2026-06-25_WaCo_SB_Tran_Window_PERMIT_SET_REV1.pdf
PDF 1 MB Posted
- Solicitation number
- 2026.067-ITB
- Issued by
- Washington County, Oregon
About this file
This is a permit set of architectural construction drawings for Washington County Facilities Division & Property Services Department for the installation of transaction windows at the Law Enforcement Center located at 215 SW Adams Street in Hillsboro, Oregon. The project scope includes demolition of an existing wall to accommodate a new ballistic-rated transaction window in the shared lobby, updates to the existing transaction counter to include a ballistic-rated window, and installation of a new access control card reader at an existing door location. The project is a tenant improvement for the Law Enforcement and Civil Services (LECS) Civil/Permits Department with a total tenant improvement area of 250 square feet. Construction must comply with the 2022 Oregon Structural Specialty Code, 2022 Oregon Electrical Specialty Code, 2022 Oregon Mechanical Specialty Code, 2023 Oregon Plumbing Specialty Code, 2021 Oregon Fire Code, 2021 Oregon Energy Efficiency Specialty Code, and ICC A117.1-2017/2010 ADA Standards. The project team includes Ankrom Moisan Architects (design architect), Coffman (electrical engineer), and a contractor to be determined. Work must be performed after hours to maintain building operations during standard business hours (Monday-Friday, 8 AM-5 PM), with background checks required for all personnel.
The construction drawings specify delegated design responsibilities for metal framing, mechanical HVAC systems, fire protection, electrical systems, and low voltage components to be provided by the contractor on a design-build basis subject to owner and architect approval. All work is to conform to applicable building codes and owner building standards. The ballistic-rated transaction window and glass specification are noted with an alternate option to provide alternate pricing for ballistic-rated glass with client confirmation of the threat rating required. Materials include quartz composite transaction countertops, clear anodized aluminum glazing channels with laminated safety glass, and standard building finishes. Shop drawings are required for casework, delegated design components, doors, frames, and hardware prior to fabrication, with a five business day review period. All parts, labor, equipment, and materials are warranted for one year after substantial completion.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATION
PROJECT TEAM
BUILDING ADDRESS 215 SW ADAMS ST.
HILLSBORO, OR 97213
OWNER/LANDLORD WASHINGTON COUNTY, F&PSD
169 N FIRST AVE., MS-42
HILLSBORO, OR 97124
CONTACT: STUART SPAFFORD
PHONE: 503.846.6775
ARCHITECT ANKROM MOISAN ARCHITECTS, INC.
38 NORTHWEST DAVIS, SUITE 300
PORTLAND, OR 97209
PHONE: 503.245.7100
FAX: 503.245.7710
CONTACT ROBERTA PENNINGTON
PHONE: 503.952.1347
ELECTRICAL ENGINEER COFFMAN
CONTACT: ANDY YANOSHEK
1050 SW 6TH AVE., STE. 1630
PORTLAND, OR 97204
PHONE: 503.552.3800
TENANT LECS CIVIL/ PERMITS DEPT
CONTRACTOR TBD
CODE INFORMATION NOTES
1. ALL CONSTRUCTION WORK SHALL BE DONE IN COMPLIANCE WITH
APPLICABLE CODE(S).
SCOPE OF WORK
1. DEMOLITION OF EXISTING WALL TO ACCOMMODATE NEW BALLISTIC-
RATED TRANSACTION WINDOW INTO SHARED LOBBY.
2. UPDATE EXISTING TRANSACTION COUNTER TO INCLUE A BALLISTIC-RATED
WINDOW.
3. ADD NEW ACCESS CONTROL CARD READER TO EXISTING DOOR
LOCATION.
ACCESSIBILITY UPGRADES SUMMARY
447.241 STANDARDS FOR RENOVATION, ALTERATION OR MODIFICATION OF
CERTAIN BUILDINGS; BARRIER REMOVAL IMPROVEMENT PLAN.
IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE UNDER THIS
SECTION, PRIORITY SHALL BE GIVEN TO THOSE ELEMENTS THAT WILL
PROVIDE THE GREATEST ACCESS. ELEMENTS SHALL BE PROVIDED IN THE
FOLLOWING ORDER:
A. PARKING;
EXISTING PROJECT SITE COMPLIES, NO PROPOSED IMPROVEMENTS.
B. AN ACCESSIBLE ENTRANCE;
EXISTING PROJECT SITE COMPLIES, NO PROPOSED IMPROVEMENTS.
C. AN ACCESSIBLE ROUTE TO THE ALTERED AREA;
EXISTING PROJECT SITE COMPLIES, NO PROPOSED IMPROVEMENTS.
D. AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE
UNISEX RESTROOM;
EXISTING PROJECT SITE COMPLIES, NO PROPOSED IMPROVEMENTS.
E. ACCESSIBLE TELEPHONES;
N/A
F. ACCESSIBLE DRINKING FOUNTAINS;
N/A
G. WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH AS
STORAGE AND ALARMS.
EXISTING PROJECT SITE COMPLIES, NO PROPOSED IMPROVEMENTS.
GENERAL SYMBOLS
TAGS
DOOR NUMBER
KEYNOTE NUMBER
REVISION NUMBER
WINDOW TYPE
INTERIOR ELEVATION
DETAIL
WALL ASSEMBLY
CEILING HEIGHT
ROOM
SYMBOLS
GRID
NORTH ARROWS
ELEVATION DATUM
A101
DESCRIPTION
NORTH PROJECT
ROOM NAME
SIM
A101
A
SIM
A6.01
10'-0'
1t
TOP/BASE CONFIGURATION
A A
ASSEMBLY TYPE
AREA OF IMPROVEMENT
OPEN
Image of Stamp
PROJECT NUMBER
© ANKROM MOISAN ARCHITECTS, INC.
38 NORTHWEST DAVIS STREET, SUITE 300
PORTLAND, OR 97209
503.245.7100
1505 5TH AVENUE, SUITE 300
SEATTLE, WA 98101
206.576.1600
115 SANSOME STREET, SUITE 1005
SAN FRANCISCO, CA 94104
415.252.7063
DATE
SHEET NUMBERSHEET NUMBER
A u to d e s k D o cs
/A
M
S e ct o r S a n d b o x
O
/2
-2
-W a
C o
T ra n W in d o w
.r v t
/1
/2
:1
:3
A
M
250810
PERMIT SET
W A
C O
T R
A N
S A
C T
IO
N
W
IN
D O
W
W A
S H
IN
G
T O
N C
O U
N T
Y
S
W A
D A
M S
H
IL
L S
B O
R O
O
R
6.15.26
COVER SHEET
A0.00
WASH. CO. - LECS CIVIL/ PERMITS DEPT
SERVICE WINDOWS
SHEET INDEX
# NAME D
D
S E
T
.1
.2
P E
R M
IT
.1
.2
A0.00 COVER SHEET ■ ■
A0.01 PROJECT NOTES ■ ■
A0.05 ICC CLEARANCE REQUIREMENTS ■ ■
A2.00 FLOOR PLAN, RCP, & ELEVATIONS ■ ■
A6.00 INTERIOR ELEVATIONS ■ ■
A7.00 INTERIOR DETAILS ■ ■
E-001 ABBREVIATIONS, SYMBOLS, SPECS & SHEET INDEX ■
E-121 LEVEL 2 - POWER FLOOR PLANS ■
1 VICINITY MAP
PROJECTNORTH NORTH
EXISTING PROPOSED
CONSTRUCTION TYPE:
SPRINKLERED:
BUILDING STORIES
(ABOVE GRADE):
BUILDING STORIES
(BELOW GRADE):
BUILDING OCCUPANCY:
TENANT IMPROVEMENT
AREA:
OCCUPANT LOAD FOR
TENANT IMPROVEMENT:
I-A UNCHANGED
YES UNCHANGED
2 (4 IN JAIL) FLOORS UNCHANGED FLOORS
0 FLOORS UNCHANGED FLOORS
B, I-3, A-3 UNCHANGED
250 USF UNCHANGED USF
- UNCHANGED
DEFERRED SUBMITTALS
BUILDING COMPONENT D
E
L E
G A
T E
D D
E S
IG
N
D E
F E
R R
E D
S U
B M
IT
T
A L
S E
P A
R A
T E
P E
R M
IT
FIRE SPRINKLER ■ ■ ■
FIRE ALARM ■ ■ ■
MECHANICAL ■ ■ ■
BUILDING INFORMATION
BUILDING CODE: 2022 OREGON STRUCTURAL SPECIALTY CODE
ELECTRICAL CODE: 2022 OREGON ELECTRICAL SPECIALTY CODE
MECHANICAL CODE: 2022 OREGON MECHANICAL SPECIALTY CODE
FUEL GAS CODE: 2023 OREGON PLUMBING SPECIALTY CODE
FIRE CODE: 2021 OREGON FIRE CODE
ENERGY CODE: 2021 OREGON ENERGY EFFICIENCY SPECIALTY CODE
ACCESSIBILITY CODES: ICC A117.1-2017 / 2010 ADA STANDARDS
1" = 40'-0"2 KEY PLAN
REVISION DATE REASON FOR ISSUE
PROJECT NOTES
1. THESE DRAWINGS ARE THE PROPERTY OF ANKROM MOISAN ARCHITECTS
AND SHALL NOT BE COPIED OR REUSED FOR ANY OTHER PROJECT.
2. VERIFY SITE CONDITIONS AND REPORT ANY DISCREPANCIES TO THE
ARCHITECT BEFORE PROCEEDING WITH CONSTRUCTION.
3. CARE HAS BEEN TAKEN TO DOCUMENT EXISTING CONSTRUCTION
CONDITIONS. HOWEVER, FIELD CONDITIONS AND HIDDEN CONDITIONS
MAY DIFFER AND POSE POTENTIAL CONFLICTS WITH THE DRAWINGS.
FAILURE TO REPORT DISCREPANCIES OR CONFLICTS TO ARCHITECT PRIOR
TO PERFORMING WORK MAY LEAD TO WORK IN QUESTION BEING
REJECTED BY TENANT OR ARCHITECT.
4. WORK SHALL BE PERFORMED PER APPLICABLE CODES AND STANDARDS.
5. SEE ACCESSIBILITY SHEET(S) FOR ACCESSIBLE CLEARANCES TO BE
PROVIDED.
6. COORDINATE THE WORK OF DELEGATED DESIGN COMPONENTS WITH
THE WORK OF OTHER TRADES.
7. IF WORK IS TO BE PERFORMED AFTER HOURS, CONTRACTOR TO CONFIRM
WORK REQUIREMENTS WITH AGENCY AND OWNER.
8. PROVIDE EMAIL CONFIRMATION TO THE ARCHITECT THAT CONTRACTOR
HAS READ AND REVIEWED THIS INFORMATION.
GENERAL REQUIREMENTS
PROTECTION AND CLEANING
1. ERECT TEMPORARY CONSTRUCTION BARRIERS AND EMPLOY NOISE, DUST
AND INFECTION CONTROL MEASURES AS NEEDED TO PROTECT PASSERS-
BY AND ADJACENT SPACES DURING CONSTRUCTION. REMOVE
TEMPORARY BARRIERS AT COMPLETION OF CONSTRUCTION AND
RESTORE THE AFFECTED AREAS TO THEIR PRE-CONSTRUCTION
CONDITION.
2. MAINTAIN THE PREMISES AND THE JOBSITE IN A NEAT, ORDERLY
CONDITION. AT THE END OF EACH WORK DAY LEAVE THE SITE FREE FROM
ACCUMULATED WASTE MATERIALS AND RUBBISH. REMOVE CRATES,
CARTONS, AND OTHER FLAMMABLE WASTE MATERIALS OR TRASH FROM
THE WORK AREA AT THE END OF EACH WORKING DAY.
