Text version

AB111

BASEMENT ABATEMENT PLAN- PHASE 2

FINAL

SUBMITTAL

U

S

D

A

AB112

FIRST FLOOR ABATEMENT PLAN- PHASE 2

FINAL

SUBMITTAL

U

S

AD111

BASEMENT DEMOLITION PLAN- PHASE 2

FINAL

SUBMITTAL

U

S

AD112

FIRST FLOOR DEMOLITION PLAN- PHASE 2

FINAL

SUBMITTAL

U

S

AD113

BASEMENT DEMOLITION RCP- PHASE 2

FINAL

SUBMITTAL

U

S

A111

BASEMENT PLAN- PHASE 2

FINAL

SUBMITTAL

U

S

A112

FIRST FLOOR PLAN- PHASE 2

FINAL

SUBMITTAL

U

S

A113

ROOF PLAN- PHASE 2

FINAL

SUBMITTAL

U

S

TOILET ACCESSORY SCHEDULE

A211

LARGE SCALE PLANS & INTERIOR

ELEVATIONS- PHASE 2

FINAL

SUBMITTAL

U

S

PHASE 2 BASEMENT ROOM FINISH SCHEDULE

ROOM NO. ROOM NAME FLOOR BASE

N E S W

WALLS

MATL HEIGHT

CEILING

REMARKS

PHASE 2 FIRST FLOOR ROOM FINISH SCHEDULE

ROOM NO. ROOM NAME FLOOR BASE

N E S W

WALLS

MATL HEIGHT

CEILING

REMARKS

A611

ROOM FINISH SCHEDULE AND DETAILS-

PHASE 2

FINAL

SUBMITTAL

U

S

SCHEMATIC SYMBOLS

PLUMBING SYMBOL LEGEND

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS APPLY TO THIS PROJECT

ABBREVIATIONS

VALVE SYMBOLS

PIPING SYMBOLS

SITE UTILITY SYMBOLS

SECTION SYMBOL

DETAIL SYMBOL

SECTION, ELEVATION, AND DETAIL TITLES

FIXTURE & EQUIPMENT SYMBOL

PLUMBING SYMBOL LEGEND

P001

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

Mesa, AZ 85210

602.996.6399 www.bpce.com

PLUMBING PLAN BASEMENT LEVEL - DEMOLITION WASTE & VENT PIPING PHASE II

PLUMBING PLAN BASEMENT

LEVEL-DEMOLITION WASTE & VENT PIPING

PD100

DEMOLITION GENERAL NOTES

DEMOLITION KEY NOTES

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

PLUMBING PLAN FIRST LEVEL - DEMOLITION WASTE & VENT PIPING PHASE I

PLUMBING PLAN FIRST LEVEL - DEMOLITION

WASTE & VENT PIPING

PD101

DEMOLITION GENERAL NOTES

DEMOLITION KEY NOTES

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

PLUMBING PLAN BASEMENT LEVEL - DEMOLITION WATER PIPING PHASE I & II

PLUMBING PLAN BASEMENT LEVEL -

DEMOLITION WATER PIPING

PPD100

DEMOLITION GENERAL NOTES

DEMOLITION KEY NOTES

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

EP1

EP2

PLUMBING PLAN BASEMENT LEVEL - NEW WASTE & VENT PIPING PHASE II

PLUMBING PLAN BASEMENT LEVEL - NEW

WASTE & VENT PIPING

PL100

GENERAL NOTES

KEY NOTES

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

SK

SK

SK

SK

SK

SK

SK

SK

SKSK

SK

SK

SK

SK

SK

SK

SK

SK

CS

CS

CS

CS

CS

CS

CS

CS

CS

CS

CS

CS

CS

CS

CS

CO

SK

3" FD3" FD

CS

3" FD

3" FD

CO

CS

SK

CS

CS

CS

CS

SK

CO

CO

PLUMBING PLAN FIRST LEVEL - NEW WASTE & VENT PIPING PHASE I

PLUMBING PLAN FIRST LEVEL - NEW WASTE

& VENT PIPING

PL101

