This is a comprehensive 100% design plan set issued by the City of Clearwater, Florida Engineering Department for the Clearwater Harbor Marina N-E Walkway and Gangway Replacement project (City Project No. 23-0030-MA, City Plan Set No. 2023016). The project scope includes replacement of seven floating docks on the main dock walkway, marginal wharf and B-Dock; three finger piers; electrical and mechanical utilities; and cable connections within the floating dock area to accommodate the removal of wave attenuators. The replacement will consist of five 13-foot-wide floating docks along the walkway, one 10-foot-wide floating dock, and three 4-foot-wide by 45-foot-long finger piers. Two new 8-foot-wide by 31-foot-long aluminum ADA-compliant gangways will be installed at the existing platform and remaining dock. New steel pipe piles (24-inch diameter, 0.75-inch thick) and pile guides will be installed to anchor the marginal wharf. The estimated quantities include 3,700 square feet of walkways, 540 square feet of finger piers, 15 steel pipe piles, and 496 square feet of gangway. The work also involves replacing water, fire, and electrical lines damaged during Hurricane Milton and required due to the removal and replacement of wave attenuators. The design was issued on April 30, 2026, with drawings sealed by Professional Engineers Nancy E. Lehr, Rodney Trammell, and Wilfredo J. Ruiz Planell.
The design plans specify compliance with the 2023 Florida Building Code, ASCE 7-22, ACI 318-19, AISC specifications, and FDOT 2025 standards. Concrete specifications require 5500 PSI 28-day strength with corrosion inhibitor admixture and calcium nitrate for chloride ion protection, reflecting the marine environment. All structural and miscellaneous steel shall be stainless steel 316L or hot-dipped galvanized per ASTM standards. Mechanical systems include HDPE DR11 piping for potable water and fire protection systems (150 and 200 PSI rated respectively), with sanitary sewer force main piping connections. Electrical work involves re-installation of existing marine substations ("NA1," "NA2," and "NB") and pedestals, replacement of service conductors, and provision of Type G/W conductors for feeder lines. The project design incorporates environmental considerations including FFWCC manatee conditions, NOAA fisheries protected species construction conditions for in-water work, and construction activities limited to daylight hours. The contractor is responsible for site verification prior to construction, utility location and coordination, erosion control, debris management, and compliance with all permit conditions and environmental regulations. The design assumes the contractor will visit the site prior to submitting a bid and will coordinate with the dock manufacturer regarding final specifications and equipment placement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
City Project No. 23-0030-MA City Plan Set No. 2023016
ISSUED: 2026-04-30
CITY OFFICIALS
Bruce Rector Mayor Ryan Cotton Councilmember Mike Mannino Councilmember David Allbritton Councilmember Lina Teixeira Councilmember Jennifer Poirrier City Manager
Tara L. Kivett, P.E.
City EnJineer
Approved For Construction
Date Approved
CITY ENGINEER Tara L. Kivett, P.E. #86611
CLEARWATER HARBOR MARINA
N-E WALKWAY AND GANGWAY
REPLACEMENT
206 PIERCE STREET CLEARWATER, FL 33755
Project Location
N
S
EW
501 E. KENNEDY BLVD, SUITE 1910
TAMPA, FL 33602
PHONE: (813) 258-8818REVISIONS
NO. DATE DESCRIPTION BY
100% DESIGN
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
MHHW +0.99
MHW +0.64
MSL
0.00
MLW -1.25
MLLW -1.75
NAVD88
-0.29
GENERAL NOTES
1. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THESE
DRAWINGS, PROJECT SPECIFICATIONS, PROJECT NOTES AND FDOT
STANDARD SPECIFICATIONS WHEN REFERENCED. FDOT STANDARD
SPECIFICATIONS ARE REFERENCED FOR MATERIAL SPECIFICATIONS AND
CONSTRUCTION METHODS UNDER DIVISION II "CONSTRUCTION DETAILS".
DIVISION I "GENERAL REQUIREMENTS AND COVENANTS" OF THE FDOT
STANDARD SPECIFICATIONS DOES NOT APPLY. THE CONTRACT WITH THE
OWNER SHALL GOVERN OVER FDOT SPECIFICATIONS. MEANS OF
MEASUREMENT AND PAYMENT SHALL BE AS STIPULATED BY THE OWNER
AND THE CONTRACT. FDOT STANDARD SPECIFICATIONS REFER TO THE
FLORIDA DEPARTMENT OF TRANSPORTATION "STANDARD SPECIFICATION
FOR ROADWAY AND BRIDGE CONSTRUCTION", 2025 EDITION AND ALL
SUPPLEMENTAL SPECIFICATIONS.
2. SITE VERIFICATION: PRIOR TO BEGINNING CONSTRUCTION THE
CONTRACTOR SHALL CHECK THE DRAWINGS AGAINST THE SITE
CONDITIONS AND NOTIFY THE ENGINEER IN WRITING OF ANY
DISCREPANCIES IN DIMENSIONS OR SITE CONDITIONS. THE CONTRACTOR
SHALL NOT BEGIN CONSTRUCTION IN ANY SUCH AFFECTED AREA UNTIL
THE DISCREPANCY HAS BEEN RESOLVED BY THE CONTRACTOR AND
APPROVED BY THE ENGINEER.
3. ALL SAFETY REGULATIONS ARE TO BE STRICTLY FOLLOWED.
4. METHODS OF CONSTRUCTION AND ERECTION OF STRUCTURAL MATERIAL
ARE THE RESPONSIBILITY OF THE CONTRACTOR.
5. THE CONTRACTOR SHALL, ON A DAILY BASIS, REMOVE FROM THE SITE
ANY EXCAVATED MATERIAL OR DEBRIS. DISPOSAL OF THE MATERIALS IS
THE RESPONSIBILITY OF THE CONTRACTOR. ALL DEBRIS SHALL BE
DISPOSED OF IN A PERMITTED SANITARY LANDFILL.
6. THE CONTRACTOR SHALL PLACE CONSTRUCTION DEBRIS CONTROL
DEVICES, BOOMS, TARPAULINS, FLOATS, STAGING, AND OTHER DEVICES
AS NECESSARY TO PREVENT CONSTRUCTION DEBRIS FROM ENTERING
THE WATER AND AIRBORNE MATERIALS FROM LEAVING THE IMMEDIATE
VICINITY OF THE SITE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
CLEAN-UP OF ANY MATERIALS DEPOSITED OUTSIDE THE WORK AREA OR
IN THE WATER. SEE PERMIT CONDITIONS.
7. THE CONTRACTOR SHALL ABIDE BY ALL APPLICABLE LOCAL
ENVIRONMENTAL PROTECTION STANDARDS, LAWS, AND REGULATIONS.
8. CONTRACTOR SHALL LOCATE ALL UTILITIES IN THE AREA OF
CONSTRUCTION PRIOR TO COMMENCING WITH CONSTRUCTION.
CONTRACTOR SHALL NOTIFY THE ENGINEER OF ALL CONFLICTS WITH
EXISTING UTILITIES PRIOR TO COMMENCING WITH WORK IN THE CONFLICT
AREA.
9. CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID FOR THE
PROJECT.
10. ANY DAMAGE TO STATE, COUNTY, OR LOCAL ROADS CAUSED BY THE
CONSTRUCTION ACTIVITIES RELATED TO THIS PROJECT SHALL BE
REPAIRED BY THE CONTRACTOR TO THE SATISFACTION OF THE OWNER
AND/OR LOCAL AUTHORITY.
11. THE CONTRACTOR IS RESPONSIBLE FOR ADHERING TO ALL PERMIT
CONDITIONS AND REPORTING REQUIREMENTS.
12. UNLESS OTHERWISE NOTED, THE CONTRACTOR SHALL RESTORE
DISTURBED AREAS TO ORIGINAL CONDITION TO MATCH ADJACENT
GRADES AND SHALL REPLACE ANY DISTURBED PAVED OR GRASSED
AREAS IN KIND.
13. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE SAFETY, SECURITY
AND PROTECTION OF PERSONNEL, EQUIPMENT, CONSTRUCTION, AND
ADJACENT FACILITIES FOR THE DURATION OF THIS CONTRACT. THE
CONTRACTOR AND HIS SUBCONTRACTORS SHALL PREPARE AND
CONFORM TO A PROJECT SPECIFIC HEALTH AND SAFETY PLAN. THE
HEALTH AND SAFETY PLAN SHALL INCLUDE APPLICABLE GUIDELINES AND
REGULATIONS SET FORTH IN CURRENT OSHA AND FLORIDA STATUTES
WITH SPECIFIC ATTENTION TO FLORIDA TRENCH SAFETY ACT AND OSHA
TRENCH EXCAVATION SAFETY STANDARDS. THE ENGINEER OF RECORD
AND OWNER WILL NOT BE RESPONSIBLE FOR JOB SITE SAFETY
PROCEDURES.
14. ALL TEMPORARY UTILITIES NECESSARY FOR CONSTRUCTION SHALL BE
PROVIDED AT THE EXPENSE OF THE CONTRACTOR.
15. THE CONTRACTOR SHALL PROVIDE EROSION CONTROL AND
SEDIMENTATION BARRIERS (HAY BALES, SILTATION CURTAINS AND
FLOATING TURBIDITY SCREENS) TO PREVENT SILTATION OF ADJACENT
PROPERTY, STREETS, STORM SEWERS, AND WATERWAYS. IF, IN THE
OPINION OF THE CITY AND/OR LOCAL AUTHORITIES, EXCESSIVE
QUANTITIES OF EARTH ARE BEING TRANSPORTED OFF-SITE EITHER BY
NATURAL DRAINAGE OR VEHICULAR TRAFFIC, THE CONTRACTOR SHALL
REMOVE AND CLEAN SAID EARTH FROM TRAVEL WAYS TO THE
SATISFACTION OF THE CITY AND/OR OTHER AUTHORITIES.
16. THE CONTRACTOR SHALL CONSIDER AND PLAN FOR, ON A DAILY BASIS,
THE EFFECT OF TIDAL FLUCTUATION AND SEA CONDITION IN THE
EXECUTION OF THE WORK.
