NORTH SIDE / SOUTH SIDE COLLECTION SYSTEM ACTUATOR REPLACEMENT Federal contract opportunity
Solicitation number
140R6019R0002
Issued by
Department of the Interior Bureau of Reclamation

About this file

This solicitation seeks replacement of collection system actuators, stems, stem covers, radial gate seals and miscellaneous electrical equipment at multiple locations in Colorado. Work includes replacing actuators and related components at Carter Creek, Mormon Creek, Middle Cunningham Creek, Ivanhoe, Granite Adit, Granite Creek, Fryingpan, No Name Creek, Midway Creek, Hunter Creek, Sawyer, Chapman, and South Fork diversions. Prospective offerors must price individual locations separately in Schedule B. The Bureau of Reclamation is the contracting agency. The window for design data collection runs from mid-July to November 23, 2019, while installation work may begin in mid-July and must be complete by October 31, 2019.

Amendment 002

View the file

Other files for this federal contract opportunity

Other files attached to NORTH SIDE / SOUTH SIDE COLLECTION SYSTEM ACTUATOR REPLACEMENT, newest first.
File Type Posted
Amendment_003_posted.pdf PDF
Amendment_001_(2).pdf PDF
Solicitation_No._140R6019R0002_-_FINAL.pdf PDF
PSN.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(x)

140R6019R0002 x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE RECEIVED AT

THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

Billings MT 59107

R60

PO Box 36900 Regional Office Great Plains Region Bureau of Reclamation

08/28/20190002

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.

Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended,

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

07/19/2019

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not, is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

NORTH SIDE / SOUTH SIDE COLLECTION SYSTEM ACTUATOR REPLACEMENT

FRYINGPAN – ARKANSAS, COLORADO

See attachment for changes incorporated by this amendment:

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

Gerri Voto-Braun

STANDARD FORM 30 (REV. 10-83)

Prescribed by GSA

FAR (48 CFR) 53.243

NSN 7540-01-152-8070

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

x

Solicitation# 140R6019R0002

Amendment No. 0002

Description of Changes:

1. In Part I – The Schedule, Section B – The Schedule, remove Section B – The Schedule in its entirety and substitute therefor the attached Revised Section B – The Schedule.

2. In Part I – The Schedule, Section C – Specifications, remove Section 01 14 12

Work Restrictions in its entirety and substitute therefor the attached Revised Section 01 14 12

Work Restrictions.

3. In Part I – The Schedule, Section C – Specifications, remove 26 05 10 - Conductors and Cables in its entirety and substitute therefor the attached Revised Section 26 05 10 - Conductors and

Cables.

4. In Part I – The Schedule, Section C – Specifications, remove 26 05 20 - Grounding and Bonding in its entirety and substitute therefor the attached Revised Section 26 05 20 - Grounding and

Bonding.

5. In Part I – The Schedule, Section C – Specifications, remove 26 05 33 - Raceways and Boxes for

Elec Sys in its entirety and substitute therefor the attached Revised Section 26 05 33 - Raceways and Boxes for Elec Sys.

6. In Part I – The Schedule, Section C – Specifications, remove 26 21 10 - Miscellaneous Electric

Equipment in its entirety and substitute therefor the attached Revised Section 26 21 10 -

Miscellaneous Electric Equipment

7. In Part I – The Schedule, Section C – Specifications, remove 26 21 13 - Single Throw Disconnect

Switch in its entirety and substitute therefor the attached Revised Section 26 21 13 - Single

Throw Disconnect Switch.

8. In Part I – The Schedule, Section C – Specifications, remove 41 22 32 - Radial Gate Hoists in its entirety and substitute therefor the attached Revised Section 41 22 32 - Radial Gate Hoists.

9. A list of questions from prospective contractors and their respective answers are attached to this amendment and are provided for informational purposes only. Additional answers to questions received will be addressed in a forthcoming amendment. No more questions will be accepted.

For convenience, essential changes on the revised solicitation pages are indicated by a vertical line in the margin where lines or paragraphs changed from the previous version. However, all portions of the revised solicitation pages shall apply whether changes thereon have or have not been indicated.

Acknowledgement: See Block 11 above regarding how to acknowledge this amendment. The

Government must receive the acknowledgement at the place designated for receipt of bids (See Block

10 of the Standard Form 1442).

Closing Date for the Receipt of Proposals- The hour and date for receipt of proposals is hereby extended to 12:00 PM (Mountain Time Zone) on September 04, 2019.

Third Party: If you have given a copy of the solicitation to someone else, please forward this amendment accordingly.

North Side / South Side Amendment No. 0002 Collection System Actuator Replacement Fryingpan – Arkansas, Colorado Solicitation No. 140R6019R0002

Work Restrictions Revised 01 14 12 - 1

SECTION 01 14 12

WORK RESTRICTIONS

PART 1 GENERAL

1.01 MEASUREMENT AND PAYMENT

A. Cost:

1. Include in prices offered in Price Schedules for other items of work.

1.02 WORK RESTRICTIONS

A. Allowable work hours are from 7:00 am to 7:00 pm daily or as approved by the COR.

B. Staging of equipment within close proximity at each diversion site will be allowed.

Contractors shall only use existing roads to access work sites or tunnels. All equipment shall be staged within 25 feet of the work site and no vegetation should be disturbed. No equipment shall be staged in recreation parking or trailhead areas without prior written USFS and Reclamation approval.

C. Fencing of staged equipment is not allowed.

D. Do not interfere with public access to the diversion sites.

E. Available window for the start of design-data-collection work begins approximately the second week of July and extends to November 23, 2019. The Government shall keep the road open to the site(s) – apart from excessive snowfall. Contractor shall be aware that these work locations are subject to extremely variable weather conditions throughout the year.

