Amendment_001_(2).pdf
PDF 5 MB Posted
- Attached to
- NORTH SIDE / SOUTH SIDE COLLECTION SYSTEM ACTUATOR REPLACEMENT Federal contract opportunity
- Solicitation number
- 140R6019R0002
About this file
This solicitation is for the replacement of collection system actuators, stems, stem covers, and miscellaneous electrical equipment at multiple locations within the North Side/South Side Collection System of the Fryingpan-Arkansas Project in Colorado. Work will involve site inspections, engineering design, removal and disposal of existing features, and installation of new actuators, stems, stem guides, and electrical components. The Bureau of Reclamation is the contracting agency. Pricing will be based on lump sum bids for site inspections and installation work at each of the locations listed. The solicitation number is 140R6019R0002 and responses are due by August 29, 2019.
Not Listed
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment_003_posted.pdf | ||
| SF30.pdf | ||
| Solicitation_No._140R6019R0002_-_FINAL.pdf | ||
| PSN.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(x)
140R6019R0002 x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE RECEIVED AT
THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
Billings MT 59107
R60
PO Box 36900 Regional Office Great Plains Region Bureau of Reclamation
08/19/20190001
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.
Items 8 and 15, and returning
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended,
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
FACILITY CODE CODE
10B. DATED (SEE ITEM 13)
10A. MODIFICATION OF CONTRACT/ORDER NO.
9B. DATED (SEE ITEM 11)
9A. AMENDMENT OF SOLICITATION NO.
CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY
PAGE OF PAGES
4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)
1. CONTRACT ID CODE
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
07/19/2019
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority) appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
E. IMPORTANT: Contractor is not, is required to sign this document and return __________________ copies to the issuing office.
ORDER NO. IN ITEM 10A.
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED
(Signature of person authorized to sign) (Signature of Contracting Officer)
Gerri Voto-Braun
STANDARD FORM 30 (REV. 10-83)
Prescribed by GSA
FAR (48 CFR) 53.243
NSN 7540-01-152-8070
Previous edition unusable
Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .
NORTH SIDE / SOUTH SIDE
COLLECTION SYSTEM ACTUATOR REPLACEMENT
FRYINGPAN – ARKANSAS, COLORADO
See attachment for changes incorporated by this amendment:
X
Solicitation# 140R6019R0002
Amendment No. 0001
Description of Changes:
1. In Part I – The Schedule, Section C – Specifications, remove 01 14 13 - Site Access in its entirety and substitute therefor the attached Revised 01 14 13 - Site Access.
2. In Part I – The Schedule, Section C – Specifications, remove 35 22 10 - Slide Gates Actuators and Stems in its entirety and substitute therefor the attached Revised 35 22 10 - Slide Gates
Actuators and Stems.
For convenience, essential changes on the revised solicitation pages are indicated by a vertical line in the margin where lines or paragraphs changed from the previous version. However, all portions of the revised solicitation pages shall apply whether changes thereon have or have not been indicated.
Acknowledgment: See Block 11 above regarding how to acknowledge this amendment. The
Government must receive the acknowledgment at the place designated for receipt of bids (See Block
10 of the Standard Form 1442).
Closing Date for the Receipt of Proposals- The hour and date for receipt of proposals is hereby extended to 12:00 PM (Mountain Time Zone) on August 29, 2019.
Third Party: If you have given a copy of the solicitation to someone else, please forward this amendment accordingly.
The Government is providing the Site Visit Attendance Records from the organized site visit, which was held on July 31, 2019 and August 01, 2019, at 10:00 AM Mountain Time Zone For informational purposes only.
A list of questions from prospective contractors and their respective answers are attached to this amendment and are provided for informational purposes only. Additional answers to questions received will be addressed in a forthcoming amendment.
A Map showing drive times between the sites is attached to this amendment.
North Side / South Side Amendment No. 001 Collection System Actuator Replacement Fryingpan – Arkansas, Colorado Solicitation No. 140R6019R0002
Site Access 01 14 13 - 1
SECTION 01 14 13
SITE ACCESS
PART 1 GENERAL
1.01 MEASUREMENT AND PAYMENT
A. Cost:
1. Include in prices offered in Price Schedules for other items of work.
1.02 SUBMITTALS
A. Submit the following in accordance with Section 01 33 00 - Submittals.
B. RSN 01 14 13-1, Site Access Plan
1. Describe plans, methods, equipment, and frequency used to access work site locations from approved Contractor use and staging areas.
1.03 PROJECT CONDITIONS
A. Access to work site locations varies from location to location. All necessary tunnel-entry clearance shall be in place prior to contractor entry. The following are work locations and the site accessibility as last known to the Government:
1. Carter Creek Diversion Site
a. Approximate coordinates: 39.3664°N, -106.5442°W
b. Approximate elevation: 10,121 feet
c. Located along Carter Creek in White River National Forest, approximately
1,500 feet north of Forest Service Road 501.
d. Site can be accessed either through Carter Tunnel or by foot. If the tunnel is not used, the hike into the site is approximately 0.65 miles and 900 vertical feet.