17. IF CONSTRUCTION IS EXPECTED TO BE PERFORMED FROM A BARGE, THE
CONTRACTOR SHALL CONDUCT OPERATIONS SO AS TO NOT INTERFERE
WITH OR BE DETRIMENTAL TO VESSEL TRAFFIC DURING THE COURSE OF
THE WORK AND SHALL PLAN FOR EFFECTS OF PASSING VESSELS AND
WAVE CLIMATE.
18. SCALE BARS ARE INTENDED FOR REFERENCE ONLY. ALL DIMENSIONS
NECESSARY FOR CONSTRUCTION SHALL BE TAKEN FROM DIMENSION
ANNOTATION AND NOT SCALED DIRECTLY FROM DRAWINGS.
SURVEY DATUM
1. ELEVATIONS SHOWN HEREIN REFER TO THE NORTH AMERICAN VERTICAL
DATUM OF 1988 (NAVD88).
2. THE FOLLOWING TIDAL DATUM RELATIONSHIP IS BASE ON NOAA CO-OPS
STATION 8726706 LOCATED IN CLEARWATER HARBOR, TO THE SOUTH OF
THE PROJECT SITE.
DEMOLITION NOTES
1. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO STRICTLY
CONTAIN THE DEMOLITION WITHIN THE LIMITS OF THE REQUIRED
CONSTRUCTION AND AVOID ANY DAMAGE TO THE EXISTING STRUCTURE
TO REMAIN.
2. ANY DAMAGE INCURRED IN EXECUTION OF THIS CONTRACT TO ANY PART
OF THE PROPERTY/STRUCTURE NOT SPECIFICALLY DESIGNATED FOR
DEMOLITION SHALL BE REPAIRED, REPLACED, AND/OR RECONSTRUCTED
BY THE CONTRACTOR TO ITS ORIGINAL CONDITION AS DIRECTED BY THE
ENGINEER AT THE EXPENSE OF THE CONTRACTOR.
3. ALL DEMOLISHED MATERIAL, EXCEPT AS NOTED OTHERWISE, BECOMES
THE PROPERTY OF, AND SHALL BE COMPLETELY REMOVED AND
DISPOSED OF BY THE CONTRACTOR. THE REMOVAL, HANDLING, AND
DISPOSAL OF ALL DEMOLITION MATERIALS SHALL BE IN STRICT
ACCORDANCE WITH ALL LOCAL, STATE, AND FEDERAL REQUIREMENTS.
4. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO BECOME
FAMILIAR WITH THE MATERIALS TO BE DISPOSED OF AND ALL GOVERNING
AGENCY REQUIREMENTS.
5. THE CONTRACTOR IS RESPONSIBLE TO CONTROL FUGITIVE DUST
ORIGINATING FROM THE PROJECT SITE DURING CONSTRUCTION BY
WATERING OR OTHER METHODS AS REQUIRED.
6. ALL SURVEY MONUMENTS WITHIN LIMITS OF CONSTRUCTION SHALL BE
PROTECTED.
7. ALL CONCRETE SHALL BE ASSUMED TO BE STEEL REINFORCED, UON.
8. CONTRACTOR SHALL LOCATE ALL UTILITIES IN THE PROJECT AREA.
RELOCATION OR REMOVAL OF UTILITIES TO BE COORDINATED WITH THE
OWNER OR ENGINEER PRIOR TO PROCEEDING WITH CONSTRUCTION.
ENVIRONMENTAL NOTES
1. CONTRACTOR SHALL ADHERE TO ALL ENVIRONMENTAL PERMIT
CONDITIONS, INCLUDING ANY COLLECTION OF DATA AND REPORTING
REQUIREMENTS INCLUDED IN THE PERMITS.
2. CONTRACTOR SHALL ADHERE TO THE FFWCC STANDARD MANATEE
CONDITIONS, AND NOAA FISHERIES PROTECTED SPECIES CONSTRUCTION
CONDITIONS FOR IN-WATER WORK.
3. CONSTRUCTION ACTIVITIES SHALL BE LIMITED TO DAYLIGHT HOURS ONLY.
GEOTECHNICAL NOTES
1. THE DESIGN DRAWINGS ARE BASED ON THE GEOTECHNICAL BOREHOLE
INFORMATION PROVIDED BY DRIGGERS ENGINEERING SERVICES
INCORPORATED (DESI) DATED SEPTEMBER 02, 2021.
VERTICAL DATUM
RELATIONSHIP
DATUM ELEV (FT)
SECTION DESIGNATION
SHEET NUMBER
VIEW REFERENCED TO
DETAIL DESIGNATION
SHEET NUMBER
VIEW REFERENCED TO
DETAIL CALLOUT
SECTION CALLOUT
SECTION DESIGNATION
SHEET NUMBER
VIEW REFERENCED TO
ELEVATION VIEW
VIEW DESIGNATION
SHEET NUMBER
VIEW REFERENCED FROM
VIEW TITLE
G-001
PLAN
SCALE: 1/4"=1'-0"
G-001
G-001
G-001
LEGEND
= CONTOUR
= MHW LINEMHW
(0.00)
ABBREVIATIONS
ACI - AMERICAN CONCRETE INSTITUTE
AISC - AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
APPROX - APPROXIMATE
ASTM - AMERICAN SOCIETY FOR TESTING
MATERIALS
AWS - AMERICAN WELDING SOCIETY
CF - CUBIC FEET
CIP - CAST IN PLACE
CHK - CHECKERED
CL - CENTERLINE
CLR - CLEAR
CONC - CONCRETE
CONST - CONSTRUCTION
CONT - CONTINUOUS
CTS - CENTERS
CY - CUBIC YARDS
DET - DETAIL
DEMO - DEMOLITION
DIA, Ø - DIAMETER
DWG - DRAWING
E - EAST
EA - EACH
EF - EACH FACE
EL, ELEV - ELEVATION
EMBED - EMBEDMENT
EP - END POINT
EQ - EQUAL
EW - EACH WAY
EX, EXIST - EXISTING
EXP - EXPANSION
F - FAHRENHEIT
FDOT - FLORIDA DEPARTMENT OF
TRANSPORTATION
FFWCC - FLORIDA FISH AND WILDLIFE
CONSERVATION COMMISSION
FT - FEET
GALV - GALVANIZED
HORIZ - HORIZONTAL
IN - INCHES
INFO - INFORMATION
JT - JOINT
KIP - 1,000 LBS
KSI - 1,000 LBS PER SQUARE INCH
KT - KNOT (NAUTICAL MILE PER HOUR)
L - LENGTH
LG - LONG
∠ - ANGLE
LB, LBS - POUND, POUNDS
LF - LINEAR FEET
LG - LONG
MAX - MAXIMUM
MHW - MEAN HIGH WATER
MHHW - MEAN HIGHER HIGH WATER
MIN - MINIMUM
MISC - MISCELLANEOUS
MLW - MEAN LOW WATER
MLLW - MEAN LOWER LOW WATER
MSL - MEAN SEA LEVEL
N - NORTH
NAD - NORTH AMERICAN DATUM
NAVD88 - NORTH AMERICAN VERTICAL DATUM 1988
NGVD - NATIONAL GEODETIC VERTICAL DATUM
NO, # - NUMBER
NOAA - NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NTS - NOT TO SCALE
OC - ON CENTER
P/S - PRESTRESSED
PERF - PERFORATED
PL - PLATE
PR, PROP - PROPOSED
PSF - POUNDS PER SQUARE FOOT
PSI - POUND PER SQUARE INCH
QTY - QUANTITY
R/C - REINFORCED CONCRETE
REQ'D, REQ - REQUIRED
RT - RIGHT
S - SOUTH
SEC - SECOND
SCH - SCHEDULE
SF - SQUARE FOOT
SF - SILT FENCE
SHT - SHEET
SPA - SPACES
SPT - STANDARD PENETRATION TEST
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STL - STEEL
T - TON
TBR - TO BE REMOVED
TC - TURBIDITY CURTAIN
TOC - TOP OF CONCRETE
TYP - TYPICAL
UON - UNLESS OTHERWISE NOTED
VA - COUNTY VULNERABILITY ASSESSMENT
VERT - VERTICAL
W - WEST
W/ - WITH
W/O - WITHOUT
WMH - WATER MANHOLE
WWF - WELDED WIRE FABRIC
' - MINUTES OR FEET
" - INCHES OR SECONDS
& - AND
° - DEGREE
± - PLUS OR MINUS
Ø - DIAMETER
INDEX OF DRAWINGS, GENERAL NOTES
AND ABBREVIATIONS
G-002 2026-01-30
KT
ARS
GWS
NEL
2NANCY LEHR
INDEX OF DRAWINGS
INDEX NO. SHEET NO. SHEET TITLE
1 G-001 COVER SHEET
2 G-002 INDEX OF DRAWINGS, GENERAL NOTES AND ABBREVIATIONS
3 G-003 STRUCTURAL NOTES
4 V-101 EXISTING CONDITIONS PLAN
5 D-101 STRUCTURAL DEMOLITION PLAN
6 S-100 OVERALL SITE PLAN
7 S-101 N-E WALKWAY AND GANGWAY REPLACEMENT PLAN
8 S-501 WALKWAY DETAILS (1 OF 2)
9 S-502 WALKWAY DETAILS (2 OF 2)
10 S-510 PILE GUIDE DETAILS
11 M-001 MECHANICAL NOTES
12 MD100 MECHANICAL DEMOLITION PLAN
13 M-100 MECHANICAL OVERALL PLAN
14 M-101 MECHANICAL PLAN (1 OF 2)
15 M-102 MECHANICAL PLAN (2 OF 2)
16 M-501 MECHANICAL DETAILS
17 E-001 ELECTRICAL NOTES
18 E-002 ELECTRICAL LEGEND & ABBREVIATIONS
19 ED101 ELECTRICAL DEMOLITION PLAN
20 E-100 ELECTRICAL OVERALL PLAN
21 E-101 ELECTRICAL PLAN (1 OF 2)
22 E-102 ELECTRICAL PLAN (2 OF 2)
23 E-501 ELECTRICAL DETAILS
24 E-601 ELECTRICAL RISER DIAGRAM
This document has been electronically signed and sealed by Nancy E. Lehr, P.E. on the date adjacent to the seal.
Signature must be verified on any electronic copies.
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
DESIGN CRITERIA
1. APPLIED LOADS:
A. WIND SPEED...................................................122 MPH, 3 SEC GUST B. WAVE LOADS WERE CALCULATED FOR A 50-YEAR STILL WATER ELEVATION OF 7.2 FT (NAVD 88).
