UNITED STATES DEPARTMENT OF AGRICULTURE

AGRICULTURAL RESEARCH SERVICE

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AMES, IOWA

FINAL TURNOVER

LSY PROJECT NO. 17060

USDA CONTRACT NO. AG-32SC-D-17-0278

ABBREVIATIONS, SYMBOLS & MATERIAL INDICATIONS LOCATION MAPINDEX OF DRAWINGS

U

S

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

VICINITY MAP

PROJECT AREAPROJECT AREA

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129 --

G-001

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

PROJECT COVER SHEET & INDEX

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

FINAL TURNOVERRLP06/22/18

I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Iowa.

06/22/2018

(signature) (date)

Printed or typed name Robert T. Darnell

License number 23863

My license renewal date is December 31, 2018

Pages or sheets covered by this seal:

G-001, M-001, M-002, MD101, MD102, MD201, MD202, MH101, MH102,

MP101, MP102,M-501, M-601

GENERAL

MECHANICAL

G-001 PROJECT COVER SHEET & INDEX

M-001 MECHANICAL GENERAL NOTES, LEGENDS, AND ABBREVIATIONS

M-002 HVAC HOT WATER HEATING ZONES - SUITES 2 THRU 5

MD101 MECHANICAL DEMOLITION PLAN - SUITES 4 & 5

MD102 MECHANICAL DEMOLITION PLAN - SUITES 2 & 3

MD201 HOT WATER HEATING PIPING DEMOLITION - MEZZANINE SUITES 4 & 5

MD202 HOT WATER HEATING PIPING DEMOLITION - MEZZANINE SUITES 2 & 3

MH101 MECHANICAL PLAN - MEZZANINE SUITES 4 & 5

MH102 MECHANICAL PLAN - MEZZANINE SUITES 2 & 3

MP101 HOT WATER HEATING PIPING PLAN - MEZZANINE SUITES 4 & 5

MP102 HOT WATER HEATING PIPING PLAN - MEZZANINE SUITES 2 & 3

M-501 MECHANICAL DETAILS, SCHEDULES, AND CONTROLS

M-601 HOT WATER HEATING PIPING DIAGRAM

GENERAL NOTES:

PIPE LINE ACCESSORIES

WITH EQUIPMENT

COMPONENTS TO BE FURNISHED

HVAC LEGEND

DETAIL/SECTION TITLE

NUMBER = DETAIL DESIGNATOR

LETTER = SECTION DESIGNATOR

DETAIL

SECTION CUT SYMBOL

SECTION

DESIGNATOR

INDICATES PERSPECTIVE

AND LIMITS OF SECTION

DETAIL/ENLARGED CALLOUT SYMBOL

INDICATES

LIMITS OF

DETAIL/SECTION

DETAIL/SECTION

DESIGNATOR

DRAWING WHERE

DETAIL/SECTION IS TAKEN

DRAWING WHERE

SECTION IS DRAWN

DRAWING WHERE

DETAIL/SECTION IS

DRAWN

CONSTRUCTION INTERFACE

EXISTING

NEW

DEMOLITION

MECHANICAL ABBREVIATIONS

GATE VALVE

OS&Y

OUTSIDE SCREW & YOKE

BUTTERFLY VALVE

CHECK VALVE

3-WAY VALVE

BALL VALVE

PDV

PUMP DISCHARGE VALVE

BALANCING VALVE

RELIEF, SAFETY OR THERMAL RELIEF VALVE

CONTROL VALVE

M

MOTORIZED CONTROL VALVE

SUCTION DIFFUSER

AV

AUTOMATIC AIR VENT ASSEMBLY

MV

MANUAL AIR VENT - SEE SPECIFICATIONS

FOR APPROPRIATE VALVE TYPE.