3. CLEAN PIPE AND DUCT SHAFTS, CHASES, FURRED SPACES, AND SIMILAR
SPACES, AND LEAVE THEM FREE OF RUBBISH, LOOSE PLASTER, MORTAR
DRIPPINGS, EXTRANEOUS CONSTRUCTION MATERIAL, DIRT, AND DUST.
4. UPON COMPLETION OF THE WORK, THOROUGHLY CLEAN THE PREMISES
AND WASH THE INSIDE OF ALL WINDOWS AND ALL INTERIOR GLAZING
AND MAKE THE SPACE OTHERWISE READY FOR OCCUPANCY.
WARRANTY
1. WARRANT ALL PARTS, LABOR, EQUIPMENT, AND MATERIALS PROVIDED
UNDER THIS CONTRACT FOR A PERIOD OF ONE (1) YEAR AFTER
SUBSTANTIAL COMPLETION.
DIMENSIONS
1. VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS PRIOR TO
CONSTRUCTION. NOTIFY THE ARCHITECT OF CONFLICTS PRIOR TO
CONSTRUCTION.
2. DO NOT SCALE THE DRAWINGS. WRITTEN DIMENSIONS GOVERN.
3. DO NOT ADJUST CLEAR DIMENSIONS WITHOUT APPROVAL OF THE
ARCHITECT.
4. DIMENSIONS ARE MEASURED FROM GRIDLINE, FACE OF CONCRETE, FACE
OF MASONRY CENTERLINE OF STUD UNLESS OTHERWISE NOTED.
5. DIMENSIONS NOTED AS ‘INSIDE CLEAR' ARE MEASURED FROM THE FACE
OF THE DEEPEST PROTRUSION FROM THE WALL SURFACE (CASEWORK,
FIXTURE, BASE, HANDRAIL, WAINSCOT, TRIM, ETC.)
6. NOTES TO 'ALIGN' REFER TO FINISHED FACE OF INDICATED SURFACES.
7. 'FLOOR LINE’, ‘FLOOR,' OR ’FLOOR LEVEL' REFER TO TOP OF CONCRETE
SLAB OR TOP OF CEMENTITIOUS UNDERLAYMENT. FINISH FLOORING IS
INSTALLED ABOVE THE FLOOR LINE.
8. 'FINISH FLOOR' REFERS TO THE TOP OF FINISH FLOORING.
1. DESIGN, FURNISH AND INSTALL THE FOLLOWING WORK ON A DELEGATED
DESIGN BUILD BASIS:
A. METAL FRAMING FOR WALLS, SOFFITS AND CEILINGS
B. MECHANICAL HVAC
C. FIRE PROTECTION
D. ELECTRICAL
E. LOW VOLTAGE
F. MODIFICATIONS TO EXISTING FIRE ALARM
2. COORDINATE DELEGATED OR DEFERRED DESIGN ITEMS FOR REVIEW AND
APPROVAL BY OWNER AND ARCHITECT PRIOR TO CONSTRUCTION.
3. PROVIDE DRAWINGS AND SPECIFICATIONS AS REQUIRED BY THE
AUTHORITY HAVING JURISDICTION (AHJ) FOR PERMITTING PURPOSES
4. CONFORM WITH THE APPLICABLE BUILDING CODES AND OTHER STATE
AND LOCAL CODES AS REQUIRED.
5. INFORMATION RELATING TO DELEGATED DESIGN IS PROVIDED FOR
DESIGN INTENT ONLY. VERIFY REQUIREMENTS OF OWNER AND AGENCY.
DELEGATED DESIGN
CODE COMPLIANCE
1. MAINTAIN REQUIRED COVERAGE FOR ALL EMERGENCY LIGHTING,
SPRINKLERS, FIRE DETECTORS, AND FIRE ALARM COMMUNICATION
DEVICES DURING CONSTRUCTION.
2. VERIFY FIRE EXTINGUISHER LOCATIONS WITH THE FIRE MARSHAL. LOCATE
FIRE EXTINGUISHERS IN ACCESSIBLE LOCATIONS, IN PLAIN VIEW, AND
SPACED A MAXIMUM OF 75 FEET APART MEASURED ALONG PATH OF
TRAVEL. VERIFY EXTINGUISHER CAPACITY TO PROVIDE NO MORE THAN
ONE EXTINGUISHER FOR EVERY 3,000 SQUARE FEET OF FLOOR AREA.
3. PROVIDE SMOKE DETECTORS PER APPLICABLE CODES.
4. PROVIDE EXIT SIGNS AND ILLUMINATION IN ACCORDANCE WITH THE
REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. REFER TO
ELECTRICAL DRAWINGS FOR MORE INFORMATION.
WORKMANSHIP
1. PROVIDE ALL WORK LISTED, SHOWN, OR IMPLIED ON CONSTRUCTION
DOCUMENTS UNLESS NOTED OTHERWISE.
2. CONFORM TO OWNER’S BUILDING STANDARD DETAILS UNLESS NOTED
OTHERWISE.
3. EXCEPT WHERE REUSE IS NOTED, ALL MATERIALS, EQUIPMENT AND
APPLIANCES USED IN THE WORK SHALL BE NEW.
4. EXERCISE CARE WHERE NEW WALL CONSTRUCTION ABUTS, INTERSECTS,
OR JOINS EXISTING ADJACENT CONSTRUCTION. MAINTAIN FIRE AND
ACOUSTIC ASSEMBLY INTEGRITY WHERE NEW WALLS ABUT, INTERSECT,
OR JOIN EXISTING.
5. PATCH, REPAIR, AND OTHERWISE RESTORE EXISTING MATERIALS,
EQUIPMENT, AND FINISHES TO AS-NEW CONDITION.
DEMOLITION
1. DISMANTLE AND REMOVE ALL ITEMS NOT SCHEDULED TO REMAIN OR TO
BE REUSED AS A PART OF NEW CONSTRUCTION. COORDINATE SALVAGE
OF MATERIALS/ITEMS WITH AGENCY.
2. REMOVE ALL UTILITIES (WIRING, CONDUITS, SWITCHES, ELECTRICAL
BOXES, EQUIPMENT, PIPING, FIXTURES, ETC.) AND OTHER
APPURTENANCES FROM EXISTING CONSTRUCTION SCHEDULED FOR
DEMOLITION BACK TO NEAREST POINT OF CONNECTION TO SOURCE.
3. REMOVE WATER SUPPLY, WASTE AND VENT PIPING FROM FIXTURES,
EQUIPMENT, WALLS, OR OTHER ITEMS SCHEDULED TO BE DEMOLISHED
BACK TO NEAREST CONCEALED POINT OF CONNECTION TO MAIN PIPING.
4. EXERCISE CARE IN CAPPING OFF ALL UNUSED ELECTRICAL AND PLUMBING
FEEDS. WHERE POSSIBLE REMOVE ALL ABANDONED UTILITY FEEDS BACK
TO THE SOURCE OF ORIGINATION. REMOVE CONDUITS WHERE POSSIBLE.
5. PENETRATING ELEMENTS THAT PROJECT THROUGH THE ROOF, FLOOR
ABOVE, OR BUILDING ENCLOSURE SHALL NOT BE ABANDONED IN PLACE.
REMOVE ELEMENT AND USE APPROPRIATELY TRAINED PERSONNEL TO
REPAIR ROOF, FLOOR, OR ENCLOSURE PENETRATION.
6. REMOVE HANGERS, SUPPORTS, BRACES AND OTHER APPURTENANCES
FROM WALLS AND CEILINGS SCHEDULED FOR DEMOLITION.
7. CONDUCT DEMOLITION TO AVOID DAMAGE TO EXISTING BUILDING
SHELL/ STRUCTURE. CEASE OPERATION AND NOTIFY OWNER
IMMEDIATELY IF SHELL/ STRUCTURE APPEARS TO BE IN DANGER. DO NOT
REMOVE ANY STRUCTURAL ELEMENTS WITHOUT PRIOR DIRECTION AND
AUTHORIZATION BY A STRUCTURAL ENGINEER.
8. DO NOT REMOVE ANY STRUCTURAL ELEMENTS WITHOUT PRIOR
DIRECTION AND AUTHORIZATION BY A STRUCTURAL ENGINEER.
9. PORTIONS OF WALLS SCHEDULED TO REMAIN MAY BE DEMOLISHED AND
REPLACED WITH NEW AT THE CONTRACTOR'S OPTION PROVIDED
QUALITY IS ACHIEVED WITHIN PROJECT BUDGET.
10. PATCH, RESTORE, OR OTHERWISE RECONSTRUCT AREAS DAMAGED OR
EXPOSED DURING DEMOLITION TO MATCH ADJACENT SURFACES.
11. RELOCATE EXISTING HVAC OR SPRINKLER HEADS IMPEDING ON NEW
WALL CONSTRUCTION. FOLLOW NECESSARY CODES AND REGULATIONS.
SUBMITTALS, SAMPLES. MOCK-UPS, AND SHOP DRAWINGS
1. NO BUILDING COMPONENT SHOWN ON THESE DRAWINGS SHALL BE
INCORPORATED INTO THE WORK UNTIL SHOP DRAWINGS, SAMPLES
(PROVIDE 3), BROCHURES OR OTHER SUBMITTALS CALLED FOR HEREIN
HAVE BEEN APPROVED BY THE ARCHITECT. ALLOW (5) BUSINESS DAYS
FOR REVIEW.
2. PROVIDE SHOP DRAWINGS OF THE FOLLOWING ITEMS FOR REVIEW AND
APPROVAL PRIOR TO FABRICATION:
A. CASEWORK
B. DELEGATED DESIGN COMPONENTS
C. DOORS, FRAMES AND HARDWARE
3. SUBMIT SAMPLES FOR THE FOLLOWING ITEMS, BUT NOT LIMITED TO:
A. PAINT DRAW-DOWNS
B. CASEWORK FINISHES
4. SUBMIT WRITTEN SUBSTITUTION REQUESTS FOR APPROVAL PRIOR TO
PURCHASE OR INSTALLATION OF ANY ITEM. WRITTEN SUBSTITUTION
REQUESTS SHALL INCLUDE REASONS FOR SUBSTITUTION PLUS
SUFFICIENT INFORMATION REGARDING COST, QUALITY, WARRANTY,
INSTALLATION, AND ANY OTHER PERTINENT INFORMATION NEEDED BY
THE OWNER AND ARCHITECT TO CONFIRM THE SUITABILITY OF THE
MATERIAL BEING PROPOSED.
5. ALLOW (5) BUSINESS DAYS FOR REVIEW OF ALL REQUESTS FOR
INTERPRETATION (RFI).
FIRE RATED CONSTRUCTION
1. PROTECT AND SEAL PENETRATIONS AND JOINTS AT FIRE RATED
CONSTRUCTION. MATCH THE FIRE-RESISTIVE RATING OF THE ASSEMBLIES
BEING PENETRATED. CONFORM TO THE REQUIREMENTS OF THE
AUTHORITY HAVING JURISDICTION.
