B08_Attachment_2_Drawings_Peirce_HVAC_DEWA.pdf
PDF 26 MB Posted
- Attached to
- DEWA REPLACE HVAC SYSTEM PEIRCE HOUSE Federal contract opportunity
- Solicitation number
- 140P4524R0009
About this file
This document is a set of engineering drawings related to the HVAC system replacement project for the Peirce House as part of Solicitation 140P4524R0009 issued by the Department of the Interior National Park Service Northeast Region. The drawings provide technical details and specifications for the HVAC system components to be installed, including equipment layout, ductwork, piping, and controls. This solicitation is seeking a contractor to replace the existing HVAC system at the Peirce House. The agency, project name, solicitation number, and other key details are provided in the related federal contract opportunity summary.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Pre-Bid_MeetingParticipating_0003.pdf | ||
| Questions_and_answers_0003.pdf | ||
| Sol_140P4524R0009_Amd_0003.pdf | ||
| Sol_140P4524R0009_Amd_0002.pdf | ||
| Sol_140P4524R0009_Amd_0001.pdf | ||
| Sol_140P4524R0009.pdf | ||
| B08_Attachment_1_SOW_Peirce_HVAC_DEWA.pdf | ||
| B08_Attachment_5_Price_Schedule_Peirce_HVAC_DEWA.pdf | ||
| B08_Attachment_4_PPQ_Peirce_HVAC_DEWA.pdf | ||
| B08_Attachment_3_WD_PA20240103_4-5-2024_Replace_HVAC_DEWA.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RESERVOIR
UPPER
BUS
RESERVOIR
YARDS CREEK
EAST STROUDSBURG
STROUDSBURG &
NETCONG
BLAIRSTOWN
D E
L A W
A R
E
R
IV
E R
HACKETTSTOWN
DOVER
NEW
JERSEY
NEW
YORK
HAMBURG
OAK RIDGE
N .J .P
.A
NEWTON
MILFORD
P .A
N
.Y
SUSSEX
SMITHFIELD BEACH
HIDDEN LAKE
FARM
SLATEFORD
POINT
KITTATINNY
V.C.
HIALEAH
MOHICIAN
DEPEW
GLEN
VANCAMPENS
WATERGATE
HQ.
VILLAGE
MILLBROOK
BEND
RIVERS
CREEK
TOMS
ACCESS
BUSHKILL
CENTER
JERSEY
NEW
EDUCATION
ENVIRONMENTAL
POCONO
CHILDS
FALLS V.C.
DINGMANS
EDUCATION
ENVIRONMENTAL
CENTER
WALPACK VALLEY
PETERS
VALLEY
ACCESS
FERRY
DINGMANS
PENNSYLVANIA
BEACH
MILFORD
RECREATION AREA
GAP NATIONAL
DELAWARE WATER
FLATBROOKVILLE
NEW YORK CITY
HAINESBURG
PORTLAND
TO
COLUMBIA
& SCRANTON
STROUDSBURG
TO 380
AMPTON CO.
NORTH
MONR OE CO.
CREEK
MARSHALLS
STROUDSBURG
EAST
SHAWNEE
JERSEY
IA
VALLEY
WALNUT
DELAWARE
RIVER
BLAIRSTOWN
BUSHKILL
SYLVAN
NEW
PENN
W A
R R
E N
C O
U N
T Y
S U
S S
E X
C O
U N
T Y
M O
N R
O E
C O
U N
T Y
P
IK
E C
O U
N T
Y CENTER
WALLPACK
ALLENTOWN
BETHLEHEM
FERRY
DINGMANS
HAINESVILLE
MILFORD
380TO
& PORT JERVIS
TO MATAMORAS
EASTON
PORT JERVIS
MATAMORAS
NEW JERSEY
PENNSYLVANIA
11 0 2 3
CHARLES PEIRCE HOUSE
294 OLD MILFORD RD
MILFORD, PA 18337
HQ.
V.C.
LEGEND
DELAWARE WATER GAP NATIONAL RECREATION AREA
1 0 1 2
CAMPGROUND
PICNIC
AREA
BOAT
LAUNCH
CREEK OR
RIVER
RANGER
STATION
PARK
HEADQUARTERS
VISITOR
CENTER
PARKING
TELEPHONE
APPALACHIAN
TRAIL
COUNTY
LINE
PAVED
ROAD
PARK
BOUNDARY
STATE
LINE
5 0 5
THIS PROJECT
A/E FIRM - P15PC00037 Mark Sheet REVISION Date Initial QUALITY DESIGN CERTIFICATION Prepared in Accordance with Design
Development (Title I)
OR
Variance from Design Development (Title I)
Approved by Superintendent on
OR
Construction Drawing Not Preceded by Design Development (Title I)
Drawing No.
Date
Project Manager Date
UNITED STATES
TITLE OF DRAWING
DEPARTMENT OF THE INTERIOR
LOCATION WITHIN PARK
NAME OF PARK
REGION COUNTY STATE
DRAWING NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
MECHANICAL
VHB
WILLIAMSBURG, VA
STRUCTURAL:
FAISANT
BALTIMORE, MD
MECHANICAL:
HENRY ADAMS
BALTIMORE, MD
ELECTRICAL:
HENRY ADEAMS
BALTIMORE, MD
:1 :1
A M
B
IM
N P S
D E W A
C h a rl e s
P e ir c e
H o u s e
H V A C
D e s ig n
D E W A
H V A C
D e s ig n
A rc h it e c tu ra l.
rv t
Project Status
NPS Office Responsible
CHARLES PEIRCE
HOUSE HVAC DESIGN
NPS Location w/in Park
DELAWARE WATER GAP NRA
NORTHEAST PIKE PENNSYLVANIA
167005
PMIS/PKG NO.
326047
1 34
SCALE OF MILES
SCALE OF MILES
SCALE OF KILOMETERS
WALL TYPE
WINDOW TYPE
DOOR NUMBER
ROOM IDENTIFICATION
DEMOLITION NOTE
CONSTRUCTION NOTE
REFERENCE POINT
ACCESSORY
RAILING
DETAIL/ PARTIAL
SECTION
REFERENCE
ELEVATION
REFERENCE
SECTION
REFERENCE
NEW WORK
KEY TO SYMBOLS
SEE MECHANICAL, ELECTRICAL, AND PLUMBING
DRAWINGS FOR SYMBOLS RELATING TO M.E.P. WORK
(ARCHITECTURAL DRAWINGS ONLY)
EXISTING
WORK
X.X
X.X
X
X
X
NAME
XXX
X
A A1
A A1
SIM
A1
SIM
X
X
CMU
PLASTER/ GWB
SURFACES
STEEL (LARGE SCALE)
STEEL (SMALL SCALE)
CONCRETE
GRAVEL / DRAIN ROCK
PLYWOOD
BLOCKING
(INTERMITTENT/ AS REQ)
END GRAIN LUMBER
(CONTINUOUS)
BATT/ ACOUSTICAL INSULATION
RIGID INSULATION
COMPACTED EARTH
BRICK
FLASHING
GLASS (ELEVATION)
KEY TO MATERIALS
SEE MECHANICAL, ELECTRICAL, AND PLUMBING
DRAWINGS FOR SYMBOLS RELATING TO M.E.P. WORK
(ARCHITECTURAL
DRAWINGS ONLY)
BRICK ELEVATION
SAND, GROUT OR MORTAR
AGGREGATE
BACKFILL
ROCK SURFACE
FINISH WOOD
A/E ARCHITECTURE/ENGINEERING
ABA ARCHITECTURAL BARRIERS ACT
ABAAS ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
ADA AMERICANS WITH DISABILITIES ACT
ADD ADDITION
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
APPROX APPROXIMATELY
AW AWNING
BLDG BUILDING
BLTS BOLTS
BO BOTTOM OF
CL CENTERLINE
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CONTRACTING OFFICER
CONC CONCRETE
DH DOUBLE-HUNG
DIA/ø DIAMETER
DWGS DRAWINGS
EL/ELEV ELEVATION
EQ EQUAL
ETR EXISTING TO REMAIN
EX/EXT EXISTING
FCU FAN COIL UNIT
F FIXED
FF FINISHED FLOOR
GL GLASS, GLAZING
GWB GYPSUM WALL BOARD
HABS HISTORIC AMERICAN BUILDING SURVEY
HM HOLLOW METAL
HSR HISTORIC STRUCTURE REPORT
IBC INTERNATIONAL BUILDING CODE
IEBC INTERNATIONAL EXISTING BUILDING CODE
INT INTERIOR
LARPM LIQUID-APPLIED REINFORCED POLYMER MEMBRANE
LG LARGE
MAL MATERIAL
MIN MINIMUM
MAX MAXIMUM
MEP MECHANICAL/ELECTRICAL/PLUMBING
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NPS NATIONAL PARK SERVICE
OC ON CENTER
OH OPPOSITE HAND
OZ OUNCE
PART PARTIAL
PT PRESSURE-TREATED
REF REFRIGERATOR
REQ'D REQUIRED
RM ROOM
RO ROUGH OPENING
SF SQUARE FEET
SH SINGLE-HUNG
SI SQUARE INCH
SIM SIMILAR
SM SMALL
SS STAINLESS STEEL
TECH TECHNICAL
TYP TYPICAL
USPP UNITED STATES PARK POLICE
VENT VENTILATION
VIF VERIFY IN FIELD
W/ WITH
WD WOOD
KEY TO ABBREVIATIONS
ARCHITECTURAL DRAWINGS ONLY
8 0 8 16
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
STRUCTURAL:
NAME
CITY, STATE
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE A
:1 :1
A M
B
IM
N P S
D E W A
C h a rl e s
P e ir c e
H o u s e
H V A C
D e s ig n
D E W A
H V A C
D e s ig n
A rc h it e c tu ra l.