FLEX CONNECTION

THERMOMETER

BP

BACKFLOW PREVENTION ASSEMBLY

SELF CONTAINED PRESSURE

REDUCING (REGULATING) VALVE

PRESSURE GAUGE

Y-TYPE STRAINER

REMOVABLE CAP

REDUCER (CONCENTRIC)

REDUCER (ECCENTRIC)

UNION

BLIND FLANGE

TEST CONNECTION

M

METER

PUMP

A

M-001

A

M-001

A

M-003

HOSE GATE VALVE DRAIN

GLOBE VALVE

ANGLE VALVE

PLUG VALVE

DBB

DOUBLE BLOCK &

BLEED PLUG VALVE

IF

INSULATING FLANGE

REMOVABLE PLUG

PIPE WITH HEAT TRACE

S

STRAINER

M

CONTROL DAMPER, MOTOR

OPERATED

MANUAL BALANCE DAMPER

BD

BACKDRAFT DAMPER

AD

AD

ACCESS DOOR (AD)

ACCESS PANEL (AP)

S

AD

S

DAMPERS:

SMOKE (SD) -

FIRE SMOKE (F/SD) -

SECURITY BARS

FLEXIBLE DUCT CONNECTION

RECTANGLUAR ELBOW WITH

TURNING VANES

RECTANGULAR TEE WITH

TURNING VANES

RECTANGULAR RADIUS ELBOW

R

RISE IN RESPECT TO AIR-FLOW

D

DROP IN RESPECT TO AIR-FLOW

SQUARE OR RECTANGULAR TO

ROUND TRANSITION

SUPPLY AIR OR OUTSIDE AIR

DUCT SECTION

RETURN AIR DUCT SECTION

EXHAUST AIR DUCT SECTION

ROUND FLEXIBLE DUCT

(5'-0" MAX LENGTH)

SQUARE OR RECTANGULAR

SUPPLY DIFFUSER

RETURN AIR DIFFUSER

EXHAUST AIR DIFFUSER

T

THERMOSTAT

CO2

CARBON DIOXIDE MONITOR

H

HUMIDISTAT

LINEAR SLOT DIFFUSER

VAV-

VARIABLE AIR VOLUME

TERMINAL BOX

(3'-0")

FINNED TUBE RADIATION.

LENGTH OF ELEMENT SHOWN IN

PARENTHESIS

ESS

EMERGENCY SHUT-OFF SWITCH

M

MOTOR

CF

CEILING FAN CONTROL PANEL

NEW

EXISTING

1. LEGEND IS GENERAL IN NATURE AND MAY INDICATE MORE INFORMATION THAN IS APPLICABLE TO PROJECT. SEE PLANS FOR

SPECIFIC SYMBOLS AND ABBREVIATIONS.

2. PROVIDE ALL MATERIALS, VALVES, HANGERS, ETC. AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL

COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY

CODE.

3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.

4.

5.

MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, CONDUITS, ETC., THROUGHOUT ACCESS ROUTES AND IN

MECHANICAL ROOMS.

6.

LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, CONTROLS, AND VALVING.

7.

VERIFY DIMENSIONS AND CONNECTION SIZE WITH FURNISHED EQUIPMENT.

8.

ALL ELEVATIONS ARE ABOVE FINISHED FLOOR TO BOTTOM OF DUCT, PIPE, OR PIPE INSULATION UNLESS NOTED OTHERWISE.

DUCT DIMENSIONS INDICATED REFER TO SHEET METAL DIMENSIONS. SHEET METAL SIZE SHALL BE AIR OPENING DIMENSION

PLUS THE THICKNESS OF ACOUSTICAL LINER WHERE LINER IS INSTALLED. WHERE LINER IS NOT INSTALLED, AIR OPENING SIZE

AND SHEET METAL SIZE SHALL BE THE SAME.

ALL EXISTING DUCTWORK SHOWN ON DRAWINGS IS SCHEMATIC AND ARE BASED ON EXISTING RECORD DRAWINGS PROVIDED

BY THE OWNER AND DO NOT REFLECT EXACT EXISTING CONDITIONS. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS

ON JOB SITE. CONTRACTOR SHALL REROUTE NEW WORK TO ACCOMMODATE EXACT LOCATIONS OF EXISTING UTILITIES, STUB-OUTS, AND/OR CONNECTIONS.