2. North Fork Diversion Site
a. Approximate coordinates: 39.3616°N, -106.5378°W
b. Approximate elevation: 10,217 feet
c. Located along North Fork Fryingpan River in White River National
Forest, approximately 800 feet north of Forest Service Road 501.
d. Site can be accessed either through Carter Tunnel or by foot. If the tunnel is not used, the hike into the site is approximately 0.2 miles and 325 vertical feet (via the same route used to get to Carter Creek Diversion Site).
Fryingpan – Arkansas, Colorado Solicitation No. 140R6019R0002
Site Access 01 14 13 - 2
3. Mormon Creek Diversion Site
a. Approximate coordinates: 39.3556°N, -106.5343°W
b. Approximate elevation: 10,085 feet
c. Located along Mormon Creek in White River National Forest.
d. Site is directly accessible from Forest Service Road 501.
4. North Cunningham Diversion Site
a. Approximate coordinates: 39.3367°N, -106.5431°W
b. Approximate elevation: 10,089 feet
c. Located along Cunningham Creek in White River National Forest.
d. Site is directly accessible from Forest Service Road 501.1B (County Road
4C).
5. Middle Cunningham Diversion Site
a. Approximate coordinates: 39.3287°N, -106.5516°W
b. Approximate elevation: 10,069 feet
c. Located along Middle Cunningham Creek in White River National Forest.
d. Site is directly accessible from Forest Service Road 538 (Cunningham
Road).
6. South Cunningham Diversion Site
a. Approximate coordinates: 39.3260°N, -106.5588°W
b. Approximate elevation: 10,443 feet
c. Located along South Cunningham Creek in White River National Forest.
d. Site is directly accessible from Forest Service Road 532.
7. Ivanhoe Diversion Site
a. Approximate coordinates: 39.2877°N, -106.5590°W
b. Approximate elevation: 10,020 feet
c. Located along Ivanhoe Creek in White River National Forest.
d. Site is directly accessible from Forest Service Road 105.3.
8. Granite Adit Site
a. Approximate coordinates: 39.2680°N, -106.5546°W
b. Approximate elevation: 10,010 feet
c. Located along Forest Service Road 505 in White River National Forest.
d. Site is directly accessible from Forest Service Road 505.
9. Fryingpan Diversion Site
Fryingpan – Arkansas, Colorado Solicitation No. 140R6019R0002
Site Access 01 14 13 - 3
a. Approximate coordinates: 39.2445°N, -106.5305°W
b. Approximate elevation: 9,970 feet
c. Located along Fryingpan River in White River National Forest.
d. Site is directly accessible from Forest Service Road 505 (Nast Tunnel
Diversion Road).
10. No Name Diversion Site
a. Approximate coordinates: 39.1837°N, -106.7195°W
b. Approximate elevation: 10,154 feet
c. Located along No Name Creek in the Hunter-Fryingpan Wilderness area inside White River National Forest, about two miles east of Warren Lakes.
d. Site can be accessed either through Hunter Tunnel or by foot. Access by foot is extremely difficult due to lack of an established trail, rugged terrain, and distance from any roads. The nearest road is Forest Service Road 131 at Warren Lakes. This is an extremely rugged 4 -wheel drive road accessed from Aspen, CO. From Warren Lakes, the hike (one way) would be 2.5 miles and about 1,500 vertical feet.
11. Midway Diversion Site
a. Approximate coordinates: 39.1910°N, -106.6855°W
b. Approximate elevation: 10,194 feet
c. Located along Midway Creek in the Hunter-Fryingpan Wilderness area inside White River National Forest, about 3.4 miles east of Warren Lakes.
d. Site can be accessed either through Hunter Tunnel or by foot. Access by foot is extremely difficult due to lack of an established trail, rugged terrain, and distance from any roads. The nearest road is Forest Service Road 131 at Warren Lakes. This is an extremely rugged four wheel drive road accessed from Aspen, CO. From Warren Lakes, the hike (one way) would be 5.5 miles and about 3,100 vertical feet.
12. Hunter Diversion Site
a. Approximate coordinates: 39.2074°N, -106.6796°W
b. Approximate elevation: 10,190 feet
c. Located along Hunter Creek in the Hunter-Fryingpan Wilderness area inside White River National Forest, about 4.2 miles east of Warren Lakes.
d. Site can be accessed either through Hunter Tunnel or by foot. Access by foot is extremely difficult due to lack of an established trail, rugged terrain, and distance from any roads. The nearest road is Forest Service Road 131 at Warren Lakes. This is an extremely rugged 4 -wheel drive road accessed from Aspen, CO. From Warren Lakes, the hike (one way) would be 6.7 miles and about 3,600 vertical feet.
Fryingpan – Arkansas, Colorado Solicitation No. 140R6019R0002
Site Access 01 14 13 - 4
13. Sawyer Diversion Site
a. Approximate coordinates: 39.2662°N, -106.6388°W
b. Approximate elevation: 10,046 feet
c. Located along Sawyer Creek in White River National Forest.
d. Site is directly accessible from Forest Service Road 504 (South Fork
Road).