rv t
DRAWING LIST
DELAWARE WATER GAP NRA
167005
245920
2 34
G1
DLR
DLR
JHG
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGNXXXXX
XXXXX
SHEET
SUB
SHEET TITLE OF SHEET
1 G0 COVER SHEET
2 G1 DRAWING LIST
3 AD.1 DEMOLITION PLANS
4 A1.1 BASEMENT & FIRST FLOOR PLAN
5 A1.2 SECOND & THIRD FLOOR PLAN
6 A8.1 WINDOW SCHEDULE & DETAILS
7 M0.1 MECHANICAL COVER SHEET
8 MD1.0 BASEMENT - MECHANICAL - DEMOLITION PLAN
9 MD1.1 FIRST FLOOR - MECHANICAL - DEMOLITION PLAN
10 MD1.2 SECOND FLOOR - MECHANICAL - DEMOLITION PLAN
11 MD1.3 THIRD FLOOR - MECHANICAL - DEMOLITION PLAN
12 M1.0 BASEMENT - MECHANICAL - NEW WORK
13 M1.1 FIRST FLOOR - MECHANICAL - NEW WORK
14 M1.2 SECOND FLOOR - MECHANICAL - NEW WORK
15 M1.3 THIRD FLOOR - MECHANICAL - NEW WORK
16 M2.1 MECHANICAL DETAILS
17 M2.2 MECHANICAL DETAILS
18 M3.1 MECHANICAL SCHEDULES
19 M3.2 MECHANICAL SCHEDULES
20 M3.3 MECHANICAL SCHEDULES
21 M4.1 AUTOMATIC TEMPERATURE CONTROLS
22 E0.1 ELECTRICAL COVER SHEET
23 EO.2 ELECTRICAL GENERAL NOTES
24 ED1.0 BASEMENT - ELECTRICAL DEMOLITION
25 ED1.1 FIRST FLOOR - ELECTRICAL DEMOLITION
26 ED1.2 THIRD FLOOR - ELECTRICAL DEMOLTION
27 E1.0 BASEMENT - ELECTRICAL NEW WORK
28 E1.1 FIRST FLOOR - ELECTRICAL NEW WORK
29 E1.2 SECOND FLOOR - ELECTRICAL NEW WORK
30 E1.3 THIRD FLOOR - ELECTRICAL NEW WORK
31 E6.1 ELECTRICAL ONE-LINE DIAGRAMS
32 E8.1 ELECTRICAL EQUIPMENT SCHEDULES
33 E8.2 PANELBOARD SCHEDULES
34 E8.3 PANELBOARD SCHEDULES
1. ITEMS SHOWN WITH LIGHT LINES ARE EXISTING.
2. ITEMS SHOWN AS DARK OR BOLD LINES ARE NEW WORK.
GENERAL NOTES
UP
BASEMENT
BASEMENT
BASEMENT
BASEMENT
004 BASEMENT
3.1
23.2
8.1
VESTIBULE
KITCHEN
CORRIDOR
WORK RM
CONFERENCE RM
FOYER
LAV
OFFICE
OFFICE
RECEPTION
CLEAN LAB
STAIR
23.1
23.1
EXISTING
PAD
BATH 1
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
GIS OFFICE
GIS LAB
GIS CLOSET
MAP RM
CORRIDOR
STAIR HALL
BATH 2
23.1
UNFINISHED
CORRIDOR
MECHANICAL
UNFINISHED
UNFINISHED
6.1 7.1 6.1 7.1
6.1 7.1
6.1 7.1
6.1 7.1
8 0 8 16
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
STRUCTURAL:
NAME
CITY, STATE
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE A
:1 :1
A M
B
IM
N P S
D E W A
C h a rl e s
P e ir c e
H o u s e
H V A C
D e s ig n
D E W A
H V A C
D e s ig n
A rc h it e c tu ra l.
rv t
DEMOLITION PLANS
DELAWARE WATER GAP NRA
167005
245920
3 34
AD.1
DLR
DLR
JHG
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGNXXXXX
XXXXX
SCALE AAD.1
1 BASEMENT - DEMOLITION
SCALE AAD.1
2 FIRST FLOOR - DEMOLITION
SCALE AAD.1
3 SECOND FLOOR - DEMOLITION
SCALE AAD.1
4 THIRD FLOOR PLAN - DEMOLITION
DEMOLITION NOTES
3.1 REMOVE PORTIONS OF CONCRETE SLAB TO
EXPAND EXISTING PIT TO 2' x 2' x 2'. SEE
MECHANCIAL FOR ADDITIONAL INFORMATION
6.1 REMOVE EXISTING WOOD FLOORING ONLY AS
NEEDED FOR INSTALLATION OF NEW INSULATION.
SALVAGE WOOD FLOOR FOR REINSTALLATION
7.1 REMOVE EXISTING BLOWN INSULATION BETWEEN
THIRD FLOOR FLOOR JOIST
23.1 REMOVE EXISTING BASEBOAD HEATING SYSTEM
23.2 REMOVE REMNANTS OF PREVIOUS HEATING
SYSTEM
23.2
GENERAL DEMOLTION NOTES:
1. REMOVE PORTIONS OF ORIGINAL PLASTER AND
WOOD LATH ONLY AS NEEDED TO INSTALL
SERVICES
2. REMOVE LOOSE OR DELAMINATED PLASTER THAT IS
BEYOND REPAIR AND REQUIRES FULL
REPLACEMENT
8.1 REMOVE EXISTING WINDOW SASH. EXTERIOR
SCREEN TO REMAIN.
UP
BASEMENT
BASEMENT
BASEMENT
BASEMENT
BASEMENT
4.1
4.2
TYP.
TYP.
VESTIBULE
KITCHEN
CORRIDOR
WORK RM
CONFERENCE RM
FOYER
LAV
OFFICE
OFFICE
RECEPTION
CLEAN LAB
STAIR
9.1
6.3
6.3
EXISTING
PAD
9.1
7.2 7.2
DN
9.1 9.1
9.1
9.1
9.1
8 0 8 16
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
STRUCTURAL:
NAME
CITY, STATE
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE A
:1 :1
A M
B
IM
N P S
D E W A
C h a rl e s
P e ir c e
H o u s e
H V A C
D e s ig n
D E W A
H V A C
D e s ig n
A rc h it e c tu ra l.
rv t
BASEMENT & FIRST
FLOOR PLAN
DELAWARE WATER GAP NRA
167005
245920
4 34
A1.1
DLR
DLR
JHG
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGNXXXXX
XXXXX
SCALE AA1.1
2 BASEMENT FLOOR PLAN
CONSTRUCTION NOTES
NO SCALE
A1.1
EXISTING PHOTOS - FOR REFERENCE ONLY
4.1 OPENINGS GREATER THAN 4" DIA. INSTALL
STAINLESS STEEL HARDWARE CLOTH (ITEM #
1/2"X1"304.063WD MANUFACTURED BY EDWARD
J. DARBY AND SON INC. OR APPROVED EQUAL).
PACK OPENING WITH MORTAR (TYPE S) COLOR
TO MATCH EXISTING AS SELECTED BY COR FROM
MANUFACTUERS FULL COLOR RANGE. TYPICAL OF
4.2 OPENINGS LESS THAN 4" DIA. FILL WITH MORTAR
(TYPE S) COLOR TO MATCH EXISTING AS
SELECTED BY COR FROM MANUFACTURER'S FULL
COLOR RANGE. TYPICAL OF 14
SCALE AA1.1
3 FIRST FLOOR PLAN
6.3 PATCH FLOOR IN-KIND AT DEMOLISHED
EQUIPMENT LOCATION
IMAGE KEY PLAN
NOT TO SCALE
NO SCALE
A1.1
VERMIN PATCHING PHOTO'S - FOR REFERENCE ONLY
IMAGE 1 IMAGE 2
4.1 4.2
IMAGE 3 - SOUTH ELEV.IMAGE 4 - SOUTHWEST ELEV.IMAGE 5 - MAIN ENTRYIMAGE 6 - NORTH ELEV.IMAGE 7 - EQUIPMENT PADIMAGE 8 - MECH. UNITS
IMAGE 12 - SERVICE ENTRY IMAGE 11 - LOUVER IMAGE 10 - SOUTEAST ELEV. IMAGE 9 - MECH. LINES
9.1 PATCH SURFACE IN-KIND AND FINISH TO MATCH
EXISTING ADJACENT SURFACE
IMAGE 13 - FOYER 105 UNITIMAGE 14 - LAV 112 UNIT
GENERAL NOTE:
1. RETAIN HISTORIC PLASTER. RESTORE DAMAGED AREA OF HISTORIC CEILING WITH
TRADITIONAL PLASTER AND LATH TO MATCH EXISTING. PROTECT ALL EXISTING ORIGINAL
PLASTER AND WOOD LATH CEILINGS TO REMAIN. RESECURE SECTIONS OF LOOSE OR
DELAMINATED PLASTER. REPAIR/REPLACE DETERIORATED PORTIONS OF PLASTER AND LATH AS
NEEDED; REPLACE INKIND TO MATCH EXISTING. REMOVE PORTIONS OF ORIGINAL PLASTER AND LATH AS NEEDED TO INSTALL SERVICES. APPLIES TO ALL EXISTING CEILING AREAS, UNLESS
NOTED OTHERWISE.
TYP. TYP.