IA INSTRUMENT AIR

INVT EL INVERT ELEVATION

L LOUVER

LR LONG RADIUS

MA MIXED AIR

MJ MECHANICAL JOINT

MW MAKE-UP WATER (AFTER BACKFLOW

PREVENTER)

MW MAKE-UP WATER (AFTER BACKFLOW

PREVENTER)

NC NORMALLY CLOSED (FAIL POSITION)

NG NATURAL GAS

NO NORMALLY OPEN (FAIL POSITION)

OA OUTSIDE AIR

OB OPPOSED BLADE

OD OVERFLOW DRAIN

PB PARALLEL BLADE

PCR PUMP CONDENSATE RETURN

PCW PROCESS COLD WATER

PFX PLATE AND FRAME HEAT EXCHANGER

PSIA POUNDS PER SQUARE INCH ABSOLUTE

PSIG POUNDS PER SQUARE INCH GAUGE

R RELIEF LINE

RA RETURN AIR

RED REDUCER-REDUCING

RG REFRIGERANT HOT GAS DISCHARGE

RL EFRIGERANT LIQUID

RMJ RESTRAINED MECHANICAL JOINT

RS REFRIGERANT SUCTION

SA SUPPLY AIR

SCH SCHEDULE

SCR SPRING RETURN CLOSED

SHR SHORT RADIUS

SO SLIP ON

SP STATIC PRESSURE SENSOR

SR SUPPLY REGISTER

ST STEAM TRAP

STM STEAM

SW SOCKET WELD

TA TRANSFER AIR

TOD TOP OF DUCT

TOS TOP OF STEEL

UH UNIT HEATER

V VENT

12"Ø ROUND DUCT DIMENSION

24x1 RECTANGULAR DUCT DIMENSION (INCHES)

24x12 RECTANGULAR DUCT DIMENSION (INCHES)

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ARF ABOVE RAISED FLOOR

ARV AIR RELEASE VALVE

BBO BOILER BLOW-OFF

BLWDN BLOWDOWN

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BP BOOSTER PUMP

BPP BOILER PRIMARY PUMP

BW BUTT WELD

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CL CENTER LINE OF PIPE ELEVATION

CONC CONCENTRIC

COND COOLING COIL CONDENSATE DRAIN

CR CONDENSATE RETURN

CT CHEMICAL TREATMENT

CTB COOLING TOWER BLOWDOWN

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

D DRAIN

DN DOWN

DRG DIFFUSER, REGISTER, GRILLE

EA EXHAUST AIR

EF EXHAUST FAN

EG EXHAUST GRILLE

EL ELEVATION

ELL ELBOW

ER EXHAUST REGISTER

ET EXPANSION TANK

EXIST EXISTING

F FAN

FCU FAN COIL UNIT

FD FEEDWATER

FF FLAT FACED

FO FLAT OVAL

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

HVAC HEATING, VENTILATION, AIR CONDITIONING

HWP HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

U

S

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129 --

M-001

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

MECHANICAL GENERAL NOTES, LEGENDS, AND ABBREVIATIONS

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

FINAL TURNOVERRLP06/22/18

CONSTRUCTION ACTIVITIES SHALL WORK AROUND THE USDA ANIMAL PROJECT SCHEDULE FOR ANY WORK ASSOCIATED WITH THIS PROJECT.

ONLY ONE SUITE IS ALLOWED TO BE TAKEN DOWN AT ANY GIVEN TIME FOR EXTENDED SHUT DOWNS. SYSTEMS WILL BE SHUT DOWN FOR DUCTWORK

TIE- INS. CONTRACTOR SHALL COORDINATE ALL WORK WITH USDA, AND PROVIDE A PROPOSED SCHEDULE TO USDA FOR REVIEW PRIOR TO ANY

WORK BEGINNING ON SITE.

BEFORE ANY CONSTRUCTION, MEASURE AND RECORD THE EXISTING AIRFLOW RATE OF EACH SUPPLY AIR OUTLET AND EACH EXHAUST AIR INTAKE.

ALSO MEASURE AND RECORD THE COINCIDENT ROOM PRESSURE. RECORD BOTH THE ACTUAL VALUES AND THE SETPOINTS. THE INTENT IS TO

RETURN THE FACILITY POST-CONSTRUCTION TO THE ORIGINAL BALANCED AIRFLOW SETPOINT AND ROOM PRESSURE SETPOINT.

NEW PIPING TIE-INS SHALL BE HOT-TAPPED INTO MAINS WITH SHUT-OFF VALVES TO MINIMIZE SYSTEM SHUT DOWNS.