2. FIRE RATED ASSEMBLIES: SEAL JOINTS, PENETRATIONS, AND
INTERSECTIONS WITH FIRE CAULKING
3. RECESSED DEVICES WITH FIRE PROTECTIVE COVERINGS SHALL MEET THE
REQUIREMENTS OF THE LISTING SOURCE. INSTALL ALL MATERIALS IN
STRICT ACCORDANCE WITH THE PUBLISHED REQUIREMENTS OF THE
LISTING SOURCE, INCLUDING BUT NOT LIMITED TO: STUD GAGE AND
SPACING, FASTENER SIZE AND SPACING, ORIENTATION OF GYPSUM
WALLBOARD, OFFSETS OF JOINTS BETWEEN ADJACENT LAYERS OR
OPPOSITE SIDES OF WALL, BRIDGING, AND CROSS BRACING.
INTERIOR WALLS
1. WOOD IN CONTACT WITH CONCRETE SHALL BE PRESERVATIVE-TREATED.
2. CONCEALED WOOD USED IN TYPE I AND TYPE II CONSTRUCTION SHALL BE
FIRE RETARDANT TREATED.
3. FASTENERS IN CONTACT WITH TREATED WOOD SHALL BE CORROSION
RESISTANT.
4. PROVIDE BLOCKING OR OTHER CONCEALED SUPPORTS WITHIN WALLS AS
REQUIRED FOR HANDRAILS, CASEWORK, GRAB BARS, ARTWORK,
SHELVING, AND OTHER APPLIED WALL MOUNTED FIXTURES, FINISHES OR
EQUIPMENT.
5. MAXIMUM STUD SPACING IS 24 INCHES ON CENTER UNLESS NOTED
OTHERWISE. MINIMUM STUDS OR FURRING GAUGE IS 25.
6. ADJUST STUD GAUGE AND SPACING TO MEET MANUFACTURER'S
PUBLISHED SPAN TABLES, SPECIFIED DEFLECTION CRITERIA, AND TO
SUPPORT ALL APPLIED LOADS FROM: FIXTURES, FURNISHINGS AND
EQUIPMENT; CASEWORK; GRAB BARS; WALL FINISHES; PRESSURIZATION;
ETC.
7. PROVIDE SMOOTH, LEVEL 4 FINISH AT NEW GYPSUM BOARD WALL
SURFACES, PER AWC I STANDARDS. APPLY A DRYWALL PRIMER
(SHEETROCK BRAND "FIRST COAT" OR EQUIV.) PRIOR TO FINAL FINISH
COAT TO MINIMIZE SURFACE TEXTURE VARIATIONS.
8. WHERE GYPSUM WALLBOARD PARTITIONS ARE INDICATED, PROVIDE 5/8"
FIRE-RATED GYPSUM WALLBOARD (TYPE 'X') AS DEFINED IN ASTM C1396.
FINISH AS INDICATED.
FIRE PROTECTION
1. PROVIDE DRAWINGS INDICATING:
A. LAYOUT, LOCATION, AND SIZE OF SPRINKLER LINES AND HEADS
B. PRESSURE REQUIREMENTS
C. SPRINKLER HEAD SPECIFICATIONS
D. LOCATION OF FIRE PROTECTION RISERS AND WALL HYDRANTS
2. VERIFY EXTENT OF EXISTING NFPA 13 FIRE SPRINKLER SYSTEM. EXISTING
AND NEW WORK SHALL INCLUDE QUICK RESPONSE HEADS IN
CONFORMANCE WITH APPLICABLE CODES AND STANDARDS.
HEATING, VENTILATION, AND AIR CONDITIONING
1. INSTALL MECHANICAL SYSTEMS AND EQUIPMENT PER APPLICABLE CODES
AND STANDARDS.
2. PROVIDE BUILDING STANDARD HVAC SYSTEM WITH ALL MATERIALS,
LABOR AND ACCESSORIES FOR COMPLETE OPERATION OF SYSTEM.
3. CONTRACTOR TO BALANCE HVAC SYSTEM AND PROVIDE BALANCE
REPORT AT COMPLETION OF WORK.
4. PROVIDE DELEGATED DESIGN MECHANICAL ENGINEERING DRAWINGS
INDICATING:
A. SIZES AND MATERIALS OF DUCTS
B. LOCATIONS OF DAMPERS, ACCESS PANELS, AND THERMOSTATS
C. AIR MOVEMENT REQUIREMENTS
D. SIZES OF GRILLS AND REGISTERS
5. CLEAN, REPAIR OR REPLACE SOILED OR DAMAGED HVAC GRILLS, FILTERS
AND THERMOSTATS.
6. RE-ZONE, ALTER OR SEPARATE HVAC AS NECESSARY AS DIRECTED BY
OWNER FOR ALTERED SUITE.
ELECTRICAL AND LOW VOLTAGE
1. COMPLETE ELECTRICAL, DATA, COMMUNICATION, AND SECURITY WORK
IN ACCORDANCE WITH ALL APPLICABLE CODES.
2. CONFORM TO APPLICABLE ENERGY CODE. VERIFY APPROVED ENERGY
CODE REQUIREMENTS AND ENERGY MANAGEMENT SYSTEM AS PART OF
THE DESIGN BUILD CONTRACT.
3. PROVIDE ALL WORK, EQUIPMENT AND LABOR FOR A COMPLETE AND
OPERABLE ELECTRICAL SYSTEM.
4. ARCHITECTURAL DRAWINGS INDICATE LOCATION ONLY OF DEVICES
SHOWN. PROVIDE DESIGN BUILD ELECTRICAL ENGINEERING DRAWINGS
INDICATING:
A. CIRCUITING
B. POWER & DATA DEVICES
5. COORDINATE DATA, COMMUNICATIONS, AND FIRE SAFETY DEVICES WITH
INTERIOR ELEVATIONS AND FINISHES.
6. AGENCY DATA AND COMMUNICATION SHALL BE SEPARATE FROM OTHER
AGENCY SPACES OR AS DIRECTED BY OWNER.
7. VERIFY EXISTING CONDITIONS. PROVIDE ALTERATIONS TO EMERGENCY
EXIT LIGHTING AND ACCESS PATHWAY LIGHTING PER APPLICABLE CODES
AND STANDARDS.
8. FIELD REVIEW LOCATION OF ALL WALL MOUNTED POWER AND DATA
BOXES AND MUD RINGS WITH THE AGENCY BEFORE INSTALLATION OF
CONDUITS AND WIRING.
9. PROVIDE SEPARATE CIRCUITS FOR AGENCY’S EQUIPMENT WHEN NOTED
ON THE CONSTRUCTION DOCUMENTS.
10. PROVIDE EXTENSION RINGS AND MOUNTING ACCESSORIES WHERE
REQUIRED FOR POWER/DATA DEVICES. COORDINATE WITH INTERIOR
FINISHES AND CASEWORK.
11. CABLING FOR VOICE AND DATA TO BE PROVIDED BY AGENCY’S VENDORS
AND SHALL BE COORDINATED BY THE BUILDING OWNER.
12. REUSE EXISTING ELECTRICAL OUTLETS WHEREVER PRACTICAL UNLESS
NOTED OTHERWISE.
13. PROVIDE NEW ELECTRICAL OUTLETS PER POWER AND DATA PLAN.
14. MOUNT NEW ELECTRICAL DEVICES AT HEIGHTS CONFORMING TO ADA.
15. GANG MULTIPLE DEVICES WHERE THEY OCCUR IN A SINGLE LOCATION.
16. BACK-TO-BACK ELECTRICAL DEVICES ARE NOT PERMITTED. OFFSET
ELECTRICAL DEVICES AT LEAST ONE STUD BAY MINIMUM AS REQUIRED
FOR ACOUSTICAL CONTROL.
1. SUBMIT WRITTEN PENETRATION DETAILS FOR REVIEW AND APPROVAL BY
THE OWNER’S STRUCTURAL ENGINEER. DO NOT CORE DRILL, TRENCH, OR
OTHERWISE PENETRATE EXISTING CONCRETE SLABS PRIOR TO RECEIVING
APPROVAL. SLEEVE AND SEAL ALL THROUGH-SLAB PENETRATIONS IN
ACCORDANCE WITH CURRENT CODE.
2. ANY AND ALL MECHANICAL FASTENING, CORE DRILLING, SLAB
TRENCHING AND/OR PENETRATIONS OF THE EXISTING CONCRETE SLAB
SHALL REQUIRE:
A. A CERTIFICATION BY THE OWNER'S STRUCTURAL ENGINEERS
B. BE SLEEVED AND SEALED AS INDICATED IN OWNER'S SHELL/CORE
BUILDING FLOOR PENETRATION DETAIL.
3. ALL PENETRATION WORK SHALL REQUIRE X-RAYING OF STRUCTURAL
SLABS. AGENCY/AGENCY'S CONTRACTORS ARE NOT PERMITTED TO CHOP
OR CUT FLOOR SLABS FOR THE PURPOSE OF TRENCH DRAINS OR ANY
RECESSED EQUIPMENT WITHOUT OWNER'S WRITTEN APPROVAL.
STRUCTURAL
GLAZING
1. PROVIDE AND INSTALL NEW GLAZED OPENINGS PER BUILDING STANDARD
UNLESS NOTED OTHERWISE.
2. SET UNITS LEVEL, PLUMB AND TRUE TO LINE AND LOCATION. ADJUST AND
REINFORCE THE ATTACHMENT SUBSTRATE AS NECESSARY FOR PROPER
INSTALLATION AND OPERATION.
3. ADJUST AND CHECK EACH OPERATING ITEM OF HARDWARE AND EACH
UNIT TO ENSURE PROPER OPERATION OR FUNCTION.
PAINT AND STAIN
1. UTILIZE MASTER PAINTERS INSTITUTE (MPI) ARCHITECTURAL PAINTING
SPECIFICATIONS. APPROVED MPI PRODUCTS TO BE UTILIZED OR PROVIDE
SUBSTITUTION FOR APPROVAL TO ARCHITECT.
2. CONFORM TO THE REQUIREMENTS OF THE "ARCHITECTURAL
SPECIFICATIONS MANUAL" (AWS) FOR PAINT SYSTEMS. LATEX PAINT: AWS
SYSTEM 3-B "CUSTOM" (2 COAT) GRADE LIGHT COLOR PAINT FINISH AND
LATEX PAINT: AWS SYSTEM 3-B "CUSTOM" (2 COAT) GRADE DEEP TONE
PAINT FINISH ON GYPSUM BOARD SURFACES.
3. PREPARE ALL PAINTED SURFACES IN STRICT ACCORDANCE WITH
MANUFACTURER’S SPECIFICATIONS.
4. FILL ALL NAIL HOLES, COUNTERSUNK SCREWS, BOLTS, CRACKS, ETC.
BEFORE APPLYING FINISH.
5. MAKE FINISH WORK UNIFORM AND SMOOTH, FREE OF RUNS, SAGS,
DEFECTIVE BRUSHING AND CLOGGING. MAKE EDGES OF PAINT ADJOINING
OTHER MATERIALS OR COLORS SHARP AND CLEAN WITHOUT
OVERLAPPING.
6. UPON COMPLETION OF WORK, REMOVE EXCESS PAINT, STAIN, SEALER,
ADHESIVE, CAULK; ETC. FROM ALL OTHER SURFACES NOT SPECIFIED TO
RECEIVE SAME.
7. TOUCH-UP AND PATCH SURFACES AS REQUIRED AFTER THE COMPLETION
OF WORK BY OTHER TRADES.
CASEWORK
1. NEW CASEWORK AND MILLWORK SHALL BE CONSTRUCTED TO AWI
“PREMIUM” STANDARDS, UNLESS NOTED OTHERWISE.
Image of Stamp
PROJECT NUMBER
© ANKROM MOISAN ARCHITECTS, INC.