C. WAVE LOAD:
WAVE HEIGHT...........................................5.64 FT
WAVE PERIOD...........................................3.56 SEC
2. DESIGN CODES AND STANDARDS:
A. FLORIDA BUILDING CODE (2023).
B. AMERICAN SOCIETY OF CIVIL ENGINEERS - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES (ASCE 7-22).
C. AMERICAN CONCRETE INSTITUTE - BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318-19).
D. AMERICAN INSTITUTE OF STEEL CONSTRUCTION MANUAL, 16TH EDITION.
E. AMERICAN WELDING SOCIETY STRUCTURAL WELDING CODE.
F. FLORIDA DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR ROAD AND
BRIDGE CONSTRUCTION, FY 2025-26.
CONCRETE AND REINFORCING STEEL
1. ALL CONCRETE WORK SHALL BE PERFORMED IN ACCORDANCE WITH ACI 301 AND 318 UNLESS
OTHERWISE NOTED.
2. ALL CONCRETE SHALL BE NORMAL WEIGHT (145 PCF).
3. ALL DETAILING, FABRICATION, AND ERECTION OF REINFORCING STEEL SHALL CONFORM TO THE ACI MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES, ACI 315.
4. MINIMUM CONCRETE COVER FOR REINFORCING BARS SHALL BE 3" UNLESS OTHERWISE NOTED.
5. LAP SPLICES SHALL BE MINIMUM CLASS "B" LAP SPLICES IN ACCORDANCE WITH ACI 318.
6. WELDING OF REINFORCING BARS SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL WELDING
CODE - REINFORCING STEEL" (AWS D1.4).
7. REINFORCEMENT HOOKS AND BENDS SHALL BE STANDARD HOOKS CONFORMING TO THE
PROVISIONS OF THE AMERICAN CONCRETE INSTITUTE (ACI 318-19), UON.
8. MATERIALS SHALL CONFORM TO THE FOLLOWING, UNLESS OTHERWISE NOTED:
A. CONCRETE STRENGTH 28 DAY
CONCRETE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5500 PSI (MIN)
B. REINFORCEMENT STEEL . . . . . . . . . . . . . . . . . . . . . . . . . . .ASTM A615 OR ASTM A706, GRADE 60
9. ALL CEMENT SHALL CONFORM TO ASTM C150, TYPE II FOR AN EXTREMELY AGGRESSIVE
ENVIRONMENT, WITH SLAG OR FLY ASH, MAXIMUM W/C RATIO IS 0.41.
10. CONCRETE SHALL INCLUDE CORROSION INHIBITOR ADMIXTURE. PROVIDE CALCIUM NITRATE FOR
CHLORIDE ION PROTECTION.
11. CONTRACTOR SHALL REPAIR ALL SURFACE BLEMISHES IN CONCRETE WITHIN 24 HOURS AFTER
FORM REMOVAL.
12. PROVIDE 3/4" CHAMFERS ON ALL EXPOSED EDGES AND CORNERS, UON.
STRUCTURAL AND MISCELLANEOUS STEEL
1. ALL STEEL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE AISC SPECIFICATIONS FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS. ALL WELDING SHALL
CONFORM TO AWS D1.1.
2. STEEL MATERIALS SHALL CONFORM TO THE FOLLOWING, UNLESS OTHERWISE NOTED:
A. THREADED BARS. . . . . . . . . .STAINLESS STEEL 316L, ASTM F593, MIN FY = 75 KSI B. SHAPES. . . . . . . . . . . . . . . . . .STAINLESS STEEL 316L, ASTM A276, MIN FY = 45 KSI C. MISC. PLATES. . . . . . . . . . . . .STAINLESS STEEL 316L, ASTM A240/A240M, MIN FY = 25 KSI
D. STEEL PIPE PILES. . . . . . . . . .ASTM A252 OR ASTM A572, MIN FY= 50 KSI
3. ALL NON-STAINLESS STEEL SHAPES, PLATES, OTHER FABRICATIONS, AND ALL NON-STAINLESS
HARDWARE SHALL BE GALVANIZED BY THE HOT-DIPPED PROCESS IN ACCORDANCE WITH THE
REQUIREMENTS OF ASTM A123 AND/OR A153, AS APPLICABLE, AFTER FABRICATION, UNLESS
OTHERWISE NOTED.
4. FIELD TREAT DAMAGED GALVANIZED FINISH WITH TWO COATS OF HIGH ZINC DUST OXIDE PAINT, COLD GALVANIZING COMPOUNDS OR APPROVED EQUAL CONFORMING TO THE REQUIREMENTS OF
ASTM A780. IN ADDITION, ALL EXPOSED THREADED SURFACES SHALL BE PAINTED WITH TWO COATS OF HIGH ZINC DUST OXIDE PAINT AFTER INSTALLATION OF UNIT. SPRAY TYPE COLD GALVANIZING
COMPOUNDS SHALL NOT BE USED.
PILE DRIVING REQUIREMENTS
1. PILE ULTIMATE LOADS (FACTOR OF SAFETY 2.25 FOR COMPRESSION, AND 3.0 FOR TENSION AND 1.5
FOR LATERAL).
2. ALL PILES SHALL BE DRIVEN TO REQUIRED CAPACITY BASED ON DRIVING CRITERIA ESTABLISHED BY THE TEST PILE AS PER SPECIFICATIONS SECTION 31 62 16.13. BUT UNDER NO CIRCUMSTANCES SHALL THE PILE TIP ELEVATION BE HIGHER THAN THE MINIMUM EMBEDMENT DEPTH INDICATED.
CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER OF ANY PILES THAT DO NOT REACH THE
REQUIRED PILE TIP ELEVATION.
3. NO JETTING ALLOWED. SEE GEOTECHNICAL REPORT FOR DRIVING RECOMMENDATIONS.
4. PILE DRIVING TOLERANCES:
· TOP OF PILE AT CUTOFF ELEVATION SHALL BE WITHIN 3" HORIZONTALLY AND 2" VERTICALLY OF
PLAN LOCATION. MANIPULATION OF PILES TO FORCE THEM INTO POSITION WILL NOT BE
PERMITTED.
· PILES SHALL BE PLACED PLUMB OR BATTERED WITH OUT-OF ALIGNMENT NOT EXCEEDING 1/4"
PER FOOT OF LENGTH AND TRUE TO LINE.
· CHECK ALL PILE FOR HEAVE. RE-VIBRATE ALL HEAVED PILES TO THE TIP ELEVATION INDICATED.
5. MAINTAIN PILE LOGS FOR ALL PILES.
6. THE CONTRACTOR SHALL SUBMIT VIBRATORY PILE HAMMER DATA FOR REVIEW BY THE ENGINEER.
7. CONTRACTOR SHALL BE PREPARED TO VIBRATE PILING THROUGH LIMESTONE LAYERS. REFER TO
GEOTECHNICAL REPORT.
8. CONTRACTOR SHALL SUBMIT PROPOSED CONSTRUCTION SEQUENCING PLAN DETAILING
INSTALLATION TECHNIQUES, QUALITY CONTROL, EQUIPMENT AND CONSTRUCTION PHASING TO THE
ENGINEER FOR REVIEW PRIOR TO INITIATING CONSTRUCTION.
STRUCTURE TYPE LOCATION ULTIMATE LATERAL
CAPACITY
ULTIMATE TENSION
CAPACITY
ULTIMATE COMPRESSION
CAPACITY MINIMUM TIP ELEVATION
24" DIA. x 0.75" THICK
STEEL PIPE PILE FINGER PIER * N/A * *
24" DIA. x 0.75" THICK
STEEL PIPE PILE WALKWAY * N/A * *
*PILE LENGTH AND REQUIRED CAPACITY TO BE DETERMINED BY THE DOCK MANUFACTURER.
STRUCTURAL NOTES G-003
2026-01-30
KT
ARS
GWS
3NANCY LEHR
This document has been electronically signed and sealed by
MHW
MHW
(9)
(9)
(8)
(15)
(10)
(17)
(16)
(14)
(13)
(12)
(11)
(15)
(10)
(5)
(14) (13)
(12) (11)
(9)
(8)
(7)
(6)
(4)
(3)
(2)
(1)
(16)
(1 5)
(10)
(1 6)
(1 4)
(1 3)
(1 2)
(1 1)
(15)
(10)
(14)
(13) (12)
(11)
(9)
(8) (7) (6)
(15)
(14) (14)
(14)
(5)
(9)
(8) (7)
(6)
(4) (3)
(2) (1)
(5) (7)
(6)
(4) (3)
(2)
(1)
(10)
(10)
(10)
(14)
(13)
(12)
(11)
(10)
(5)
(13)
(12)
(11)
(9)
(8)
(7) (6)
(4) (3)
(2)
(1)
(14)(13)
(15)
(16)
(16)
(10)
(5)
(14)
(13)
(12)
(11)
(9)
(8)
(7)
(6)
(4)
(3)
(2)
(10)
(10)
(12)
(12)
(11)
(11)
(3)
(2)
(5)
(4)
(10) (11)
(9) (8)
(7)
MHW
MHW
MHW
MHW
MHW
MHW
MHW
MHW
MHW
MHW
MHW
N
REMOVE FLOATING
WALKWAY AND
FINGER PIERS SEE
D-101
C
LE
A R
W A
TE
R
M E
M O
R
IA
L C
A U
S E
W A
Y
CL
EA
RW
AT
ER
M
EM
ORI
AL
C
AU
SE
W
AY
WALKWAY
TO REMAIN
DAMAGED GANGWAYS
TO BE REMOVED AND
REPLACED IN KIND SEE 2
D-101
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
50' 0' 50' 100'
SCALE: 1''=50'
LEGEND:
MOORING PILES
P/S CONCRETE GUIDE PILE
MHWL
BATHYMETRY
EASEMENT
MHW
(4)
EXISTING CONDITIONS PLAN V-101
2026-01-30
KT
ARS
GWS
4NANCY LEHR
(5)
(7)
(6)
(4)
(3)
(2)
(1)
N
REMOVE
WALKWAY (TYP)
WALKWAY
TO REMAIN
REMOVE
FINGER DOCK
(TYP)
REMOVE
20" SQ GUIDE
PILE (TYP)
10'-0"
5.