F. Available window for the start of installation work begins approximately in the second week of July and extends to October 31, and shall be approved by the COR. The Contractor shall be aware that these work locations are subject to extremely variable weather conditions throughout the year. Typically, construction is not feasible after November 1 due to adverse weather conditions that typically exist at many of the sites after that time of year.

G. Contractor shall stage equipment and personnel so that each site can be completed within the construction season it was started.

PART 2 PRODUCTS

Not Used

Fryingpan – Arkansas, Colorado Solicitation No. 140R6019R0002

Work Restrictions

Revised 01 14 12 - 2

PART 3 EXECUTION

END OF SECTION

Revised 01 14 12 - 1

SECTION 01 14 12

WORK RESTRICTIONS

PART 1 GENERAL

1.01 MEASUREMENT AND PAYMENT

A. Cost:

1. Include in prices offered in Price Schedules for other items of work.

1.02 WORK RESTRICTIONS

A. Allowable work hours are from 7:00 am to 7:00 pm daily or as approved by the COR.

B. Staging of equipment within close proximity at each diversion site will be allowed.

Contractors shall only use existing roads to access work sites or tunnels. All equipment shall be staged within 25 feet of the work site and no vegetation should be disturbed. No equipment shall be staged in recreation parking or trailhead areas without prior written USFS and Reclamation approval.

C. Fencing of staged equipment is not allowed.

D. Do not interfere with public access to the diversion sites.

E. Available window for the start of design-data-collection work begins approximately the second week of July and extends to November 23, 2019. The Government shall keep the road open to the site(s) – apart from excessive snowfall. Contractor shall be aware that these work locations are subject to extremely variable weather conditions throughout the year.

F. Available window for the start of installation work begins approximately in the second week of July and extends to October 31, and shall be approved by the COR. The Contractor shall be aware that these work locations are subject to extremely variable weather conditions throughout the year. Typically, construction is not feasible after November 1 due to adverse weather conditions that typically exist at many of the sites after that time of year.

G. Contractor shall stage equipment and personnel so that each site can be completed within the construction season it was started.

PART 2 PRODUCTS

Revised 01 14 12 - 2

PART 3 EXECUTION

Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002

Conductors and Cables

26 05 10 - 1

SECTION 26 05 10

CONDUCTORS AND CABLES

PART 1 GENERAL

1.01 MEASUREMENT AND PAYMENT

A. Carter Creek Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Carter Electrical Equipment.

B. Mormon Creek Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Mormon Creek Electrical Equipment.

C. Middle Cunningham Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Middle Cunningham Electrical Equipment.

D. Ivanhoe Electrical Equipment:

1. Payment: Lump sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing four new enclosed local disconnects.

E. Granite Adit Electrical Equipment:

1. Payment: Lump sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing one new enclosed local disconnects.

F. Granite Creek Electrical Equipment:

1. Payment: Lump sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials for two new enclosed local disconnects.

G. Fryingpan Electrical Equipment:

1. Payment: Lump sum prices offered in Price Schedule B.

26 05 10 - 2

a. Includes cost of furnishing materials and performing work required for installing and testing five new enclosed local disconnects.

H. No Name Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for No Name Electrical Equipment.

I. Midway Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Midway Electrical Equipment.

J. Hunter Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Hunter Electrical Equipment.

K. Sawyer Electrical Equipment:

1. Payment: Lump sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing two new enclosed local disconnects.

L. Chapman Electrical Equipment:

1. Payment: Lump sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing five new enclosed local disconnects.

M. South Fork Electrical Equipment:

1. Payment: Lump sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing five new enclosed local disconnects.

1.02 REFERENCE STANDARDS

A. ASTM International (ASTM)

1. ASTM B 8-11(2017) Concentric-Lay-Stranded Copper

Conductors, Hard, Medium-Hard, or Soft

B. Institute of Electrical and Electronics Engineers (IEEE)

1. IEEE C2-2017 National Electrical Safety Code (NESC)

26 05 10 - 3

C. National Fire Protection Association (NFPA)

1. NFPA 70-2017 National Electrical Code (NEC)

1.03 DESIGN REQUIREMENTS

A. Determine conductor rating based on fused disconnect, gate actuator motor characteristics, and the requirements of NFPA 70.

B. Conductors in good condition and in compliance with NFPA 70 shall be reused.

1.04 SUBMITTALS

A. Submit the following in accordance with Section 01 33 00 - Submittals and Section 01 33 26 - Electrical Drawings and Data.

B. RSN 26 05 10-1, Current Inventory:

1. Inventory of existing wire sizes based on contractor field verification.

C. RSN 26 05 10-2, Calculations:

1. Calculations and recommended conductor sizing.

D. RSN 26 05 10-3, Approval Data:

1. Manufacturer’s data.

E. RSN 26 05 10-4, Test Reports.

1.05 DEFINITIONS

A. Cable: Cable, cables, wire, or wires of one or more insulated conductors.

B. Power Cable: For power loads including receptacle outlets; motors; alternating- and direct-current distribution circuits; heating, ventilating, and air-conditioning and lighting circuits; and cable that is used for controlling heating, ventilating, air-conditioning, and lighting equipment.

C. Control Cable: For control, metering, indication, annunciation, and relaying circuits; and circuits not identified as power circuits.

D. Outdoor Cable: Cable with any portion located outdoors.

1.06 PROJECT CONDITIONS

A. Locations of existing cables indicated on drawings are approximate.

Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002

Conductors and Cables 26 05 10 - 4

PART 2 PRODUCTS

2.01 CABLE

A. Manufactured no more than 24 months prior to Notice to Proceed.

B. Round, except for 2-conductor cable with parallel conductors.

C. Copper conductor: ASTM B 8, class B or C.

D. AWG or kcmil designation.

E. Coverings or insulation: Suitable for installation in vertical position without injury to covering or deformation of insulation when supported in accordance with NFPA 70, article 300-19.