14. Chapman Diversion Site
a. Approximate coordinates: 39.2629°N, -106.6306°W
b. Approximate elevation: 10,059 feet
c. Located along Chapman Gulch in White River National Forest.
d. Site is directly accessible from Forest Service Road 504 (South Fork
Road).
15. South Fork Diversion Site
a. Approximate coordinates: 39.2378°N, -106.5902°W
b. Approximate elevation: 10,010 feet
c. Located along South Fork Fryingpan River in White River National
Forest.
d. Site is directly accessible from Forest Service Road 504 (South Fork
Road).
B. The Carter and Hunter tunnels may be used to access some of the work sites. The following are details of the tunnels as last known to the Government:
1. Carter Tunnel
a. Carter Tunnel Outlet Portal approximate location information:
1) 39.3601°N, -106.5362°W
2) 10,105 feet elevation
b. Carter Tunnel Inlet Portal approximate location information:
1) 39.3659°N, -106.5431°W
2) 10,113 feet elevation
c. Carter Tunnel can be used to access the Carter Creek and North Fork Diversion Sites. The tunnel is accessed through the Outlet Portal, which is directly accessible from Forest Service Road 501.
d. The North Fork Intake Shaft attaches to Carter Tunnel 678 feet from the Outlet Portal. The shaft is approximately 113 feet tall (from the tunnel floor to the ground elevation above) and 5 feet in diameter.
Fryingpan – Arkansas, Colorado Solicitation No. 140R6019R0002
Site Access 01 14 13 - 5
e. The tunnel terminates at the Inlet Portal, which is 2,895 feet from the Outlet Portal. The tunnel varies in cross section size, but is nominally about eight feet wide and eight feet tall inside. The Carter Creek Diversion structure is an additional 330 feet from the Inlet Portal.
f. Applicable drawings for Carter Tunnel:
1) 382-D-2267 Tunnel Alinement and Profile
2) 382-D-2268 Carter Tunnel – Typical Tunnel Sections and
Lining Transitions
3) 382-D-3594 Carter Tunnel Inlet Portal Area and Feeder Conduit – Plans and Sections
4) 382-D-2274 Carter Tunnel Inlet and Outlet Portal Areas – Plans and Sections
5) 382-D-2275 Carter Tunnel Inlet Structure – Plan and Sections
6) 382-D-2276 Carter Tunnel Outlet Structure – Plans and Sections
2. Hunter Tunnel
a. Hunter Tunnel Outlet Portal approximate location information:
1) 39.2610°N, -106.6305°W
2) 10,100 feet elevation
b. Hunter Tunnel can be used to access the Hunter, Midway, and No Name Diversion Sites. The tunnel is accessed through the Outlet Portal, which is directly accessible from Forest Service Road 504 (South Fork Road). The Outlet Portal is 700 feet south of the Chapman Diversion Site.
c. Hunter Tunnel is approximately 7.6 miles long (39,991 feet) with a gradual elevation change from 10,140.5 feet at the No Name Creek Intake Shaft to 10,070.69 feet at the Outlet Portal. The tunnel is large enough and suitable to drive a small vehicle through (i.e. a John Deere Gator or similarly sized vehicle). At each of the three diversion sites, there is a 10.5-foot diameter vertical shaft with a ladder for personnel access and a hatch for equipment. The access shafts vary in depth for the sites as follows:
1) No Name: 39 feet
2) Midway: 62 feet
3) Hunter: 60 feet
d. Applicable drawings for Hunter Tunnel:
1) 382-D-2009 Completed Outlet Portal Area
Fryingpan – Arkansas, Colorado Solicitation No. 140R6019R0002
Site Access 01 14 13 - 6
2) 382-D-2010 Sta. 0+00 to Sta. 160+74.10BK. – Alinement and Profile
3) 382-D-2012 Sta. 0+00 to Sta. 399+59 – Typical Tunnel Sections and Lining Transitions
4) 382-D-2014 Hunter Creek Intake Shaft – Completion Work for Existing Intake Shaft
5) 382-D-2015 Midway Creek Intake Shaft – Plan and Sections
6) 382-D-2016 No Name Creek Intake Shaft – Plan, Sections, and Details
7) 382-D-2019 Outlet Channel – Plan, Sections, and Details
PART 2 PRODUCTS
Not Used
PART 3 EXECUTION
3.01 SITE ACCESS
A. Access work site locations in accordance with approved plan.
END OF SECTION
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 1
SECTION 35 22 10
SLIDE GATE ACTUATORS AND STEMS
PART 1 GENERAL
1.01 MEASUREMENT AND PAYMENT
A. Carter Creek Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
B. North Fork Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
C. Mormon Creek Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
D. North Cunningham Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
E. Middle Cunningham Site Inspection:
1. Payment: Lump -sum price offered in Price Schedule A.
a. Includes:
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 2
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators and components.