7.2 PATCH EXTERIOR SIDING IN-KIND AT DEMOLISHED
EXHAUST FAN. PRIME AND PAINT TO MATCH
EXISTING
BATH 1
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
GIS OFFICE
GIS LAB
GIS CLOSET
MAP RM
STAIR HALL
BATH 2
9.2
9.2
9.3
DN
9.1 9.1
9.1
UNFINISHED
CORRIDOR
MECHANICAL
UNFINISHED
UNFINISHED
W1 W2 W3 W4 W5
W6 W7
W8
W9
W10
W11
W12W13W14W16W17W18W19
W20
W21
W22
8.1
6.1 6.2 7.1 6.1 6.2 7.1
6.1 6.2 7.1
6.1 6.2 7.1
6.1 6.2 7.1
W39 W40
W41
W42 7.2
7.2
DN
6 7
W23 W24
W25 W26
W27 W28
W29 W30
W31
W32 W33
W34 W35
W36 W37
W38
8.1
8 0 8 16
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
STRUCTURAL:
NAME
CITY, STATE
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE A
:1 :1
A M
B
IM
N P S
D E W A
C h a rl e s
P e ir c e
H o u s e
H V A C
D e s ig n
D E W A
H V A C
D e s ig n
A rc h it e c tu ra l.
rv t
SECOND & THIRD
FLOOR PLAN
DELAWARE WATER GAP NRA
167005
245920
5 34
A1.2
DLR
DLR
JHG
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGNXXXXX
XXXXX
CONSTRUCTION NOTES
6.1 REINSTALL SALVAGED WOOD FLOOR
SCALE AA1.2
1 SECOND FLOOR PLAN
SCALE AA1.2
2 THIRD FLOOR PLAN
6.2 RE-SECURE LOOSE BOARDS, REPLACE MISSING
OR DETERIORATED BOARDS IN-KIND, LEAVE
SPACES BROOM SWEPT AND VACUUMED
7.1 INSTALL BLOWN INSULATION BETWEEN EXISTING
THIRD FLOOR JOISTS TO FILL CAVITIES. PROVIDE
MAXIMUM THICKNESS ALLOWED
8.1 RE-USE EXISTING MECHANICAL LOUVER.
REFERENCE MECHANICAL DRAWINGS
9.2 PATCH PLASTER AT DEMOLISHED EQUIPMENT
LOCATION
IMAGE KEY PLAN - SECOND FLOOR
NOT TO SCALE
IMAGE KEY PLAN - THIRD FLOOR
NOT TO SCALE
NO SCALE
A1.2
EXISTING PHOTOS - FOR REFERENCE ONLY
IMAGE 1 - BATH 211
IMAGE 4 - 301
GENERAL NOTE:
1. RETAIN HISTORIC PLASTER. RESTORE DAMAGED AREA OF HISTORIC CEILING WITH
TRADITIONAL PLASTER AND LATH TO MATCH EXISTING. PROTECT ALL EXISTING ORIGINAL
PLASTER AND WOOD LATH CEILINGS TO REMAIN. RESECURE SECTIONS OF LOOSE OR
DELAMINATED PLASTER. REPAIR/REPLACE DETERIORATED PORTIONS OF PLASTER AND LATH AS
NEEDED; REPLACE INKIND TO MATCH EXISTING. REMOVE PORTIONS OF ORIGINAL PLASTER AND LATH AS NEEDED TO INSTALL SERVICES. APPLIES TO ALL EXISTING CEILING AREAS AND WALLS, UNLESS NOTED OTHERWISE.
SCALE AA1.2
3 THIRD FLOOR CLERESTORY PLAN
IMAGE 3 - MAP RM 208
IMAGE 5 - 301IMAGE 6 - MECHANICAL 303IMAGE 7 - 305IMAGE 8 - 305IMAGE 9 - 304
IMAGE 2 - BATH 213
GENERAL CONSTRUCTION NOTE:
1. ASSUME 25% OF EXISTING WOOD FLOOR AT
THIRD FLOOR WILL REQUIRE FULL REPLACEMENT.
7.2 PATCH EXTERIOR SIDING IN-KIND AT DEMOLISHED
EXHAUST FAN. PRIME AND PAINT TO MATCH
EXISTING
9.3 SCRAPE LOOSE CEILING JOINTS FREE OF DEBRIS.
PACK CRACKED JOINTS WITH GYPSUM
COMPOUND, TAPE AND FEATHER TO MATCH
ADJACENT SURFACES. SAND SMOOTH. PRIME AND
PAINT TO MATCH EXISTING CEILING COLOR
9.1 PATCH SURFACE IN-KIND AND FINISH TO MATCH
EXISTING ADJACENT SURFACE
DOUBLE/SINGLE HUNG
CASEMENT
JAMB
EXTERIOR
EXISTING
WINDOW HEAD
EXISTING
WINDOW SILL
2X WOOD BLOCK
AS REQUIRED FOR
STORM WINDOW
INSTALLATION, TYP.
EXISTING SASH
REMOVEABLE
ALUMINUM STORM
WINDOW SASH
ALUMINUM LOCKING
CHANNEL
1/4"
1/2"
GLASS
EXISTING WALL
CONSTRUCTION
EXISTING WINDOW
STILE
GLASS
REMOVEABLE
ALUMINUM
STORM WINDOW
INTERIOR
2X WOOD BLOCKING AS
REQUIRED FOR STORM
WINDOW INSTALLATION, TYP.
EXISTING WALL
CONSTRUCTION
2X WOOD BLOCKING
AS REQUIRED FOR
STORM WINDOW
INSTALLATIN, TYP.
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
STRUCTURAL:
NAME
CITY, STATE
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
:1 :1
A M
B
IM
N P S
D E W A
C h a rl e s
P e ir c e
H o u s e
H V A C
D e s ig n
D E W A
H V A C
D e s ig n
A rc h it e c tu ra l.
rv t
WINDOW SCHEDULE &
DETAILS
DELAWARE WATER GAP NRA
167005
245920
6 34
A8.1
DLR
DLR
JHG
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGNXXXXX
XXXXX
NO SCALEA8.1
1 TYPICAL STORM WINDOW DETAILS
GENERAL NOTES
1. INSTALL NEW INTERIOR STORM WINDOWS. TYPICAL
OF ALL THIRD FLOOR WINDOWS, INCLUDING ALL
DORMERS AT CLERESTORY.
2. DIMENSIONS PROVIDED FOR CONTRACTORS
CONVENIENCE ONLY. ACTUAL DIMENSIONS TO BE
VERIFIED IN FIELD.
Window Schedule
Mark FLOOR
WINDOW STORM WINDOW
COMMENTSSILL HEIGHT HEIGHT WIDTH Head Sill Jamb
W1 THIRD FLOOR PLAN 1' - 4" 4' - 6" 2' - 8" 1/A8.0 1/A8.0 1/A8.0
W2 THIRD FLOOR PLAN 1' - 4" 4' - 6" 2' - 8" 1/A8.0 1/A8.0 1/A8.0
W3 THIRD FLOOR PLAN 3' - 5" 2' - 10" 1' - 8" 1/A8.0 1/A8.0 1/A8.0
W4 THIRD FLOOR PLAN 1' - 4" 4' - 6" 2' - 8" 1/A8.0 1/A8.0 1/A8.0
W5 THIRD FLOOR PLAN 1' - 4" 4' - 6" 2' - 8" 1/A8.0 1/A8.0 1/A8.0
W6 THIRD FLOOR PLAN 1' - 8" 4' - 6" 2' - 8" 1/A8.0 1/A8.0 1/A8.0
W7 THIRD FLOOR PLAN 1' - 8" 4' - 6" 2' - 8" 1/A8.0 1/A8.0 1/A8.0
W8 THIRD FLOOR PLAN 1' - 5" 4' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W9 THIRD FLOOR PLAN 0" 5' - 9" 1' - 6" 1/A8.0 1/A8.0 1/A8.0
W10 THIRD FLOOR PLAN 0" 5' - 9" 1' - 6" 1/A8.0 1/A8.0 1/A8.0
W11 THIRD FLOOR PLAN 1' - 5" 4' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W12 THIRD FLOOR PLAN 1' - 8" 5' - 0" 4' - 1" 1/A8.0 1/A8.0 1/A8.0
W13 THIRD FLOOR PLAN 1' - 8" 5' - 0" 4' - 1" 1/A8.0 1/A8.0 1/A8.0
W14 THIRD FLOOR PLAN 5' - 0" 2' - 5" 2' - 5" 3/A8.0 3/A8.0 3/A8.0 OUTDOOR AIR INTAKE LOUVER
W16 THIRD FLOOR PLAN 1' - 8" 5' - 0" 3' - 8" 1/A8.0 1/A8.0 1/A8.0
W17 THIRD FLOOR PLAN 1' - 8" 5' - 0" 3' - 8" 1/A8.0 1/A8.0 1/A8.0
W18 THIRD FLOOR PLAN 1' - 5" 5' - 0" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W19 THIRD FLOOR PLAN 1' - 5" 5' - 0" 3' - 0" 3/A8.0 3/A8.0 3/A8.0
W20 THIRD FLOOR PLAN 2' - 8" 3' - 10" 2' - 4" 1/A8.0 1/A8.0 1/A8.0
W21 THIRD FLOOR PLAN 2' - 8" 3' - 10" 2' - 4" 1/A8.0 1/A8.0 1/A8.0
W22 THIRD FLOOR PLAN 2' - 8" 3' - 10" 2' - 4" 1/A8.0 1/A8.0 1/A8.0
W23 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W24 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W25 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W26 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W27 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W28 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W29 THIRD FLOOR PLAN 13' - 4" 3' - 1" 1' - 7" 1/A8.0 1/A8.0 1/A8.0
W30 THIRD FLOOR PLAN 13' - 4" 3' - 1" 1' - 7" 1/A8.0 1/A8.0 1/A8.0
W31 THIRD FLOOR PLAN 13' - 4" 3' - 1" 1' - 7" 1/A8.0 1/A8.0 1/A8.0
W32 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W33 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W34 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W35 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W36 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W37 THIRD FLOOR PLAN 15' - 2" 1' - 10" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W38 THIRD FLOOR PLAN 13' - 4" 3' - 10" 2' - 4" 1/A8.0 1/A8.0 1/A8.0 EXHAUST AIR INTAKE LOUVER
W39 THIRD FLOOR PLAN 0" 6' - 2" 4' - 0" 1/A8.0 1/A8.0 1/A8.0
W40 THIRD FLOOR PLAN 0" 6' - 2" 4' - 0" 1/A8.0 1/A8.0 1/A8.0
W41 THIRD FLOOR PLAN 0" 6' - 8" 3' - 0" 1/A8.0 1/A8.0 1/A8.0
W42 THIRD FLOOR PLAN 0" 6' - 8" 5' - 2" 1/A8.0 1/A8.0 1/A8.0
NO SCALE
A8.1
EXISTING PHOTOS - FOR REFERENCE ONLY
TYPICAL CLERESTORY WINDOW TYPICAL THIRD FLOOR WINDOW
** NOTE - ALL WINDOW DIMENSIONS SHALL BE VERIFIED IN FEILD **
MECHANICAL GENERAL NOTES
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
1. COORDINATE ALL MECHANICAL WORK WITH PLUMBING WORK, ELECTRICAL WORK, AND WORK OF OTHER TRADES SHOWN ON OTHER
DRAWINGS.