GENERAL NOTES

KEY NOTES

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

SECTION/ELEVATION

PLAN VIEW

C2

SEWAGE EJECTOR DETAIL DOMESTIC WATER HEATER DETAIL

C3

D1

FLOOR CLEANOUT

C1

CIRCUIT SOLVER ASSEMBLY DETAIL

PLUMBING DETAILS

P501

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

A2

WASTE AND VENT SCHEMATIC

A1

ISLAND WASTE AND VENT DETAIL

B1

WASTE SCHEMATIC - BASEMENT

A4

WASTE SCHEMATIC -MECHANICAL ROOM - BASEMENT

D4

WASTE SCHEMATIC -MECHANICAL ROOM - BASEMENT

PLUMBING SCHEMATICS

P601

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

C4

WASTE SCHEMATIC LAB ROOM

C3

WASTE SCHEMATIC LAB ROOM

C2

WASTE SCHEMATIC LAB ROOM

C1

WASTE SCHEMATIC LAB ROOM

A1

WASTE SCHEMATIC LAB ROOM

A2

WASTE SCHEMATIC LAB ROOM

PLUMBING SCHEMATICS

P602

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

LOCATE AT THE END OF THE BRANCH LINE BETWEEN THE LAST

FIXTURES AND ANOTHER BRANCHES OVER 20 FEET IN LENGTH.

BASED ON J.R. SMITH.

WATER HAMMER ARRESTOR SCHEDULE

ZURN AND MIFAB ARE ACCEPTABLE MANUF.

PROVIDE WALL ACCESS PANEL.

EXISTING PLUMBING FIXTURE AND PIPING DEMO SCHEDULE (REFERENCE ONLY)

SYMBOL

ROUGH-IN SIZE

TRAP REMARKSCW HW WASTE V

(E)P1

WATER CLOSET - FLOOR MTD. -

FLUSH VALVE

1" - 4" 2" INTEGRAL

FIXTURE TO REMAIN, WASTE AND VENT PIPING, WASTE ARM & RING ALONG

WITH THE COLD WATER PIPING INCLUDING THE FLUSH VALVE TO BE REMOVED.

(E)P2

URINAL - WALL MTD. - FLUSH

VALVE

3/4" - 2" 2" INTEGRAL

(E)P3 1/2" 1/2" 2" 1-1/2" 1-1/4" X 1-1/2"

(E)P4 SERVICE SINK (FLR MTD) 1/2" 1/2" 3" 2" 3"

SERVICE SINK 3/4" 3/4" 3" 2" 3"

(E)P8 SINK (BASEMENT)

1/2" 1/2" 2" 2" 1-1/2"

(E)P7

FLOOR MOUNTED TANK TYPE

WATER CLOSET

3/4"

- 4" 2" 2"

LAVATORY - WALL MTD.

(E)P5

- 2"1/2" 2"

ELECT.WATER COOLER

FIXTURE TO REMAIN, EXISTING 2" WASTE, 1-1/2" VENT PIPING AND TRAP TO BE

REMOVED ALONG WITH THE WATER PIPING AND STOP.

1-1/4" X 1-1/2"

FIXTURE & FAUCET TO REMAIN, WASTE, TRAP AND VENT PIPING, ALONG WITH

THE COLD WATER PIPING INCLUDING THE STOPS AND RISER TO BE REMOVED.

FIXTURE TO REMAIN, WASTE AND VENT PIPING, ALONG WITH THE COLD WATER

PIPING INCLUDING THE FLUSH VALVE TO BE REMOVED.

FIXTURE & FAUCET TO REMAIN, WASTE, TRAP AND VENT PIPING, ALONG WITH

THE COLD WATER PIPING INCLUDING THE STOPS AND RISER TO BE REMOVED.

(E)P6

1/2" 1/2" 2" 1-1/2" 1-1/2" X 1-1/2"

COUNTER TOP SINK

FIXTURE & FAUCET TO REMAIN, WASTE, TRAP AND VENT PIPING, ALONG WITH

THE COLD WATER PIPING INCLUDING THE STOPS AND RISER TO BE REMOVED.

FIXTURE & FAUCET TO REMAIN, WASTE, TRAP AND VENT PIPING, ALONG WITH

THE COLD WATER PIPING INCLUDING THE STOPS AND RISER TO BE REMOVED.

