Solicitation (RFQ) – 12805B20Q0161- Boiler Replacement

USDA ARS Akron, CO

Questions & Answers

Answers are in Red:

1. What controller is currently serving this boiler and what control points are existing? Please provide panel or node and/or Siemens as built with project number. Siemens Controls, Node 1.

2. Is there currently a BACnet connection? If not, will Siemens be required to integrate into new boiler? No BACnet connection directly to the Boiler. The current Boiler is controlled by a hard wired enable system that communicates to Node 1, an Ethernet panel. A BACnet panel that runs the Chiller is available for boiler points, but the boiler enabled points are to be hard wired from the boiler to communicate directly with the Ethernet Panel. All none-enabled boiler points are to be connected to the BACnet panel, which is connected to the

Siemens Controls Ethernet panel.

Yes, Contractor will need to hire a Siemens Technicians to integrate and program the existing Siemens Building Automation System for the new Boiler.