PROMENADE
TO REMAIN
45'±
45'±
4' -0
4'
-0
2'-0"
GUIDE PILES
TO REMAIN
REMOVE GALVANIZED
STEEL FRAME CORNER
GUIDE PILES
TO REMAIN
FLOATING WALKWAY
TO REMAIN
49'-11 1/2"
49'-11 1/2"
'-3
4'-6"
(10)
(5)
(12)
(11)
(9)
(8)
(7)
(6)
(4)
(3)
(2)
(10)
(12)
(11)
(5)
(10)
(11)
(9)
(8)
(7)
31'-0"
8'-0"
N
REMOVE
GANGWAY (TYP)
DOCKS TO
REMAIN
DOCKS TO REMAIN
8'-0"
31'-0"
GANGWAY
PLATFORM
TO REMAIN
8'-6"
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
LEGEND:
DEMOLITION
MOORING PILES
P/S CONCRETE GUIDE PILE
P/S CONCRETE GUIDE PILE TO BE REMOVED
MHWL
BATHYMETRY
EASEMENT
MHW
(4)
STRUCTURAL DEMOLITION PLAN D-101
2026-01-30
KT
ARS
GWS
5NANCY LEHR
V-101
PLAN- GANGWAY DEMOLITION
SCALE: 1" = 20'
V-101
PLAN - WALKWAY DEMOLITION
SCALE: 1" = 20'
20'-0" 0'-0'' 20'-0" 40'-0"
SCALE: 1''=20'
ESTIMATED DEMOLITION QUANTITIES
MATERIAL QUANTITY
WALKWAY 3152 SF
FINGER PIER 540 SF
SQ P/S CONCRETE PILE 8 (UNITS)
GANGWAY 496 SF
This document has been electronically signed and sealed by
MHW
(9)
(9)
(8)
(15)
(10)
(17)
(16)
(14)
(13)
(12)
(11)
(15)
(10)
(5)
(14) (13)
(12) (11)
(9)
(8)
(7)
(6)
(4)
(3)
(2)
(1)
(16)
(1 5)
(10)
(1 6)
(1 4)
(1 3)
(1 2)
(1 1)
(15)
(10)
(14)
(13) (12)
(11)
(9)
(8) (7) (6)
(15)
(14) (14)
(14)
(5)
(9)
(8) (7)
(6)
(4) (3)
(2) (1)
(5) (7)
(6)
(4) (3)
(2)
(1)
(10)
(10)
(10)
(14)
(13)
(12)
(11)
(10)
(5)
(13)
(12)
(11)
(9)
(8)
(7) (6)
(4) (3)
(2)
(1)
(14)(13)
(15)
(16)
(16)
(10)
(5)
(14)
(13)
(12)
(11)
(9)
(8)
(7)
(6)
(4)
(3)
(2)
(10)
(10)
(12)
(12)
(11)
(11)
(3)
(2)
(5)
(4)
(10) (11)
(9) (8)
(7)
MHW
MHW
MHW
MHW
MHW
MHW
MHW
MHW
MHW
MHW
MHW
N
REPLACE
WALKWAY
S-101
C
LE
AR
W
AT
ER
M
EM
O R
IA
L
C
AU
SE
W
AY
CL
EA
RW
AT
ER
M
EM
ORI
AL
C
AU
SE
W
AY
WALKWAY
TO REMAIN
REPLACE GANGWAYS 2
S-101
REPLACE 4-0.6"Ø
TENSION CABLES
INSTALL NEW
TENSION CABLE
CONNECTIONS
INSTALL NEW
TENSION CABLE
CONNECTIONS
REPLACE 2-0.6"Ø
TENSION CABLES
EXISTING GANGWAY
TO BE TEMPORARILY
REMOVED, STORED
AND REINSTALLED
INCLUDING NEW
CONNECTION TO NEW
FLOATING WALKWAY.
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
50' 0' 50' 100'
SCALE: 1''=50'
LEGEND:
MOORING PILES
STEEL GUIDE PILE
MHWL
BATHYMETRY
EASEMENT
MHW
(4)
OVERALL SITE PLAN S-100
2026-01-30
KT
CML
GWS
6NANCY LEHR
ESTIMATED PROPOSED QUANTITIES
MATERIAL QUANTITY
WALKWAYS 3,700 SF
FINGER PIER 540 SF
24"x0.75" STEEL PIPE PILES 15 (UNIT)
GANGWAY 496 SF
This document has been electronically signed and sealed by
(10)
(5)
(11)
(9)
(8)
(7)
(6)
(4)
(3)
(2)
(10)
(9)
(8)
(7)
31'-0"
8'-0"
N
GANGWAY
8'x31' (TYP)
DOCKS TO
REMAIN
DOCKS TO REMAIN
8'-0"
31'-0"
PLATFORM TO REMAIN
BLAST CLEAN AND RECOAT
8'-6"
(5)
(7)
(6)
(4)
(3)
(2)
(1)
N
WALKWAY
12.33'x47' (TYP)
EXISTING
WALKWAY
12'-0"
5.
EXISTING
PROMENADE
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
FINGER PIER
4'x45' (TYP)
12'-4"
24"Ø GUIDE
PILE (TYP)
30'-0" 15'-0"
3'-0"
49'-11 1/2"
WALKWAY 8'x49.96'
INCLUDING CONNECTION
WALKWAY
8'x48.8'
48'-9 1/2"
FRAME GUIDE PILE1
S-510
S-501
33'-0"±
'-1
'-1
45'-0"
(TYP)
6'-2" 6'-2"
6'-0" 6'-0"
2"
(TYP)
4' -0
EXISTING GANGWAY TO
BE TEMPORARILY
REMOVED, STORED AND
REINSTALLED INCLUDING
NEW CONNECTION TO
NEW FLOATING WALKWAY.
8' -0
8' -0
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
LEGEND:
MOORING PILES
STEEL GUIDE PILE
MHWL
BATHYMETRY
EASEMENT
MHW
(4)
N-E WALKWAY AND GANGWAY
REPLACEMENT PLAN
S-101 2026-01-30
KT
ARS
GWS
NEL
7NANCY LEHR
S-100
PLAN - GANGWAY
SCALE: 1" = 20'
S-100
PLAN - WALKWAY
SCALE: 1" = 20'
20'-0" 0'-0'' 20'-0" 40'-0"
SCALE: 1''=20'
S-501
This document has been electronically signed and sealed by
VARIES, SEE S-101 FOR WIDTH
PRECAST CONCRETE
WALKWAY FLOAT,
SEE NOTE 3
TOP OF PILE
EL +18.50' NAVD 88
15" CLEAT (TYP)
D E
P
TH
P E
R M
AN
UF
AC
TU
RE
R'
S
RE
CO
M
M
EN
DA
TI
ON
S
GUIDE PILE
FOAM CORE
S-501
TOP OF DECK
NOTE:
MATERIALS, COATINGS AND DETAILS NOT
SHOWN TO BE PROVIDED BY MANUFACTURER.
FOAM CORE
1"Ø PVC DRAIN
UTILITY CHASE AND/OR RACEWAY
REFER TO MECHANICAL AND
ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION
COATING
FR
EE
BO
AR
D
PE
R
SP
EC
IF
IC
AT
IO
NS RUB BOARD, DEPTH SHALL BE
SUFFICIENT TO COVER ANY
UTILITIES HANGING ON SIDE OF
DOCK ABOVE WATER LINE
DOCK BUMPER (TYP)
WALER IF REQ'D (TYP)
2' -1
0" T
O
'-2
NON-SLIP DECKING
7'-0"
CLEAR
PROVIDE ADA HANDRAIL
1 1/4 " TO 1 1/2" Ø
1 1/2" MIN
8'-0"
TRANSVERSE FLOOR BEAM PER
MANUFACTURER´S RECOMENDATIONS.
ALUMINUM TUBE TRUSS FRAME
PER MANUFACTURER'S
RECOMMENDATIONS
HDPE SLEEVE, SEE NOTE 6
STEEL PIPE PILE, 24"Ø,
MIN 3/4" WALL THICKNESS
MUDLINE AT APPROXIMATELY
EL -10.00' NAVD 88
S
LE
E V
E E
M B
E D
M E
N T
5' -0
" M
IN
TIP EL TO BE DETERMINED
BY THE DOCK MANUFACTURER
TOP OF PILE
EL +18.50' NAVD 88
BASE FLOOD LEVEL
EL +12.00' NAVD 88
EL +0.99' NAVD 88 (MHHW)
EL -1.75' NAVD 88 (MLLW)
DESIGN FLOOD (VA INCLUDED)
EL +13.50' NAVD 88
HDPE PILE HAT
(2) 1/2"Ø SS
THROUGH BOLTS
WELDED 1/2"
CLOSURE PLATE
SEE CLEAT NOTE 2
CLEAT NOTES:
1. MOUNT CLEAT ON DOCK OR WALER PER
MANUFACTURER'S RECOMMENDATIONS.
2. MINIMUM CLEAT SIZES SHALL BE 15" .
CONNECTION PER
MANUACTURER'S
RECOMMENDATIONS
THRU BOLT W/ NUT &
WASHER (TYP)
FLOATING DOCK
& RUBBOARDCLEAT,
SEE NOTE 1
S-5018' WIDE x 31' LONG GANGWAY
8' WIDE x 31' LONG GANGWAY
EXISTING 8'-6" WIDE x 8' LONG
INTERMEDIATE PLATFORM
FLOATING DOCK
MINI-RAMP 1/4"x 8' WIDE x 6' LONG
S-101
ELEVATION - ADA ALUMINUM GANGWAY
SCALE: 1/4" = 1'-0"
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
NOTES:
1. REFER TO ELECTRICAL AND PLUMBING DRAWINGS FOR UTILITY ROUTING.
2. FINAL LOCATION AND SIZE OF UTILITY CHASE OR SLEEVES MUST BE
DETERMINED BY DOCK MANUFACTURER.
3. DOCK MODULE CONNECTION SYSTEM, INCLUDING GUIDE PILE FRAMES,
MUST BE DETERMINED BY DOCK MANUFACTURER IN ACCORDANCE WITH
THE SPECIFICATIONS.
4. DOCK MANUFACTURER TO CONFIRM EXISTING CONDITION FREEBOARD
OF THE DOCKS.