F. Stranded conductors.

G. Cable Color Coding:

1. Three-phase Power Cable:

a. Phase A - Brown.

b. Phase B - Orange.

c. Phase C - Yellow.

2. Control and Instrumentation Cable:

a. In accordance with NEMA WC 57.

b. Colored insulation or jacket compound. Do not apply color coatings to insulation or jacket surface.

H. Conductor Sizes:

1. Determine size of power circuits in accordance with NFPA 70 based on

60 degrees Celsius conductor temperature for sizes No. 1 AWG and smaller and 75 degrees Celsius conductor temperature for sizes No. 1/0 AWG and larger.

2. Determine all other conductor sizes in accordance with: NFPA 70 or use minimum conductor size No. 12 AWG. In event of conflict with NFPA 70 and minimum conductor size, use larger conductor.

2.02 OUTDOOR POWER CABLE

A. Single-conductor or multi-conductor, non-shielded type.

B. UL listed and labeled "UL-TYPE TC" on outer surface per NFPA 70.

C. Suitable for direct burial.

26 05 10 - 5

2.03 MULTICONDUCTOR CONTROL CABLE

A. Suitable for installation in cable trays and conduit, for direct burial, and for general use.

B. Insulation on Individual Conductors:

1. Type XHHW insulation in accordance with NFPA 70.

2. For No. 12 AWG: 30 mils [0.76 millimeter] thick.

C. Binder tape or jacket covering.

D. Shielding: Conform to NEMA WC 57.

E. Overall flame-retardant covering (jacket) of thermoplastic or neoprene: For cable with No. 12 AWG individual conductors, jacket shall be at least 60 mils thick, except 12-conductor cable shall be at least 80 mils thick.

2.04 INSTRUMENTATION CABLE

A. Twisted pair for transducer output circuits and twisted triad for RTD circuits.

B. Suitable for installation in cable trays and conduit, for direct burial, and for general use.

C. Conductor Size: No. 18 AWG.

D. Conductor Insulation: 600 volts and suitable for operation at an ambient temperature of 105 degrees Celsius.

E. Shielding: Copper or aluminum tape which completely covers pair or triad assembly.

Provide shielding with a tinned, stranded copper drain wire.

F. Jacket:

1. Flame-retardant.

2. 600 volts.

2.05 ACCESSORIES

A. Conductor Markers:

1. White.

2. Self-laminating-vinyl type or heat-shrink type.

3. Marked with conductor designation.

4. Computer generated lettering.

B. Cable Tags:

1. Suitable for outdoor use.

26 05 10 - 6

2. Shape: Rectangular.

3. Color: White.

C. Terminal Connectors:

1. Heavy-duty, pre-insulated, pressure-crimp-type with ring tongues.

2. Tin-plated copper.

3. Serrated inner barrel.

4. 600-volt-rated nylon insulation.

5. Insulation support sleeve for vibration resistance.

6. UL listed.

7. Compatible with conductor size and type of cable for which it is used.

PART 3 EXECUTION

3.01 INSTALLATION

A. Comply with NFPA 70 and IEEE C2.

B. Install cable without exceeding allowable pulling tensions and sidewall pressures recommended by cable manufacturer.

C. Do not splice multiconductor control cables.

D. Buried cables within fenced yards.

1. Install in accordance with standard drawing 40-D-5370.

E. Buried cables not within fenced yard areas.

1. Depth: 24 inches, minimum.

2. Install by trenching method. Do not plow cables in.

3. Surround cables by 2 inches of sand, minimum.

4. Install polyethylene warning tape 18 inches above cable.

F. Conduit Installation:

1. Do not pull cable into conduits until conduit runs have been cleaned and are free from obstructions and sharp corners.

2. Draw a clean, dry, tight-fitting rag through conduit immediately before installing cable.

3. Install cable to prevent cuts or abrasions in insulation or protective covering, or kinks in cable.

26 05 10 - 7

4. Block cable opening in sleeves under equipment or passing through blockouts, with silicone-foam, fire-retardant type material in accordance with NFPA 70.

5. Lubricant:

a. Use only as aid to pulling.

b. Soapstone or other suitable material not injurious to cable sheath.

G. Grounding:

1. Provide one nonactive conductor grounded at both ends in each non-twisted pair shielded control cable. Ground shielding of each shielded control cable on both ends directly to equipment ground bus by method indicated on standard drawing 40-D-4335, Figure 8.

2. Ground shielding of twisted pair shielded cables only to source equipment ground bus using pressure crimp type connectors with ring tongues on drain wire.

3. Ground spare conductors by wire jumpers from equipment terminal block points to equipment ground bus.

H. Marking:

1. Mark conductors, whether single-conductor cables or individual conductors of multiconductor control, instrumentation, and power cables at each end with conductor designation on first line followed by cable designation on second line as indicated on approved wiring diagrams.

2. Mark spare conductors of multiconductor cables with cable designation and word

"SPARE".

3. Numerically sequence markings (e.g., 2CSA-CSB-SPARE1).

I. Spare Conductors:

1. Provide spare conductors in accordance with Government-furnished information marked on Contractor's approval wiring diagram drawings.

J. Tagging:

1. Tag multiconductor cables at each end.

2. Attach tags to cable by self-locking cable ties.

3. Mark tags with cable designation.

a. Cable designations: As indicated on approved wiring diagrams.

b. Provide computer-generated lettering.

K. Terminate control and instrumentation wire with terminal connectors.

L. Wiring Methods:

26 05 10 - 8

1. Form conductors into neat packs, or lace conductors, or tie conductors with self-locking cable ties at termination point of multiconductor cable.

2. Do not combine alternating- and direct-current circuits, or current and potential transformer circuits in same multiconductor cable.