2. INFORMATION SHOWN ON THE MECHANICAL DRAWINGS PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO DEMOLITION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING AND AWAIT WRITTEN DIRECTION BEFORE PROCEEDING WITH THE
WORK.
3. REMOVE ALL EXISTING HEATING WATER PIPING, REFRIGERANT PIPING, FUEL OIL PIPING, DUCTWORK, EQUIPMENT, AND MATERIALS NOT REQUIRED FOR RE-USE OR RE-INSTALLATION (SHOWN OR OTHERWISE). ALL EXISTING MATERIALS AND EQUIPMENT WHICH ARE REMOVED AND ARE DESIRED BY THE COR, OR ARE INDICATED TO REMAIN THE PROPERTY OF COR SHALL BE DELIVERED BY THE COR'S CONTRACTOR WHERE DIRECTED BY THE COR'S CONSTRUCTION MANAGER. ALL OTHER MATERIALS AND EQUIPMENT WHICH ARE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED BY THE CONTRACTOR FROM THE PREMISES.
4. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, ETC.
5. EXISTING MECHANICAL DUCTWORK, AIR DEVICES, AND MATERIALS AFFECTED BY DEMOLITION OR NEW WORK INSTALLATION AND REQUIRED TO REMAIN IN SERVICE SHALL BE RE-INSTALLED OR SUPPORTED AS REQUIRED IN ACCORDANCE WITH THE SPECIFICATIONS. ALL WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE COR'S CONSTRUCTION MANAGER AND AT NO ADDITIONAL CONTRACT COST.
6. REMOVE ALL ACCESSORIES, CONTROLS, ENCLOSURES, SUPPORTS, HANGERS, PADS, ETC. ASSOCIATED WITH ALL EQUIPMENT SHOWN TO BE REMOVED. REPAIR AND PAINT DAMAGED SURFACES AND ALL SURFACES BEHIND ALL EQUIPMENT SHOWN TO BE REMOVED TO MATCH
EXISTING ADJACENT SURFACES.
7. RUN ALL DRAIN PIPING WITH 2 PERCENT MINIMUM GRADE UNLESS OTHERWISE NOTED.
8. INSTALL PIPING AND DUCTWORK SO THAT ALL VALVES AND DAMPERS ARE ACCESSIBLE.
9. UNLESS OTHERWISE NOTED, ROUTE ALL PIPING AND DUCTWORK OVERHEAD, TIGHT TO UNDERSIDE OF SLAB, WITH SPACE FOR INSULATION
IF REQUIRED.
10. CERTAIN ITEMS SUCH AS ACCESS DOORS, CLEANOUTS, RISE AND DROPS IN DUCTWORK AND PIPING, ETC., ARE INDICATED ON THE DRAWINGS FOR CLARITY OR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THESE ITEMS AS REQUIRED ELSEWHERE IN THE
CONTRACT DOCUMENTS.
11. WHERE THE INSTALLATION OF NEW SERVICES OR THE EXTENSION OF EXISTING SERVICES REQUIRES CUTTING OF EXISTING FLOORS, WALLS, PARTITIONS, ETC., CHECK FOR THE PRESENCE OF EXISTING MECHANICAL, PLUMBING AND ELECTRICAL SERVICES WITHIN OR IMMEDIATELY BENEATH CONSTRUCTION. EXERCISE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE SERVICES OR INJURY TO PERSONNEL DUE TO CONTACT WITH SAME. TEMPORARILY DISCONNECT SERVICES DURING THE CUTTING OPERATION. SCHEDULE SERVICE
OUTAGES IN ADVANCE WITH THE COR.
12. FLOW SCHEMATIC AND RISER DIAGRAMS INDICATE FLOW AND OPERATION CONCEPTS AS WELL AS GENERAL ARRANGEMENT OF EQUIPMENT.
VALVES, PRESSURE GAUGES, ETC. ARE INDICATED FOR THIS PURPOSE. PROVIDE ADDITIONAL VALVES, PRESSURE GAUGES, ETC. AS SHOWN ON VARIOUS EQUIPMENT DETAILS. SEE PLANS AND DETAILS FOR PIPE SIZES NOT INDICATED ON FLOW SCHEDULES AND RISER
DIAGRAMS.
13. RECOVER REFRIGERANTS FROM REFRIGERATION EQUIPMENT IN ACCORDANCE WITH AHRI AND EPA STANDARDS. PLACE RECOVERED
REFRIGERANT IN CONTAINERS LABELED IN ACCORDANCE WITH AHRI AND EPA STANDARDS.
BLOWER DOOR AND AIRFLOW TEST
A. SUMMARY
1. EMPLOY AN INDEPENDENT THIRD-PARTY SUBCONTRACTOR, NOT AN AFFILIATED OR SUBSIDIARY OF THE PRIME CONTRACTOR, TO
CONDUCT THE BLOWER DOOR AND AIR FLOW TEST ON THE BUILDING IN ACCORDANCE WITH ASTM E779 STANDARD TEST METHOD FOR DETERMINING AIR LEAKAGE RATE BY FAN PRESSURIZATION OR ASTM E1827 STANDARD TEST METHODS FOR DETERMINING AIR
TIGHTNESS OF BUILDINGS USING AN ORIFICE BLOWER DOOR.
B. REPORTING WORK
1. PROVIDE A CERTIFIED AIR LEAKAGE TEST REPORT WHICH INCLUDES THE DATE, TEST AGENDA, EQUIPMENT LIST AND SIGNATURE OF
THE RESPONSIBLE PARTY RESPONSIBLE FOR COMPLETING AND PREPARING THE TESTING REPORT.
C. TEST SHALL OCCUR FOLLOWING COMPLETION OF CONSTRUCTION.
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
:4 :1
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
MECHANICAL COVER
SHEET
DELAWARE WATER GAP NRA
167005
245920
7 34
M0.1
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
MECHANICAL LEGEND
DESCRIPTIONSYMBOL
DIFFUSER TAG:
TOP- NECK SIZE
CENTER- SPECIFICATION TYPE
BOTTOM- AIRFLOW IN CFM
8x8 D-1
SWITCHS
FLEXIBLE CONNECTION
VOLUME DAMPER
MOTOR OPERATED DAMPER
BAROMETRIC BACKDRAFT DAMPER
THERMOSTAT/TEMPERATURE SENSORT
HUMIDISTAT/HUMIDITY SENSORH
RETURN AIR DUCT
OUTDOOR AIR OR SUPPLY AIR DUCT
EXHAUST AIR DUCT
PLAN/ SECTION DESIGNATION
TOP - PLAN/ SECTION REFERENCE,
BOTTOM - REFERENCED DRAWING
A M-1
END POINT OF REMOVAL OF EXISTING
CONNECT TO EXISTING
REFRIGERANT SUCTIONRS
REFRIGERANT LIQUIDRL
CONDENSATE DRAIND
PUMP DISCHARGEPD
MECHANICAL ABBREVIATIONS
ACCU AIR-COOLED CONDENSING UNIT
CFM CUBIC FEET PER MINUTE
BAS BUILDING AUTOMATION SYSTEM
BDD BACKDRAFT DAMPER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
D DAMPER/DIAMETER/DIFFUSER/DEEP/DEPTH/
DRAIN
DB DRY BULB
DN DOWN
DOAS DEDICATED OUTDOOR AIR SYSTEM
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
ES END SWITCH
ESP EXTERNAL STATIC PRESSURE
EX EXISTING
F FAHRENHEIT
FCU FANCOIL UNIT
FT FEET/FOOT
H HUMIDITY SENSOR
HP HORSEPOWER
HPU HEAT PUMP UNIT
IN INCHES
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
M MECHANICAL
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MCOP MAXIMUM CIRCUIT OVER PROTECTION
MD MECHANICAL DEMOLITION
MIN MINIMUM
N NORTH
NO NUMBER
OA OUTDOOR AIR
R RADIUS/REGISTER
RA RETURN AIR
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
S SWITCH
SA SUPPLY AIR
T TEMPERATURE SENSOR
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
WB WET BULB
WC WATER COLUMN
WG WATER GAUGE
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
CONDENSATE DRAIN
DESCRIPTIONSYMBOL
PUMP DISCHARGE
REFRIGERANT LIQUID
REFRIGERANT SUCTION
PLAN/SECTION DESIGNATION
TOP - PLAN/SECTION REFERENCE
BOTTOM - REFERENCED DRAWING
END POINT OF REMOVAL OF EXISTING
CONNECT TO EXISTING
EXHAUST AIR DUCT
OUTDOOR AIR SUPPLY DUCT
RETURN AIR DUCT
HUMIDISTAT/HUMIDITY SENSOR
THERMOSTAT/TEMPERATURE SENSOR
BAROMETRIC BACKDRAFT DAMPER
MOTOR OPERATED DAMPER
VOLUME DAMPER
FLEXIBLE CONNECTION
DIFFUSER TAG
TOP - NECK SIZE
CENTER - SPECIFICATION TYPE
BOTTOM - AIRFLOW IN CFM
PD
D
RS
RL
SWITCH
1 1
E
E
D
D
C
C
B
BA
A
RX
UH-2
RX
AH-2
RX
AH-1
RX
UH-1
RX
BOILER-1
RX BOILER
PUMPS
RX DUCTWORK, TYP
RX PIPING, TYP
BASEMENT
BASEMENT
BASEMENT
BASEMENT
BASEMENT
RX D, TYP
RX D, TYP
RX DUCTWORK, TYP
RX OA DUCT UP
RX REFRIGERANT
PIPING, TYP OF
4 SETS
RX FUEL OIL FILL
AND FUEL OIL VENT
RX DUCT TO EX FLOOR
DIFFUSER, TYP. REFER TO
DRAWING NOTE 4 FOR
MORE INFORMATION.