5. DOCK DIMENSIONS SHOWN ON DRAWING S-101 ARE NOMINAL AND
INCLUDE THE STRUCTURAL ELEMENTS OF THE FLOATS (CONCRETE
FLOAT AND STRUCTURAL WALER).
6. PROVIDE UV STABILIZED HDPE SLEEVE WITH MIN 1/2" WALL THICKNESS.
SLEEVE INNER DIAMETER MUST BE NO MORE THAN 1" INCH GREATER
GUIDE PILE OUTER DIAMETER.
7. ALL STAINLESS STEEL HARDWARE MUST BE TYPE 316L.
8. RECOMMENDED FREEBOARD TO BE PROVIDED BY DOCK MANUFACTURER
TO MATCH EXISTING FLOATING DOCKS TO AVOID TRIPPING HAZARD.
S-501
TYPICAL WALKWAY FLOAT SECTION
SCALE: 1/2" = 1'-0"
S-501
SECTION - ADA ALUMINUM GANGWAY
SCALE: 1" = 1'
GANGWAY NOTES:
1. CONNECTION SHALL INCLUDE TRANSITION PLATES
SPANNING FROM THE GANGWAY TO THE WALKWAY.
2. CONNECTION SHALL BE INCLUDED WITH GANGWAY
SUBMITTAL FOR APPROVAL.
3. CONNECTION SHALL BE DESIGNED TO MEET
PERFORMANCE CRITERIA IN SPECIFICATION
INCLUDING BUT NOT LIMITED TO CHANGES IN
WATER LEVEL, LIVE LOAD, DIFFERENTIAL
MOVEMENT AND WEIGHT OF GANGWAY.
S-101
SECTION - GUIDE PILE
SCALE: 3/4" = 1'-0"
1'-0" 0'-0'' 1'-0" 2'-0"
SCALE: 1"=1'-0''
4'-0" 0'-0'' 4'-0" 8'-0"
SCALE: 1/4"=1'-0''
2'-0" 0'-0'' 1'-0" 2'-0"
SCALE: 3/4"=1'-0''
2'-0" 0'-0'' 2'-0" 4'-0"
SCALE: 1/2"=1'-0''
S-501
DETAIL - CLEAT
SCALE: 1" = 1'
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04WALKWAY DETAILS (1 OF 2) S-501
2026-01-30
KT
ARS
GWS
8NANCY LEHR
CLEAT (TYP)
PRECAST CONCRETE FLOAT,
SEE NOTE 3
RUB BOARD, DEPTH SHALL BE
SUFFICIENT TO COVER ANY
UTILITIES HANGING ON SIDE OF
DOCK ABOVE WATER LINE
DOCK
BUMPER, (TYP)
WALER IF
REQ'D, (TYP)
CLEAT (TYP)
NOMINAL WIDTH
4'-0"
PRECAST CONCRETE FLOAT,
SEE NOTE 3 ON S-501
CONCRETE WIDTH
RUB BOARD, DEPTH SHALL BE
SUFFICIENT TO COVER ANY
UTILITIES HANGING ON SIDE OF
DOCK ABOVE WATER LINE
DOCK
BUMPER, (TYP)
WALER IF
REQ'D, (TYP)
UTILITY CHASE
WHERE REQUIRED,
SEE NOTE 1 ON S-501
ACTUAL WIDTH
SEE NOTE 4 ON S-501
FR
EE
BO
AR
D
PE
R
SP
EC
IF
IC
AT
IO
NS
45'-0" FINGER PIER
CLEAT (TYP)
PILE GUIDE
PRECAST CONC
FLOATING DOCK
PILE HAT (TYP)
TIMBER OR UHMW-PE FACING
BOARD @ END OF FINGER PIER
S-502
S-501
WALKWAY
GUIDE PILE @ END OF
FINGER PIER WHERE REQ'D
EXIST MUDLINE, EL VARIES
REUSED EXISTING 1/2" THK
THRUST WASHER
PVC CAP
0.60" STAINLESS
STEEL CABLE LOCKER
FILL RECESS WITH MASTERSEAL
NPS (LIMESTONE COLOR) OR
APPROVED EQUAL
EXISTING 2" PIPE
EXISTING 1/2" PLATE
EXISTING SLEEVE
EXISTING FLOAT
0.60"Ø TOTALLY ENCASED POST
TENSION CABLE
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
NOTES:
1. SEE NOTES ON SHEET S-501.
2'-0" 0'-0'' 2'-0" 4'-0"
SCALE: 1/2"=1'-0''
S-502
ELEVATION - FINGER PIER DOCK
SCALE: 1/4" = 1'-0"
S-502
SECTION - FINGER PIER
SCALE: 1/2" = 1'-0"
4'-0" 0'-0'' 4'-0" 8'-0"
SCALE: 1/4"=1'-0''
WALKWAY DETAILS (2 OF 2) S-502
2026-01-30
KT
ARS
GWS
9NANCY LEHR
S-502
CABLE TERMINATION SKETCH
SCALE: 3" = 1'-0"
6" 0'-0'' 3" 6"
SCALE: 3"=1'-0''
This document has been electronically signed and sealed by
1'-9"
(SEE NOTE)
3'-6"
(SEE NOTE)
1'-9"
(SEE NOTE)
4' -1
/2
(S
E E
N O
TE
2' -1
/2
(S
E E
N O
TE
1' -9
(S
E E
N O
TE
3"x6"x3/8" SS
HSS (TYP)
3/4" 316 SS PIN (TYP)
3"x6" UHMW
ROLLER (TYP)
2'-8" 2'-8"
5'-4"
1/4" SS STEEL
BACKER PL (TYP)
5/8"Ø THROUGH
SS BOLT (TYP)
1'-0" 1'-0" 1'-0" 1'-0"
1/
2"
3/8"x6"x6" SS
STEEL GUSSET
PLATE (TYP)
CJP
CJP
3/16x12" (TYP)
1"x2" LONG
SLOT (TYP)
3"x6"x3/8"
HSS SS
SS STEEL
BACKER PL (TYP)
S-510
L6"x3 1/2"x1/2" SS
12" OC
7/8" DIA PVC PIPE W/ 5/8" DIA
SS THROUGH ROD (TYP)
S-510
5/8"Ø SS
THROUGH ROD
GUSSET PLATE
SS (TYP)
24"Ø PIPE PILE
L3"x3 1/2"x1/2"
(TYP)
1" MIN
(TYP)
NOTE:
DIMENSION IS BASED ON A 24"Ø PIPE
PILE W/MIN 1/2" HDPE SLEEVE. IF
SLEEVE THICKNESS INCREASES,
ADJUST DIMENSIONS ACCORDINGLY.
S-510
GUSSET
PLATE (TYP)
8" 8"
5'-4"
SLEEVE
C L
B O
LT
C L
P
IL
E
6"x3"x3/8" HSS SS
5/8"Ø THRU ROD SS
(TYP, 5 LOCATIONS)
EXISTING
FLOATING DOCK
EXIST 7/8"Ø PVC
SLEEVE
3/8" GUSSET PLATE
SS (BEYOND, TYP)
1/
2"
3/16x9"
CPJ
3"x5"x1/4" BACKER
PLATE SS W/
SLOTTED HOLES
5/8"Ø THROUGH ROD SS
(TYP, 2 LOCATIONS)
L 6"x3 1/2"x1/2" SS
15" ALUM
S-CLEAT
9'-2"
2"
FR
E E
B O
A R
D
CONCRETE
3' -4
2" SIDE WALLS
2" DECK
(3) #6 EA SIDE
(3) #6 EA SIDE
0.60" Ø TOTALLY ENCASED
CABLE PVC SLEEVE FOR
0.60"Ø CABLE
2x6 WALER
4x6 WALER
EXISTING PVC
SLEEVE FOR 5/8"Ø
THROUGH ROD SS
EXISTING 4"x4"x4 GA.
WIRE MESH MATS
EXPANDED
POLYSTYRENE
0.95 LB/CU FT MIN
POLYURETHANE COATED BOTTOM
AVERAGE THICKNESS 0.125"
PILE GUIDE
5/8"Ø THROUGH
ROD SS
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
23SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
1'-0" 0'-0'' 6" 1'-0"
SCALE: 1 1/2"=1'-0''
S-101
PLAN - PILE GUIDE
SCALE: 1 1/2" = 1'-0"
S-510
DETAIL - CONNECTION
SCALE: 3" = 1'-0"
6" 0'-0'' 3" 6"
SCALE: 3"=1'-0''
S-510
DETAIL
SCALE: 1 1/2" = 1'-0"
S-510
SECTION - EXISTING FLOATING WALKWAY
SCALE: 1" = 1'-0"
1'-0" 0'-0'' 1'-0" 2'-0"
SCALE: 1"=1'-0''
PILE GUIDE DETAILS S-510
2026-01-30
KT
ARS
GWS
10NANCY LEHR
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
21SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04MECHANICAL NOTES M-001
2026-01-30
KJG
APB
NEL
WRP
10NANCY LEHR
SYMBOLS DESCRIPTIONABBREV
LEGEND AND ABBREVIATIONS
AHJ AUTHORITY HAVING JURISDICTION
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
CU COPPER
DIA DIAMETER
DR DIMENSION RATIO
DWG DRAWING
ELL ELBOW
EX EXISTING EQUIPMENT
FLEXIBLE HOSE
EXISTING SEWER FORCE MAIN
FM SEWER FORCE MAIN
FT FEET
EXISTING FIRE WATER
FEC FIRE EXTINGUISHER CABINET
FW FIRE WATER
FWHC FIRE WATER HOSE CONNECTION
GAL GALLONS
GPM GALLONS PER MINUTE
HDPE HIGH DENSITY POLYETHYLENE
MFR MANUFACTURER
MLW MEAN LOW WATER
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NPT NATIONAL PIPE THREAD
NSF NATIONAL SANITATION FOUNDATION INTERNATIONAL
OC ON CENTER
POC POINT OF CONNECTION
PPM PARTS PER MILLION
PVC POLYVINYL CHLORIDE PIPE
PSI POUNDS PER SQUARE INCH
SPU SEWAGE PUMPOUT UNIT
SS STAINLESS STEEL
STD STANDARD
TYP TYPICAL
TBR TO BE REMOVED
UL UNDERWRITERS LABORATORIES, INC.