3. Support cable installed in a vertical or inclined plane by cable grips (including hooks). Installed cable with slack spans between supports.

4. Clamp cable entering equipment with commercial type cable clamps.

5. Leave sufficient length cable ends to make connections conveniently to equipment, fixtures, and devices.

6. Retain spare single conductors at each end of a multiconductor cable in a length equal to longest single conductor of multiconductor cable.

7. Run both positive and negative leads of a circuit in same cable.

3.02 CONTRACTOR FIELD QUALITY TESTING

A. Perform testing after installation, but before connection to equipment.

B. Test cables in large groups to minimize number of testing sessions.

C. Notify COR, in writing, of date, time, and cables to be tested at least 5 working days before testing.

D. Perform following tests:

1. Insulation resistance tests for power, control, and instrumentation cables;

a. Measure insulation resistance between each conductor and station ground with all other conductors in same cable or conduit grounded.

b. Test voltage: 1,000 volts direct-current, minimum.

c. Minimum acceptable insulation resistance: R in MΩ = (rated voltage in kV + 1) x 1000/length in ft.

d. Record following test data on test report for each conductor tested:

1) Date of test.

2) Name or names of Contractor's personnel who performed test.

3) Name of Government inspector who witnessed test.

4) Conductor identification.

5) Megohms between conductor and ground.

6) Total length of conductor.

Grounding and Bonding

26 05 20 - 1

SECTION 26 05 20

GROUNDING AND BONDING

PART 1 GENERAL

1.01 MEASUREMENT AND PAYMENT

A. Carter Creek Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Carter Electrical Equipment.

B. Mormon Creek Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Mormon Creek Electrical Equipment.

C. Middle Cunningham Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Middle Cunningham Electrical Equipment.

D. Ivanhoe Grounding and Bonding for Electrical Systems:

1. Cost:

a. Include cost in prices offered in Price Schedule B for Ivanhoe Electrical Equipment.

E. Granite Adit Grounding and Bonding for Electrical Systems:

1. Cost:

a. Include cost in prices offered in Price Schedule B for Granite Adit Electrical Equipment.

F. Granite Creek Grounding and Bonding for Electrical Systems:

1. Cost:

a. Include cost in prices offered in Price Schedule B for Granite Creek Electrical Equipment.

G. Fryingpan Grounding and Bonding for Electrical Systems:

1. Cost:

26 05 20 - 2

a. Include cost in prices offered in Price Schedule B for Fryingpan Electrical Equipment.

H. No Name Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for No Name Electrical Equipment.

I. Midway Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Midway Electrical Equipment.

J. Hunter Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Hunter Electrical Equipment

K. Sawyer Grounding and Bonding for Electrical Systems:

1. Cost:

a. Include cost in prices offered in Price Schedule B for Sawyer Electrical Equipment.

L. Chapman Grounding and Bonding for Electrical Systems:

1. Cost:

a. Include cost in prices offered in Price Schedule B for Chapman Electrical Equipment.

M. South Fork Grounding and Bonding for Electrical Systems:

1. Cost:

a. Include cost in prices offered in Price Schedule B for South Fork Electrical Equipment.

1.02 REFERENCE STANDARDS

A. ASTM International (ASTM)

1. ASTM B 3-13(2018) Soft or Annealed Copper Wire

2. ASTM B 8-11(2017) Concentric-Lay-Stranded Copper

Conductors, Hard, Medium-Hard, or Soft

26 05 20 - 3

3. ASTM B 228-11a(2016) Concentric-Lay-Stranded Copper-Clad Steel Conductors

B. Institute of Electrical and Electronic Engineers (IEEE)

1. IEEE 837-2014 Qualifying Permanent Connections Used in

Substation Grounding

2. IEEE C2-2017 National Electrical Safety Code (NESC)

C. National Fire Protection Association (NFPA)

1. NFPA 70-2017 National Electric Code (NEC)

1.03 SUBMITTALS

A. Submit the following in accordance with Section 01 33 00 – Submittals and 01 33 26 – Electrical Drawings and Data.

B. RSN 26 05 20-1, As-built Drawings:

1. Specifications drawings indicating “as-built” changes made to grounding systems.

1.04 PROJECT CONDITIONS

A. Locations of existing ground conductors indicated on drawings are approximate.

PART 2 PRODUCTS

2.01 MATERIALS

A. Ground Cable:

1. Annealed Bare-copper Cable:

a. ASTM B 8, class B.

b. Solid wires used in forming the copper cable: ASTM B 3.

2. Copper-clad Steel Cable: ASTM B 228.

3. Concentric stranded.

4. Sizes:

a. As indicated on drawings.

b. Where not shown, minimum sizes:

1) Ground risers and electrode conductors: 4/0 AWG.

2) Equipment grounding conductors:

a) Major equipment: Equal to size to electrode conductors.

26 05 20 - 4

b) Minor equipment: No. 4 AWG

3) Equipment ground ring bus: Equal in size to largest riser.

4) Electrode interconnecting conductors: Equal in size to electrode conductors.

2.02 ACCESSORIES

A. Cable Connectors:

1. Welded, bolted solderless or compression type.

2. Current-carrying capacity: Equal to cable with which they are used.

3. Connectors for ground cables, including fittings, lugs, bolts, nuts, and washers:

Copper alloy containing not more than 4 percent zinc.

4. Bolted solderless or compression type connectors: IEEE 837.

5. Ground connectors that will be direct buried or embedded in concrete: Listed for direct burial use in accordance with the requirements of UL 467.