F. South Cunningham Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
G. Ivanhoe Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
H. Granite Adit Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of sleeve valve actuator, stem, and components.
I. Fryingpan Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
J. No Name Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
K. Midway Site Inspection:
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 3
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
L. Hunter Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
M. Sawyer Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
N. Chapman Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
O. South Fork Site Inspection:
1. Payment: Lump-sum price offered in Price Schedule A.
a. Includes:
1) Site Visit, Design Data Collection, Engineering Design for the furnishing, removal and replacement of slide gate actuators, stems, and components.
P. Carter Creek Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing three new slide gate actuators and one
1.5 inch diameter slide gate stem.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 4
Does not include removal and disposal of existing features. Include cost of removing and disposing of existing three slide gate actuators (one diversion, one bypass, and one winter bypass slide gate) and one 1.125 inch diameter slide gate stem in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
Q. North Fork Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing two new slide gate actuators and one 1.5 inch diameter slide gate stem.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing two slide gate actuators (one diversion and one bypass slide gate) and one 1.125 inch diameter slide gate stem in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
R. Mormon Creek Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing three new slide gate actuators and one
1.5 inch diameter slide gate stem.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing three slide gate actuators (one diversion, one bypass, and one winter bypass slide gate) and one 1.125 inch diameter slide gate stem in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
S. North Cunningham Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing two new slide gate actuators and one 1.5 inch diameter slide gate stem.
b. Does not include removal and disposal of existing features. Includes cost of removing and disposing of existing two slide gate actuators (one diversion and one bypass slide gate) and one 1.125 inch diameter slide gate stem in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
T. Middle Cunningham Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing three new slide gate actuators and one
1.5 inch diameter slide gate stem.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 5
b. Does not include removal and disposal of existing features. Includes cost of removing and disposing of existing three slide gate actuators (one diversion, one bypass, and one winter bypass slide gate) and one 1.125 inch diameter slide gate stem in unit price offered in the Price Schedule B for Removal and Disposal of Existing Features.
U. South Cunningham Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing two new slide gate actuators and one 1.5 inch diameter slide gate stem.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing two slide gate actuators (one diversion and one sluiceway slide gate) and one 1.125 inch diameter slide gate stem in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
V. Ivanhoe Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing three new slide gate actuators and one
1.5 inch diameter slide gate stem.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing three slide gate actuators (two diversions and one bypass slide gate) and one 0.875 inch diameter slide gate stem in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
W. Granite Adit Sleeve Valve Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing new sleeve valve actuator.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing sleeve valve actuator in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
X. Granite Creek Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing two new slide gate actuators (one diversion and one sluiceway slide gate) and one 1.5 inch diameter slide gate stem.
Y. Fryingpan Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 6
a. Includes furnishing and installing five new slide gate actuators.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing five slide gate actuators (four diversion, and one sluiceway slide gate) in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
Z. No Name Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing three new slide gate actuators and two
1.5 inch diameter slide gate stems.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing three slide gate actuators (one diversion, one bypass, and one winter bypass slide gate) and two 1.125 inch diameter slide gate stems in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
AA. Midway Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing three new slide gate actuators and two
1.5 inch diameter slide gate stems.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing three slide gate actuators (one diversion, one bypass, and one winter bypass slide gate) and two 1.125 inch diameter slide gate stems in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
BB. Hunter Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing three new slide gate actuators and one
1.5 inch diameter slide gate stems.
b. Does not include removal and disposal of existing features. Includes cost of removing and disposing of existing three slide gate actuators (one diversion, one bypass, and one winter bypass slide gate) and one 1.125 inch diameter slide gate stems in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
CC. Sawyer Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing two new slide gate actuators.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 7
b. Does not include removal and disposal of existing features. Includes cost of removing and disposing of existing two slide gate actuators (one diversion and one bypass slide gate) in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
DD. Chapman Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing five new slide gate actuators.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing five slide gate actuators (four diversions and one sluiceway slide gate) in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
EE. South Fork Slide Gate Actuators:
1. Payment: Lump-sum price offered in Price Schedule B.
a. Includes furnishing and installing five new slide gate actuators.
b. Does not include removal and disposal of existing features. Include cost of removing and disposing of existing five slide gate actuators (four diversions and one sluiceway slide gate) in unit price offered in Price Schedule B for Removal and Disposal of Existing Features.
FF. Cost:
a. Include cost of furnishing training for the operation and maintenance of the actuators in prices offered in Price Schedule B for other items of work.
b. The site of the training will be determined by the COR.
1.02 REFERENCES STANDARDS
A. ASTM International (ASTM)
1. ASTM A276/A276M-17 Stainless Steel Bars and Shapes
2. ASTM F593-17 Stainless Steel Bolts, Hex Cap Screws, and Studs
B. American Water Work Association (AWWA)
1. AWWA C542-16 Electric Motor Actuators for Valves and Slide Gates
2. AWWA C560-14 Cast Iron Slide Gates
C. International Electrotechnical Commission (IEC)
1. IEC 60529 Ed. 2.2 b:2013 Degrees of protection provided by enclosures
D. National Electrical Manufacturers Association (NEMA)
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 8
1. NEMA 250-2014 Enclosures for Electrical Equipment (1000 Volts Maximum)
2. NEMA ICS 5-2017 Industrial Control and Systems: Control Circuit and Pilot Devices
3. NEMA MG 1-2016 Motors and Generators
1.03 DEFINITIONS
A. Seating and unseating heads: Vertical distance from center of gate opening to maximum water surface.
B. Gate actuator: Motor-operated gate lift.
C. Operations and Maintenance (O&M) Manuals: The final documentation package that is delivered for the governor system containing all information necessary for the Government to operate and maintain each site.
