PPIs-Amd0002_0002.pdf

PDF 107 KB Posted

Attached to
INDE - IDS ALARM REPLACEMENT Federal contract opportunity
Solicitation number
140P4323Q0073
Issued by
Department of the Interior National Park Service Northeast Region

About this file

This document contains questions and answers related to solicitation number 140P4323Q0073 for an INDE alarm replacement project for the Department of the Interior National Park Service Northeast Region. The requirement is for the installation of twenty alarm panels as specified in the Performance Work Statement. Existing conduit may be used for new wire runs. Plenum wire is acceptable. There is pipe chase connection between floors. Highly recommend including a UPS with 12 hours of battery backup. The existing Genetec contract for cameras lapsed in January 2021. The project does not include exterior cameras or new access control systems. All systems must meet NIST cybersecurity standards. A site visit will be held on August 15, 2023 to answer questions about ceiling types and alarm panel locations. Equipment substitutions will not be allowed. After hours access must be coordinated with NPS.

View the file

Other files for this federal contract opportunity

Other files attached to INDE - IDS ALARM REPLACEMENT, newest first.
File Type Posted
Amendment0006_0006.pdf PDF
Sol_140P4323Q0073_Amd_0006.pdf PDF
Sol_140P4323Q0073_Amd_0005.pdf PDF
Amd0004_0004.pdf PDF
A05_INDE_IDS_PWS-Amd4_0004.pdf PDF
Sol_140P4323Q0073_Amd_0004.pdf PDF
Amd0003_0003.pdf PDF
Sol_140P4323Q0073_Amd_0003.pdf PDF
Sol_140P4323Q0073_Amd_0002.pdf PDF
Sol_140P4323Q0073_Amd_0001.pdf PDF
A05_INDE_IDS_PWS_0001.pdf PDF
A05_INDE_IDS_PWS.docx DOCX document
B03_WD_INDE_2015-4233_Rev27_6_30_23.pdf PDF
Sol_140P4323Q0073.pdf PDF
A06_INDE_MAP_Panel_Locations.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INDE Alarm Replacement, Solicitation 140P4323Q0073

Amendment 0002

The PWS has been attached as an adobe document on Amendment 0001

Question 1: Are Scaled Drawings available, if so please post.

Government response: Per PWS 1.1 technical, Specific locations of the IDS will be given upon contract award. Note: To scale building drawings will depend on availability.

Question 2: Are Ceilings Suspended? Or Hard Lid?

Government response: This will be able to be answered at the site visit on 8/15/2023 at 10:00AM

EDT.

Question 3: Is there existing Cable Trays for wiring above ceilings?

Government response: No.

Question 4: Can Existing Wiring be utilized?

Government response: Yes

Question 5: Is a “UPS” required? If so, What Time/Power Duration is required?

Government response: Highly recommend. 12 hours.

Question 6: Are “Or Equal” Equipment substitutions allowed?

Government response: Equipment has been specified for the, Digital Monitoring Panel (DMP)

XR550, this is specified in the PWS. Substitutions will not be allowed.

Question 7: Is “Plenum Wire” acceptable?

Government response: Yes, plenum wire is acceptable.

Question 8: Is “After Hours Access” for said work, available to contractor at no additional cost to the

Government?

Government response: There will be extremely little in terms of afterhours support. If after hour work is being done in Independence Hall compound and the Liberty Bell Center, it will have to be coordinated with NPS.

Question 9: What is the height of Exterior Cameras? (If any)

Government response: This requirement does not include cameras.

Question 10: Please provide a list of equipment to be installed.

Government response: Alarm Panels per the PWS is the only equipment needed for install on this requirement.

Question 11: Is there an incumbent vendor who has been servicing the existing system?

Government response: No. NPS does not have a servicing contract for the existing system. There was a SMA with Genetec for cameras that lapsed. NextGen is the system integrator. Current work is paid for when purchased.

Question 12: If so, what is the most current contract number and amount?

Government response: The Genetec System ID is GSC-151028-374907. The Genetec contract number is 01-3174-1015. Genetec Advantage expired on Jan 31st, 2021.

Question 13: Is there any requirement for the readers to be FICAM-compliant?

Government response: Equipment has been specified for the, Digital Monitoring Panel (DMP)

XR550, this is specified in the PWS. This requirement is only for Alarm panels this is NOT for cameras or access control systems.

Question 14: Are there any requirements for the system to be cyber-secure?

Government response: This is a closed system, but all systems implemented should follow NIST standards.

Question 15: Is there existing conduit, if so, can it be used for the new wire runs?

Government response: Yes, there is existing conduit.

Question 16: If new conduit is needed, please show on the drawings with approximate footage.

Government response: This requirement is for the installation of twenty (20) alarm panels as indicated in the PWS.

Question 17: Is there pipe chase connection between the floors?

Government response: Yes