2.03 WELDING PROCESS

A. Use Cadweld, Thermoweld, or equivalent exothermic process.

B. Molds and Weld Metal:

1. Use fresh stock from same manufacturer.

2. Weld metal and starting material: No significant quantities of hazardous ingredients.

PART 3 EXECUTION

3.01 INSTALLATION

A. Install in accordance with NFPA 70, IEEE C2, and this Section.

B. Connect equipment, metal conduit, steel structures, metal pull box covers, exposed metal surfaces, and other miscellaneous metalwork to grounding system as indicated on standard drawings 40-D-4334, 40-D-4335, 40-D-4753; and as shown on specification drawings.

C. Ground equipment and miscellaneous metalwork that is required to be grounded, but is not indicated on drawings to grounding system.

D. Connections:

26 05 20 - 5

1. Make all ground connections between equipment and miscellaneous metalwork, and ground plates of grounding system whether or not such grounding connections are indicated on drawings.

2. Number of grounding connections for equipment may be one, two, or more in some cases.

3. Remove paint, enamel, scale, oil, grease, or other foreign nonconductive material from point of contact on metal surfaces before making ground connections.

4. Repair damaged or removed paint or galvanizing material on metal finishes.

5. Make ground connections that will be direct buried or embedded in concrete:

a. Exothermic process.

b. In accordance with manufacturer's instructions.

26 05 20 - 6

This page intentionally left blank.

Fryingpan - Arkansas – Colorado Solicitation No.

Raceways and Boxes for Electrical Systems

Revised 26 05 33 - 1

SECTION 26 05 33

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

PART 1 GENERAL

1.01 MEASUREMENT AND PAYMENT

A. Carter Creek Raceways and Boxes for Electrical Systems .

1. Cost:

a. Include cost in prices offered in Price Schedule B for Carter Creek Electrical Equipment.

B. Mormon Creek Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Mormon Creek Electrical Equipment.

C. Middle Cunningham Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Middle Cunningham Electrical Equipment.

A. Ivanhoe Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Ivanhoe Electrical Equipment.

B. Granite Adit Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Granite Adit Electrical Equipment.

C. Granite Creek Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Granite Creek Electrical Equipment.

D. Fryingpan Raceways and Boxes for Electrical Systems.

Fryingpan - Arkansas – Colorado Solicitation No.

Raceways and Boxes for Electrical Systems Revised 26 05 33 - 2

a. Include cost in prices offered in Price Schedule B for Fryingpan Electrical Equipment.

E. No Name Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for No Name Electrical Equipment.

F. Midway Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Midway Electrical Equipment.

G. Hunter Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Hunter Electrical Equipment.

H. Sawyer Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Sawyer Electrical Equipment.

I. Chapman Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Chapman Electrical Equipment.

J. South Fork Raceways and Boxes for Electrical Systems.

1. Cost:

a. Include cost in prices offered in Price Schedule B for South Fork Electrical Equipment.

1.02 REFERENCE STANDARDS

A. American National Standards Institute (ANSI):

1. ANSI C80.1-2015 Electric Rigid Steel Conduit (ERSC) B. National Electrical Manufacturers Association (NEMA):

1. NEMA FB 1-2014 Fittings, Cast Metal Boxes, And Conduit Bodies For Conduit, Electrical Metallic Tubing And Cable

Revised 26 05 33 - 3

C. National Fire Protection Association, Inc. (NFPA):

1. NFPA 70-2017 National Electric Code (NEC)

D. Underwriters Laboratories (UL):

1. UL 360-2013 Liquid-Tight Flexible Steel Conduit

1.03 DESIGN REQUIREMENTS

A. Contractor to determine routing of conduit.

B. Conduit in good condition and in compliance with NFPA 70 shall be reused.

1.04 SUBMITTALS

A. Submit the following in accordance with Section 01 33 00 - Submittals.

B. RSN 26 05 33-1, Product Data:

1. Manufacturer’s catalog data.

PART 2 PRODUCT

2.01 CONDUIT

A. General:

1. UL listed.

2. Sized per NFPA 70.

B. Rigid Steel Conduit and Attached Fittings:

1. Zinc-coated and in accordance with ANSI C 80.1.

C. Liquidtight Flexible Metal Conduit (LFMC):

1. Galvanized interlocked steel construction with flame-retardant PVC jacket, with Liquidtight connectors.

2. Color: Silver or Grey.

3. IP67 rated or better.

4. Conform to NFPA 70 and UL 360.

5. Fittings conform to NEMA FB 1.

Revised 26 05 33 - 4

2.02 ACCESSORIES

A. Fittings required to complete electrical conduit systems. Includes, caps, connectors, couplings (excluding expansion and expansion-deflection couplings), nipples, reducers, elbows, pipe plugs, locknuts, bondnuts, and any other fittings.

B. Devices required to fasten, clamp, attach, and support conduit in place. Includes supports and clamps complete with bolts, washers, and nuts.

C. Locknuts and Bushings:

1. Locknuts: Steel. Die cast locknuts are not acceptable.

2. Bushings: Insulated and pressure cast or malleable iron. Grounding bushing to be lay-in saddle type.

D. Thread Lubricant: Lithium, graphite, or zinc based material designed to inhibit corrosion and to lubricate metal-to-metal joints.

PART 3 EXECUTION

3.01 GENERAL

A. Install in accordance with NFPA 70.

B. Remove burrs and sharp corners at ends of metal conduit.

C. Coat male threads of metal conduit joints with suitable graphite or zinc sealing material before making joints.

D. Tighten conduit joints securely to ensure electrical continuity and to prevent entrance of moisture or foreign material.

E. Install with necessary fittings and supports.

F. Tighten conduit to electrical equipment mounted on tubular metal structures securely and support rigidly in place by conduit clamps, hex head nuts, and threaded 3/8-inch stud fasteners driven by powder-actuated tools.

G. Exposed Conduit Runs:

1. Straight and parallel with each other and with centerlines of room or structure.

2. Support conduit rigidly in place and in accordance with NFPA 70. Do not weld conduit to conduit supports or structural steel.