(E)P9

FIXTURE & FAUCET TO REMAIN, WASTE, TRAP AND VENT PIPING, ALONG WITH

THE COLD WATER PIPING INCLUDING THE STOPS AND RISER TO BE REMOVED.

FLOOR DRAIN

- 2" 2" 2"

FLOOR DRAIN TO REMAIN, EXISTING WASTE PIPING TO BE REMOVED. SEE NEW

PIPING PLAN.

(E)FD

LAB SINK 3/4"

3/4"

(E)SK

CUP SINK

3/4"

- 2" 1-1/2" 1-1/2"

EXISTING CUP SINK TO REMAIN, EXISTING WASTE, VENT AND WATER PIPING TO

BE REMOVED. SEE NEW PIPING PLAN.

(E)CS

FIXTURE TO REMAIN, WASTE AND VENT PIPING, WASTE ARM & RING ALONG

WITH THE COLD WATER PIPING INCLUDING STOP AND RISER TO BE REMOVED.

2" 2" 1-1/2"

SINK TO REMAIN, WASTE, TRAP AND VENT PIPING, ALONG WITH THE COLD AND

HOT WATER PIPING INCLUDING THE STOPS AND RISER TO BE REMOVED.

NOTE: UNLESS NOTED OTHER WISE ALL FAUCETS SHALL REMAIN, ONLY THE STOPS, RISERS AND TRAP TO BE REPLACED.

DOUBLE COMPARTMENT SINK

3/4"

2" 2" 2"(E)P10

FIXTURE TO REMAIN, WASTE AND VENT PIPING, WASTE ARM & RING ALONG

WITH THE WATER PIPING INCLUDING STOPS AND RISERS TO BE REMOVED.

3/4"

WALL HYDRANT

3/4"

HYDRANT TO REMAIN, EXISTING WATER PIPING TO BE REMOVED. SEE NEW

PIPING PLAN.

(E)WH

SEWAGE EJECTOR PUMP SCHEDULE

NEW DISCHARGE PIPE SHALL TERMINATE AT THE NEW SANITARY PIPING LOCATED IN CEILING OF BASEMENT.

ZOELLER DUPLEX

SEWAGE EJECTOR

SYSTEM MODEL NO. 840

NEW EQUIPMENT, INCLUDING CONTROL PANELS, ALARMS. SHALL BE INSTALLED PER MANUFACTURE RECOMMENDATION.

3 PLUMBING CONTRACTOR SHALL VERIFY ALL NEW ELECTRICAL EQUIPMENT TO BE ADEQUATE FOR THE INSTALLATION OF NEW PUMPS.

EXISTING EQUIPMENT WILL BE REMOVED AND REPLACED, ELECTRICAL CONTRACTOR SHALL DISCONNECT AND RECONNECT

WIRING TO ALL EQUIPMENT. EXTEND EXISTING WIRING TO EQUIPMENT AS REQUIRED.

1 3

1 3

ZOELLER DUPLEX

SEWAGE EJECTOR

SYSTEM MODEL NO. 840

EMERGENCY SHOWER

1"

WATER FROM BASEMENT.

(E)ESW

DUPLEX

PUMPS

SUBMERSIBLE

DUPLEX

PUMPS

SUBMERSIBLE

38 23

23 36X48

36x60 2

2 3450

3450 230/3

230/3

VOLT/PH.RPMHPBASIN

HEAD

(FT)

GPM

CAPACITY

TYPELOCATION

MECHANICAL

ROOM

BASEMENT

BASEMENT

MANUFACTURER

MODEL NO.

REMARKSSERVICETAG

EP-1

SANITARY /

WASTE

SANITARY /

WASTE

EP-2

NOTES:

EXISTING

FIXTURE

NOTES:

21 3 4

J.R. SMITH

MODEL No.

P.D.I

SYMBOL

FIXTURE

UNIT RATING

A

SIZE

REMARKS

5040 E

D

C

B

A 1-11

12-32

33-60

61-113

114-154 1

3/4

21 3 4

21 3 4

21 3 4

FLOOR SINK

- 3" 2" 3" FLOOR SINK EQUAL TO "JR SMITH" MODEL NO 3150Y 12"X12"x 6" DEEP SUMP.