4 0 4 8
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
:4 :3
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
BASEMENT -
MECHANICAL DEMO
DELAWARE WATER GAP NRA
167005
245920
8 34
MD1.0
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH DASHED LINE,
3. REMOVE ENTIRE HOT WATER HEATING SYSTEM INCLUDING FUEL OIL, COLD WATER MAKEUP, ETC.
4. FLOOR DIFFUSERS TO REMAIN. REMOVE DUCT TO POINT OF CONNECTION BELOW FLOOR. LEAVE ENOUGH
EXISTING DUCT TO ALLOW FOR NEW AIRTIGHT CONNECTION.
5. REMOVE ALL EXISTING DUCTWORK AND FLEXIBLE DUCTWORK UNLESS OTHERWISE NOTED.
6. CONTRACTOR SHALL TAKE PRE-CONSTRUCTION AIRFLOW READINGS AT ALL AIR HANDLING UNITS AND AIR
DEVICES PRIOR TO ANY DEMOLITION OR NEW WORK.
SCALE BMD1.0
1 BASEMENT - MECHANICAL - DEMOLITION PLAN
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
RX ALL CONDENSATE DRAINAGE PIPING1
RX FUEL OIL TANK, PIPING, ETC.2
RX HEATING WATER AND REFRIGERANT PIPING UP3
E
E
D
D
C
C
B
BA
A
RX FLOOR MOUNTED
SA REGISTER, TYP
RX OA DUCT UP/DN
EX FLOOR MOUNTED
RA REGISTER, TYP
EX 13x13 SIDEWALL
RA REGISTER
EX 13x13 SIDEWALL
RA REGISTER
EX 9x13 SIDEWALL
RA REGISTER
VESTIBULE
LAV
CORRIDOR
KITCHEN
110 CLEAN LAB
STAIR
RECEPTION
OFFICE
FOYER
CONFERENCE RM
OFFICE
WORK RM
EX 12x6
EX 10x6 EX 12x6
EX 12x6
EX 12x4
EX 14x6 RX 14x6
EX 12x6
EX 12x6 EX 12x6
EX 12x6
EX 12x6
EX 14x6
EX 12x4 T
T
RX
RX
EX 14x14
EX 14x14
RX 14x6
EX DUCTWORK
4 0 4 8
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
:4 :3
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
FIRST FLOOR -
MECHANICAL DEMO
DELAWARE WATER GAP NRA
167005
245920
9 34
MD1.1
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
SCALE BMD1.1
1 FIRST FLOOR - MECHANICAL - DEMOLITION PLAN
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH DASHED LINE,
3. ALL NEW AND EXISTING OPENINGS CREATED IN ANY WALLS, FLOORS, CEILINGS, ETC. DUE TO DEMOLITION, NEW WORK OR EXISTING CONDITIONS, SHALL BE SEALED TO MAKE VERMIN PROOF.
4. REMOVE ALL EXISTING DUCTWORK AND FLEXIBLE DUCTWORK UNLESS OTHERWISE NOTED.
5. CONTRACTOR SHALL TAKE PRE-CONSTRUCTION AIRFLOW READINGS AT ALL AIR HANDLING UNITS AND AIR
DEVICES PRIOR TO ANY DEMOLITION OR NEW WORK.
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
RX ELECTRICAL BASEBOARD HEATER AND PATCH DRYWALL
OPENING.
RX EXHAUST FAN DUCTWORK, ETC. AND PATCH DRYWALL
OPENING.
RX HEATING WATER AND REFRIGERANT PIPING UP/DN3
NOT USED4
RX EXHAUST FAN5
PATCH AND SEAL WALL6
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
RELOCATE FLOOR DIFFUSER TO ROOM 110 KITCHEN. NEW
LOCATION SHOWN ON DWG M1.1.
RELOCATE FLOOR DIFFUSER TO ROOM 109 WORK ROOM.
NEW LOCATION SHOWN ON DWG M1.1.
E
E
D
D
C
C
B
BA
A
RX OA DUCT UP/DN
RX WINDOW
TYPE AC UNIT
CORRIDOR
BATH 1
OFFICE
OFFICE
STAIR HALL
OFFICE
BATH 2
OFFICE
MAP RM
GIS OFFICE
GIS LAB
GIS CLOSET
CORRIDOR
209T
RX5
T
RX5
EX 14x14
EX 12x12
EX 12x12
EX 12x12EX 12x12EX 12x12EX 12x12
EX 14x14
EX 12x12
EX 12x12
EX 14x14
EX 14x14
EX 14x14
EX 12x12
EX 12x12
EX 14x14
EX 12x12
EX 12x12
EX 14x14
EX 14x14
EX 12x12
EX 14x14EX 14x14
CEILING MOUNTED
SA DIFFUSER, TYP
CEILING MOUNTED
RA GRILLE, TYP
4 0 4 8
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
:4 :4
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
SECOND FLOOR -
MECHANICAL DEMO
DELAWARE WATER GAP NRA
167005
245920
10 34
MD1.2
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
SCALE BMD1.2
1 SECOND FLOOR - MECHANICAL - DEMOLITION PLAN
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH DASHED LINE,
3. ALL NEW AND EXISTING OPENINGS CREATED IN ANY WALLS, FLOORS, CEILINGS, ETC. DUE TO DEMOLITION, NEW WORK OR EXISTING CONDITIONS, SHALL BE SEALED TO MAKE VERMIN PROOF.
4. REMOVE ALL EXISTING DUCTWORK AND FLEXIBLE DUCTWORK UNLESS OTHERWISE NOTED.
5. CONTRACTOR SHALL TAKE PRE-CONSTRUCTION AIRFLOW READINGS AT ALL AIR HANDLING UNITS AND AIR
DEVICES PRIOR TO ANY DEMOLITION OR NEW WORK.
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
RX ELECTRICAL HEATER1
RX EXHAUST FAN DUCTWORK, ETC. INSTALL NEW EXHAUST
GRILLE IN THIS SAME LOCATION.
RX HEATING WATER AND REFRIGERANT PIPING UP/DN3
NOT USED4
PATCH AND SEAL WALL5
E
E
D
D
C
C
B
BA
A
RX
UH-3
RX
AH-3
RX
AH-4
RX OA
DUCT DN
UNFINISHED
CORRIDOR
UNFINISHED
UNFINISHED
MECHANICAL
RX D, TYP
RX DUCTWORK, TYP
RX PIPING, TYP
RX DUCTWORK, TYP
RX ALL FLEXIBLE
DUCTWORK, TYP
RX DUCT TO EX
DIFFUSER, TYP. REFER TO
DRAWING NOTE 4 FOR
MORE INFORMATION.
4 0 4 8
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
:4 :4
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
THIRD FLOOR -
MECHANICAL DEMO
DELAWARE WATER GAP NRA
167005
245920
11 34
MD1.3
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
SCALE BMD1.3
1 THIRD FLOOR - MECHANICAL - DEMOLITION PLAN
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH DASHED LINE,
3. ALL NEW AND EXISTING OPENINGS CREATED IN ANY WALLS, FLOORS, CEILINGS, ETC. DUE TO DEMOLITION, NEW WORK OR EXISTING CONDITIONS, SHALL BE SEALED TO MAKE VERMIN PROOF.
4. CEILING DIFFUSERS TO REMAIN. REMOVE DUCT TO POINT OF CONNECTION ABOVE CEILING. LEAVE ENOUGH
EXISTING DUCT TO ALLOW FOR NEW AIRTIGHT CONNECTION.
5. REMOVE ALL EXISTING DUCTWORK AND FLEXIBLE DUCTWORK UNLESS OTHERWISE NOTED.
6. CONTRACTOR SHALL TAKE PRE-CONSTRUCTION AIRFLOW READINGS AT ALL AIR HANDLING UNITS AND AIR
DEVICES PRIOR TO ANY DEMOLITION OR NEW WORK.
