT

WHETHER OR NOT SPECIFICALLY SHOWN ON DRAWINGS.

3. ALL CONDUIT, WIRING AND ELECTRICAL EQUIPMENT SHALL BE INSTALLED AND GROUNDED IN ACCORDANCE WITH THE LATEST STANDARDS

OF THE NATIONAL & STATE ELECTRICAL CODES AND ANY APPLICABLE LOCAL REGULATIONS.

4. ALL FLOOR, MASONRY WALLS AND STRUCTURAL CEILING PENETRATIONS SHALL BE SLEEVED.

5. PROVIDE FIRE/MOISTURE SEAL FOR WALL, FLOOR OR CEILING PENETRATIONS.

6. DO NOT LAY CABLES OR RACEWAY ON, OR SUPPORT FROM SUSPENDED CEILING OR PIPING AND DUCTWORK.

7. OUTLET BOXES SHALL BE MOUNTED FLUSH. CONDUIT SHALL BE RUN CONCEALED. WHERE WALLS ARE BLOCK, DEVICES AND WIRING SHALL BE SURFACE MOUNTED. PROVIDE WIREMOLD OR EQUAL TO SURFACE MOUNTED RACEWAY WITH FINISHED BOXES.

8. NO CONDUIT SMALLER THAN 3/4 INCH ELECTRICAL TRADE SIZE SHALL BE USED, UNLESS SPECIFICALLY CALLED FOR ON THE DRAWINGS.

9. ALL WIRING WITHIN UTILITY CLOSETS MAY BE IN SURFACE MOUNTED CONDUIT. EMT MAY BE UTILIZED.

10. FLEXIBLE CONDUIT CONNECTIONS SHALL BE A MAXIMUM OF 6'-0".

11. MC TYPE CONDUCTOR WITH INTEGRAL GROUND WIRE MAY BE UTILIZED FOR POWER AND LIGHTING CIRCUITS. MC CABLE SHALL BE

UTILIZED ONLY WHERE COMPLETELY CONCEALED AND INSTALLED IN ACCORDANCE WITH CODE.

12.

STEEL OR FIRE-RATED ELECTRICAL BOXES (SWITCHES, OUTLETS, JUNCTION BOXES, ETC.) SHALL BE PROVIDED AND INSTALLED IN ALL FIRE RATED ASSEMBLIES AS IN ACCORDANCE WITH BUILDING AND ELECTRICAL CODES. UL LISTED MOLDABLE PUTTY PADS OR FIREBLOCK/SPRAY FOAM INSULATE SHALL BE USED TO SEAL ALL ANNULAR SPACES/PENETRATIONS AROUND OUTLET BOXES. FIRE RATED ASSEMBLIES INCLUDE EXTERIOR WALLS, FIRE-RATED WALLS, FLOOR/CEILING ASSEMBLIES AND ROOF/CEILING ASSEMBLIES.

13.

RECESSED ELECTRICAL ENCLOSURES SUCH AS BUT NOT LIMITED TO; PANELBOARDS, LOW VOLTAGE MEDIA CENTERS, ETC. SHALL BE PROVIDED WITH FIRE-RATED BOXES WHERE INSTALLED IN FIRE-RESISTANCE-RATED ASSEMBLIES. REFER TO ARCHITECTURAL PLANS FOR

LOCATIONS OF FIRE-RATED ASSEMBLIES.

14.

ALL EQUIPMENT AND WIRING ON DWGS IS SHOWN DIAGRAMMATICALLY. EXACT LOCATION AND METHOD OF SUPPORT SHALL BE DETERMINED IN THE FIELD, EXCEPT WHERE SPECIFIC DIMENSIONS AND DETAILS ARE SHOWN. ALL CONDUIT RUNS SHALL BE RIGIDLY

SUPPORTED.

15.

COORDINATE WITH ARCHITECTURAL FURNITURE LAYOUTS FOR EXACT LOCATION OF WALL MOUNTED POWER AND COMMUNICATIONS DEVICES. COORDINATE ALL LIGHTING FIXTURES, UNDER CABINET LIGHTING FIXTURES AND SWITCH LOCATIONS WITH ARCHITECTURAL

REFLECTED CEILING PLANS AND ELEVATIONS.