38 NORTHWEST DAVIS STREET, SUITE 300
PORTLAND, OR 97209
503.245.7100
1505 5TH AVENUE, SUITE 300
SEATTLE, WA 98101
206.576.1600
115 SANSOME STREET, SUITE 1005
SAN FRANCISCO, CA 94104
415.252.7063
DATE
SHEET NUMBERSHEET NUMBER
A u to d e s k D o cs
/A
M
S e ct o r S a n d b o x
O
/2
-2
-W a
C o
T ra n W in d o w
.r v t
/1
/2
:1
:3
A
M
250810
PERMIT SET
W A
C O
T R
A N
S A
C T
IO
N
W
IN
D O
W
W A
S H
IN
G
T O
N C
O U
N T
Y
S
W A
D A
M S
H
IL
L S
B O
R O
O
R
6.15.26
PROJECT NOTES
A0.01
ABBREVIATIONS
ABBREVIATION TERM
A/V AUDIO VISUAL
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISH FLOOR
ALUM ALUMINUM
ARCH ARCHITECTURAL
BD BOARD
BLDG BUILDING
BOT/BTM BOTTOM
CAB CABINET
CFS CLEAR FLOOR SPACE
CG CORNER GUARD
CL CENTER LINE
CLG CEILING
CLR CLEAR
COL COLUMN
CONC CONCRETE
CORR CORRIDOR
CTR CENTER
D/W DISHWASHER
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIM DIMENSION
DWG DRAWING
DWR DRAWER
(E)/EXIST EXISTING
EA EACH
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQPT EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FIN FINISH
FIXT FIXTURE
FLR FLOOR
FLS FIRE AND LIFE SAFETY
FO FACE OF
FOIC FURNISHED BY OWNER INSTALLED BY CONTRACTOR
FOIO FURNISHED BY OWNER INSTALLED BY OWNER
FURRG FURRING
GA GAUGE
GD GARBAGE DISPOSAL
GL GLASS
GYP GYPSUM
HDW HARDWARE
HR HOUR
HT HEIGHT
JAN JANITOR
LAM LAMINATE
LAV LAVATORY
LF LINEAL FEET, LINEAR FOOTAGE
MDF MEDIUM DENSITY FIBERBOARD
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
MW MICROWAVE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OH OVERHEAD
OPNG OPENING
PTN PARTITION
RCP REFLECTED CEILING PLAN
REF REFERENCE
REFR REFRIGERATOR
RR REST ROOM
SCHED SCHEDULE
SD SOAP DISPENSER
SHWR SHOWER
SIM SIMILAR
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STOR STORAGE
STR STAIR, STAIRS
TEL TELEPHONE
THK THICK
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VFY VERIFY
VIF VERIFY IN FIELD
VNR VENEER
W/ WITH
W/H WATER HEATER
W/O WITHOUT
WC WATER CLOSET
WD WOOD
APPROACH DIRECTION
TURNING CIRCLE
WHEELCHAIR CLEAR FLOOR
SPACE & CLEAR AREA REQUIRED
BEYOND DOOR SWING
48" IN TYPE B UNITS
52"
T-SHAPED TURNING SPACE
OPTION 3
WHEREVER TURNING SPACE IS
REQ'D, EITHER TURNING CIRCLE
OR ONE OF T-SHAPED TURNING
SPACE OPTIONS MAY BE USED
HATCHED AREA IS
ONLY AREA
PERMITTED KNEE
AND TOE CLEARANCE
T-SHAPED TURNING SPACE
OPTION 2
T-SHAPED TURNING SPACE
OPTION 1
FOR T-TURN, KNEE
AND TOE CLEARANCE
CAN BE ON EITHER
THE BASE OR ONE
ARM. SEE PLAN FOR
OPTION SELECTED.
8" 8" 36" 8" 8"
68"
11" 42" 11"
64"
12" 40" 12"
64" ø 5' - 7"
CLEAR FLOOR SPACE IN ALCOVE
52"
60" MIN
X
30"
36" MIN
X
CLEAR FLOOR SPACE AND TURNING
SPACES TO BE 2% MAXIMUM SLOPE
IN ALL DIRECTIONS.
M A
X
PER ICC A117.1-2017 SECTION 304 AND 305 AND 2010 ADA SECTION 304 AND 305
LIMITS OF PROTRUDING OBJECTS
OBJECTS IN ANY PATH OF
CIRCULATION ARE REQUIRED TO
COMPLY WITH LIMITS SHOWN
HERE. OBJECTS THAT CANNOT
COMPLY, SUCH AS STANDPIPES
IN STAIRS AND CONTROL BOXES
IN PARKING GARAGE, SHALL
HAVE ADDED CANE DETECTION.
4" MAX
1. THESE PICTOGRAPHS DO NOT DESCRIBE ALL CONDITIONS WHICH MAY BE ENCOUNTERED IN THE
FIELD. VERIFY QUESTIONS WITH ARCHITECT
2. INFORMATION IN THESE DRAWINGS IS COMPLEMENTARY TO THE PLANS, SECTIONS, ELEVATIONS
AND DETAILS, AND SHALL BE USED IN CONJUNCTION WITH THEM
3. PROVIDE WORK SHOWN OR REFERRED TO HEREIN AS THOUGH SHOWN ON ALL OTHER
ARCHITECTURAL DRAWINGS
4. INFORMATION REGARDING THE LOCATION OF MECHANICAL, ELECTRICAL AND PLUMBING ITEMS IS
PROVIDED AS DESIGN CRITERIA FOR THE CONVENIENCE OF THOSE DESIGNERS OF RECORD WHO
SHALL BEAR RESPONSIBILITY FOR COMPLIANCE WITH THE APPLICABLE CODE STANDARDS
ILLUSTRATED AND CITED HEREIN
5. PROVIDE GRAB BARS, AS ILLUSTRATED HEREIN.
6. COMPLY WITH MOUNTING HEIGHTS INDICATED HEREIN FOR WALL-MOUNTED ITEMS.
CODE MINIMUM AND MAXIMUM HEIGHTS ARE NOTED. SPECIFIC HEIGHT MAY BE CALLED OUT ON
INTERIOR ELEVATIONS FOR COORDINATION WITH ACCESSORIES ABOVE GRAB BARS.
7. COMPLY WITH GENERAL BUILDING CLEARANCE REQUIREMENTS AS INDICATED HEREIN.
8. ENCROACHMENT INTO FLOOR CLEARANCE AREAS AT DOORS, CASEWORK, APPLIANCES OR
EQUIPMENT IS NOT ALLOWED UNLESS OTHERWISE NOTED.
9. NOTIFY THE ARCHITECT IMMEDIATELY IF CONFLICTS ARE DISCOVERED BETWEEN THE
REQUIREMENTS ILLUSTRATED HEREIN AND THOSE ON OTHER DRAWINGS.
10. THE SPACE BETWEEN THE GRAB BAR AND PROJECTING OBJECTS BELOW AND AT THE ENDS OF THE
GRAB BAR SHALL BE 1 1/2" MIN. THE SPACE BETWEEN THE GRAB BAR AND PROJECTING OBJECTS
ABOVE THE GRAB BAR SHALL BE 12" MIN.
11. OPERABLE PARTS SHALL BE OPERATED WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
PARTS SHALL BE 5.0 POUNDS (22.2 N) MAXIMUM.
GENERAL NOTES - ACCESSIBILITY SHEETS
B E
V E
LE
D
:2
M A
X
/2
M
A X
V E
R T
IC
A
L T
R A
N
SI
T
IO
N
/4
M
A X
V E
R T
IC
A
L T
R A
N
SI
T
IO
N
/4
M
A X
/2
M
A X
PER 2010 ADAS AND ICC A117.1 SECTION 303
M
A X
20" MAX.
M
A X
MAX.
20"-25"
M
A X
MAX.
> 10" - 24"
MAX.
10"
M
A X
MAX.
10"
M
A X
M
IN
M
A X
M
IN
M
A X
M
A X
SIDE REACH DIAGRAMS FORWARD REACH DIAGRAMS
NOTE: SEE TYPE B UNIT SHEET FOR EXCEPTIONS
TO SIDE REACH WITHIN TYPE B RESIDENTIAL UNITS
PULL SIDE - FRONT APPROACH
PUSH SIDE - FRONT APPROACH
WITHOUT LATCH & CLOSER
PULL SIDE - HINGE APPROACH
OPTION 2
PULL SIDE - HINGE APPROACH
OPTION 1
PUSH SIDE - HINGE APPROACH
WITHOUT LATCH & CLOSER
FRONT APPROACH POCKET OR HINGE APPROACH
MANEUVERING CLEARANCE AT MANUAL SWINGING DOORS
PULL SIDE - LATCH APPROACH
WITHOUT LATCH & CLOSER
MANEUVERING CLEARANCE
AT SLIDING DOORS, FOLDING DOORS, AND OPENINGS
RECESSED DOORS - PULL SIDE RECESSED DOORS - PUSH SIDE
RECESSED DOORS - PUSH SIDE
WITH CLOSER AND LATCH
MANEUVERING CLEARANCE AT RECESSED DOORS
STOP OR LATCH APPROACH
M
IN
18" MIN 36" MIN
M
IN
42" MIN
M
IN
24" MIN
M
IN
M
IN
22" MIN
M
IN
24" MIN
M
IN
18" MIN
X
M
IN
NOTE: DOOR
MANEUVERING CLEARANCES
MEASURED FROM FACE OF
BASE TRIM TO NEAREST
OBSTRUCTION. DOOR
MANEUVERING CLEARANCES
CAN BE OFFSET UP TO 8"
FROM FACE OF DOOR.
F O
S T
O P
F O
D O
O R
A T
F O
S T
O P
F O
D O
O R
F O
S T
O P
F O
D O
O R
CLR OPENING
32" MIN
CLR OPENING
32" MIN
CLR OPENING
32" MIN
36" MIN
36" MIN
M
A X
CLEAR DIMENSIONS
MEASURED AT TRIM OR
OTHER ITEMS THAT RESTRICT
CLEARANCE
32" MIN
PER 2017 ICC A117.1 AND 2010 ADAS 404 FOR NEW CONSTRUCTION
PULL SIDE - LATCH APPROACH
WITH LATCH & CLOSER
24" MIN
M
IN
M
IN
M
IN
22" MIN
PUSH SIDE - FRONT APPROACH
WITH LATCH & CLOSER
M
IN
12" MIN
PUSH SIDE - HINGE APPROACH
WITH LATCH & CLOSER
M
IN
22" MIN
PUSH SIDE - LATCH APPROACH
WITHOUT LATCH & CLOSER
24" MIN
M
IN
PUSH SIDE - LATCH APPROACH
WITH LATCH & CLOSER
24" MIN
M
IN
X
X
CLOSER AND LATCH
12" MIN WITH5
M
IN
M
IN
DOORS FOR USER PASSAGE
AND >24" DEEP CLOSET
BIFOLD DOORS INTENDED FOR USER
PASSAGE AND >24" DEEP CLOSET
SLIDING DOORS INTENDED
FOR USER PASSAGE AND >24"
DEEP CLOSET
ACCESSIBLE ROUTE WIDTH
X
WHEN X > 8", FOLLOW
REQUIREMENTS FOR
RECESSED DOORS
M A
X
M A
X
M A
X
M A
X
WHEN FACE OF DOOR
MORE THAN 8" FROM
SURROUNDING WALL,
ONLY FORWARD
APPROACH ALLOWED
MEN
F.E.C.