D. Design Data Collection: Gathering of all information to facilitate the completion of the work. The information includes, (but is not limited to) the following:
1. Electrical Equipment and Components:
a. Sizing of fuses and wiring.
b. Conduit sizes, grounding requirements, and miscellaneous connectors and associated hardware and adhesives.
2. Mechanical Equipment and Components:
a. Gate size and head.
b. Stem length, diameter, threading, and stem guide location.
c. Pedestal actuator flange bolt pattern.
d. Radial gate seal size and length.
e. Radial gate seal bolt hole pattern.
f. Size, and quantity of redial gate bolts, nuts, and washers.
g. Radial gate hoist mounting adaptors dimensions, bolt patters, bolt sizes, reinforcement, weld sizes, and materials.
h. Radial gate limit switch mounting assemblies and brackets.
i. Radial gate electric motor horsepower, output torque, torque capacity, and speed capacity.
1.04 SUBMITTALS
A. Submit the following in accordance with Section 01 33 00 – Submittals.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 9
B. RSN 35 22 10-1, Field Surveys:
1. A field verified list of slide gate stems diameter, and stem threading.
C. RSN 35 22 10-2, Design Calculations:
1. Actuator sizing calculations, including conditions of operation, maximum loading, friction factors, stem factors, and run time.
2. Stem calculations, including stem factors, and loading.
3. Recommended torque settings.
D. RSN 35 22 10-3, Product Data:
1. Submit manufacturer’s product data in accordance with AWWA C542.
2. Following manufacturer’s data for each actuator:
a. Manufacture.
b. Model or series.
c. Stem diameter.
d. Stem material.
e. Stem nut RPM.
f. Applied thrust.
g. Stem factor.
h. Motor data:
1) Motor running amps.
2) Locked rotor torque: Foot-pounds.
3) Full load torque: Foot-pounds.
4) Horsepower rating.
5) Voltage rating.
6) Locked rotor current: Amperes.
7) Full load current: Amperes.
8) Duty rating.
9) Motor information data on standard drawing 40-D-6032.
3. Manufacture drawings showing general dimensions and layout of actuators.
4. Stem nut threading and material.
5. Complete system wiring diagrams, electrical schematics and panel layout drawings with nameplate list and bill of materials.
6. Stem guide manufactures data including material standard.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 10
7. Weights and dimensions of individual components and assembled units for installation, shipping, and handling.
8. Data on anti-seizing compound.
9. Instructions:
a. Shipping, storage, protection, and handling instructions.
b. Installation and adjustment procedures.
E. RSN 35 22 10-4. Shop Testing Results:
1. Shop testing procedures to verify all operational aspects of gate actuators.
2. Initial conditions for operational demonstrations.
3. Results of shop testing.
F. RSN 35 22 10-5. Field Test Results:
1. Final settings for each actuator:
a. Torque settings for opening and closure.
b. Travel settings.
c. Measured running Amps for opening and closure.
2. Note the following conditions for each actuator at the time of programing actuator settings:
a. Balanced or unbalanced.
b. If unbalanced, head from center of gate.
c. Opening and closing time.
G. RSN 35 22 10-6, Manuals:
1. O & M manuals for actuators.
2. List of special tools and spare parts for actuators:
a. Spare parts to be furnished.
b. Tools, appliances, handling devices and templates to be furnished.
3. Photographs:
a. Front, left, and right sides of actuators, and leaf to show new stem connection.
1.05 DELIVERY, STORAGE, AND HANDLING
A. Actuators to be shipped in accordance with AWWA C542 and manufacturer’s recommendations.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 11
B. Support actuators in wooden crates.
C. Supports to be wood block or fabricated wood supports.
D. Clearly stamp the wooden crate or shipping container’s exterior, on four sides, with permanent marking to indicate the total weight of the container and its contents and the recommended storage practice for the enclosed assembly.
E. Secure movable parts to prevent loss or damage by vibration or rough handling.
F. Protect fragile parts from damage during shipping.
G. Tightly seal storage parts and electrical components that are susceptible to moisture to prevent rusting and damage.
H. Notify COR 48 hours prior to each delivery of materials or equipment.
1.06 SPECIAL TOOLS AND SPARE PARTS
A. Special Tools:
1. Furnish special tools and wrenches of unusual pattern not usually furnished in a mechanic tool set, which are necessary for installation, assembly and disassembly of the gate actuators.