H. Liquid tight Flexible Metal Conduit:

1. Use flexible conduit for connections to equipment that is subject to vibration, where flexibility is required or where shown, in accordance with NFPA 70.

Revised 26 05 33 - 5

2. Maximum length of a flexible conduit section is not to exceed 48 inches.

I. Conduit Terminations:

1. Install bushings or chase-type nipples on ends of conduit to protect insulation of insulated conductors from abrasion.

2. Install locknuts and bond nuts to provide tight ground connections between conduit and boxes, panel boards, and cabinets.

Revised 26 05 33 - 6

Miscellaneous Electrical Equipment

26 70 10 - 1

SECTION 26 70 10

MISCELLANEOUS ELECTRICAL EQUIPMENT

PART 1 GENERAL

1.01 MEASUREMENT AND PAYMENT

A. Carter Creek Miscellaneous Electrical Equipment.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Carter Creek Electrical Equipment.

B. Mormon Creek Miscellaneous Electrical Equipment.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Mormon Creek Electrical Equipment.

C. Middle Cunningham Miscellaneous Electrical Equipment.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Middle Cunningham Electrical Equipment.

A. Ivanhoe Miscellaneous Electrical Equipment.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Ivanhoe Electrical Equipment.

B. Granite Adit Miscellaneous Electrical Equipment.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Granite Adit Electrical Equipment.

C. Granite Creek Miscellaneous Electrical Equipment.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Granite Creek Electrical Equipment.

D. Fryingpan Miscellaneous Electrical Equipment.

Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002

Miscellaneous Electrical Equipment 26 70 10 - 2

a. Include cost in prices offered in Price Schedule B for Fryingpan Electrical Equipment.

D. No Name Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for No Name Electrical Equipment.

E. Midway Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Midway Electrical Equipment.

F. Hunter Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Hunter Electrical Equipment.

E. Sawyer Miscellaneous Electrical Equipment.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Sawyer Electrical Equipment.

F. Chapman Miscellaneous Electrical Equipment.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Chapman Electrical Equipment.

G. South Fork Miscellaneous Electrical Equipment.

1. Cost:

a. Include cost in prices offered in Price Schedule B for South Fork Electrical Equipment.

1.02 REFERENCES STANDARDS

A. National Electrical Manufacturers Association (NEMA)

1. NEMA 250 -2018 Enclosures for Electrical Equipment

2. NEMA FU 1-2012 Low Voltage Cartridge Fuses

3. NEMA KS 1-2013 Heavy Duty Enclosed and Dead-Front

Switches (600 Volts Maximum)

26 70 10 - 3

B. National Fire Protection Association, Inc. (NFPA)

1. NFPA 70-2017 National Electrical Code (NEC)

1.03 DESIGN REQUIREMENTS

A. Determine disconnect switch and fuse ratings based on gate actuator motor characteristics and the requirements of NFPA 70.

B. Replacement disconnect switch to be affixed to the existing support structure.

1.04 SUBMITTALS

A. Submit in accordance with Section 01 33 00 - Submittals and Section 01 33 26 - Electrical Drawings and Data.

G. RSN 26 70 10-1 Inventory of Existing Fuse and Wire Sizing:

1. Based on contractor field verification from site visit.

H. RSN 26 70 10-2 Approval Data:

1. Manufacturer’s technical data.

2. Calculations and recommended disconnect fuse sizing based on approved inventory.

PART 2 PRODUCTS

1.05 ENCLOSED LOCAL DISCONNECT

A. Use: Local disconnect for gate actuator.

A. Type: Heavy-duty industrial, single throw, three-pole, fused disconnect.

B. Enclosure:

1. Type 4X in compliance with NEMA 250 with hinged door.

2. Padlockable door.

3. Furnished with hubs and equipment ground lugs.

4. 316 type stainless steel.

C. Voltage Rating:

1. 240 volts, 60Hz for 208 volt 60 Hz supplied gate actuators.

2. 600 volts, 60Hz for 460 volt, 60Hz supplied actuators.

26 70 10 - 4

D. Current Rating: Sized based on gate actuator motor characteristics and in compliance with NFPA 70 - 2014.

E. Switch Mechanism/Handle:

1. Switch Operating Mechanism: Made from 316 type stainless steel, with no plastic parts.

2. Switch Operating Handle:

a. Integral part of the switch enclosure. Use of cover as disconnect device is not acceptable.

b. Made from 316 type stainless steel, with no plastic parts other than handle grip.

c. Have provisions for padlocking in the ON position.

d. Have provisions for padlocking in the OFF position.

F. Switch Cover Interlock:

1. Prevent unintentional opening of switch cover when switch is ON.

2. Prevent closing switch with switch cover open.

G. Current Carrying Parts: Plated to resist corrosion.

H. Fuses:

3. Current limiting type suitable for local motor disconnect.

4. Voltage rating: Sized based on gate actuator characteristics.

5. Current rating: Sized based on gate actuator characteristics.

B. Spring reinforced fuse clips.

C. Disconnect switch to conform to NEMA KS 1 and UL listed.

D. Fuses conform to NEMA FU 1 and UL listed.

PART 3 EXECUTION

1.06 INSTALLATION

A. Install equipment and devices in accordance with manufacturer’s instructions and recommendations.

B. Local motor disconnects:

1. Installed at the approximate location of the existing switch.

2. Grounding cable: Attached to the ground lug.

26 70 10 - 5

C. Make electrical conduit and cable connections.

D. Make grounding and bonding connections in accordance with NFPA 70.

26 70 10 - 6

Single Throw Disconnect Switch

Revised 26 21 13 - 1

SECTION 26 21 13

SINGLE THROW DISCONNECT SWITCH

PART 1 GENERAL

1.01 MEASUREMENT AND PAYMENT

A. Carter Creek Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Carter Creek

Electrical Equipment.