FIRE ALARM
PULL STATION
FIRE
EXTINGUISHER
ENVIRONMENTAL
CONTROLS ELECTRICAL
& COMMUNICATION
@ PULL
HANDLE
PAPER TOWEL
DISPENSER/TRASH
RECEPTACLE
SOAP
DISPENSER
PAPER
TOWEL
DISPENSER
NOT IN
PICTOGRAM
FIELD
SIGNAGE: HEIGHT AND CLEAR FLOOR SPACEHOOKTELEPHONE/
ENTRY CALL
BOX
M
A X
SE
E
IN
T
. E
LE
V
SE
E
T A
B
LE
SE
E
T A
B
LE
M
IN
M
IN
LOWEST
OPERABLE
PART
SURFACE
MOUNTED SEAT
COVER DISPENSER
SE
E
T A
B
LE
M
A X
M
A X
M
IN
M
A X
M
A X
TABLE 603.6 MAXIMUM REACH DEPTH AND HEIGHT FOR OPERABLE PARTS ON TOWEL DISPENSERS AND HAND DRYERS SERVING ACCESSIBLE LAVATORIES.
MAXIMUM
REACH DEPTH
MAXIMUM
REACH HEIGHT
0.5 INCH
(13 MM)
48 INCHES
(1220 MM)
2 INCH
(51 MM)
46 INCHES
(1170 MM)
5 INCH
(125 MM)
42 INCHES
(1065 MM)
6 INCH
(150 MM)
40 INCHES
(1015 MM)
9 INCH
(230 MM)
36 INCHES
(915 MM)
11 INCH
(280 MM)
34 INCHES
(865 MM)
P R
O T
R U
SI
O
N
M
A X
IF
T H
A N
M
A X
HIGHEST OPERABLE PART INCLUDING
FIRE EXTINGUISHER HANDLE. VERIFY
HEIGHT WITH OSHA AND FIRE INSPECTOR
IN WASHINGTON, ALSO
APPLIES TO CLEANSING
PRODUCT DISPENSERS AND
DISPOSAL FIXTURES
MIRROR OVER
LAVATORY OR
CABINET
MIRROR NOT
OVER
OBSTRUCTION
LOCKERS 5% OF TOTAL PROVIDED
SHALL BE COMPLETELY WITHIN
REACH RANGE
ACCESSIBLE LOCKER
WITH ACCESSIBLE
HANDLE
AUTOMATIC HAND
DRYERS (VARIOUS TYPES)
SIDE VIEW
SE
E
T A
B
LE
/2
" TACTILE RAISED
CHARACTERS
5/8" TO 2"
0" - 80" AFF
18" MIN
M
IN
CENTERED
ON TACTILE
CHARACTERS
T O
B O
T T
O M
S H
E
LF
M
IN
T O
P O
F A
C C
E S
SI
B
LE
L
O C
K E
R
M
A X
SPECIMEN PASS
THROUGH
CABINET
M
A X
SE
E
T A
B
LE
M
IN
KEY TO REFILL
EXEMPT
SANITARY
NAPKIN
DISPENSER
ALL DIMENSIONS TO
HIGHEST OPERABLE
PART UNO
A
FF
32" MIN
DOOR CLOSERS AND DOOR
STOPS MAY PROJECT DOWN TO
78 INCHES ABOVE FLOOR
PROJECTIONS LIMITED TO 34
INCHES TO 80 INCHES ABOVE
FLOOR
DOOR FRAME
DOOR
PANIC HARDWARE OR OTHER
DOOR HARDWARE
4" MAX
CLEAR WIDTH - NO PROJECTIONS
WITHIN THIS AREA
Image of Stamp
PROJECT NUMBER
© ANKROM MOISAN ARCHITECTS, INC.
38 NORTHWEST DAVIS STREET, SUITE 300
PORTLAND, OR 97209
503.245.7100
1505 5TH AVENUE, SUITE 300
SEATTLE, WA 98101
206.576.1600
115 SANSOME STREET, SUITE 1005
SAN FRANCISCO, CA 94104
415.252.7063
DATE
SHEET NUMBERSHEET NUMBER
A u to d e s k D o cs
/A
M
S e ct o r S a n d b o x
O
/2
-2
-W a
C o
T ra n W in d o w
.r v t
/1
/2
:1
:4
A
M
250810
PERMIT SET
W A
C O
T R
A N
S A
C T
IO
N
W
IN
D O
W
W A
S H
IN
G
T O
N C
O U
N T
Y
S
W A
D A
M S
H
IL
L S
B O
R O
O
R
6.15.26
ICC CLEARANCE
REQUIREMENTS
A0.05
3/8" = 1'-0"1 TYPICAL SYMBOLS LEGEND
3/8" = 1'-0"3 PROTRUDING OBJECTS
3/8" = 1'-0"4 FLOOR LEVEL TRANSITIONS
3/8" = 1'-0"5 REACH DIAGRAMS
3/8" = 1'-0"6 DOOR MANEUVERING CLEARANCES
3/8" = 1'-0"9 MOUNTING HEIGHTS
3/8" = 1'-0"2 DOOR CLEAR WIDTH & PROJECTIONS
CR
CR
(E
(E
(E
(E
LEGEND
NOT IN CONTRACT (NIC)
EXISTING TO REMAIN
NEW CONSTRUCTION
KEYNOTE
CARD READER
ABBREVIATIONS
PHASING
(E) EXISTING
(N) NEW
(D) DEMOLISH
01-01
FLOOR PLAN NOTES
1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR
TO CONSTRUCTION.
2. EXISTING CEILING SYSTEMS TO REMAIN AS-IS UNLESS NOTED
OTHERWISE.
3. EXISTING FLOORING TO REMAIN AS-IS. PROTECT FOR DURATION OF
CONSTRUCTION.
4. ALL SUBCONTRACTOR DESIGNED ITEMS ARE TO BE SUBMITTED TO
AND APPROVED BY THE ARCHITECT PRIOR TO CONSTRUCTION.
PROVIDE SHOP DRAWINGS FOR ALL GLAZING.
5. ALL WORK LISTED, SHOWN OR IMPLIED ON ANY CONSTRUCTION
DOCUMENTS SHAL BE SUPPLIED AND INSTALLED BY THE GENERAL
CONTRACTOR, UNLESS NOTED OTHERWISE.
6. EXISTING POWER/DATA OUTLETS IN EXISTING WALLS TO REMAIN AS-
IS, UNLESS NOTED OTHERWISE.
7. MATCH EXISTING CONDITIONS AND FINISHES AT ALL LOCATIONS
UNLESS NOTED OTHERWISE.
A6.004
A6.00
1' - 4"
1' - 4"
02-01
02-01
02-03
02-03
02-04
A6.003 C
LR
A L
IG
N
12' - 3 3/8"
A L
IG
N
2' - 0" 5' - 0" 3' - 0"
PERMITS LOBBY
CIVIL LOBBY
02-06
(N)
(N)
(N)
+18"
(N)
(N)
02-02
02-02
02-03
6 1/2" 3"
6 1/2"
E'
24.8
E'.5
01-01
2' - 0" 5' - 0" 3' - 0"
01-02
01-05
01-06
D'
E'
24.8
E'.5
01-07 01-03
01-04
E'
24.8
E'.5
8' - 2"
04-03
04-02
E'
24.8
E'.5
Image of Stamp
PROJECT NUMBER
© ANKROM MOISAN ARCHITECTS, INC.
38 NORTHWEST DAVIS STREET, SUITE 300
PORTLAND, OR 97209
503.245.7100
1505 5TH AVENUE, SUITE 300
SEATTLE, WA 98101
206.576.1600
115 SANSOME STREET, SUITE 1005
SAN FRANCISCO, CA 94104
415.252.7063
DATE
SHEET NUMBERSHEET NUMBER
A u to d e s k D o cs
/A
M
S e ct o r S a n d b o x
O
/2
-2
-W a
C o
T ra n W in d o w
.r v t
/2
/2
:0
:1
A
M
250810
PERMIT SET
W A
C O
T R
A N
S A
C T
IO
N
W
IN
D O
W
W A
S H
IN
G
T O
N C
O U
N T
Y
S
W A
D A
M S
H
IL
L S
B O
R O
O
R
6.15.26
FLOOR PLAN, RCP, &
ELEVATIONS
A2.00
KEYNOTE LEGEND
01-01 DEMOLISH EXISTING COUNTER TOP AND PREPARE FOR NEW. PROTECT
EXISTING DESK STRUCTURE.
01-02 DEMOLISH PORTION OF WALL. PATCH AND REPAIR ADJACENT WALLS AS
REQUIRED.
01-03 DEMOLISH PORTION OF EXISTING CEILING GRID AND TILE. PREPARE FOR
NEW GYP. BD. SOFFIT.
01-04 EXISTING GYP BD SOFFIT TO REMAIN
01-05 DEMOLISH ELECTRICAL AND DATA OUTLET. PATCH AND REPAIR WALL TO
MATCH EXISTING ADJACENT FINISH.
01-06 DEMOLISH OPENING IN WALL FOR NEW DOOR. SEE PLAN.
01-07 DEMOLISH COUNTERTOP AND CASEWORK. PATCH CARPET AND WALLS.
02-01 NEW QUARTZ COMPOSITE TRANSACTION COUNTER TOP.
02-02 NEW TRANSACTION GLASS WITH COMMUNICATION OPENING AND PASS
THRU. GLASS SPEC: CLEAR ANODIZED ALUMINUM GLAZING CHANNEL WITH
3/4” CLEAR LAMINATED SAFETY GLASS, POLISHED EDGES.
02-03 ALTERNATE: PROVIDE ALTERNATE PRICING FOR BALLISTIC RATED GLASS.
CONFIRM RATING WITH CLIENT.
02-04 NEW CARD READER TO TIE IN/MATCH EXISTING BUILDING SYSTEM.
02-06 NEW DOOR, FRAME AND HARDWARE TO MATCH EXISTING IN CORRIDOR.
NEW ELECTRONIC ENTRY HARDWARE. COORDINATE WITH BUILDING
MANAGER FOR REQUIREMENTS.
04-02 NEW EXHAUST GRILLE TO PLENUM
04-03 NEW SUPPLY GRILLE
PROJECT1/4" = 1'-0"3 LEVEL 2 - FLOOR PLAN
1/4" = 1'-0"1 LEVEL 2 - DEMOLITION PLAN
PROJECT 1/4" = 1'-0"2 LEVEL 2 - DEMOLITION RCP
1/4" = 1'-0"4 LEVEL 2 - REFLECTED CEILING PLAN
PROJECT
PROJECT
KEY PLAN - LEVEL 2
REVISION DATE REASON FOR ISSUE
2 06.24.26 ASI 01
ASI 01
ASI 01
M A
T C
H (E
) A D
JA
C
E N
T D
O O
R
(E) SOFFIT TO REMAIN
LAMINATED GLASS
TRANSACTION WINDOW
GLAZING CHANNEL TOP AND
BOTTOM, TYP.
COUNTER TOP
RUBBER BASE TO MATCH
EXISTING
A7.00
2' - 6"
EQ EQ
2' - 5" 2' - 2" 2' - 5"
A7.00
A7.00
EQ EQ
SOFFIT
GLASS TRANSACTION
WINDOW
GLAZING CHANNEL TOP
AND BOTTOM, TYP.
COUNTER TOP
RUBBER BASE TO
MATCH EXISTING
A7.00
A7.00
2' - 6"
P E
R R
C P
3' - 11" 2' - 2" 3' - 11"
3/8" = 1'-0"4 RECEPTION - WEST
3/8" = 1'-0"5 RECEPTION - NORTH
Image of Stamp
PROJECT NUMBER
© ANKROM MOISAN ARCHITECTS, INC.