DEMOLITION OF EXISTING PIPING TO COILS THAT WILL BE REMOVED WILL REQUIRE A SYSTEM SHUT DOWN AND DRAINING. CONTRACTOR SHALL

COORDINATE THIS WORK TO BE COMPLETED AT ONCE, AND DURING A TIME WHEN REHEAT IS NOT REQUIRED. CONTRACTOR SHALL COORDINATE ALL

WORK WITH USDA, AND PROVIDE A PROPOSED SCHEDULE TO USDA FOR REVIEW PRIOR TO ANY WORK BEGINNING ON SITE.

UPON COMPLETION OF PIPING AND COIL INSTALLATION, CONTRACTOR SHALL FLUSH NEW PIPING AND COILS. CONTRACTOR SHALL PROVIDE MEANS

TO DRAIN PIPING TO THE EXTERIOR, OR OTHER SUITABLE LOCATION, AS APPROVED BY OWNER. THIS WORK SHALL BE COORDINATED WITH OWNER

TO DETERMINE AN ACCEPTABLE LOCATION FOR DRAINAGE.

CONSTRUCTION PHASING:

1.

2.

3.

4.

5.

SUITE 5

ZONE DC-5-5A

70°F (ADJ)

SUITE 5

ZONE DC-5-5B

70°F (ADJ)

SUITE 5

ZONE DC-5-1A

70°F (ADJ)

SUITE 5

ZONE DC-5-1B

70°F (ADJ)

SUITE 5

ZONE DC-5-1C

70°F (ADJ)

SUITE 5

ZONE DC-5-1D

70°F (ADJ)

SUITE 4

ZONE DC-4-9A

70°F (ADJ)

SUITE 4

ZONE DC-4-5A

90°F (ADJ)

SUITE 3

ZONE DC-3-1A

90°F (ADJ)

SUITE 3

ZONE DC-3-5A

70°F (ADJ)

SUITE 2

ZONE DC-2-2A

70°F (ADJ)

SUITE 2

ZONE DC-2-2E

70°F (ADJ)

SUITE 4

ZONE DC-4-2

90°F (ADJ)

SUITE 4

ZONE DC-4-9B

70°F (ADJ)

SUITE 4

ZONE DC-4-9C

70°F (ADJ)

SUITE 4

ZONE DC-4-9D

70°F (ADJ)

SUITE 4

ZONE DC-4-5B

90°F (ADJ)

SUITE 4

ZONE DC-4-5C

90°F (ADJ)

SUITE 4

ZONE DC-4-5D

90°F (ADJ)

SUITE 3

ZONE DC-3-1B

90°F (ADJ)

SUITE 3

ZONE DC-3-1C

90°F (ADJ)

SUITE 3

ZONE DC-3-1D

90°F (ADJ)

SUITE 3

ZONE DC-3-5B

70°F (ADJ)

SUITE 2

ZONE DC-2-2B

70°F (ADJ)

SUITE 2

ZONE DC-2-2C

70°F (ADJ)

SUITE 2

ZONE DC-2-2D

70°F (ADJ)

U

S

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

M002

HOT WATER HEATING ZONES

24'

SCALE IN FEET

0 8' 16'

N O

R T

H

GENERAL NOTES:

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

KEYED NOTES:

EXISTING TEMPERATURE SENSOR IN EXHAUST

AIR DUCT SHALL REMAIN AND SERVE NEW

ZONE DUCT COIL.

PROVIDE NEW TEMPERATURE SENSOR IN

EXHAUST AIR DUCT ABOVE TO SERVE NEW

ZONE DUCT COIL. TYPICAL UNLESS NOTED

OTHERWISE.

(TYP)

(TYP)

M-002

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

HVAC HOT WATER HEATING ZONES - SUITES 2 THRU 5

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

FINAL TURNOVERRLP06/22/18

U

S

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

MD101

MECHANICAL DEMOLITION PLAN

N O

R T

H

16'8'4'0

SCALE IN FEET

GENERAL NOTES:

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

3. FOR PIPING DEMOLITION AT DUCT COILS, SEE

MD201.

KEYED NOTES:

DEMOLISH EXISTING HOT WATER DUCT COIL

(DC-X) AND DUCTWORK TRANSITIONS TO COIL.

PREPARE DUCTS FOR NEW WORK. SEE MH101.