B. Spare Parts:
1. Furnish two spare stem nuts that match each size and thread configuration used..
1.07 PROJECT CONDITIONS
A. Coatings on the gate actuators contain heavy metals. See Section 51 09 96 – Analytical Test Results.
B. South Cunningham, Granite Adit, Granite Creek, and Sawyer are not operated via
SCADA.
C. Every effort has been made to ensure accurate referencing of informational drawings;
however, references are not warranted to be accurate or complete in all instances.
D. The current as-built gate dimensions are unknown, and the relevant dimension shall be measured by the Contractor to ensure correct fit of the replacement parts before commencement of fabrication of new parts.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 12
PART 2 PRODUCTS
2.01 MOTOR-OPERATED GATE ACTUATOR
A. Provide equipment in accordance with AWWA C542 and as specified:
1. Actuator Enclosure:
a. Double O-ring sealed.
b. Watertight to IEC 60529, IP66/IP68.
c. At a minimum NEMA 250, Type 4, 6 at 15 meters for 96 hours.
d. Removal of the terminal cover shall not change the actuator NEMA ratings.
e. Breathers and drains shall not be permitted.
2. Torque Sensing Mechanism:
a. Integral part of motor operator.
b. Protect gate and actuator in both opening and closing directions.
c. Torque sensing:
1) Torque limitation shall be adjustable without removing any actuator covers.
2) Torque sensing shall be from direct measurement of force at the output of the actuator, governed by a solid-state torque sensor that directly measures the output torque of the actuator or data derived from the motor speed, voltage and temperature fluctuations.
3) Methods of determining torque using mechanical torque switches is not acceptable.
4) Adjustable settings and independent adjustment for opening and closing directions.
d. Contacts rating designation: NEMA ICS 5 A300.
3. Limit Position Sensing Mechanism:
a. Limit position sensing and associated gearing:
1) Integral part of motor operator.
2) Measured via a solid-state absolute encoder device that eliminates the use of counting gear trains or potentiometers.
b. Position limits shall be adjustable without removing any actuator covers.
c. Position measurement shall be contactless.
d. Position setting range shall be at a minimum 2.5 to 8000 turns of the actuator, with resolution to 7.5° of actuator output.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 13
e. Absolute encoder shall be capable of maintaining positon measurement during power outages without need for backup power source.
f. A monitor relay shall be provided as standard, which can be used to indicate actuator available for remote operation.
g. The contacts shall be rated for 5mA to 5A, 120V AC, 30V DC.
h. Four separate contacts shall be provided which can be selected to indicate any position of the gate.
i. Provide at least four additional independent contacts, set to function in accordance with schedule as listed below:
1) Electrically independent contacts: Close at fully-open position.
2) Electrically independent contacts: Open at fully-open position.
3) Electrically independent contacts: Close at fully-closed position.
4) Electrically independent contacts: Open at fully-closed position.
j. Provision shall be made for the selection of a normally closed or open contact form.
k. Contacts shall operate when all external power to the actuator is lost.
4. When sizing the actuator use a coefficient of friction of 0.60.
5. Seating and unseating heads: Design to be suitable for seating and unseating heads as listed on the drawings.
6. Operating Speed: Match existing speed plus or minus 10 percent.
7. Handwheel and declutching mechanism:
a. A handwheel shall be provided for emergency operation.
b. Motor drive shall be restored automatically by starting the motor.
c. The hand auto lever shall be padlockable in at least the automatic position.
d. It should be possible to select hand operation while the actuator is running without damage to the drive train.
e. The handwheel drive must be mechanically independent of the motor drive, and any gearing should be such as to permit emergency manual operation in a reasonable time.
f. Raised markings on the hanwheel showing rotation to open or close the gate.
g. Handwheel rim force, maximum 40 pounds when raising or lowering the gate under maximum load.
8. Enclose gears in a housing.
9. Stem nut and lifting nut: Bronze, conforming to AWWA C560.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 14
10. Position Potentiometer:
a. Measurement divisions: Feet, inches, and tenths of an inch or percent open.
11. Stem cover:
a. Conforming to AWWA C560.
b. Aluminum.
c. Coating:
1) According to manufacturer’s recommendations for outdoor use.
2) Match color with actuator.
12. Local Controls:
a. Control knob for OPEN and CLOSE operation.
b. Control knob for LOCAL, OFF, and, REMOTE operation.
c. LED type pilot lights to indicate gate OPEN, gate CLOSED, and gate in mid-travel (both lights illuminated), minimum.
13. Digital Control Module (DCM):
a. Provide each gate actuator with DCM to allow for remote monitoring and control of the actuator.
b. Microprocessor based electronics with control software stored in non-volatile EEPROM memory.
c. Two serial communication ports, minimum.
d. Built in transient and lightning protection.
e. Perform self-diagnostics.
f. Control signal of 4-20mA current loop.
14. Communication Protocol (for future upgrade): Modbus RTU.
15. Printed circuit card interconnects have gold-plated connectors.
16. Self-locking, a rated running torque equal to 20 percent of motor starting torque at a rated running time of 15 minutes continuous, without exceeding allowable NEMA temperature rise for insulation class used.