LIGHTING NOTES

1. ALL CONDUIT, FIXTURES AND OUTLETS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION AND METHOD OF SUPPORT SHALL BE

DETERMINED IN THE FIELD, EXCEPT WHERE SPECIFIC DIMENSIONS AND DETAILS ARE SHOWN.

2. ALL LIGHTING FIXTURE SPACING DIMENSIONS AND MOUNTING HEIGHTS ARE RECOMMENDED LOCATIONS. SLIGHT VARIATIONS WHERE

NECESSARY TO AVOID INTERFERENCE SHALL BE DETERMINED IN THE FIELD.

3. WHERE REQUIRED, ADDITIONAL SUPPORT STEEL FOR THE LIGHTING INSTALLATION SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL

CONTRACTOR. SEISMIC RESTRAINTS SHALL BE INCLUDED AS PER STATE BUILDING CODE.

4. PROVIDE SEPARATE UN-SWITCHED NEUTRAL TO ALL EXIT SIGNS, EMERGENCY BATTERY UNITS AND EMERGENCY LIGHT FIXTURES

CONTAINING EMERGENCY BALLASTS.

5.

FIRE-RATED BOXES/ENCLOSURES FOR RECESSED LIGHTING FIXTURES SHALL BE PROVIDED AND INSTALLED IN FIRE-RATED ASSEMBLIES AS IN ACCORDANCE WITH BUILDING AND ELECTRICAL CODES. FIRE-RATED ASSEMBLIES INCLUDE; FIRE-RATED WALLS, FLOOR/CEILING ASSEMBLIES AND ROOF/CEILING ASSEMBLIES. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF FIRE-RATED ASSEMBLIES.

POWER NOTES

1. ALL CONDUITS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION AND METHOD OF SUPPORT SHALL BE DETERMINED IN THE FIELD, EXCEPT WHERE SPECIFIC DIMENSIONS AND DETAILS ARE SHOWN. ALL CONDUIT RUNS SHALL BE RIGIDLY SUPPORTED.

2. NEC - 406.12 TAMPER-RESISTANT RECEPTACLES - IN ALL AREAS SPECIFIED IN 406.12 PARAGRAPHS (1-7) AND ASSEMBLY SUBSETS LISTED IN NEC 518.2, ALL NONLOCKING-TYPE, 125 VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER RESISTANT RECEPTACLES.

3.

CONDUCTORS AND CABLE SHALL BE MINIMUM #12 AWG, 600 VOLT, COPPER WITH TYPE THHN/THWN INSULATION. PROVIDE SEPARATE GREEN GROUND IN ALL FEEDERS. WIRE SIZE #8 AWG AND LARGER SHALL BE STRANDED, #10 AWG AND SMALLER SHALL BE SOLID. COLOR CODE CONDUCTORS BLACK, RED, BLUE, WITH WHITE NEUTRAL AND GREEN GROUND EXCEPT AS NOTED FOR 120 VOLT.

4. ELECTRICAL CONTRACTOR SHALL CONFIRM ALL NEMA CONFIGURATIONS AND REQUIRED ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT

SPECIFICATIONS PRIOR TO ROUGH-IN.

DEMOLITION NOTES

1.

REFER TO THE ARCHITECTURAL DRAWINGS FOR THE FULL EXTENT OF THE SCOPE OF DEMOLITION. DISCONNECT AND MAKE SAFE ALL ELECTRICAL EQUIPMENT IDENTIFIED FOR REMOVAL ON THE HVAC, PLUMBING AND FIRE PROTECTION PLANS. THE ELECTRICAL SCOPE MAY EXTEND BEYOND THE AREA DEFINED BY THE ARCHITECTURAL DEMOLITION LIMITS TO FULLY COMPLY WITH VARIOUS REQUIREMENTS

DEFINED BY THESE NOTES.

2.