DEMOLISH EXISTING DUCT AND CAP.

EXISTING DUCTS & FITTINGS TO BE RELOCATED

FOR NEW WORK. SEE MH101.

EXISTING TEMPERATURE SENSOR IN EXHAUST

AIR DUCT TO REMAIN TO SERVE NEW DUCT

COIL.

EXISTING SA VERTICAL DUCTWORK DOWN THRU

FLOOR TO REMAIN. TEMPORARILY CAP FOR

CONNECTION TO NEW WORK. SEE MH101.

DEMOLISH EXISTING COIL AND REPLACE WITH

NEW IN SAME LOCATION.

EXISTING DUCT IN THIS LOCATION SHALL BE

REMOVED TO ALLOW FOR INSTALLATION OF

NEW DUCT COIL. SEE MH101.

DEMOLISH TO ALLOW FOR RELOCATION OF

EXISTING SA DUCT. SEE MH101.

5 5 5

5 5 5

5 5 5

MD101

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

MECHANICAL DEMOLITION, MEZZANINE - SUITES 4 & 5

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

FINAL TURNOVERRLP06/22/18

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

MD102

MECHANICAL DEMOLITION PLAN

N O

R T

H

16'8'4'0

SCALE IN FEET

GENERAL NOTES:

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

3. FOR PIPING DEMOLITION AT DUCT COILS, SEE

MD202.

KEYED NOTES:

DEMOLISH EXISTING HOT WATER DUCT COIL

(DC-X) AND DUCTWORK TRANSITIONS TO COIL.

PREPARE DUCTS FOR NEW WORK. SEE MH102.

DEMOLISH EXISTING DUCT AND CAP.

EXISTING DUCT TO BE RELOCATED FOR NEW

WORK. SEE MH102.

EXISTING TEMPERATURE SENSOR IN

EXHAUST AIR DUCT TO REMAIN AND SERVE

NEW DUCT COIL.

EXISTING SA VERTICAL DUCTWORK DOWN

THRU FLOOR TO REMAIN. TEMPORARILY CAP

FOR CONNECTION TO NEW WORK. SEE MH102.

EXISTING DUCT IN THIS LOCATION SHALL BE

REMOVED TO ALLOW FOR INSTALLATION OF

NEW DUCT COIL. SEE MH102.

3 3

5 5 5

MD102

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

MECHANICAL DEMOLITION, MEZZANINE - SUITES 2 & 3

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

MD201

HOT WATER HEATING

PIPING DEMOLITION PLAN

N O

R T

H

16'8'4'0

SCALE IN FEET

GENERAL NOTES:

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

3. FOR DUCT DEMOLITION AT DUCT COILS, SEE

MD101.

4. COILS BEING REMOVED SHALL BE ISOLATED

AND DRAINED. SEE M-001, AND SPECIFICATION

23 21 13 FOR REQUIREMENTS.

KEYED NOTES:

DEMOLISH EXISTING HOT WATER DUCT COIL

(DC-X), ASSOCIATED PIPING, AND CONTROL

VALVES. VALVE AND CAP FOR CONNECTION

TO NEW WORK. SEE MP101 FOR NEW WORK.

DEMOLISH EXISTING HOT WATER DUCT COIL

(DC-X), ASSOCIATED PIPING, AND CONTROL

VALVES. CAP AT EXISTING PIPING MAIN.

SALVAGE EXISTING CONTROL VALVES FOR

OWNER. SEE MP101 FOR NEW WORK.

COIL WILL BE REPLACED IN SAME LOCATION

WITH NEW PIPING CONNECTIONS TO MAIN.

MD201

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

HVAC HOT WATER HEATING PIPING DEMOLITION, MEZZANINE - SUITES 4 & 5

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

MD202

HOT WATER HEATING

PIPING DEMOLITION PLAN

N O

R T

H

16'8'4'0

SCALE IN FEET

GENERAL NOTES:

KEYED NOTES:

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

3. FOR DUCT DEMOLITION AT DUCT COILS, SEE

MD102.

4. COILS BEING REMOVED SHALL BE ISOLATED

AND DRAINED. SEE M-001, AND SPECIFICATION

23 21 13 FOR REQUIREMENTS.

5.