17. Motor:
a. Motor protection using a thermostat embedded in the motor end windings.
b. Lost phase protection shall be incorporated into the design.
c. Induction type.
d. Rated: 230 volts, 3-phase, 60 hertz.
e. Designed for required service:
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 15
1) For ON/OFF duty.
2) Meets or exceeds Class F.
3) Suitable for 60 starts per hour.
1) A time rating of at least 15 minutes at 104°F or twice the gate stroking time, whichever is the longer, at an average load of at least 33% of maximum gate torque.
2) Removal of the motor should be possible without draining the oil from the actuator.
f. Conforms to NEMA MG 1.
g. Totally enclosed.
h. Locked-rotor torque, minimum: 250 percent of full-load torque.
i. Motor overload: Operation will stop.
18. Integral Motor Starter: Full-voltage, electro-mechanical, reversing type.
a. The reversing starter, control transformer, and local controls shall be integral with the gate actuator, suitably housed to prevent breathing and condensation buildup.
b. Electro-mechanical type suitable for 60 starts per hour, and of rating appropriate to motor size.
c. Control Power Transformer: Provide suitable voltage for control circuits.
d. Connections and terminal blocks:
1) Conductors:
a) Copper, type THW, THWN, or XHHW.
b) Enclosed in liquid-tight conduit with black jacket flexible metal conduit, or rigid steel conduit.
c) Attached identification marker near each conductor termination.
2) Furnish conductors necessary for interconnecting enclosures mounted on the motor-operated gate actuators.
3) Terminate, on terminal blocks in one-enclosure, power and control conductors for connection external to gates.
4) Mark terminals with terminal designations.
5) Hub: Suitable for liquid-tight flexible-metal or rigid steel conduit.
19. Actuator Control Compartment:
a. Watertight, dustproof, and O-ring sealed to meet NEMA 250, Type 4.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems
35 22 10 - 16
b. Compartment to house motor contactor, torque and positions switches, and communication modules.
20. Actuator Termination Compartment:
a. Separate, sealed termination compartment.
b. Terminals: Allow installation of conductors with crimped ring connectors.
c. Terminal Identification: Integral part of terminal strip.
21. All motor-operated gates actuators to be of the same manufacture, model, size, or series within torque and stem diameter limitations, maximizing part interchangeability.
B. Nameplates:
1. Equipment nameplates identify the gates and the actuators.
2. The nameplate to indicate size, capacity, rating, amount of grease or oil to be used, manufacturer name, Model No., and Serial No.
3. Attach the nameplate to the equipment by means of screws or rivets.
4. Stamped or raised markings.
5. Non rusting metal.
C. Provide four setting tools (remote controls, specialized computers), if such a device is required, to commission, program, or set actuator limits.
D. Actuator able to operate continuously through at least one complete cycle under normal operating conditions.
E. Lockable tamper-proof cover over display and all electrical controls.
F. Actuator pedestal mounts to match existing pedestals.
G. All external fasteners used conform to ASTM F593, 300 series stainless steel.
H. All mounting brackets to conform to ASTM A276, 300 series stainless steel.
I. Use anti-seizing compound on all external fasteners.
2.02 STEM
A. Replace all stem that are less than 1.5 inches in diameter with stems that are 1.5 inches in diameter.
B. Provide Equipment in accordance with AWWA C560, except:
1. No portion of the stem shall have a cross-sectional area smaller than the root area of the threaded portion of the stem.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 17
2. The root diameter of the threads is to be used to calculate the radius of gyration and area for the threaded parts.
3. Stem diameter selected so that the maximum unsupported stem length is not greater than 200 times the radius of gyration of the stem.
4. Match new 1.5 inch diameter stem threading to existing 1.5 inch diameter stem threading.
a. If existing 1.5 inch diameter stem threading is not consistent, then match stem threading as directed by the COR.
C. Stems machined to match stem nut.
D. Cutting of stems to determine stem threading is not allowed.
E. Approximate stem diameters and lengths are given below for stems that have a diameter less than 1.5 inches, however all existing stem diameters and lengths are to be field verified by the Contractor, excluding Granite Creek.
Diversion Stem Diameter Stem Length
Carter Creek 1.125 inches 11 feet
North Fork 1.125 inches 15 feet
Mormon Creek 1.125 inches 11 feet
North Cunningham 1.125 inches 8 feet
Middle Cunningham 1.125 inches 11 feet
South Cunningham 1.125 inches 15 feet
Ivanhoe 0.875 inches 18 feet
Granite Creek 1.125 inches 17 feet
No Name 1.125 inches 18 feet and 20 feet
Midway 1.125 inches 15 feet and 17 feet
Hunter 1.125 inches 15 feet
Sawyer 1.125 inches 17 feet
2.03 STEM GUIDES
A. Provide and install new stem guide collars with new stems.
B. Modifications to the new stem guide collars or existing stem guide brackets may not be made.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 18
1. Provide and install new stem guide brackets if new stem guide collars are not compatible with existing stem guide brackets.