THE ELECTRICAL DEMOLITION PLANS AND DETAILS INDICATE THE GENERAL INTENT AND ARE NOT INTENDED TO SHOW ALL ITEMS TO BE REMOVED OR RETAINED. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO THE SUBMISSION OF BIDS TO BECOME FAMILIAR WITH THE ACTUAL CONDITIONS AND EXTENT OF WORK. DEVICES AND EQUIPMENT LOCATED ON WALLS AND/OR CEILINGS TO BE REMOVED SHALL BE DISCONNECTED AND MADE SAFE. THE ELECTRICAL CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY

UNANTICIPATED HIDDEN CONDITIONS ENCOUNTERED DURING DEMOLITION.

3.

THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ALL SYSTEMS OR BUILDING COMPONENTS DAMAGED DURING THE EXECUTION OF THE WORK. DAMAGE SHALL INCLUDE BUT NOT BE LIMITED TO DESTRUCTION OR DISPOSAL OF ITEMS INTENDED TO

REMAIN OR TO BE SALVAGED.

4.

THE ELECTRICAL CONTRACTOR SHALL CIRCUIT TRACE AND LABEL ALL EXISTING BRANCH CIRCUITS AND FEEDERS WITHIN THE AREA OF DEMOLITION SCOPE PRIOR TO DE-ENERGIZING AND DISCONNECTION. ALL CIRCUITS WITHIN PANELBOARDS IDENTIFIED FOR REMOVAL SHALL BE TRACED AND LABELED TO ENSURE THAT NO AREA OUTSIDE THE DEMOLITION SCOPE LIMIT IS AFFECTED.

5.

THE ELECTRICAL CONTRACTOR SHALL IDENTIFY ALL BRANCH CIRCUITS, FEEDERS AND SYSTEM COMPONENTS, WHICH ARE TO REMAIN WITHIN THE AREA OF DEMOLITION SCOPE. THERE SHALL BE NO INTERRUPTION OF SERVICE TO ANY AREA OUTSIDE THE SCOPE LIMITS WITHOUT APPROVAL FROM THE OWNER'S REPRESENTATIVE. EXISTING EQUIPMENT TO REMAIN SHALL BE LEFT IN A CODE COMPLIANT

MANNER.

6.

THE ELECTRICAL CONTRACTOR SHALL DE-ENERGIZE AND REMOVE ALL CONDUCTORS AND RACEWAYS TO THEIR POINTS OF ORIGIN WITHIN THE AREA OF DEMOLITION SCOPE. ITEMS IDENTIFIED FOR DEMOLITION SHALL NOT BE ABANDONED IN PLACE. RACEWAYS THAT ENTER MASONRY WALLS AND FLOORS SHALL BE CUT FLUSH AT THE SURFACE FOR PATCHING BY OTHERS. ALL CIRCUIT BREAKERS ASSOCIATED

WITH THE DEMOLITION SCOPE SHALL BE DE-ENERGIZED AND LABELED SPARE.

7.

THE ELECTRICAL CONTRACTOR SHALL TEMPORARILY SUPPORT ALL ITEMS TO REMAIN THAT ARE AFFECTED BY THE DEMOLITION OF BUILDING STRUCTURAL COMPONENTS (WALLS, CEILINGS, ETC.). TEMPORARILY SUPPORTED ITEMS SHALL BE PERMANENTLY SUPPORTED

AND INSTALLED WHEN FINALIZED STRUCTURES ARE IN PLACE.

8. ALL REMOVED ITEMS SHALL BE LEGALLY DISPOSED OF UNLESS IDENTIFIED FOR REUSE. THE OWNER'S REPRESENTATIVE SHALL INSPECT ALL RETAINED ITEMS PRIOR TO PLACEMENT IN THE IDENTIFIED STORAGE LOCATION BY THE ELECTRICAL CONTRACTOR.

9.

THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN FULLY FUNCTIONAL DURING THE ENTIRE DEMOLITION AND CONSTRUCTION PERIOD.

REUSE OF EXISTING FIRE ALARM SYSTEM RACEWAYS SHALL NOT BE ALLOWED. ALL REQUIRED SYSTEM SHUTDOWNS SHALL BE COORDINATED WITH AND APPROVED BY THE OWNER'S…