38 NORTHWEST DAVIS STREET, SUITE 300
PORTLAND, OR 97209
503.245.7100
1505 5TH AVENUE, SUITE 300
SEATTLE, WA 98101
206.576.1600
115 SANSOME STREET, SUITE 1005
SAN FRANCISCO, CA 94104
415.252.7063
DATE
SHEET NUMBERSHEET NUMBER
A u to d e s k D o cs
/A
M
S e ct o r S a n d b o x
O
/2
-2
-W a
C o
T ra n W in d o w
.r v t
/1
/2
:1
:4
A
M
250810
PERMIT SET
W A
C O
T R
A N
S A
C T
IO
N
W
IN
D O
W
W A
S H
IN
G
T O
N C
O U
N T
Y
S
W A
D A
M S
H
IL
L S
B O
R O
O
R
6.15.26
INTERIOR
ELEVATIONS
A6.00
3/8" = 1'-0"3 NEW TRANSACTION WINDOW
SEE RCP FOR DIMENSIONS
SEE RCP
SEE RCP
SE
E
A
SS
E M
B
LI
E S
SE
E
A
SS
E M
B
LI
E S
SEE ASSEMBLIES
GYPSUM WALLBOARD - C
GYPSUM WALLBOARD - C
- BRACING AS REQUIRED
SEE REFLECTED CEILING PLAN
FOR FINISH
FLOOR STRUCTURE ABOVE
BACKING AS REQUIRED
3/4" LAMINATED GLASS
V.I.F.
GLAZING CHANNEL
3" x 3 1/2" x 3'-6" STEEL C SHAPE
- 4'-0" ON CENTER AND AT ENDS
OF WALL
- PRE-DRILL HOLES IN WEB @ 6"
ON CENTER FOR #10 SCREW
- MINIMUM 2" EMBED
1/4" x 3" x 8" STEEL BASE PLATE.
SEE PLAN DETAIL.
- LAP 1 ADDITIONAL METAL STUD
ONTO EACH SIDE OF CHANNEL
SECTION
PLAN
ANCHOR
CL
EQ EQ
METAL STUD TRACK
METAL STUD
STEEL C SHAPE
BOD: WEDGE ANCHOR - HILTI - KWIK BOLT TZ-CS 3/8
3/16"
3/16"
3 SIDES
CL
EQ EQ
C L
/2
C L
/2
C L
C L C L
/2
/2
C L
/2
ANCHOR BOLT
STEEL PLATE
3"
1' - 4"
2" TYP
QUARTZ COMPOSITE
TRANSACTION COUNTER
3/4" LAMINATED GLASS
CONTINUOUS 1/2" UL LISTED
BULLET RESISTANT FIBERGLASS
COMPOSITE PANEL FOR THREAT
LEVEL 3
BATTEN STRIP CUT FROM
COMPOSITE FULL SHEET
OFFICE SIDE
LOBBY SIDE
5/8" GYP BOARD,
BOTH SIDES
WALL BASE AS
SCHEDULED
CUT AND FINISH GWB AROUND BRACKET
STEEL PLATE COUNTER SUPPORT
WELDED TO CHANNEL
1' - 0"
6 1/2" 3" 6 1/2"
GLAZING CHANNEL
SUSPENDED ACOUSTICAL CEILING SYSTEM
UNDERSIDE OF STRUCTURE
3625S125-18 BRACE, 4 FEET OC
ALTERNATE DIRECTIONS PER LATERAL
BRACING DETAIL.
NEOPRENE FOAM TAPE, CONTINUOUS
GYP BD CASING BEAD
TRIM FLANGE, BEND WEB AND FASTED
TO WALL TOP TRACK AT 2 FEET OC THRU
NEOPRENE FOAM TAPE W/ (2) #6 S.M.S.
GYPSUM BOARD, ONE LAYER EACH SIDE
METAL STUDS, SEE MTL. STUD SCHEDULE
FOR GAGE, SPACING, AND HEIGHT.
0.157 HILTI XU W/ 1-1/4" EMBED. AT 4 FEET OC
MAX INTO DECK.
SOUND BATT INSULATION EXTENDING
4'-0" OF EACH SIDE OF WALL
SOUND BATT INSULATION, WHERE NOTED
ACOUSTICAL SEALANT AT FLOOR SLAB
STC RATING 45-49
WITH INSULATION
TRIM FLANGE, BEND WEB AND
FASTEN TO LOW FLUTE WITH
1/4" DIA. (1.625" EMBED) HILTI
KH-EZ
WALL BRACE ABOVE CEILING.
ALTERNATE DIRECTION TO
STRUCTURE.
PER ASCE 7-10 SECTION 13.5.8.1
PARTITIONS
LATERAL WALL BRACING IN LIEU
OF BRACING ABOVE CEILING.
PROVIDE ADJACENT WALL
FRAMING FOR LATERAL SUPPORT
OF WALL.
REFER TO CURRENT STEEL STUD MANUFACTURERS' ASSOCIATION (SSMA) TABLES FOR NON-STRUCTURAL
COMPOSITE AND NON-COMPOSITE BRACED AT 48" O.C. SECTIONS IN INTERIOR APPLICATIONS (5 PSF) WITH
DEFLECTION LIMIT OF L/240 FOR GYPSUM APPLICATIONS. L-40 TO BE UTILIZED WHEN RIGID MATERIALS
SUCH AS PLASTER OR TILES ARE APPLIED.
1. VALUES FOR COMPOSITE SECTION REQUIRES MINIMUM 1/2 INCH THICK GYPSUM BOARD ON BOTH
SIDES WITH #6 TYPE S DRYWALL SCREWS SPACED AT 12" O.C. MAX FOR STUDS AT 24" SPACING AND 16"
O.C. MAX FOR STUDS AT 16" SPACING.
2. HEIGHT LIMITS ARE LESS WHERE GYPSUM BOARD IS ON ONE SIDE. PROVIDE BLOCKING OR STRAPPING
ON OPPOSITE SIDE AND USE NON-COMPOSITE BRACED AT 48" O.C. SECTION VALUES.
CEILING WIRE ATTACHMENT
CONSTRUCTION TYPE FASTENER
WOOD 1/4" x 3" SCREW EYES
STEEL DECK PRE-DROP WIRES, CMI DC 1 OR DC 2-1/4" METAL DECK SCREW EYES.
POST TENSION CONCRETE PRE-DROP WIRES, EMBEDS, 1/4" x 3/4" METAL HIT ANCHORS.
POURED IN PLACE CONCRETE PRE-DROP WIRES, EMBEDS, 1/4" x 3/4" METAL HIT ANCHORS.
NOTE:
THIS TABLE IS PROVIDED TO GIVE GUIDANCE FOR ALTERNATIVES: FOR OTHER STATES VERIFY WITH
AUTHORITY HAVING JURISDICTION
NTS7 ASSEMBLY FRAMING SCHEDULE
Image of Stamp
PROJECT NUMBER
© ANKROM MOISAN ARCHITECTS, INC.
38 NORTHWEST DAVIS STREET, SUITE 300
PORTLAND, OR 97209
503.245.7100
1505 5TH AVENUE, SUITE 300
SEATTLE, WA 98101
206.576.1600
115 SANSOME STREET, SUITE 1005
SAN FRANCISCO, CA 94104
415.252.7063
DATE
SHEET NUMBERSHEET NUMBER
A u to d e s k D o cs
/A
M
S e ct o r S a n d b o x
O
/2
-2
-W a
C o
T ra n W in d o w
.r v t
/1
/2
:1
:4
A
M
250810
PERMIT SET
W A
C O
T R
A N
S A
C T
IO
N
W
IN
D O
W
W A
S H
IN
G
T O
N C
O U
N T
Y
S
W A
D A
M S
H
IL
L S
B O
R O
O
R
6.15.26
INTERIOR DETAILS
A7.00
1 1/2" = 1'-0"2 GYPSUM CEILING - SOFFIT
3" = 1'-0"10 METAL WALL @ PARTIAL HEIGHT
REVISION DATE REASON FOR ISSUE
1 1/2" = 1'-0"1 TI - WALL - TYPE A / B - TO GRID
1 1/2" = 1'-0"6 LATERAL BRACING @WALL
EXIT
PLAN
ELEVATION
ADJACENT FLUSH PANELBOARDS
SHALL HAVE MATCHING HEIGHT
DIMENSIONS.
RELAYS OR
CONTACTORS
MOUNTED IN SKIRTS
W/LOCKING DOORS.
CENTERLINE OF BOXES @
SAME HEIGHTS SHALL ALIGN
HORIZONTALLY. (TYP).
AAAA
T4
AH
AT2T1
AH A
SURFACE MOUNTED
PANELBOARD
W/SKIRT TO FLOOR.
CENTERLINE OF BOXES @
DIFFERENT HEIGHTS
SHALL ALIGN
VERTICALLY. (TYP).
T4
A A
T4T1 W ab H
T4
T1 T2
T1
T1 W ababcd
NOTES:
1. THIS IS A TYPICAL DETAIL. AND DEVICES SHOWN
HERE MAY NOT BE INCLUDED IN THE PROJECT.
2. A = 4" TO CENTERLINE OF RECEPTACLE, ABOVE
COUNTER OR BACKSPLASH.
FLOORH
(7
(1
(8
(1
(4
(7
(1
.(1
(4
(V A
R
IE
S
(V A
R
IE
S
(1
(4
(V A
R
IE
S
(V A
R
IE
S
EXIT
abcd T1 W
W W
P
W
CENTER IN BASE.
CENTER BETWEEN TOP OF DOOR FRAME
AND CEILING (9'-0" OR LESS) OR 6" ABOVE
FRAME FOR CEILING HIGHER THAN 9'-0".
(4
F FFF
BASIC MATERIALS AND METHODS
PART 1 -- GENERAL
1.01 REFERENCES
A. UNDERWRITERS LABORATORIES INC.:
UL 6 RIGID STEEL CONDUIT.
UL 797 ELECTRICAL METALLIC TUBING.
B. AMERICAN NATIONAL STANDARDS INSTITUTE:
ANSI/NEMA FB 1 FITTINGS AND SUPPORTS FOR CONDUIT AND CABLE ASSEMBLIES.
ANSI/NEMA OS 1 SHEET-STEEL OUTLET BOXES, DEVICE BOXES, COVERS AND BOX
SUPPORTS.
ANSI C80.1 RIGID STEEL CONDUIT.
ANSI C80.3 ELECTRICAL METALLIC TUBING.
C. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION:
NEMA WC 5 THERMOPLASTIC INSULATED WIRE AND CABLE FOR THE
TRANSMISSION AND DISTRIBUTION OF ELECTRICAL ENERGY.
1.02 SUPPORT SYSTEMS
A. SUPPORT SYSTEMS SHALL BE ADEQUATE FOR WEIGHT OF EQUIPMENT AND CONDUIT,
INCLUDING WIRING, WHICH THEY CARRY.
PART 2 -- PRODUCTS
2.01 RIGID METAL CONDUIT AND FITTINGS
A. GALVANIZED RIGID STEEL CONDUIT: UL 6 AND ANSI C80.1; THICK WALL STEEL, HOT-DIP
GALVANIZED, THREADED.
B. FITTINGS AND CONDUIT BODIES: ANSI/NEMA FB 1; THREADED TYPE, MATERIAL TO MATCH
CONDUIT.
C. INTERMEDIATE METAL CONDUIT (IMC): UL 1242 AND ANSI C80; STEEL, HOT DIPPED
GALVANIZED, THREADED.