UNO UNLESS NOTED OTHERWISE
UP UTILITY PEDESTAL
VIC VICTAULLIC
EXISTING POTABLE WATER
W POTABLE WATER
W/ WITH
F
FM
W
MECHANICAL GENERAL NOTES
1. INSTALLATION OF PLUMBING SYSTEMS, INCLUDING COORDINATION WITH
OTHER TRADES, MUST COMPLY WITH THE 2023 FLORIDA PLUMBING CODE 8TH
ED., THE 2023 FLORIDA FIRE PREVENTION CODE 8TH ED., THE CODE OF
ORDINANCES CITY OF CLEARWATER FLORIDA, AND MUST BE COORDINATED
WITH THE WATER, FIRE, SEWER, AND OTHER AHJ DEPARTMENTS. PRIOR
APPROVAL OF AND NOTICE TO PROCEED WITH THE TIE-INS TO EXISTING
UTILITIES ARE REQUIRED BY THE LOCAL AHJ FOR THE WATER, FIRE, AND
SEWER SYSTEMS. AUTHORIZED REPRESENTATIVE MUST WITNESS TIE-IN, AS
REQUIRED.
2. ALL PIPING MUST FOLLOW THE GENERAL ARRANGEMENT SHOWN. PIPING MUST
BE RUN AS INDICATED, CARE BEING TAKEN TO AVOID INTERFERENCE WITH
OTHER PIPING, CONDUIT, OR EQUIPMENT. THE LOCATION OF PIPING TO BE RUN
ON THE DOCK MUST BE COORDINATED WITH ELECTRICAL CONDUITS
SPECIFIED. BEFORE JOINTING AND ERECTION OF PIPING, THOROUGHLY CLEAN
INTERIORS OF PIPE AND COMPONENTS. MAINTAIN CLEANLINESS BY CLOSURE
OF PIPE OPENINGS WITH CAPS OR PLUGS.
3. THE CONTRACTOR MUST OBTAIN ALL REQUIRED BUILDING/TRADE PERMITS
AND PROVIDE ALL REQUIRED TESTING.
4. THE CONTRACTOR MUST ENSURE SUFFICIENT PIPE FLEXIBILITY AND
ANCHORAGE IS PROVIDED FOR ALL LINES FOR THERMAL EXPANSION AND
CONTRACTION, AND PRESSURE. THE DOCK STRUCTURE AND COMPONENTS
MUST ACCOMMODATE THE PIPING LAYOUT REQUIREMENTS SUCH THAT THE
PIPE MUST NOT BECOME OVERSTRESSED. THE PIPING MUST BE PROPERLY
SUPPORTED AND ANCHORED.
5. CONTRACTOR MUST INSPECT MATERIALS DELIVERED TO SITE FOR DAMAGE.
UNLOAD AND STORE WITH MINIMUM HANDLING. STORE MATERIALS ON SITE IN
ENCLOSURES OR UNDER PROTECTIVE COVERING. STORE PLASTIC PIPING
UNDER COVER OUT OF DIRECT SUNLIGHT. DO NOT STORE MATERIALS
DIRECTLY ON THE GROUND. KEEP INSIDE OF PIPES, FITTINGS AND EQUIPMENT
FREE OF DIRT AND DEBRIS. HANDLE PIPE, FITTINGS, VALVES, AND OTHER
ACCESSORIES IN SUCH MANNER AS TO ENSURE DELIVERY TO THE
INSTALLATION LOCATION IN A SOUND UNDAMAGED CONDITION.
6. ALL POTABLE WATER, FIRE WATER, AND SEWER MATERIALS (PIPE, VALVES,
ETC.) MUST BE FURNISHED BY THE CONTRACTOR. ALL SUCH MATERIALS MUST
BE NEW, MEET DISTRICT, COUNTY, WATER, AND SEWER UTILITY COMPANY AND
OTHER AHJ SPECIFICATION REQUIREMENTS FOR EACH ITEM. PRIOR TO
INSTALLATION, MATERIALS MUST BE APPROVED IN WRITING BY THE ENGINEER
AND AHJ.
7. SHOULD THERE BE A CONFLICT BETWEEN THESE GENERAL NOTES, CONTRACT
DRAWINGS, AND/OR CONTRACT DOCUMENTS, THE MOST RESTRICTIVE
INTERPRETATION MUST PREVAIL. THE CONTRACTOR MUST BE RESPONSIBLE
FOR OBTAINING FROM THE ENGINEER ANY CLARIFICATION OR
INTERPRETATION OF GENERAL NOTES, CONTRACT DRAWINGS, AND/OR
SPECIFICATIONS IN WRITING AND IN ADVANCE OF THE BEGINNING OF
CONSTRUCTION
8. THE CONTRACTOR MUST PROVIDE ALL NECESSARY PROTECTIVE MEASURES
TO PROTECT EXISTING UTILITIES FROM DAMAGE DURING CONSTRUCTION OF
THIS PROJECT. SHOULD SPECIAL EQUIPMENT BE REQUIRED TO WORK OVER
AND AROUND THE UTILITIES, THE CONTRACTOR MUST BE REQUIRED TO
FURNISH SUCH EQUIPMENT. THE COST OF PROTECTING UTILITIES FROM
DAMAGE AND FOR FURNISHING SPECIAL EQUIPMENT MUST BE INCLUDED IN
THE BID FOR CONSTRUCTION.
9. THE CONTRACTOR MUST BE RESPONSIBLE FOR CONTACTING ALL AFFECTED
UTILITY OWNERS PRIOR TO SUBMITTING A BID TO COORDINATE SCHEDULING
OF WORK FOR THE PROJECT. THE CONTRACTOR MUST RECEIVE NO
ADDITIONAL COMPENSATION FOR ANY DELAYS OR INCONVENIENCE CAUSED
BY NECESSARY UTILITY COMPANY ADJUSTMENTS TO THE PROJECT SCHEDULE.
10. SUPPORTS AND HARDWARE MUST BE TYPE 316 STAINLESS STEEL. FIELD
BENDING IS NOT PERMITTED. VALVE SUPPORTS MUST BE INSTALLED ON
ADJACENT PIPING ON BOTH SIDES OF THE VALVE. SUBMIT SHOP DRAWINGS
OR CATALOG DATA FOR REVIEW AND APPROVAL. A DIELECTRIC ISOLATION
SHEET MUST BE PLACED WHERE DISSIMILAR METALS CONTACT ON THE
SUPPORT.
11. ALL UNSUITABLE MATERIAL, AS DETERMINED BY THE ENGINEER, OR
THROUGH TESTING, MUST BE REMOVED, LEGALLY DISPOSED, AND
REPLACED WITH SUITABLE MATERIAL, WITH CORRESPONDING CLOSURE
REPORT(S), AND ACCEPTABLE TO THE ENGINEER AND REGULATORY
AUTHORITIES.
12. DIELECTRIC COUPLINGS MUST BE USED AT DISSIMILAR METAL PIPING
CONNECTIONS.
13. ALL PIPING MATERIAL, AND APPURTENANCES MUST BE SUBMITTED ALONG
WITH SHOP DRAWINGS TO THE OWNERS REPRESENTATIVE FOR APPROVAL
BEFORE INSTALLATION.
14. HDPE PIPING EXPOSED TO SUNLIGHT MUST BE UVR AND SURFACE PREPARED
AND PAINTED WITH A WATER-BASED LATEX PAINT FOR UV RESISTANCE.
POTABLE WATER NOTES
1. PIPING AND FITTINGS MUST BE HDPE DR11, PER ASTM D3035 OR ASTM D2239
WITH A MINIMUM WORKING PRESSURE OF 150 PSI. PIPE AND FITTINGS OF THE
SAME MATERIAL MUST BE FROM ONE MANUFACTURER. PIPING AND
INSTALLATION MUST CONFORM TO THE FLORIDA PLUMBING CODE AND CODE
OF ORDINANCES OF THE CITY OF CLEARWATER, FLORIDA.
2. THE POTABLE WATER SYSTEM MUST BE PRESSURE TESTED DOWNSTREAM OF
THE POC. FLUSH PIPING WITH CLEAN WATER TO REMOVE DEBRIS. APPLY AND
MAINTAIN 150 PSI TEST PRESSURE FOR 4 HOURS, DURING WHICH TIME THERE
WILL BE NO REDUCTION IN TEST PRESSURE. SHOULD A REDUCTION OCCUR,
LEAKS MUST BE LOCATED, REPAIRED AND THE TEST REPEATED. THE POTABLE
WATER SYSTEM FROM THE POC, MUST BE STERILIZED PRIOR TO USE. A
SOLUTION OF CHLORINE AND WATER CONTAINING NOT LESS THAN 50 P.P.M. OF
FREE CHLORINE MUST BE INJECTED INTO THE SYSTEM IN SUCH A MANNER AS
TO ENSURE THAT THE ENTIRE SYSTEM IS COMPLETELY FILLED WITH THE
SOLUTION. AFTER INJECTION, THE SYSTEM MUST BE ISOLATED AND THE
SOLUTION HELD FOR A MINIMUM PERIOD OF 24 HOURS. THE SYSTEM MUST
THEN BE FLUSHED WITH FRESH WATER UNTIL THE CHLORINE LEVEL IS WITHIN
ACCEPTABLE LIMITS AS DETERMINED BY THE AUTHORITY HAVING
JURISDICTION. THE CONTRACTOR MUST ENSURE THAT THE WATER IN THE
SYSTEM IS NOT USED FOR HUMAN CONSUMPTION DURING THE STERILIZATION
PROCESS AND THAT STERILIZATION SOLUTION IS DISPOSED OF IN
ACCORDANCE WITH LOCAL REQUIREMENTS.
3. MAXIMUM DISTANCE OF PIPE BETWEEN PIPE SUPPORTS PER 2020 FLORIDA
BUILDING CODE MUST NOT EXCEED THE FOLLOWING, UNO:
4. HDPE MUST BE MARKED BY MANUFACTURER FOR POTABLE WATER AND/OR BE
NSF LISTED.
FIRE WATER SYSTEM NOTES
1. FIRE PROTECTION PLANS MUST BE APPROVED BY THE LOCAL FIRE
DEPARTMENT PRIOR TO THE INSTALLATION OF ANY PIPE. DURING
CONSTRUCTION, A SET OF APPROVED PLANS MUST BE MAINTAINED AT ALL
TIMES ON THE JOB SITE.