DEMOLISH EXISTING HOT WATER DUCT COIL

(DC-X), ASSOCIATED PIPING, AND CONTROL

VALVES. VALVE AND CAP FOR CONNECTION

TO NEW WORK. SEE MP102 FOR NEW WORK.

DEMOLISH EXISTING HOT WATER DUCT COIL

(DC-X), ASSOCIATED PIPING, AND CONTROL

VALVES. CAP AT EXISTING PIPING MAIN.

SALVAGE EXISTING CONTROL VALVES FOR

OWNER. SEE MP102 FOR NEW WORK.

MD202

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

HVAC HOT WATER HEATING PIPING DEMOLITION, MEZZANINE - SUITES 2 & 3

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

T

TTT

T T T

T T

T

T T T

36x18

36x18

U

S

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

MH101

MECHANICAL PLAN - MEZZANINE

N O

R T

H

16'8'4'0

SCALE IN FEET

GENERAL NOTES:

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

3. FOR PIPING CONNECTIONS TO DUCT COIL, SEE

MP101 AND DETAIL ON M-501.

4. VERIFY DUCTWORK LAYOUT WITH EXISTING

CONDITIONS PRIOR TO FABRICATION TO AVOID

CONFLICT WITH EXISTING UTILITIES.

5. SEE M-002 FOR DUCT COIL ZONES AND SPACE

TEMPERATURE SETPOINTS.

KEYED NOTES:

PROVIDE DUCT TRANSITION AT INLET AND

OUTLET OF NEW DUCT COIL. SEE M-501 FOR

COIL SIZES AND INSTALLATION DETAIL.

RELOCATED EXISTING SA DUCT. PROVIDE

NEW DUCT TO RECONNECT TO EXISTING

VERTICAL SA DOWN THROUGH FLOOR.

PROVIDE NEW TEMPERATURE SENSOR IN

EXISTING EA DUCT. SEE M-002.

EXISTING TEMPERATURE SENSOR IN DUCT

TO REMAIN. RE-LABEL SENSOR TO MATCH

NEW DUCT COIL EQUIPMENT TAG.

CONNECT THE RELOCATED SA DUCT TO THE

EXISTING DUCT MAIN HERE.

DC-5-5A

DC-5-5A

DC-5-1A

DC-5-1B

DC-5-1D

DC-4-9B

DC-4-9A

DC-4-9C

DC-4-9D

DC-4-2

DC-4-5A

DC-4-5B DC-4-5C

DC-4-5D

DC-5-1C

1 1

2 2

2 2

3 3 3

18x8 SA

(TYP)

18x8 SA

(TYP)

20x8 SA

(TYP)

30x18 x

MH101

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

MECHANICAL PLAN, MEZZANINE - SUITES 4 & 5

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

T T

T

T T T

T

T

U

S

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

MH102

MECHANICAL PLAN - MEZZANINE

N O

R T

H

16'8'4'0

SCALE IN FEET

GENERAL NOTES:

KEYED NOTES:

DC-3-1B

DC-3-1A

DC-3-1C

DC-3-1D

DC-3-5A

DC-3-5B

DC-2-2A

DC-2-2E

DC-2-2B

DC-2-2C

DC-2-2D

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

3. FOR PIPING CONNECTIONS TO DUCT COIL, SEE

MP102 AND DETAIL ON M-501.

4. VERIFY DUCTWORK LAYOUT WITH EXISTING

CONDITIONS PRIOR TO FABRICATION TO AVOID

CONFLICT WITH EXISTING UTILITIES.

5. SEE M-002 FOR DUCT COIL ZONES AND SPACE

TEMPERATURE SETPOINTS.

PROVIDE DUCT TRANSITION AT INLET AND

OUTLET OF NEW DUCT COIL. SEE M-501 FOR

COIL SIZES AND INSTALLATION DETAIL.

RELOCATED EXISTING SA DUCT. PROVIDE

NEW DUCT TO RECONNECT TO EXISTING

VERTICAL SA DOWN THROUGH FLOOR.

PROVIDE NEW TEMPERATURE SENSOR IN

EXISTING EA DUCT. SEE M-002.

EXISTING TEMPERATURE SENSOR IN DUCT

TO REMAIN. RE-LABEL SENSOR TO MATCH

NEW DUCT COIL EQUIPMENT TAG.