2.02 ELECTRICAL METALLIC TUBING (EMT) AND FITTINGS
A. EMT: UL 797 AND ANSI C80.3; STEEL TUBING, HOT-DIP GALVANIZED.
B. FITTINGS: ANSI/NEMA FB 1; STEEL, RAINTIGHT, INSULATED THROAT, COMPRESSION TYPE.
2.03 FLEXIBLE METAL CONDUIT AND FITTINGS
A. FLEXIBLE METAL CONDUIT: FS WW-C-566; GALVANIZED STEEL.
B. LIQUIDTIGHT CONDUIT: FLEXIBLE METAL CONDUIT WITH COPPER BONDING TAPE AND
WEATHERPROOF JACKET.
C. FITTINGS: ANSI/NEMA FB 1; STEEL, INSULATED THROAT.
2.04 CONDUIT SUPPORTS
A. CONDUIT CLAMPS, STRAPS, AND SUPPORTS: STEEL OR MALLEABLE IRON.
2.05 SUPPORTING DEVICES
A. SUPPORT CHANNEL: ELECTRO-GALVANIZED, 12 GAUGE, 1-5/8" X 1-5/8" MINIMUM SIZE.
B. HARDWARE: CORROSION RESISTANT.
2.06 BUILDING WIRE
A. THERMOPLASTIC-INSULATED BUILDING WIRE: NEMA WC 5.
1. INTERIOR FEEDERS, BRANCH CIRCUITS #8 AND LARGER, AND CONTROL WIRING:
COPPER, STRANDED CONDUCTOR, 600 VOLT INSULATION, 90 DEGREE TYPE THHN/THWN.
SOLID CONDUCTOR IS UNACCEPTABLE.
2. BRANCH CIRCUITS#10 AND #12 WIRING: COPPER, SOLID CONDUCTOR, 600 VOLT
INSULATION, 90 DEGREE TYPE THHN/THWN OR EQUIVALENT MC CABLE.
3. CONTROL PANEL WIRING: COPPER, STRANDED CONDUCTOR, 600 VOLT INSULATION,
EXTRA FLEXIBLE TYPE MTW.
2.07 IDENTIFICATION
A. TAPE LABELS: EMBOSSED ADHESIVE TAPE, 3/8 INCH, WHITE LETTERS ON BLACK
BACKGROUND.
B. WIRE AND CABLE MARKERS: CLOTH MARKERS, SPLIT SLEEVE OR TUBING TYPE.
2.08 GENERAL-GRADE DUPLEX STRAIGHT-BLADE RECEPTACLES
A. DUPLEX STRAIGHT-BLADE RECEPTACLES.
1. LISTING CRITERIA: INVESTIGATED, LABELED, AND MARKED BY QUALIFIED ELECTRICAL
TESTING LABORATORY IN ACCORDANCE WITH GUIDE INFORMATION AND STANDARDS
SPECIFIED FOR THE FOLLOWING UL PRODUCT CATEGORIES:
A. RECEPTACLES FOR PLUGS AND ATTACHMENT PLUGS: UL CCN RTRT AND UL 498.
2. STANDARD FEATURES:
A. DEVICE COLOR: WHITE
B. CONFIGURATION
GENERAL-DUTY, NEMA 5-20R
3. OTHER AVAILABLE FEATURES REQUIRED BY THE PROJECT:
A. HAS FACTORY-TERMINATED CONNECTORS ON WIRING DEVICE PIGTAILS FOR QUICK
INSTALLATION.
4. ACCESSORIES:
A. COVER PLATE: 0.060 INCH THICK, HIGH-IMPACT THERMOPLASTIC (NYLON) WITH
SMOOTH FINISH AND COLOR MATCHING WIRING DEVICE, FROM SAME
MANUFACTURER AS WIRING DEVICE.
B. SECURING SCREWS FOR COVER PLATE: METAL WITH HEAD COLOR MATCHING
WALLPLATE FINISH.
PART 3 -- EXECUTION
3.01 CONDUIT INSTALLATION
A. CUT CONDUIT SQUARE USING A SAW OR PIPE CUTTER; DE_BURR CUT ENDS.
B. BRING CONDUIT TO THE SHOULDER OF FITTINGS AND COUPLINGS AND FASTEN SECURELY.
C. USE CONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS, ON
APPROVAL OF ENGINEER ONLY.
D. WHERE CONDUITS ENTER/EXIT FLOOR, PROVIDE THREADED COUPLING WITH UPPER END
FLUSH WITH FINISHED FLOOR. INSTALL THREADED PLUGS IN UNUSED CONDUITS.
E. USE HYDRAULIC ONE_SHOT CONDUIT BENDER OR FACTORY ELBOWS FOR BENDS IN
CONDUIT LARGER THAN 1-1/4 INCH SIZE.
F. USE SUITABLE CONDUIT CAPS TO PROTECT INSTALLED CONDUIT AGAINST ENTRANCE OF
DIRT AND MOISTURE.
G. PROVIDE SUITABLE PULL STRING IN ALL SPARE AND DATA/COMMUNICATION CONDUITS
INSTALLED OR ACCESSED IN THIS CONTRACT, EXCEPT SLEEVES AND NIPPLES.
H. SEAL BETWEEN RACEWAY AND BUILDING WHERE RACEWAY PASSES THROUGH EXTERIOR
WALL OR RATED FIREWALL PER THE FOLLOWING:
1. CONCRETE CONSTRUCTION: CAST CONDUIT IN WALL OR CORE DRILL WALL AND HARD
PACK WITH EQUAL PARTS OF SAND AND CONCRETE OR AN EQUIVALENT
METHOD AS APPROVED BY OWNER.
3.03 COORDINATION OF BOX LOCATIONS
A. PROVIDE ELECTRICAL BOXES AS SHOWN ON THE DRAWINGS, AND AS REQUIRED FOR
SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND CODE
COMPLIANCE.
B. SUPPORT BOXES INDEPENDENT OF CONDUIT.
C. ELECTRICAL BOX LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE UNLESS
DIMENSIONED. VERIFY LOCATION OF OUTLETS IN OFFICES AND WORK AREAS PRIOR TO
ROUGH-IN.
D. LOCATE AND INSTALL BOXES TO ALLOW ACCESS. WHERE INSTALLATION IS
INACCESSIBLE, COORDINATE LOCATIONS AND SIZES OF REQUIRED ACCESS DOORS.
E. LOCATE AND INSTALL TO MAINTAIN HEADROOM AND TO PRESENT A NEAT APPEARANCE.
ELECTRICAL SPECIFICATIONS
3.04 SUPPORTING DEVICES
A. FASTEN HANGER RODS, CONDUIT CLAMPS, AND OUTLET AND JUNCTION BOXES TO
BUILDING STRUCTURE.
B. DO NOT FASTEN SUPPORTS TO PIPING, DUCTWORK, MECHANICAL EQUIPMENT, OR
CONDUIT.
C. DO NOT USE POWDER-ACTUATED ANCHORS.
3.05 GENERAL WIRING METHODS
A. USE NO WIRE SMALLER THAN 12 AWG FOR POWER AND LIGHTING CIRCUITS, AND NO
SMALLER THAN 14 AWG FOR CONTROL WIRING, UNLESS OTHERWISE NOTED ON THE
DRAWINGS.
B. SIZE CONDUCTORS AS SHOWN ON THE DRAWINGS. NO SIZE DEVIATION SHALL BE
PERMITTED. UNLESS NOTED OTHERWISE ON DRAWING.
C. SPLICE ONLY IN JUNCTION OR OUTLET BOXES. NO SPLICING SHALL BE PERMITTED IN
PANELBOARD ENCLOSURES.
D. FEEDERS SHALL NOT BE SPLICED WITHOUT SPECIFIC APPROVAL FROM OWNER.
E. NEATLY TRAIN AND LACE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS.
3.06 WIRING INSTALLATION IN RACEWAYS
A. PULL ALL CONDUCTORS INTO A RACEWAY AT THE SAME TIME. USE UL LISTED WIRE
PULLING LUBRICANT FOR PULLING 4 AWG AND LARGER WIRES.
B. INSTALL WIRE IN RACEWAY AFTER ALL MECHANICAL WORK LIKELY TO DAMAGE
CONDUCTORS HAS BEEN COMPLETED.
3.07 WIRING CONNECTIONS AND TERMINATIONS
A. SPLICE ONLY IN ACCESSIBLE JUNCTION BOXES.
B. USE UL LISTED COMPRESSION TYPE CONNECTORS WITH INSULATING COVERS FOR
COPPER WIRE SPLICES AND TAPS. FOR 8 AWG AND SMALLER, USE INSULATED SPRING
CONNECTORS WITH PLASTIC CAPS; 3M SCOTCHLOK OR EQUAL.
C. THOROUGHLY CLEAN WIRES BEFORE INSTALLING LUGS AND CONNECTORS.
D. MAKE SPLICES, TAPS, AND TERMINATIONS TO CARRY FULL AMPACITY OF CONDUCTORS
WITHOUT PERCEPTIBLE TEMPERATURE RISE.
E. TERMINATE DEAD-ENDED CONDUCTORS WITH ELECTRICAL TAPE AND MAKE SAFE.
3.08 FIELD QUALITY CONTROL
A. INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE AND PROPER CONNECTION.
B. TORQUE TEST CONDUCTOR CONNECTIONS AND TERMINATIONS TO MANUFACTURER'S
RECOMMENDED VALUES.
3.09 COLOR CODING
A. WIRING SHALL CONFORM TO THE FOLLOWING COLOR CODE. SIZES #8 AWG AND SMALLER
SHALL BE COLORED, #6 AWG AND LARGER MAY BE COLORED WITH PLASTIC TAPE OF THE
APPROPRIATE COLOR.
DESCRIPTION 208Y/120V CONTROL
PHASE A (LEFT) BLACK -
PHASE B (CENTER) RED -
PHASE C (RIGHT) BLUE -
NEUTRAL WHITE WHITE
GROUND GREEN GREEN
120 VAC CONTROL - RED
120 VAC CONTROL NEUTRAL - WHITE
DC CONTROL (+) - BLUE
DC CONTROL (-) - BLUE/WHITE
EXTERNAL SOURCE - YELLOW
3.10 IDENTIFICATION
A. DEGREASE AND CLEAN SURFACES TO RECEIVE NAMEPLATES AND TAPE LABELS.
B. INSTALL NAMEPLATES ON ALL EQUIPMENT DISCONNECTS, CONTROL PANELS, ETC.,
INSTALLED. INSTALL PARALLEL TO EQUIPMENT LINES.
C. SECURE NAMEPLATES TO EQUIPMENT USING SCREWS.
D. INSTALL LABELS (EMBOSSED TAPE) ON ALL OTHER BOXES AND DEVICES, INCLUDING BUT
NOT LIMITED TO SWITCHES, RECEPTACLES.
E. NAMEPLATES AND LABELS SHALL INDICATE PANEL AND CIRCUIT NUMBER EQUIPMENT IS
SERVED FROM. ("PNLA:2" FOR CIRCUIT 2 FROM PANEL A).
F. PROVIDE WIRE MARKERS ON EACH CONDUCTOR IN PANELBOARD GUTTERS, PULL BOXES,
OUTLET AND JUNCTION BOXES, AND AT ALL LOAD CONNECTIONS. IDENTIFY WITH BRANCH
CIRCUIT OR FEEDER NUMBER AS INDICATED ON DRAWINGS. FOR CONTROL WIRING,
IDENTIFY WITH WIRE NUMBER INDICATED ON THE SCHEMATIC OR INTERCONNECTION
DIAGRAMS. PROVIDE MEGGER RESULTS. USE ATTACHED FORM A (16050), LOW VOLTAGE
(600V AND LESS) INSULATION MEGGER TEST REPORT.