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
RX OA DUCTS TO LOUVER1
RX EXHAUST FAN DUCTWORK, ETC.2
RX HEATING WATER AND REFRIGERANT PIPING DN3
D
D
C
C
B
BA
A
RS/L TO HPU'S
ON GRADE, TYP
OF 4 SETS
SA DUCT UP TO
FLOOR MOUNTED
REGISTER, TYP
RA DUCT
UP, TYP
RS/L UP, TYP
OF 4 SETS
SA DUCT UP TO
FLOOR MOUNTED
REGISTER, TYP
R S
R L
RL
RS
RS
RL
8x8
8x10 SA
6x8 EA UP
T FCU-BEDH-B
EDH-4
EDH-2
EDH-3
8x6 SA UP
EX 8x14
RA UP
14x12
BASEMENT
BASEMENT
BASEMENT
BASEMENT
BASEMENT
8x10
EA UP
12x12 OA UP
8x10 SA
3 3
1-1/2" CO
RL
RS
RL
RS
16x10 x1
FCU-4B
FCU-4A
FCU-B
FCU-2
FCU-3
FCU-8
EX ELEC
PANEL
1" CO
PD
3" CO
D D
PD
PD
PD
P D x1
R S R L
12x10
12x8 x6
10x8 x6 x6 x8
10x10 x8
12x8
1" CO
PD
6x6
VD, 25
CFM
x1
8x8 OA. VD, 320 CFM
8x8 OA. VD, 290 CFM x1 x8
10x8
VD, 320
CFM
10x8
4x4 OA
6x14 EA UP x8
12x4 SA UP12x4 SA UP
8x8
R L R S
RS
RL
TFCU-8
VD, 75
CFM
VD, 370
CFM
12x12
1" CO PD
EX ELEC PANELS
10ø
10x12
10ø
6ø
10x10 ø
6ø 8x10 ø
8ø
8ø
10x12
8ø 8ø
8ø
12ø
12ø
14x12
8ø
8ø
6ø
6ø 10x10
10x10 ø ø6ø
6x6
10x4 SA UP
PD
1" CO
18" SERVICE
CLEARANCE, TYP
36" SERVICE
CLEARANCE, TYP
4 4
3" 3"
1-1/2"
1"
1-1/2"
2" CO2" D UP
4 0 4 8
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
:4 :1
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
BASEMENT -
MECHANICAL NEW WORK
DELAWARE WATER GAP NRA
167005
245920
12 34
M1.0
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
3. ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
ALL TYPES OF VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT DOCUMENTS TO THE
COR FOR RESOLUTION.
4. ALL NEW AND EXISTING OPENINGS CREATED IN ANY WALLS, FLOORS, CEILINGS, ETC. DUE TO DEMOLITION, NEW WORK OR EXISTING CONDITIONS, SHALL BE SEALED TO MAKE VERMIN PROOF.
5. ALL REGRIFERANT PIPING SHALL BE SIZED BY EQUIPMENT MANUFACTURER.
SCALE BM1.0
1 BASEMENT - MECHANICAL - NEW WORK
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
EXPAND EXISTING PIT TO 30"x30"x24" FOR INSTALLATION OF
PUMP-1.
SUPPORT FROM ABOVE2
PROVIDE CONDENSATE PUMP, CP-13
SUPPORT FROM ABOVE4
TERMINATE 3" CONDENSATE DRAIN THROUGH WALL AND ONTO
EXISTING CONCRETE STORM WATER TROUGH
TERMINATE 1-1/2" CONDENSATE DRAIN THROUGH WALL AND
ONTO EXISTING CONCRETE STORM WATER TROUGH
8x8 SA, R-3, 170 CFM7
8x8 SA, R-3, 170 CFM8
12x8 RA, R-3, 170 CFM9
INSTALL NEW REFRIGERANT PIPING IN EXISTING HOLES
WHERE REFRIGERANT AND HEATING WATER PIPING AND
DUCTWORK WAS REMOVED
EXTEND PLENUM AS NECESSARRY TO ALLOW FLEXIBLE
DUCTWORK CONNECTION, TYP ALL CONNECTIONS TO EX
FLOOR DIFFUSERS
E
E
D
D
C
C
B
BA
A
RS/L UP/DN,
TYP OF 4 SETS
FLOOR MOUNTED
SA REGISTER, TYP
HPU-2
HPU-3
HPU-4
HPU-1
EX 12x4, 100 CFM
EX 12x6, 240 CFM
EX 14x6, 240 CFM
EX 12x6, 130 CFM
EX 12x6, 130 CFM
EX 13x13, 335 CFM
EX 10x6, 110 CFM
EX 12x6, 110 CFM
EX 12x4, 90 CFM
EX 14x6, 115 CFM
EX 9x13, 370 CFM
EX 14x14, 410 CFM
EX 14x14, 510 CFM
FLOOR MOUNTED
RA REGISTER, TYP
EX 12x6, 160 CFM
EX 12x6, 160 CFM
EX 12x6, 70 CFM
EX 12x6, 70 CFM
VESTIBULE
KITCHEN
CLEAN LAB
107 STAIR
LAV
WORK RM
OFFICE
RECEPTION
CORRIDOR
FOYER
CONFERENCE RM
OFFICE
EX EA DUCT
EX EA DUCT
R-1
10x4
R-1
14x6 R-1
14x6
EF-2
EF-3
12x12 OA UP/DN
EX 13x13 SIDEWALL
RA REGISTER, 580
CFM
EX DUCTWORK
R-3
8x62
R-3
8x6
5 5
14x6 EA UP/DN
2" D DN
2" D UP
T FCU-4B
TFCU-4A
T FCU-2
T FCU-3
S
S
R-1
14x6
R-1
14x68
4 0 4 8
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
:4 :1
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
FIRST FLOOR -
MECHANICAL NEW WORK
DELAWARE WATER GAP NRA
167005
245920
13 34
M1.1
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
3. ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
ALL TYPES OF VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT DOCUMENTS TO THE
COR FOR RESOLUTION.
4. ALL NEW AND EXISTING OPENINGS CREATED IN ANY WALLS, FLOORS, CEILINGS, ETC. DUE TO DEMOLITION, NEW WORK OR EXISTING CONDITIONS, SHALL BE SEALED TO MAKE VERMIN PROOF.
5. ALL REGRIFERANT PIPING SHALL BE SIZED BY EQUIPMENT MANUFACTURER.
SCALE BM1.1
1 FIRST FLOOR - MECHANICAL - NEW WORK
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
MOUNT HPU'S ON EXISTING CONCRETE PAD1
INSTALL 1/2-INCH ABOVE FINISHED FLOOR2
MOUNT EXISTING AIR DEVICE FOR AIRFLOW INDICATED3
EXHAUST TO DOAS-14
COORDINATE FINAL LOCATION WITH COR5
RELOCATE DIFFUSER FROM 109 WORK RM TO THIS
LOCATION.
RELOCATE DIFFUSER FROM 110 KITCHEN TO THIS LOCATION.7
REUSE EX FLOOR OPENING. CONNECT NEW REGISTER TO EX
DUCT.
E
E
D
D
C
C
B
BA
A
CEILING MOUNTED
RA GRILLE, TYP
M2.2
FCU-1
RS/L UP
M2.2
EX 12x12, 120 CFM
EX 12x12, 160 CFM
EX 14x14, 180 CFM
EX 12x12, 210 CFM
EX 12x12
EX 12x12
EX 14x14 EX 14x14, 290 CFM
EX 14x14, 225 CFM
CORRIDOR
OFFICE
BATH 1
OFFICE
STAIR HALL
CORRIDOR
MAP RM
BATH 2
OFFICE
GIS LAB
GIS CLOSET
GIS OFFICE
EX 14x14, 360 CFM
EX 12x12
EX 12x12, 210 CFM
EX 14x14, 200 CFM
EX 12x12
EX 12x12, 270 CFM
EX 12x12, 200 CFM
EX 12x12, 225 CFM
EX 12x12, 250 CFM
EX 12x12
EX 14x14, 315 CFM
EX 14x14, 315 CFM
EX 14x14, 250 CFM
6x8 RA UP
CEILING MOUNTED
SA DIFFUSER, TYP
R-2
6x6 D-1
6x6
D-1
6x6
R-2
6x6
RS/L UP/DN,
TYP OF 4 SETS
12x12 OA UP/DN
EX 14x14, 430 CFM
R-3
8x6
14x6 EA UP/DN
TR-2
8x8
2" D UP/DN
TFCU-7
T FCU-5
T FCU-6
4 0 4 8
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
:4 :2
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
SECOND FLOOR -
MECHANICAL NEW WORK
DELAWARE WATER GAP NRA
167005
245920
14 34
M1.2
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
3. ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
ALL TYPES OF VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT DOCUMENTS TO THE
COR FOR RESOLUTION.
4. ALL NEW AND EXISTING OPENINGS CREATED IN ANY WALLS, FLOORS, CEILINGS, ETC. DUE TO DEMOLITION, NEW WORK OR EXISTING CONDITIONS, SHALL BE SEALED TO MAKE VERMIN PROOF.
5. ALL REGRIFERANT PIPING SHALL BE SIZED BY EQUIPMENT MANUFACTURER.
SCALE BM1.2
1 SECOND FLOOR - MECHANICAL - NEW WORK
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
EXHAUST TO DOAS-11
INSTALL AT LOCATION WHERE EXHAUST FAN WAS REMOVED.2
BLANK OFF EXISTING DIFFUSER IN ATTIC SPACE3
D
D
C
C
B
BA
A
OA INTAKE LOUVER PROVIDED
UNDER ANOTHER DIVISION
RA DUCT
DN, TYP
M2.2
12x8
16x12 SA
8x10 10x10
6x4 EA DN
RS/L DN, TYP
OF 4 SETS
RS/L DN
TO FCU-1
FAN-1
FCU-A
M2.2
12x8 RA
14x14 EA
14x6 RA
8x6
EDH-7
EDH-5
EDH-6
10ø
8x12 OA
RL
RS
8ø
UNFINISHED
CORRIDOR
UNFINISHED
UNFINISHED
MECHANICAL
8x6 RA DN
12x12 OA DN
18" DEEP INSULATED
SPLIT PLENUM. WIDTH
AND HEIGHT SHALL
MATCH LOUVER SIZE.