2. COMPLETED WORK MUST BE SUBJECTED TO A FIRE WATER PRESSURE TEST
OF 200 PSI FOR TWO HOURS, DURING WHICH THERE IS TO BE NO REDUCTION IN
TEST PRESSURE. IF A REDUCTION SHOULD OCCUR, LEAK(S) MUST BE LOCATED,
REPAIRED AND THE TEST REPEATED. IN ADDITION, ALL NEWLY INSTALLED FIRE
SERVICE LINES MUST PASS HYDROSTATIC AND HYDRODYNAMIC TESTING
REQUIREMENTS AS PERFORMED BY THE LOCAL FIRE MARSHAL.
3. THE SYSTEM MUST ONLY EMPLOY THE USE OF APPROVED MATERIALS AND
DEVICES OF NO LESS THAN 200 PSI RATED WORKING PRESSURE. MARINA FIRE
WATER PIPING MUST BE HDPE DR 11 TO BE CONSISTENT WITH EXISTING PIPE.
4. PIPING MATERIAL & FIREWATER SYSTEM MUST BE IN COMPLIANCE WITH NFPA
14 (2019), NFPA 303 (2021), FLORIDA FIRE PREVENTION CODE, AND
REQUIREMENTS OF AUTHORITY HAVING JURISDICTION. ALL MATERIALS MUST
BE UL LISTED WHERE AVAILABLE.
5. THE MARINA FIRE WATER SYSTEM MUST BE A MANUAL WET CLASS 1
STANDPIPE SYSTEM, PER NFPA 14. THE INTENT IS TO REPLACE A PORTION OF
THE STANDPIPE SYSTEM IN KIND AS APPROVED BY THE CLEARWATER CITY
FIRE INSPECTOR.
6. FLEXIBLE HOSE CONNECTIONS AT GANGWAYS MUST BE FACTORY ASSEMBLED
LENGTHS OF CONTINENTAL PLICORD SUPER BLACK FLEXWING OR APPROVED
EQUAL, 7" MIN BEND RADIUS ON A 3" HOSE, 300 PSI WORKING PRESSURE WITH
MARINE 316 STAINLESS STEEL COUPLINGS EACH END.
7. MAXIMUM DISTANCE OF ABOVEGROUND PIPE BETWEEN PIPE SUPPORTS (PER
NFPA) MUST NOT EXCEED THE FOLLOWING UNO:
8. MODIFICATIONS TO THE FIRE PROTECTION STANDPIPE SYSTEM MUST BE
PERFORMED BY A LICENSED FIRE PROTECTION CONTRACTOR AND PLANS
MUST BE SUBMITTED UNDER A SEPARATE PERMIT BY SAID CONTRACTOR.
SANITARY SEWER SYSTEM NOTES
1. PIPING AND FITTINGS MUST BE HDPE DR11, PER ASTM D3035 OR ASTM D2239
WITH A MINIMUM WORKING PRESSURE OF 150 PSI.
2. PRIOR TO INSTALLATION, THE CONTRACTOR MUST SUBMIT SHOP DRAWINGS
TO THE AUTHORITY HAVING JURISDICTION FOR APPROVAL OF THE INDICATED
FORCE MAIN SEWER SYSTEM, INCLUDING PIPE AND FITTINGS, AND LAYOUT TO
THE POC WITH AN EXISTING GRAVITY SEWER SYSTEM, INDICATING DETAILS OF
FITTINGS AND APPURTENANCES. THE CONTRACTOR IS RESPONSIBLE TO
PROVIDE A COMPLETE WORKING SEWER SYSTEM, AND PROVIDE COMPATIBLE
PIPING AND FITTING MATERIALS.
3. NO MODIFICATIONS TO THE PUMPOUT UNIT ARE REQUIRED. REMOVE AND
REPLACE SEWER FORCE MAIN PIPING AS INDICATED ON THE DRAWINGS.
4. WHERE POSSIBLE, TWO 45° ELLS MUST BE USED IN LIEU OF 90° ELL. 90° ELLS
MUST BE LONG RADIUS.
5. MAXIMUM DISTANCE BETWEEN PIPE SUPPORTS MUST COMPLY WITH POTABLE
WATER SYSTEM NOTE 3.
6. ALL LINES MUST BE HYDROTESTED AS A WATER LINE OF 150 PSI.
NOMINAL
PIPE SIZE
3" 2"
1 1/2" 1"
HDPE PIPE
SPAN, FEET
2 1/2" 3"
NOMINAL
PIPE SIZE
HDPE PIPE
SPAN, FEET
W
F
FM
This document has been electronically signed and sealed by Wilfredo J. Ruiz Planell, P.E. on the date adjacent to the seal.
Signature must be verified on any electronic copies.
W
F
FM
FM
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
F
F
F
F
F
F
F
F
FM
FM
FM
FM
FM
F F
F
FM F
F
F
F
F
F
F
F
F F
F W
W
F F F F F F F F
W
EXISTING FIRE RISERS TO
BE REPLACED PER M-101
FIRE WATER PIPING AND
SUPPORTS TO BE DEMOLISHEDCUT AND CAP FIRE
STANDPIPE
EXISTING PUMPOUT
UNIT TO REMAIN
STEEL FIRE RISER
PEDESTAL TO BE
REINSTALLED (TYP)
DEMO PIPING AND
EQUIPMENT WITH
WAVE ATTENUATORS
CUT AND CAP UTILITIES
PRIOR TO DEMOLITION
EXISTING POTABLE WATER
AND FIRE STANDPIPE TO
REMAIN
EXISTING FIRE STANDPIPE
AND RISERS TO REMAIN
EXISTING POTABLE
WATER PIPE TO REMAIN
GANGWAY AND UTILITIES TO BE
DEMOLISHED. CUT AND CAP
FOR FUTURE RECONNECTION.
EXISTING POTABLE
WATER PIPE TO REMAIN
EXISTING GANGWAY TO BE REMOVED
DURING CONSTRUCTION AND
REINSTALLED. SEE NOTE #5.
BULKHEAD
FIXED PIER
TRANSIENT DOCK
I N T E R C O A S T A L W A T E R W A Y
CUT AND CAP UTILITIES
PRIOR TO DEMOLITION
GANGWAY PLATFORM
TO REMAIN
DOCKS TO REMAIN
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
21SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
MECHANICAL DEMOLITION PLAN
SCALE: 1" = 40'
MECHANICAL DEMOLITION PLAN MD101
2026-01-30
KJG
APB
NEL
WRP
11NANCY LEHR
40' 0' 40' 80'
SCALE: 1''=40'
NOTES
1. FIVE WAVE ATTENUATORS ARE BEING REMOVED. SEE
STRUCTURAL DRAWINGS.
2. REMOVE ALL PIPING AND SUPPORTS IN LIMITS OF
DEMOLITION.
3. CUT AND TEMPORARILY CAP EXISTING HDPE PIPING.
PREPARE PIPE ENDS FOR FUTURE ELECTRO-FUSION.
4. SHOP DRAWINGS MUST BE SUBMITTED FOR
APPROVAL PRIOR TO CONSTRUCTION.
5. DETACH FLEXIBLE HOSES AND PIPING SO THAT THEY
CAN BE REUSED AFTER GANGWAY IS REINSTALLED.
PIPING, FITTINGS, AND SUPPORTS MUST BE REPLACED
IN-KIND IF THEY ARE DAMAGED DURING REMOVAL.
LEGEND
DEMOLITION
UTILITY PEDESTAL
FIRE HOSE CONNECTION
SEWER PUMPOUT UNIT
FLEXIBLE HOSE
N
This document has been electronically signed and sealed by Wilfredo J. Ruiz Planell, P.E. on the date adjacent to the seal.
I N T E R C O A S T A L W A T E R W A Y
C
LE
A R
W A
TE
R
M E
M O
R
IA
L C
A U
S E
W A
Y
CL
EA
RW
AT
ER
M
EM
ORI
AL
C
AU
SE
W
AY
S O U T H B A S I N N O R T H B A S I N
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
21SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
MECHANICAL OVERALL PLAN
SCALE: 1" = 50'
MECHANICAL OVERALL PLAN M-100
2026-01-30
KJG
APB
NEL
12NANCY LEHR
50' 0' 50' 100'
SCALE: 1''=50'
M-101 M-102
N
This document has been electronically signed and sealed by Wilfredo J. Ruiz Planell, P.E. on the date adjacent to the seal.
FIRE RISER (TYP)
NEW 3" HDPE
DR11 FM
EXISTING 3"
HDPE DR11 FW
EXISTING 3"
HDPE DR11 FW
EXISTING 3"
HDPE DR11 FM
BULKHEAD
UTILITY PEDESTAL
(TYP)
W
W F
F
W W
WW
W
W
F F
F
FM
FM
FM
FM
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
F
F
F
F
F
F
F
F
F
F
F
F
F
F F F
W
F F
F
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
F
F F
F F
F
F
F
F
F
F F
F F
F F
F F
F F
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
W W
W W W W W W W W
W W
WW
W
W
WW
W W W W
F F F F F F F F F F F F F F F FF F F F F F F F F F F F F F F F
F F
F F
F F
W
FF
EXISTING 2"
HDPE DR11 PW
CONNECT NEW
FIRE WATER PIPE
TO EXISTING PIPE
M-501
EXISTING HDPE
DR11 PW
NEW 3" HDPE
DR11 FW
M-501
EXISTING
HDPE DR11 PW
EXISTING HOSE
PEDESTAL (TYP)
NEW 3" HDPE DR11 FW
NEW WAVE
ATTENUATOR
RE-COUPLE OLD FLEXIBLE
HOSES TO NEW UTILITIES
FIRE EXTINGUISHER
CABINET (TYP)
M-501
RECONNECT POTABLE
WATER TO PEDESTALS THAT
WERE REPLACED (TYP)
NEW 3" HDPE
DR11 PW
EXISTING FIRE RISER (TYP)
I N T E R C O A S T A L W A T E R W A Y
ELECTROFUSE EXISTING
FLOATING WALKWAY PIPING
TO NEW PIPE
NEW 2" HDPE
DR11 PW
NEW 3" HDPE
DR11 FW
ELECTROFUSE EXISTING
FLOATING WALKWAY PIPING
TO NEW PIPE
ELECTROFUSE EXISTING
FLOATING DOCK PIPING
TO NEW PIPE
UTILITY CHASE IN THE
FLOATING DOCK
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
21SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
MECHANICAL PLAN
SCALE: 1" = 20'
MECHANICAL PLAN (1 OF 2) M-101
2026-01-30
KJG
APB
NEL
13NANCY LEHR
20' 0' 20' 40'
SCALE: 1''=20'
M A
TC
H
L
IN
E
S E
E S
H E
E T
M -1
LEGEND
UTILITY PEDESTAL
FIRE HOSE CONNECTION
SEWER PUMPOUT UNIT
EXISTING FORCE MAIN
NEW FORCE MAIN
EXISTING FIRE WATER
NEW FIRE WATER
EXISTING POTABLE WATER
NEW POTABLE WATER
FIRE EXTINGUISHER CABINET
FLEXIBLE HOSE
F
FM
W
W
F
FM
N
NOTES
1. PIPE SUPPORT SPACING MUST BE A MAXIMUM OF 6FT FOR 3" PIPING AND 4FT FOR 2"
PIPING.