B. Mormon Creek Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Mormon Creek Electrical Equipment.

C. Middle Cunningham Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Middle Cunningham Electrical Equipment.

D. Ivanhoe Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Ivanhoe Electrical Equipment.

E. Granite Adit Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Granite Adit Electrical Equipment.

F. Granite Creek Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Granite Creek Electrical Equipment.

G. Fryingpan Single Throw Disconnect Switch.

Revised 26 21 13 - 2

a. Include cost in prices offered in Price Schedule B for Fryingpan Electrical Equipment.

H. No Name Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for No Name Electrical Equipment.

I. Midway Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Midway Electrical Equipment.

J. Hunter Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Hunter Electrical Equipment.

K. Sawyer Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Sawyer Electrical Equipment.

L. Chapman Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for Chapman Electrical Equipment.

M. South Fork Single Throw Disconnect Switch.

1. Cost:

a. Include cost in prices offered in Price Schedule B for South Fork Electrical Equipment.

1.02 REFERENCES

A. National Electrical Manufacturers Association (NEMA)

1. NEMA 250 -2018 Enclosures for Electrical Equipment

2. NEMA FU 1-2012 Low Voltage Cartridge Fuses

3. NEMA KS 1-2013 Heavy Duty Enclosed and Dead-Front

Switches (600 Volts Maximum)

Revised 26 21 13 - 3

B. National Fire Protection Association, Inc. (NFPA)

1. NFPA 70-2017 National Electrical Code (NEC)

1.03 DESIGN REQUIREMENTS

A. Determine disconnect switch and fuse ratings based on gate actuator motor characteristics and the requirements of NFPA 70.

B. Replacement disconnect switch to be affixed to the existing support structure.

1.04 SUBMITTALS

A. Submit in accordance with Section 01 33 00 - Submittals and Section 01 33 26 - Electrical Drawings and Data.

B. RSN 26 70 10-1, Current Inventory

1. Inventory of existing fuses based on contractor field verification.

C. RSN 26 70 10-2, Calculations

2. Calculations and recommended fuse sizing.

D. RSN 26 70 10-3, Approval Data:

1. Manufacturer’s technical data.

1.05 LIST OF DIVERSIONS WITH DISCONNECTS

A. Below is a list of diversions with number of single throw disconnect switches to be replaced.

Diversion Number of Single Throw Disconnects to be Replaced

Carter Creek 1

Mormon Creek 1

Middle Cunningham 1

Ivanhoe 4

Granite Adit 1

Granite Creek 2

Revised 26 21 13 - 4

Fryingpan 5

No Name 1

Midway 1

Hunter 1

Sawyer 2

Chapman 5

South Fork 5

PART 2 PRODUCTS

2.01 ENCLOSED LOCAL FUSED DISCONNECT

A. Use: Local disconnect for gate actuator.

B. Type: Heavy-duty industrial, single throw, three-pole, fused disconnect.

C. Enclosure:

1. Type 4X in compliance with NEMA 250 with hinged door.

2. Padlockable door.

3. Furnished with hubs and equipment ground lugs.

4. 316 type stainless steel.

D. Voltage Rating:

1. 240 volts, 60Hz for 208 volt, 60 Hz supplied gate actuators.

2. 600 volts, 60Hz for 460 volt, 60Hz supplied actuators.

E. Current Rating: Sized based on gate actuator motor characteristics and in compliance with NFPA 70 - 2014.

F. Switch Mechanism/Handle:

1. Switch Operating Mechanism: Made from 316 type stainless steel, with no plastic parts.

2. Switch Operating Handle:

Revised 26 21 13 - 5

a. Integral part of the switch enclosure. Use of cover as disconnect device is not acceptable.

b. Made from 316 type stainless steel, with no plastic parts other than handle grip.

c. Have provisions for padlocking in the ON position.

d. Have provisions for padlocking in the OFF position.

G. Switch Cover Interlock:

1. Prevent unintentional opening of switch cover when switch is ON.

2. Prevent closing switch with switch cover open.

H. Current Carrying Parts: Plated to resist corrosion.

I. Fuses:

3. Current limiting type suitable for local motor disconnect.

4. Voltage rating: Sized based on gate actuator characteristics.

5. Current rating: Sized based on gate actuator characteristics.

J. Spring reinforced fuse clips.

K. Disconnect switch to conform to NEMA KS 1 and UL listed.

L. Fuses conform to NEMA FU 1 and UL listed.

PART 3 EXECUTION

3.01 INSTALLATION

A. Install equipment and devices in accordance with manufacturer’s instructions and recommendations.

B. Local motor disconnects:

1. Installed at the approximate location of the existing switch.

2. Grounding cable: Attached to the ground lug.

C. Make electrical conduit and cable connections.

D. Make grounding and bonding connections in accordance with NFPA 70.

Revised 26 21 13 - 6

Radial Gate Hoists

Revised 41 22 32 - 1

SECTION 41 22 32

RADIAL GATE HOISTS

PART 1 GENERAL

1.01 MEASUREMENT AND PAYMENT

A. Carter Creek Radial Gate Hoist:

1. Payment: Lump-sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing one new hoist brakemotor and hoist limit switch.

b. Includes cost of determining required mounting flange and output shaft adaptor to insure new hoist brakemotor functions with existing gear box.

B. Mormon Creek Radial Gate Hoist:

1. Payment: Lump-sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing one new hoist brakemotor and hoist limit switch.

b. Includes cost of determining required mounting flange and output shaft adaptor to insure new hoist brakemotor functions with existing gear box.

C. Middle Cunningham Radial Gate Hoist:

1. Payment: Lump-sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing one new hoist brakemotor and hoist limit switch.

b. Includes cost of determining required mounting flange and output shaft adaptor to insure new hoist brakemotor functions with existing gear box.

