This document is a statement of work for a federal contract to replace pneumatic control systems at the National Center for Cool-Cold Water Aquaculture facility in Leetown, West Virginia. The contractor shall remove thirty-eight existing pneumatic actuators and valves, and install replacement electronic actuators and valves that integrate with the existing Ecostruxure/Schneider Electric building automation system. The contractor shall also remove thirty-eight pneumatic dampener actuators and install replacement electronic dampener actuators, remove all pneumatic supply lines, and commission and test the new electronic control system. The performance period is 180 calendar days. The solicitation was issued by the US Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Northeast Area under solicitation number 12305b23q0082 to replace the aging pneumatic control systems and improve energy efficiency at the National Center for Cool-Cold Water Aquaculture facility.

View the file

Other files for this federal contract opportunity

Other files attached to Replace Pneumatic Control Systems at NCCCWA, newest first.
File Type Posted
RFI 1.docx DOCX document
12305B23Q0082a1.pdf PDF
10.2 mep 1 of 2.pdf PDF
10.0 Prov Clauses - WV Controls.docx DOCX document
10.3 MEP 2 O 2.pdf PDF
10.1 DIVISION 1 22MAR2023 USDA GEN. REQUIREMENTS.pdf PDF
12305B23Q0082.pdf PDF
8.0 WD.txt TXT text file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

National Center for Cool-Cold Water Aquaculture, Leetown, WV

STATEMENT OF WORK

3/23/2023

1.0 BACKGROUND INFORMATION:

Project Title: Replace Pneumatic Control Systems at NCCCWA

Project Location: National Center for Cool-Cold Water Aquaculture

11861 Leetown Road Kearneysville, WV 25430

The mission of the National Center for Cool and Cold-Water Aquaculture (NCCCWA) is to enhance the nation's aquaculture production by developing improved germplasm and technologies that increase farm efficiency, product quality, and environmental sustainability. Research focuses primarily on rainbow trout and encompasses genetics, genomics, physiology, aquatic animal health, and aquaculture engineering.

The building located at 11861 Leetown Road was constructed in 2001. The current pneumatic actuators and controls were installed with the original construction; are approximately twenty (20) years old; and have reached the end of their useful life and need to be replaced with and electronic control system utilizing energy efficient electronic actuators.

The current Building Automation System (BAS) is an Ecostruxure/Schneider Electric System that is only capable of monitoring the current pneumatic actuators in additional to some digital sensors.

The project intent is to replace seventy-six (76) pneumatic actuators with electronically controlled actuators that are fully integrated into the current BAS for a fully functional Environmental Control System.

2.0 STATEMENT OF WORK

2.1 The contractor shall provide all services including all labor, equipment, parts, materials, supplies, supervision, tools, equipment, transportation, and insurance necessary to provide pneumatic conversion over to electronic actuated devices which shall include but not be limited to the following:

2.1.1 Remove thirty-eight (38) Phoenix Valve Controllers with Pneumatic Actuators

2.1.2 Install thirty-eight (38) replacement valves with electronic actuators capable of communicating with the existing BAS.

2.1.3 Install required power source and associated power supply and control wiring to the actuators.

2.1.4 Types of phoenix valves to be replace consist of the following:

• 12x Phoenix Large Dual Valve

• 13x Phoenix Small Dual Valve

• 13x Phoenix Single Units

2.1.5 Contractor to verify quantities of each valve required.

2.1.6 Contractor shall modify existing dampers as required to accommodate the new electronic actuators.

2.2 The contractor shall provide all services including all labor, equipment, parts, materials, supplies, supervision, tools, equipment, transportation, and insurance necessary to provide pneumatic conversion over to electronic actuated devices which shall include but not be limited to the following:

2.2.1 Remove thirty-eight (38) pneumatic actuators on dampeners/louvers for exhaust, supply, and makeup air.

2.2.2 Install thirty-eight (38) dampener/louver electronic actuators capable of communicating with the current BAS.

2.2.3 Install required power source and associated power supply and control wiring to the actuators.

2.2.4 The types of dampener/louver pneumatic actuators to be replaced consists of the following:

• Twenty-six (26) pneumatic actuators on exhaust air dampeners and louvers in rooms: 101 Boiler Room, Fan Room 200/North Laboratory Penthouse, Electrical Room 204, Fan Room 205, Mechanical Room 206/South Laboratory Penthouse, and Mechanical Room 208/Tank Aquaria Penthouse.