(N)FS

DISTILLED WATER EQUIPMENT

VOLT/PH.

GPM

CAPACITY

LOCATION

MANUFACTURER

MODEL NO.

SERVICETAG REMARKS

DSE-1

LAB

ROOMS

MECHANICAL

ROOM

10 240/1

PURE WATER NO.

C6O/75

TOTAL SOLIDS BETWEEN 0.3 -3 PPM

GAS

MBH

300,000 - 800,000

OHMS

ELECTRICAL

RESISTANCE

PLUMBING CONTRACTOR SHALL VERIFY ALL NEW ELECTRICAL EQUIPMENT TO BE ADEQUATE FOR THE INSTALLATION OF NEW PUMPS.

EXISTING EQUIPMENT WILL BE REMOVED AND REPLACED, ELECTRICAL CONTRACTOR SHALL DISCONNECT AND RECONNECT WIRING

TO ALL EQUIPMENT. EXTEND EXISTING WIRING TO EQUIPMENT AS REQUIRED.

PLUMBING SCHEDULES

DETAILS & SCHEMATIC'S

P702

FINAL

SUBMITTAL

U

S

D

A

1839 South Alma School Road., Suite 300

Sheets and Views
AB111 BASEMENT ABATEMENT PLAN- PHASE 2
BASEMENT ABATEMENT PLAN
ABATEMENT PLAN LEGEND
AB112 FIRST FLOOR ABATEMENT PLAN- PHASE 2
FIRST FLOOR ABATEMENT PLAN
ABATEMENT PLAN LEGEND
ABATEMENT DSICLAIMER
AD111 BASEMENT DEMOLITION PLAN- PHASE 2
BASEMENT DEMOLITION PLAN
DEMOLITION PLAN LEGEND
Plan Legend
DEMOLITION PLAN NOTES
AD112 FIRST FLOOR DEMOLITION PLAN- PHASE 2
FIRST FLOOR DEMOLITION PLAN
DEMOLITION PLAN LEGEND
Plan Legend
DEMOLITION PLAN NOTES
AD113 BASEMENT DEMOLITION RCP- PHASE 2
BASEMENT DEMOLITION RCP
EXISTING RCP LEGEND
DEMOLITION RCP LEGEND
A111 BASEMENT PLAN- PHASE 2
BASEMENT PLAN
Plan Legend
NEW WORK LEGEND
FLOOR PLAN NOTES
A112 FIRST FLOOR PLAN- PHASE 2
FIRST FLOOR PLAN
Plan Legend
NEW WORK LEGEND
FLOOR PLAN NOTES
A113 ROOF PLAN- PHASE 2
ROOF PLAN
VENT STACK DEMOLITION DETAIL
VENT STACK DETAIL
ROOF LEGEND
A114 BASEMENT RCP- PHASE 2
BASEMENT RCP
EXISTING RCP LEGEND
RCP LEGEND
A211 LARGE SCALE PLANS & INTERIOR ELEVATIONS- PHASE 2
TOILET ACCESSORY SCHEDULE
TOILET 013 WEST ELEVATION
TOILET 013 SOUTH ELEVATION
TOILET 013 EAST ELEVATION
TOILET 013 NORTH ELEVATION
INTERIOR ELEVATION KEY NOTES
013 TOILET DEMOLITION PLAN
013 TOILET PLAN
TRENCH SECTION DETAIL
A611 ROOM FINISH SCHEDULE AND DETAILS- PHASE 2
ROOM FINISH SCHEDULE
Partition Types
DOOR TYPES
G001 COVER SHEET- PHASE 2
COVER SHEET
Phase 2 7933P-001_pe.pdf
Sheets and Views
7933P-001-P-001
7933P-100-PD100
7933P-101-PD101
7933P-100-PPD101
7933P-100-PL-100
7933P-101-PL-101
7933P-100-PP100
7933P-101-PP-101
7933P-500 & 600-P-501
7933P-500 & 600-P-601
7933P-500 & 600-P-602
7933P-701-P702