D. No Name Radial Gate Hoist:

1. Payment: Lump-sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing one new hoist gear brakemotor and hoist limit switch.

b. Includes cost of determining required mounting to existing base and output shaft to insure new hoist gear brakemotor functions with existing output shaft connection.

E. Midway Radial Gate Hoist:

1. Payment: Lump-sum prices offered in Price Schedule B.

Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002

Radial Gate Hoists Revised 41 22 32 - 2

a. Includes cost of furnishing materials and performing work required for installing and testing one new hoist gear brakemotor and hoist limit switch.

b. Includes cost of determining required mounting to existing base and output shaft to insure new hoist gear brakemotor functions with existing output shaft connection.

F. Hunter Radial Gate Hoist:

1. Payment: Lump-sum prices offered in Price Schedule B.

a. Includes cost of furnishing materials and performing work required for installing and testing one new hoist gear brakemotor and hoist limit switch.

b. Includes cost of determining required mounting to existing base and output shaft to insure new hoist gear brakemotor functions with existing output shaft connection.

1.02 DESCRIPTION

A. Where the singular is used in reference to the hoists, features thereof, or any associated equipment or structures, such reference includes, if applicable, all hoists, or all such equipment or features.

B. Principal components of work to be performed under this paragraph are as follows:

1. Furnishing, installing, and testing one hoist brakemotor and one hoist limit switch on each of the following locations’ hoists:

a. Carter Creek Diversion Dam.

b. Middle Cunningham Creek Diversion Dam.

c. Mormon Creek Diversion Dam.

2. Furnishing, installing, and testing one hoist gear brakemotor and one hoist limit switch on each of the following locations’ hoists:

a. Hunter Creek Diversion Dam.

b. Midway Creek Diversion Dam.

c. No Name Creek Diversion Dam.

3. Coat appurtenant hoist equipment with manufacturer’s standard industrial outdoor coatings.

1.03 REFERENCE STANDARDS

A. American Gear Manufacturers Association (AGMA)

1. AGMA 6034-B92(R2010) Enclosed Cylindrical Wormgear Speed

Reducers and Gearmotors

Revised 41 22 32 - 3

B. American Institute of Steel Construction (AISC)

1. AISC 325-17 Steel Construction Manual

C. ASTM International (ASTM)

1. ASTM A48/A48M-03(2016) Gray Iron Castings

2. ASTM A148/A148M-15a Steel Castings, High Strength, for Structural

Purposes

3. ASTM A290/A290M-16 Carbon and Alloy Steel Forgings for Ring for Reduction Gears

4. ASTM A291/A291M-16a Steel Forgings, Carbon and Alloy, for

Pinions, Gears and Shafts for Reduction Gears

5. ASTM F3125/F3125M-15a High Strength Structural Bolts, Steel and Alloy Steel, Heat Treated, 120 ksi and 150 ksi Minimum Tensile Strength

6. ASTM A513/A513M-15 Electric-Resistance-Welded Carbon and Alloy Steel Mechanical Tubing

7. ASTM A519/A519M-17 Seamless Carbon and Alloy Steel Mechanical Tubing

8. ASTM A563-15 Carbon and Alloy Steel Nuts

9. ASTM A572/A572M-15 High-Strength Low-Alloy Columbium-

Vanadium Structural Steel

10. ASTM A992/A992M-11(2015) Structural Steel Shapes

11. ASTM A1011/A1011M-17 Steel, Sheet and Strip, Hot-Rolled Carbon, Structural, High-Strength Low-Alloy, High- Strength Low-Alloy with Improved Formability, and Ultra-High Strength

12. ASTM F436-11 Hardened Steel Washers

D. American Welding Society, Inc. (AWS)

1. AWS D1.1/D1.1M-15 Structural Welding Code - Steel

E. Code of Federal Regulations (CFR)

1. 29 CFR Part 1910 Occupational Safety and Health Standards

F. Crane Manufacturers Association of America (CMAA)

1. CMAA 70-15 Top Running Bridge and Gantry Type

Multiple Girder Electric Overhead Traveling Cranes

Revised 41 22 32 - 4

G. National Electrical Manufactures Association (NEMA)

1. NEMA 250-14 Enclosures for Electrical Equipment (1000

Volts Maximum)

2. NEMA MG 1-16 Motors and Generators

H. National Fire Protection Association (NFPA)

1. NFPA 70-17 National Electrical Code (NEC)

1.04 SUBMITTALS

A. General:

1. Data and drawings:

a. In accordance with Section 01 33 00 – Submittals.

b. Drawings signed and dated with title blocks designating a unique drawing number and drawing title, including revision number and date.

Distinguish between each of the installations.

c. Drawings prepared by computer-aided drafting only.

2. Indicate differences, (dimensions, sizes, etc.), in the data at each location, as applicable.

B. RSN 41 22 32-1, Approval Data:

1. Calculations:

a. Design and sizing calculations verifying choice of components and equipment, including motors and gear reducers. Include design considerations and list of reference publications and standards:

1) Sizing and gear reduction calculations for limit switches.

2. Drawings:

a. Mounting adaptors: Complete layout, dimensions, assembly and details of motor and/or switch mounting adaptors as needed. Provide connection details, including dimensions, bolt patterns, bolt sizes, and reinforcement.

b. Checked shop drawings: Show dimensions, weld sizes, and materials of the mounting adaptors. Include details of the mounting assemblies and brackets for the instrumentation assemblies, (limit switch and associated drive assemblies).

c. Electrical Schematics and Wiring Diagrams.

3. Commercial Products Data – Provide dimensional and rating data. Mark data sheets to indicate specific make, model number and features of equipment to be furnished:

a. Electric…