2. PIPE SUPPORTS AND FASTENERS MUST BE 316 STAINLESS STEEL. ALL PIPING MUST BE
ELECTROFUSED PER ASTM F1055.
3. FLOATING DOCK UTILITY ROUTING TO BE COORDINATED WITH DOCK VENDOR. SHOP
DRAWINGS MUST BE SUBMITTED FOR APPROVAL PRIOR TO CONSTRUCTION.
4. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION ON CONDUIT
LAYOUT.
5. REFER TO STRUCTURAL DRAWINGS FOR ADDITIONAL GANGWAY AND FLOATING DOCK
INFORMATION.
6. REFER TO G-002 FOR TIDAL INFORMATION.
This document has been electronically signed and sealed by Wilfredo J. Ruiz Planell, P.E. on the date adjacent to the seal.
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
W W W
F F FF F F
EXISTING 2"
HDPE DR11 PW
NEW 3" HDPE
DR11 FW
EXISTING 3"
HDPE DR11 FW
EXISTING 3"
HDPE DR11 FW
EXISTING FIRE RISER (TYP)
NEW 3" FLEXIBLE
HOSE (TYP)
EXISTING
HDPE DR11 PW
M-501
FIRE RISER (TYP)
BULKHEAD
FIXED PIER
EXISTING HOSE
PEDESTAL (TYP)
TRANSIENT DOCK
CONNECT POTABLE
WATER TO PEDESTALS
THAT WERE REPLACED
NEW 3" HDPE
DR11 FW
I N T E R C O A S T A L W A T E R W A Y
ELECTROFUSE NEW PIPING
TO EXISTING PIPING
TOWARDS FIXED PIER
5M -501
NEW GANGWAY
EXISTING PLATFORM
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
21SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
MECHANICAL PLAN
SCALE: 1" = 20'
MECHANICAL PLAN (2 OF 2) M-102
2026-01-30
KJG
APB
NEL
14NANCY LEHR
20' 0' 20' 40'
SCALE: 1''=20'
M A
TC
H
L
IN
E
S E
E S
H E
E T
M -1
LEGEND
UTILITY PEDESTAL
FIRE HOSE CONNECTION
SEWER PUMPOUT UNIT
FLEXIBLE HOSE
EXISTING FIRE WATER
NEW FIRE WATER
EXISTING POTABLE WATER
F
W
F
N NOTES
1. PIPE SUPPORT SPACING MUST BE A MAXIMUM OF 6FT FOR 3" PIPING AND 4FT FOR 2"
PIPING.
2. PIPE SUPPORTS AND FASTENERS MUST BE 316 STAINLESS STEEL. ALL PIPING MUST BE
ELECTROFUSED PER ASTM F1055.
3. FLOATING DOCK UTILITY ROUTING TO BE COORDINATED WITH DOCK VENDOR. SHOP
DRAWINGS MUST BE SUBMITTED FOR APPROVAL PRIOR TO CONSTRUCTION.
4. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION ON CONDUIT
LAYOUT.
5. REFER TO STRUCTURAL DRAWINGS FOR ADDITIONAL GANGWAY AND FLOATING DOCK
INFORMATION.
6. REFER TO G-002 FOR TIDAL INFORMATION.
This document has been electronically signed and sealed by Wilfredo J. Ruiz Planell, P.E. on the date adjacent to the seal.
NEW 2 1/2" ANGLE BRASS
VALVE W/ FIRE DEPARTMENT
HOSE CONNECTION
M
IN
' T
O M
A X
3"X3" TEE
NEW WAVE
ATTENUATOR
REUSE STEEL RISER
PEDESTAL AND BASE
PENETRATION
THROUGH WALER
3" FW
NEW 2.5" SS
PIPE RISER
NOTE: PIPING AND SUPPORTS
MUST BE INSTALLED ABOVE THE
WATER. STAGGER THE SUPPORTS
TO ALLOW FOR MORE SPACE
EATON B3180 SS PIPE STRAP W/ SS
EXPANSION ANCHOR BOLTS (TYP)
3" HDPE TO SS TRANSITION FITTING
FEMALE W/ 2.5" SS BUSHING
3" FM OR 2" PW,
SEE PLANS
1" F
R E
E B
O A
R D
UTILITY PEDESTAL UL
LISTED, SEE ELECTRICAL
DRAWINGS FOR DETAILS
3" OR 2" PW
3/4" TAP SADDLE
FITTING OR TEE DOCK UTILITY CHASE
OR BLOCKOUT
NEW WAVE
ATTENUATOR
BALL VALVE
3/4" HOSE BIBB W/
VACUUM BREAKER
3/4" FLEXIBLE HOSE
WALER
10# ABC DRY
CHEMICAL
EXITINGUISHER
3/8"Ø X 3" SS ANCHOR
BOLTS (TYP), VERIFY WITH
CABINET MANUFACTURER
FIRE EXTINGUISHER CABINET
CONSTRUCTED OF CORROSION
RESISTANT MATERIAL BY MEE OR
APPROVED EQUAL
NEW WAVE
ATTENUATOR
GANGWAY (TYP)
EXISTING INTERMEDIATE
PLATFORM
FLOATING DOCK
MINI-RAMP
EXISTING 3"
HDPE DR11 FW
24"±1" FREEBOARD
3"Ø STEEL VIC COUPLING
OR APPROVED EQUAL (TYP)
3" HDPE TO SS TRANSITION
OR APPROVED EQUAL (TYP)3" FLEXIBLE
HOSE (TYP)
3" HDPE DR11 ELL, ELECTROFUSE
TO EXISTING PIPING
SS CLEVIS HANGER (TYP),
6' MAX SUPPORT SPACING
45° HDPE DR11 BEND (TYP),
ADJUST BEND ANGLES TO
ALIGN PIPE CENTERLINES
ELECTROFUSE EXISTING
PIPING FROM FIXED PIER TO
NEW 45° HDPE DR11 BEND
EXISTING 3" HDPE
DR11 FW PIPING
NEW 3" HDPE DR11
FW PIPING (TYP)
EXISTING
FIXED PIER
M-501
NOTE: ALLOW ADEQUATE SLACK IN THE FLEXIBLE HOSE FOR
TIDAL MOVEMENT. AVOID FLEXIBLE HOSE SUBMERGING IN
THE WATER WHERE POSSIBLE.
3" HDPE DR11
FW LINE SS CLEVIS
HANGER
1/2" SS
HANGER ROD
ATTACH TO THE
PLATFORM OR
THE GANGWAY
AS NEEDED
REVISION BY DATE
DATE DRAWN:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
CITY PROJECT NO.:
CITY OF CLEARWATER, FLORIDA
ENGINEERING DEPARTMENT
100 S. MYRTLE AVE.
CLEARWATER, FL 33756
CLEARWATER HARBOR MARINA N-E WALKWAY AND GANGWAY
M&N JOB NO.: CHECKED BY:
SHEET REFERENCE NO.
INDEX: OF
100% DESIGN
ISSUED: 2026-04-30
21SUBMITTED BY:
CITY PLAN SET NO.:
23-0030-MA
2023-016
230886-04
M-101
DETAIL: FIRE RISER
SCALE: 1"=1'-0"
M-102
NOTES
1. PIPE SUPPORT SPACING MUST BE A MAXIMUM OF 6FT
FOR 3" PIPING AND 4FT FOR 2" PIPING.
2. PIPE SUPPORTS AND FASTENERS MUST BE 316
STAINLESS STEEL. ALL PIPING MUST BE
ELECTROFUSED PER ASTM F1055.
3. FLOATING DOCK UTILITY ROUTING TO BE
COORDINATED WITH DOCK VENDOR. SHOP DRAWINGS
MUST BE SUBMITTED FOR APPROVAL PRIOR TO
CONSTRUCTION.
4. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION ON CONDUIT LAYOUT.
5. REFER TO STRUCTURAL DRAWINGS FOR ADDITIONAL
GANGWAY AND FLOATING DOCK INFORMATION.
6. REFER TO G-002 FOR TIDAL INFORMATION.
MECHANICAL DETAILS M-501
2026-01-30
KJG
APB
NEL
15NANCY LEHR
M-101
DETAIL: FIRE EXTINGUISHER CABINET
SCALE: NTS
M-101
DETAIL: UTILITY PEDESTAL
SCALE: NTS
1'-0" 0'-0'' 1'-0" 2'-0"
SCALE: 1"=1'-0''
M-101
SECTION: TRANSIENT DOCK TO FIXED PIER TRANSITION
SCALE: 3/8" = 1'-0"
M-101
DETAIL: CLEVIS HANGER
SCALE: NTS
4'-0" 0'-0'' 2'-0" 4'-0"
SCALE: 3/8"=1'-0''
This document has been electronically signed and sealed by Wilfredo J. Ruiz Planell, P.E. on the date adjacent to the seal.
ELECTRICAL GENERAL NOTES
1. GENERAL CONDITIONS:
A. UNDER THIS SECTION THE CONTRACTOR MUST PROVIDE ALL LABOR, MATERIAL, EQUIPMENT, APPURTENANCES, SERVICES AND SUPERVISION FOR A COMPLETE AND OPERATIONAL ELECTRICAL
SYSTEM AS SHOWN ON THE DRAWING. ALL MATERIAL AND EQUIPMENT MUST BE WORKED INTO A
COMPLETE,…