3.11 COMMUNICATION CABLE
A. CAT5e - SUPERIOR ESSEX 24 GAUGE, FOUR TWISTED PAIR SOLID COPPER, DATA GRADE FOR 100Mbps LAN SYSTEM. CABLE SHALL BE PLENUM RATED.
3.12 CABLE SUPPORTS AND WRAPS
A. CABLE J-HOOK:
1. APPROVED MANUFACTURES AND CADDY, B-LINE, OR APPROVED EQUIVALENT.
2. BRIDAL RINGS ARE NOT APPROVED FOR USE.
3. J HOOK WIDTH SHALL BE MINIMUM 3/4". PROVIDE SIZE APPROPRIATE FOR CONDUCTOR
QUANTITY. MULTI-TIER J-HOOKS SHALL BE PROVIDED TO SEPARATE DIFFERENT LOW
VOLTAGE SYSTEMS WHERE A COMMON ROUTE OR PATHWAY IS USED.
B. TIE WRAP
1. APPROVED MANUFACTURES ARE LEVITON OR APPROVED EQUIVALENT.
2. TIE WRAPS SHALL BE RECLOSEABLE LOOP WRAP STYLE. AVAILABLE IN 1/2" WIDE, 15'-75'
BULK ROLLS OF HOOK AND LOOP WRAP.
3. PLASTIC FASTENERS ARE NOT APPROVED.
3.13 VOICE/DATA CONNECTORS
A. LEVITON , RJ-45 CONFIGURATION MULTI-MEDIA JACK, CAT 6 E1A/TIA 569B COMPLIANT
FLUSH MOUNT. LEVITON #5G110-R15
B. ALL PLATE SHALL BE SINGLE GANG, 6-PORT IVORY AS STANDARD, WITH DESIGNATION
WINDOW, LEVITON #42080-4IS.
3:15 TERMINATIONS
A. ALL TERMINATIONS MUST BE MADE BY CERTIFIED PERSONNEL IN STRICT ACCORDANCE
WITH THE CONNECTOR MANUFACTURERS INSTALLATION PROCEDURE. AS A CONDITION OF
THE CONTRACT AWARD, THE CONTRACTOR MUST PROVIDE EVIDENCE THAT THE
PERSONNEL PERFORMING THE TERMINATIONS ARE CERTIFIED BY THE CONNECTOR
MANUFACTURER.
B. ALL TERMINATIONS MUST BE MADE BY CERTIFIED PERSONNEL IN STRICT ACCORDANCE
WITH THE CONNECTOR MANUFACTURERS INSTALLATION PROCEDURE. AS A CONDITION OF
THE CONTRACT AWARD, THE CONTRACTOR MUST PROVIDE EVIDENCE THAT THE
PERSONNEL PERFORMING THE TERMINATIONS ARE CERTIFIED BY THE CONNECTOR
MANUFACTURER.
C. ALL CABLES MUST BE TERMINATED USING A COMPRESSION CONNECTION TOOL ALL CABLES
SHALL BE INSTALLED USING EIA/TIA 568, 569, 570, BICSI AN STANDARDS AS FOLLOWS: WIRE
PAIR TWISTS MUST BE MAINTAINED TO 1/2" OF IDC CONTACTS ON EACH JACK, JACKETING
MUST BE UNDAMAGED FOR THE FULL LENGTH OF THE CABLE RUN AND MUST CONTINUE TO
WITHIN TWO INCHES OF THE IDC CONTACT ON EACH JACK, EACH END OF EACH CABLE MUST
BE SECURED TO THE JACK MODULE WITH A CABLE TIE. ANY CABLES DAMAGED DURING
PULLING SHALL BE THE RESPONSIBILITY OF THE PULLING PARTY/PARTIES (ELECTRICAL
CONTRACTOR OR LAN INSTALLER). ANY FAILING TESTS SHALL BE RE-TERMINATED, RE-
ROUTED, RE-TESTED, ETC., UNTIL NO OTHER ALTERNATIVES EXISTING, AT WHICH TIME IT
WILL BE ASSUMED THAT A BAD CABLE RUN (TOO MUCH TWISTING OF THE CABLE,
COMPRESSION OF JACKETING AND WIRE PAIRS, ETC) HAS RESULTED (AT THE DISCRETION
OF THE LAN TESTER) AN THE PULLING PARTY/PARTIES WITH HAVE TO BEAR THE
RESPONSIBILITY OF RE-PULLING NEW CABLE TO REPLACE IT.
END OF SECTION
ELECTRICAL SPECIFICATIONS
www.coffman.com
1050 SW 6th Avenue
Suite 1630
Portland, OR 97204 ph 503.552.3800
PROJECT NUMBER
© ANKROM MOISAN ARCHITECTS, INC.
38 NORTHWEST DAVIS STREET, SUITE 300
PORTLAND, OR 97209
503.245.7100
1505 5TH AVENUE, SUITE 300
SEATTLE, WA 98101
206.576.1600
115 SANSOME STREET, SUITE 1005
SAN FRANCISCO, CA 94104
415.252.7063
DATE
SHEET NUMBERSHEET NUMBER
C U s e rs
\a d d is o n
.s c o tt
\D o c u m e n ts \2
-2
-W a C o T ra n
W in d o w -E le c a d d is o n
.s c o tt
L
Z G
W .r v t
/2
/2
:0
:5
P
M
250810
CONSTRUCTION
SET
W A
C O
T R
A N
S A
C T
IO
N
W
IN
D O
W
W A
S H
IN
G
T O
N C
O U
N T
Y
S
W A
D A
M S
H
IL
L S
B O
R O
O
R
06.25.26
ABBREVIATIONS,
SYMBOLS, SPECS &
SHEET INDEX
E-001
SHEET INDEX
SHEET NUMBER SHEET INDEX
E-001 ABBREVIATIONS, SYMBOLS, SPECS & SHEET INDEX
E-121 LEVEL 2 - POWER FLOOR PLANS
A
AC
AFF
AHJ
AHU
AL
ARCH
BFP
BKBD
CAB
CATV
CB
CGB
CCTV
CKT
CONC
COND
C
CO
CONN
CONTR
COORD
CU
CUH
CNTRL
D
DDC
DEMARC
DISC
ELEC
EWC
EF
EXP
EXT
FA
FC
FLR
F/SD
FUOC
FUT
GND
GFI
HOA
HP
HWH
IDF
IG
JB
KW
KVA
LT(S)
MDF
MDS
MRF
MC
MOA
MS
MSGB
MTGB
MT(D)
MTR
NEC
NL
NIC
NTS
NO
NC
OC
OFCI
OFOI
OH
OS&Y
PDU
PB
PIV
PRI
PVC
PC
SPEC
SQ
SS
STD
SO
SU
SURF
SW
SWBD
TEL
TGB
TS
UBC
UG
UH
V
WG
WP
W
XFMR
ABBREVIATIONS
AMPERE
AIR CONDITIONING UNIT
ABOVE FINISH FLOOR
AUTHORITY HAVING JURISDICTION
AIR HANDLING UNIT
ALUMINUM
ARCHITECT(URAL)
BACKFLOW PREVENTOR
BACKBOARD
CABINET
CABLE TELEVISION
CIRCUIT BREAKER
COMMUNICATIONS GROUND BUSBAR
CLOSED CIRCUIT TELEVISION
CIRCUIT
CONCRETE
CONDUCTOR
CONDUIT
CONDUIT ONLY
CONNECTION
CONTRACTOR
COORDINATE
COPPER OR CONDENSING UNIT
CABINET UNIT HEATER
CONTROLLER
DEMOLISH
DIRECT DIGITAL CONTROL SYSTEM
DEMARCATION
DISCONNECT SWITCH
ELECTRIC(AL)
ELECTRIC WATER COOLER
EXHAUST FAN
EXPLOSION PROOF
EXTERIOR
FIRE ALARM
FAN COIL
FLOOR
FIRE/SMOKE DAMPER
FURNISHED UNDER OTHER CONTRACT
FUTURE
GROUND
GROUND FAULT INTERRUPTER
HAND-OFF-AUTO
HORSEPOWER OR HEAT PUMP
HOT WATER HEATER
INTERMEDIATE DISTRIBUTION FRAME
ISOLATED GROUND
JUNCTION BOX
KILOWATT(S)
KILOVOLT-AMPERE(S)
LIGHT(S)
MAIN DISTRIBUTION FRAME
MAIN DISTRIBUTION SWITCHBOARD
MANUFACTURER
MOMENTARY CONTACT
MULTIPLE OUTLET ASSEMBLY
MANUAL STARTER
MAIN SERVICE GROUND BUSBAR
MAIN TELECOM GROUND BUSBAR
MOUNT(ED)
MOTOR
NATIONAL ELECTRIC CODE (LATEST EDITION)
NIGHT LIGHT (DUSK TO DAWN OPERATION)
NOT IN CONTRACT
NOT TO SCALE
NORMALLY OPEN
NORMALLY CLOSED
ON CENTER(S)
OWNER FURNISHED, CONTRACTOR INSTALLED
OWNER FURNISHED, OWNER INSTALLED
OVERHEAD
OS&Y VALVE
POWER DISTRIBUTION UNIT
PUSHBUTTON
POST INDICATOR VALVE
PRIMARY
POLYVINYL CHLORIDE
PHOTOCELL
SPECIFICATION(S)
SQUARE
STAINLESS STEEL
STANDARD
STUB OUT
STUB UP
SURFACE
SWITCH
SWITCHBOARD
TELEPHONE
TELECOM GROUND BUSBAR
TIME SWITCH
UNIFORM BUILDING CODE (LATEST EDITION)
UNDERGROUND
UNIT HEATER
VOLT(S)
WIRE GUARD
WEATHERPROOF
WATTS
TRANSFORMER
XXX
REFERENCE SYMBOLS
100A
X/E7.0X
XX01
KEYED NOTE IDENTIFIER, SEE KEYED NOTES
EQUIPMENT IDENTIFIER, SEE EQUIPMENT SCHEDULES
DOOR IDENTIFICATION SYMBOL
DETAIL REFERENCE
GENERAL NOTES:
1. UNLESS OTHERWISE NOTED, DEVICE MOUNTING HEIGHTS MEASURED TO CENTER OF BOX SHALL BE AS FOLLOWS: RECEPTACLES & SYSTEMS OUTLETS +18" AFF SWITCHES & CONTROL DEVICES +
46" AFF CLOCKS - SEE INTERIOR ELEVATIONS OR AS NOTED. 'A' DENOTES ABOVE COUNTER.
COORDINATE HEIGHTS WITH CASEWORK AND GENERAL CONTRACTOR.
2. ALL BRANCH CIRCUITS SHALL INCLUDE A DEDICATED NEUTRAL AND A GREEN INSULATED
EQUIPMENT GROUND CONDUCTOR, MINIMUM WIRE SIZE #12 AWG.
3. MINIMUM WIRE SIZE TO BE #12 AWG UNLESS OTHERWISE NOTED.
CONDUIT AND WIRING SYMBOLS
CIRCUIT HOMERUN
CONCEALED CONDUIT
LOW VOLTAGE CABLE
CONDUIT SLEEVE THRU WALL ABOVE CEILING, QUANTITY AND SIZE AS NOTED
CONDUIT STUBOUT OR STUBUP INTO ACCESSIBLE CEILING SPACE
CONDUIT STUBOUT WITH ENDCAP
STUB-UP LOCATION
UNDERGROUND COMMUNICATIONS CONDUIT
GENERAL ELECTRICAL SYMBOLS
MAIN SERVICE AND DISTRIBUTION EQUIPMENT
BRANCH CIRCUIT…