C. Design and manufacture in accordance with AWWA C560, except:
1. Stem guides: Fully adjustable.
2. Anchors:
a. Sized according to manufacturer’s recommendations.
b. Material: ASTM F593, 300 series stainless steel.
c. Minimum embedment depth: 6 inches or as recommended by the stem guide manufacturer.
d. On each anchor bolt, a minimum of three threads shall be exposed past the nut.
e. Use appropriate anti-seizing compound.
2.04 COATINGS
A. Coat gate actuators according to manufacturer’s recommendations for outdoor use.
B. No coating on stainless steel parts is required.
PART 3 EXECUTION
3.01 FIELD SURVEYS
A. Collect design data for the furnishing, removal and replacement of all gate and valve actuators, stems, and components that are listed on drawing 382-D-60057.
B. Exclude Granite Creek.
3.02 SHOP ASSEMBLY AND TEST
A. Shop assemble the actuators and performance test in accordance with AWWA C542 performance test standards and as specified below:
1. Verify all operational aspects of gate actuators.
2. Notify the COR in writing at least 14 days prior to shop testing.
3. Government Representative will witness all tests, unless otherwise directed by the
CO.
3.03 INSTALLATION
A. Properly dispose of removed actuators and stems in accordance with Section 02 41 07 Removal and Disposal of Existing Features.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 19
B. Configure new actuator to match existing actuator SCADA requirements.
1. Current data transferred through SCADA: Gate opening in feet and inches to the hundredth.
C. Verify and lubricate stem and actuators in accordance with manufacturer's instructions.
3.04 FIELD TESTING
A. Set all actuator torque settings.
1. Initially set recommended torques settings.
2. Adjust settings to insure that the gate will open and close, and seal when closed.
B. All limit settings to be adjusted and tested to prove their ability to stop motor operations in both directions of travel and that the gate will fully open and seal closed.
C. Measure and record running Amps for opening and closure of actuators.
D. Equipment operation to be observed for signs of undue noise and vibration.
E. Government Representative will witness all tests, unless otherwise directed by the CO.
F. The equipment manufacturers shall provide a manufacturer’s representative for inspection and start-up assistance of the gate actuators.
1. The manufacturer’s representative shall inspect the equipment after the actuators are installed and assist the start-up operation.
2. Operate the gates and the actuators through all modes of operation.
G. After installation, operate the gate through not less than three complete cycles of opening and closing, where in one of the cycles, the gate operation is stopped and started at an intermediate position in each direction of travel.
H. Seat test:
1. If in the opinion of the OGR not enough water is available to test the seating of a gate using water, adjust the actuator torque and travel limit settings to minimize potential leakage using gauges and/or light test.
2. If in the opinion of the OGR not enough water is available to test the seating of a gate using water, adjust the actuator torque and travel limit settings to the point where a 0.004 inch thickness gauge cannot be inserted between seating faces.
3. Adjustments of slide gate wedges is not required for seat testing.
I. Correct all defects demonstrated by the above tests to make the equipment fully operational.
Fryingpan - Arkansas – Colorado Solicitation No. 140R6019R0002
Slide Gate Actuators and Stems 35 22 10 - 20
J. Evidence of improper fit, misalignment, galling, overheating or other defects will be considered defective work and be repaired or defective equipment replaced until such time that the defect or defective equipment has been eliminated.
3.05 TRAINING
A. The equipment manufacturers shall provide a manufacturer’s representative for operational training of the gate actuators.
1. Onsite training for up to 5 people, at a location to be determined by the COR.
2. Not to exceed 3 hours.
3. Bound operating and maintenance manuals to be provided for each trainee at training.
4. Training shall fully cover maintenance and operation of all system components.
5. Provide any operating and maintenance manuals on CD.
END OF SECTION
lc g
N
-n -
‘ 0 0 CD
CD
O
2° U t.
0 -r I
CD -D 0 CD 3 CD D
F I
9 2 z CD t
EJ c-
C-
F c b 1’ f o m
I
Prospective Contractor Questions and Answers
1. Specification section 35 22 10 Part 2 Products
2.01 6: Operating speed – The specifications call out for 12 inches per minute which is an
AWWA standard, but we found many of the existing gates operating at 5 inches per minute. We usually operate gates in this type of application at the 5 to 6 inches per minute so should we use the existing gate speeds?
A: Refer to revised specifications Section 352210, Slide Gate Actuators and Stems. The following is incorporated into specifications Section 352210, Paragraph 2.01 A.6.
“Operating Speed: Match existing speed plus or minus 10 percent.”
2. Specification section 35 22 10 Part 2 Products
2.01 11: Stem Cover – The specifications call out for galvanized stem covers with slotted holes with clear plastic windows for gate position. The existing stem covers are painted steel schedule 40 pipe without slots. Based on the weather conditions these gates are in and our experience the slotted holes will end up allowing water inside the covers and with the freeze / thaw temperatures you will end up with problems inside the actuator or gearbox.
Can we supply galvanized schedule 40 stem covers or aluminum stem covers? The aluminum stem covers are less weight for removal plus the threads do not rust over time and make it hard to remove.
A: Refer to revised specifications Section…