DOAS-1
BDD
8Ø RA
DN
6x4 EA
R S R L
10x8
BDD
4 4
14x6 RA
EX ELEC
PANEL
FCU-7
FCU-6
12x10
14x10
FCU-5
x1
18x8 RA
PD
PD
PD
RS
RL
1" PD
x1
RS
RL
R S R L
6x14 EA
DN
8x8
6Ø SA DN
8x14
6Ø SA DN
6x4 EA
6x4 EA DN
T FCU-A
T EF-1, 4
18" DEEP INSULATED
PLENUM. WIDTH AND
HEIGHT SHALL MATCH
LOUVER SIZE.
18x18 EA
10x10
10x6
8x8 EA
DN
16x14 OA
14x14 EA
14x12 OA
8x8 OA
16x14 OA
14x12 SA
FAN-2
FC, TYP
10x10 6
14x14 EA
6 6
8ø SA
8x14
10x4 OA 6
12x14 RA
DN
8Ø
10ø
10ø
10ø ø
10ø
12ø
10Ø DN
10ø x1
10ø
8ø
8ø
36" SERVICE
CLEARANCE, TYP
18" SERVICE
CLEARANCE, TYP
BDD
P D
P
D71" CO
EA LOUVER
PROVIDED UNDER
ANOTHER DIVISION.
MOD
12x10 RA
1" CO
1-1/2"
2"
2"
2" PD DN
PD
4 0 4 8
SCALE OF FEET
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
:4 :2
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
THIRD FLOOR -
MECHANICAL NEW WORK
DELAWARE WATER GAP NRA
167005
245920
15 34
M1.3
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
3. ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
ALL TYPES OF VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT DOCUMENTS TO THE
COR FOR RESOLUTION.
4. ALL NEW AND EXISTING OPENINGS CREATED IN ANY WALLS, FLOORS, CEILINGS, ETC. DUE TO DEMOLITION, NEW WORK OR EXISTING CONDITIONS, SHALL BE SEALED TO MAKE VERMIN PROOF.
5. ALL REGRIFERANT PIPING SHALL BE SIZED BY EQUIPMENT MANUFACTURER.
SCALE BM1.3
1 THIRD FLOOR - MECHANICAL - NEW WORK
(APPLICABLE TO THIS DRAWING ONLY)
8x12 OED, ATTIC VENT DUCT, 500 CFM1
NOT USED2
PROVIDE CONDENSATE PUMP, CP-1. EXTEND EMERGENCY
DRAIN PAN BEYOND UNIT TO ALLOW INSTALLATION OF PUMP
WITHIN.
BLANK OFF EXISTING DIFFUSER IN FLOOR4
LOUVER IS LOCATED ABOVE WINDOW ON CLERESTORY LEVEL5
MOUNT DUCT ABOVE THIRD FLOOR RAFTERS6
MOUNT ON FLOOR7
MOUNT ABOVE DOOR8
VD IN VERTICAL9
CUT HOLE IN RECTANGULAR DUCT LARGE ENOUGH SO THAT
ROUGH METAL EDGE DOES NOT PROJECT INTO AIR STREAM.
NOTES:
1. DO NOT USE 45° TAP FITTINGS EXCEPT WHERE TIGHT
CONDITION PREVENTS USE OF OTHER FITTINGS INDICATED.
SPECIAL NOTES:
AIR FLOW
ROUND DUCT
DO NOT USE
BACKWARD BENDING
MITRE OR RADIUS
IMMEDIATELY AFTER TAP
R=D
CONICAL TEE
FITTING WITH
FLANGEROUND DUCT
AIR FLOW
45° TAP FITTING
WITH FLANGE
MITRED 45° TAP
FITTING WITH FLANGE.
TAPOFF FROM RECTANGULAR DUCT TO ROUND DUCT
RECTANGULAR DUCT
RECTANGULAR DUCT
AIR FLOW
CUSHION HEAD
(SUPPLY ONLY) D/2
(MINIMUM 6")
AIR OUTLET
CEILINGD
NOTES:
1. AIR FLOW IS REVERSE FOR RETURN AND EXHAUST.
OUTLET LOCATED AT END OF RUN
AIR FLOW
6" MINIMUM
NOTES:
1. SAME FOR RETURN AND EXHAUST DUCTS
EXCEPT AIR FLOW IS REVERSED.
REGISTER OR DIFFUSER
DIFFUSER OR REGISTER TAPOFF AND TRANSITION
15° MAXIMUM
TAKEOFFS FROM TOP OF RECTANGULAR DUCTS
TOP VIEWTOP VIEW
RADIUS A X B
AIR FLOW
TRANSITION AFTER
TAKEOFF (IF REQUIRED)
SECTION
AIR FLOW
SECTION
D
B
A
R=D
NOTES:
1. BOTTOM TAKEOFFS SIMILAR.
2. SAME FOR RETURN AND EXHAUST DUCTS EXCEPT AIR FLOW IS REVERSED.
SPECIAL NOTES:
15° MAXIMUM
45°
45° TAP PERMITTED FOR DUCTWORK RATED 2" W.G. OR LESS.1
TAPOFF AND TRANSITION FROM SIDE OF DUCT
AIR FLOW
D
R=D (6" MINIMUM)
NOTES:
1. SEE SMACNA MANUAL FOR METHODS OF SECURING TAP-OFF CONNECTION TO MAIN.
2. SAME FOR RETURN AND EXHAUST DUCTS EXCEPT AIR FLOW IS REVERSED.
SPECIAL NOTES:
45° TAP PERMITTED FOR DUCTWORK RATED 2" W.G. OR LESS.
15° MAXIMUM
AIR FLOW
ROUND DUCT
NOTES:
1. FOR AIR FLOW IN OPPOSITE DIRECTION, TRANSITION
COLLAR SHALL OVERLAP EXTERIOR OR ROUND DUCT.
15°
MAXIMUM
RECTANGULAR TO ROUND DUCT TRANSITION
STRUCTURE ABOVE
ROD
DUCT WITH INSULATION
ATTACH
PER
SMACNA
ANGLE
PROTECT DUCT INSULATION
FROM BEING CRUSHED BY
DUCT SUPPORTS
DUCT WITH INSULATION
DUCT STRAP
MAINTAIN VAPOR BARRIER
AT PENETRATION
ATTACH DUCT STRAP
PER SMACNA
NOTES:
1. REFER TO SMACNA FOR ADDITIONAL HANGERS AND SUPPORTS
2. DETAIL FOR HUNG FROM ABOVE ONLY. UNDERSUPPORTS NOT SHOWN.
DUCT INSULATION SUPPORT DETAIL
DOUBLE RADIUS
TURNING VANES
DOUBLE
RADIUS
TURNING VANES
SECTION A-A A
A
DUCT SPLITS
1 2 3
4 5 6
8 9
FAN COIL UNIT PIPING AND DRIP PAN
PROVIDE GALVANIZED
STEEL DRIP PAN UNDER
ALL FLOOR MOUNTED
HEAT PUMP UNITS.
EXTEND DRIP PAN MIN
6" ALL AROUND UNIT,
TYPICAL
3/4" HOSE
BIBB WITH CAP
RESILIENT MOUNTING
PADS, TYP
PD
FLOOR
MIN 3"
FAN COIL
R S R L
D CONDENSATE
PUMP
FLEXIBLE
CONNECTION, TYP
SUPPLY AIR DUCT
RETURN AIR DUCT
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
:4 :2
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
MECHANICAL DETAILS
DELAWARE WATER GAP NRA
167005
245920
16 34
M2.1
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
PLENUM CONNECTION TO EXISTING LOUVER
E X
TE
R
IO
R
W A
LL
E X
TE
R
IO
R
W A
LL
PLENUM
SLOPE
ARCHITECTURAL
LOUVER PROVIDED
UNDER ANOTHER
DIVISION
SEAL AIR AND WATER
TIGHT AROUND PERIMETER
OF PLENUM
CONNECT
BOTTOM OF
PLENUM TO
TOP OF RAIN
STOP
OPENING
FOR
DRAINAGE
CONDENSATE PUMP W/BWV
CO
PD
PD
CONDENSATE PUMP
CO
UNION
D
1. INSTALL IN EMERGENCY DRAIN PAN
PITCH
DEPTH OF SEAL AS
REQUIRED TO
OVERCOME OPERATING
STATIC PRESSURE
DIFFERENTIAL.
SIZE AS INDICATED,
EXCEPT NO SMALLER
THAN DRAIN PAN
NIPPLE.
CLEANOUT PLUG
MINIMUM AS
REQUIRED BY
MANUFACTURER
DRAIN PAN
FCU CONDENSATE DRAIN TRAP4
SUPPLY DIFFUSER RUNOUT DETAIL
1. INSULATED FLEXIBLE DUCT SHALL NOT BE USED TO CHANGE
DIRECTION OF AIR FLOW.
2. MAXIMUM VERTICAL DIFFERENTIAL OF INSULATED FLEXIBLE DUCT
SHALL BE 12".
3. INSULATED FLEXIBLE DUCT CONNECTIONS SHALL BE METAL
BANDED, SEALED AND SUPPORTED TO ALIGN THE CONNECTION
BETWEEN THE INSULATED FLEXIBLE DUCT AND THE SHEETMETAL
DUCT.