• Ten (10) make-up air pneumatic actuators to include rooms: 101 Boiler Room, Fan Room 200/North Laboratory Penthouse, Electrical Room 204, Fan Room 205, Mechanical Room 206/South Laboratory Penthouse, and Mechanical Room 208/Tank Aquaria Penthouse.

• Two (2) pneumatic supply dampener actuators on AHU 1&2 in room Mechanical

Room 206/South Laboratory Penthouse.

• Note: AHU3 does not have a pneumatic supply dampener.

2.3 The contractor shall remove and dispose of all pneumatic supply lines to the actuators within the building including but not limited to a Curtis 80-gallon controls air compressor inside the Boiler Room and any electrical lines, conduit, copper piping and associated hangers and accessories that are not being used under this conversion.

3.0 SYSTEM INTEGRATION

3.1 The Contractor shall commission and startup the new electronic actuators after installation and test system functionality using the current BAS controlling software maintained by Control Systems Inc of Hagerstown, MD.

3.2 The contractor shall demonstrate to location personnel that all electronic control actuators are functioning as intended.

4.0 PERIOD OF PERFORMANCE

Contractor has 180 calendar days to complete the contract from the award/NTP date.

5.0 GENERAL REQUIREMENTS

USDA DIVISION 01 – GENERAL REQUIREMENTS (attached) is part of this Statement of Work.

6.0 KEY PERSONNEL

Name and Address Phone E-Mail Address Contracting Officer (CO) TBD

Contracting Officer Representative (COR)

Shawn Thomas, AFRS 2217 Wiltshire, RD Kearneysville, WV 25430

304-725-3451x344 shawn.thomas@.usda.gov

Engineering Project Manager

(EPM)

Wayne Shekailo, USDA 10300 Baltimore Ave. Bldg. 003/302 Beltsville, MD 20705

301-504-0805 wayne.shekailo@usda.gov

Administrative Officer

(AO)

Stephanie Kreger, AFRS 2217 Wiltshire Rd.

304-725-3451 x 322 stephanie.kreger@usda.gov

Facility Manager (FM)/ Location Monitor (LM)

Shawn Thomas, AFRS 2217 Wiltshire, RD

304-725-3451x344 shawn.thomas@.usda.gov

Safety, Health, & Environmental

Bonnie DiSalvo, USDA 600 E. Mermaid Lane Wyndmoor, PA. 19038

215-233-6592 bonnie.disalvo@usda.gov

Property EBSC Lisa Bynum Claudette Joyner 10300 Baltimore Ave. Bldg. 426A Beltsville MD 20705

301-504-5188 301-504-5221 lisa.bynum@usda.gov claudette.joyner@usda.gov mailto:wayne.shekailo@usda.gov mailto:stephanie.kreger@usda.gov mailto:shawn.thomas@.usda.gov mailto:bonnie.disalvo@usda.gov mailto:lisa.bynum@usda.gov mailto:claudette.joyner@usda.gov

7.0 SITE VISIT

Bidders are strongly encouraged to visit the site of the proposed work and review the existing conditions relating to construction and labor, and to be fully informed as to the facilities involved, and the difficulties and restrictions that may affect the performance of the Contract. Failure to visit the site will not disqualify bidder. However, change order requests for items that could have been reasonable ascertainable from a site visit (and included in a bid) will be reviewed by the Government and evaluated accordingly.

To schedule a site visit contact: Shawn Thomas Facilities Operations Specialist Email: Shawn.thomas@usda.gov Work Number: 681-247-0488.

8.0 PAYMENTS

Payment will be made through the Invoice processing Platform (IPP)

9.0 DELIVERABLES

Redlined Mechanical Drawings Operations and Maintenance Manual

10.0 ATTACHMENTS:

DOL Wage Determination No.: 2015-4285 Revision No 24 Location Building Drawings Images/Pictures Phoenix Valve Information

USDA DIVISION 01- GENERAL REQUIREMENTS

mailto:Shawn.thomas@usda.gov

The building located at 11861 Leetown Road was constructed in 2001. The current pneumatic actuators and controls were installed with the original construction; are approximately twenty (20) years old; and have reached the end of their useful life and ...
The current Building Automation System (BAS) is an Ecostruxure/Schneider Electric System that is only capable of monitoring the current pneumatic actuators in additional to some digital sensors.