NOTES:
SUPPLY AIR DIFFUSER
(SEE PLANS FOR
SIZES AND TYPE)
STRAIGHT,
NO OFFSET
ADJUSTABLE BAND
CLAMP, TYP
FLEXIBLE DUCT
ELBOW SUPPORT
SUPPORT FLEXIBLE
DUCT TO PREVENT
SAGGING
INSULATED FLEXIBLE DUCT
(60" MAXIMUM LENGTH)
INSULATED ROUND DUCT
VD
MIN RADIUS
= DIA
SEAL AND TAPE
INSUL. JOINT
CEILING
SUBMERSIBLE SUMP PUMP
FLOAT SWITCH
PIT
CHECK VALVE
UNION
DISCHARGE
NOPIT COVER
THIRD FLOOR
18' - 1"
ATTIC
26' - 0"
C
DOAS-1
R-2
12x12
14x8 SA
14x14 EA
16x14 OA
14x14 EA 16x14 OA
4x10 OA
14x14 EA
14x14 EA
14x8 SA
BLANK OFF
EX 12x12
OFFICE
MECHANICAL
MAP RM
FC, TYP
10x12 RA
SECOND FLOOR
9' - 1"
THIRD FLOOR
18' - 1"
ATTIC
26' - 0"
RS/L RS/L
6x14 EA
10x8 SA
UNFINISHED
MECHANICAL
GIS OFFICE
MAP RM
8x10 SA
6x14 RA 10x10 EA12x12 OA
6x14 RA
6x14 EA 12x12 OA
2" PD PD
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
:4 :2
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
MECHANICAL DETAILS
AND SECTIONS
DELAWARE WATER GAP NRA
167005
245920
17 34
M2.2
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
SCALE BM2.2
6 DOAS-1 MECHANICAL NEW WORK - SECTION
SCALE B
4 0 4 8
SCALE OF FEET
SCALE BM2.2
7 DUCT CHASE SECTION
A/E FIRM - 140P2021D0003
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
:4 :2
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
MECHANICAL
SCHEDULES
DELAWARE WATER GAP NRA
167005
245920
18 34
M3.1
CEL
MAV
SRH
03/14/2022
CHARLES PEIRCE HOUSE HVAC
DESIGN
VARIABLE REFRIGERANT FAN COIL UNITS
UNIT
NO. TYPE LOCATION ROOMS SERVED UNIT TYPE
SUPPLY FAN
OUTDOOR
AIR CFM
COOLING COIL HEATING COIL ELECTRICAL CONNECTION
NOTESCFM ESP (IN WC)
TOTAL
COOLING
(MBH)
SENSIBLE
COOLING
(MBH)
EAT TOTAL
HEATING
(MBH) EAT DB MCA MOCP VOLTAGE PHASEDB WB
FCU-1 B GIS CLOSET 207 WALL MOUNTED 290 - - 7.9 7.9 75.0 63.0 1.3 70.0 0.4 15 240 1 FCU-2 A BASEMENT 103 HORIZONTAL 800 0.5 290 27.4 20.0 77.7 65.3 19.3 60.7 1.8 15 240 1 FCU-3 A BASEMENT 101, 102, 104, 109, 112 HORIZONTAL 730 0.5 320 28.1 20.3 78.0 65.6 26.8 58.5 2.8 15 240 1 FCU-4A A BASEMENT 104, 105, 106, 107 HORIZONTAL 655 0.5 320 25.2 17.9 78.4 65.9 19.6 56.8 1.6 15 240 1 FCU-4B A BASEMENT 108, 110 HORIZONTAL 580 0.5 0 13.1 12.5 75.0 63.0 9.4 70.0 1.6 15 240 1 FCU-5 A THIRD FLOOR 206 HORIZONTAL 630 0.5 150 20.6 16.1 76.2 64.0 13.3 65.5 1.8 15 240 1 FCU-6 A THIRD FLOOR 201, 205, 208, 209, 210, 212, 213 HORIZONTAL 945 0.5 170 29.2 22.9 76.0 63.8 28.4 66.8 2.8 15 240 1 FCU-7 A THIRD FLOOR 202, 203, 204, 211 HORIZONTAL 890 0.5 150 30.2 30.2 75.8 63.7 21.9 67.1 2.9 15 240 1 FCU-8 B BASEMENT 001 WALL MOUNTED 245 - - 5.6 5.6 75.0 63.0 10.7 70.0 0.3 15 240 1 FCU-A B THIRD FLOOR ATTIC MECH ROOM WALL MOUNTED 280 - - 15.6 15.6 75.0 63.0 19.1 70.0 0.6 15 240 1 FCU-B A BASEMENT BASEMENT HORIZONTAL 380 0.5 25 12.0 9.3 75.0 63.0 7.9 68.8 1.6 15 240 1
VARIABLE REFRIGERANT AIR COOLED OUTDOOR HEAT PUMP UNITS
UNIT NO LOCATION UNITS SERVED
CAPACITY ELECTRICAL
NOTES
COOLING HEATING
COOLING
INPUT KW
HEATING
INPUT KW VOLTAGE PHASE HERTZTOTAL MBH
CONDENSER
EAT
TOTAL
MBH
CONDENSER
EAT
HPU-1 ON GRADE FCU 1, 2, AND 5 55.9 88 33.9 0 5.8 4.18 240 1 60
HPU-2 ON GRADE FCU 3 AND 6 57.3 88 55.2 0 5.8 4.18 240 1 60
HPU-3 ON GRADE FCU 4A AND 7 55.4 88 41.5 0 5.8 4.18 240 1 60
HPU-4 ON GRADE FCU A, B, 4B, AND 8 46.3 88 47.1 0 4.73 4.26 240 1 60
DEDICATED OUTDOOR AIR SYSTEM UNITS
UNIT
NO LOCATION SERVICE
FILTERS FANS ENERGY RECOVERY WHEEL
NOTESPRE FINAL
OA
CFM
EA
CFM
OA
ESP
OA
TSP
OA
HP
EA
ESP
EA
TSP
EA
HP
SUMMER WINTER
SUPPLY AIR EXHAUST AIR SUPPLY AIR EXHAUST AIR
EAT
DB
EAT
WB
LAT
DB
LAT
WB
EAT
DB
EAT
WB
LAT
DB
LAT
WB
EAT
DB
EAT
WB
LAT
DB
LAT
WB
EAT
DB
EAT
WB
LAT
DB
LAT
WB
DOAS-1 ATTIC ALL FLOORS - D 1,435 895 1.0 1.25 1.5 1.0 1.06 0.75 95.0 78.0 83.1 70.0 75.0 62.5 - - 0.0 -1.0 38.8 22.7 70.0 54.3 - -
FANS
UNIT
SYMBOL TYPE LOCATION SERVICE CFM CLASS TSP
MOTOR HP
(WATTS) NOTES
EF-2 L 109 WORK ROOM EXHAUST 150 I 0.3 128 WATTS
EF-3 L 107 CLEAN ROOM EXHAUST 150 I 0.3 128 WATTS
FAN-1 P THIRD FLOOR THIRD FLOOR 500 I 0.3 0.25
FAN-2 P THIRD FLOOR THIRD FLOOR 500 I 0.3 0.25
PUMPS
UNIT NO TYPE LOCATION SERVICE FLUID GPM FPD HP NOTES
CP-1 P FCU'S AND ACU'S CONDENSATE WATER 0.5 15 1/30
PUMP-1 M BASEMENT SUMP PIT WATER 50 22 3/4
NOTES FOR CONDENSATE PUMPS:
1 PROVIDE LITTLE GIANT MODEL VCMA-15ULS OR APPROVED EQUAL.
2 MOUNT IN EMERGENCY DRAIN PAN
1 2
NOTES FOR VARIABLE REFRIGERANT FAN COIL UNITS:
1 R-410A REFRIGERANT
1 22
NOTES FOR VARIABLE REFRIGERANT AIR COOLED OUTDOOR HEAT PUMP UNITS:
1 R-410A REFRIGERANT
2 REFRIGERANT PIPE SIZES AND ROUTING, REFRIGERANT CHARGE, ETC., SHALL ALL BE PROVIDED BY THE MANUFACTURER.
ELECTRIC DUCT HEATERS
UNIT NO LOCATION FCU SERVED
ELECTRICAL
NOTES
HEATING
INPUT KW VOLTAGE PHASE HERTZ
EDH-2 BASEMENT FCU-2 1.5 120 1 60
EDH-3 BASEMENT FCU-3 1.5 120 1 60
EDH-4 BASEMENT FCU-4 2.5 120 1 60
EDH-5 THIRD FLOOR FCU-5 1.5 120 1 60
EDH-6 THIRD FLOOR FCU-6 1.5 120 1 60
EDH-7 THIRD FLOOR FCU-7 1.5 120 1 60
EDH-B BASEMENT FCU-B 1.0 120 1 60
NOTES FOR ELECTRIC DUCT HEATERS:
1 PROVIDE SINGLE STAGE OF HEAT
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
:4 :3
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
MECHANICAL
SCHEDULES
DELAWARE WATER GAP NRA
167005
245920
19 34
M3.2
CEL
MAV
SRH
03/14/2022
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
ELECTRICAL
HENRY ADAMS
BALTIMORE, MD
MECHANICAL
HENRY ADAMS
BALTIMORE, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
:4 :3
A M
B
IM
N P S
D E W A
C h a rl e s P e ir c e
H o u se
H V A C
D e si g n P e ir c e
H o u se
M e c h
C e n tr a l
R e vi t le b ro .r vt
MECHANICAL
SCHEDULES
DELAWARE WATER GAP NRA
167005
245920
20 34
M3.3
CEL
MAV
SRH
03/14/2022
RS
RL
FAN COIL
UNIT
DOAS-1
HPU
VRF
SYSTEM
CONTROL
PANEL
RETURN AIRSUPPLY AIR
OUTDOOR AIR
EXHA…