CONNECT THE RELOCATED SA DUCT TO THE

EXISTING DUCT MAIN HERE.

CONTRACTOR SHALL INSTALL DC-2-2A IN

LOCATION THAT IS NOT IN CONFLICT WITH

EXISTING CABLE TRAY AND SHALL PROVIDE

EASY ACCESS FOR MAINTENANCE TO COIL

AND HYDRONIC ACCESSORIES.

20x8 SA

(TYP)

18x8 SA

(TYP)

42x24 x

MH102

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

MECHANICAL PLAN, MEZZANINE - SUITES 2 & 3

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

FINAL TURNOVERRLP06/22/18

1 1/2" HWS/R

1" HWS/R

1" HWS/R

1 1/2" HWS/R

1"

1 1/2"

3/4"

3/4" 3/4"

3/4"1"

3/4"

1"

3/4" 3/4"

1" 3/4"

3/4"

3/4"

3/4"

3/4"

1 1/2" 1"

1 1/2"

HWS/R

U

S

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

MP101

PIPING PLAN - MEZZANINE

N O

R T

H

16'8'4'0

SCALE IN FEET

GENERAL NOTES:

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

3. ROUTE NEW HWS & HWR PIPING AS HIGH AS

POSSIBLE TO MAINTAIN SERVICE

ACCESS/CLEARANCE FOR SERVICE CORRIDORS

THROUGHOUT SPACE.

4. SEE M-501 FOR DUCT COIL PIPING DETAIL.

5. NEW COILS AND PIPING SHALL BE CLEANED AND

FLUSHED TO THE OUTDOORS. SEE M-001, AND

SPECIFICATION SECTION 23 21 13 FOR

REQUIREMENTS.

6. SEE M-601 FOR VALVES LOCATIONS.

DC-5-5A

DC-5-5A

DC-5-1A

DC-5-1B

DC-5-1D

DC-4-9BDC-4-9A

DC-4-9C DC-4-9D

DC-4-2

DC-4-5A

DC-4-5B

DC-4-5C

DC-4-5D

DC-5-1C

MP101

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

HOT WATER HEATING PIPING PLAN, MEZZANINE - SUITES 4 & 5

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

FINAL TURNOVERRLP06/22/18

COORDINATE WITH EXISTING

PIPING TO MAINTAIN

REQUIRED CLEARANCES

AND ACCESS (TYP)

KEYED NOTES:

INSTALL NEW 3-WAY CONTROL VALVE

UPSTREAM OF DC-5-1 DUCT COILS.

1 1/2" HWS/R

1 1/2"

3/4"

3/4" 3/4"

3/4"1"

1"

1 1/2" HWS/R

1"

1"

1" 3/4"

3/4" 3/4"

1 1/2"

1 1/2"

3/4"

U

S

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

MP102

PIPING PLAN - MEZZANINE

N O

R T

H

16'8'4'0

SCALE IN FEET

GENERAL NOTES:

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

3. ROUTE NEW HWS & HWR PIPING AS HIGH AS

POSSIBLE TO MAINTAIN SERVICE

ACCESS/CLEARANCE FOR SERVICE CORRIDORS

THROUGHOUT SPACE.

4. SEE M-501 FOR DUCT COIL PIPING DETAILS.

5. NEW COILS AND PIPING SHALL BE CLEANED

AND FLUSHED TO THE OUTDOORS. SEE M-001,

AND SPECIFICATION SECTION 23 21 13 FOR

REQUIREMENTS.

6. SEE M-601 FOR VALVE LOCATIONS.

DC-3-1B

DC-3-1A

DC-3-1D

DC-3-5A

DC-3-5B

DC-2-2A

DC-2-2E

DC-2-2B

DC-2-2C

DC-2-2D

DC-3-1C

MP102

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

HOT WATER HEATING PIPING PLAN, MEZZANINE - SUITES 2 & 3

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

FINAL TURNOVERRLP06/22/18

COORDINATE WITH EXISTING

PIPING TO MAINTAIN

REQUIRED CLEARANCES

AND ACCESS (TYP)

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

M501

DUCT HEATING COIL DETAIL

M501

DUCT HEATING COIL PIPING

WITH 2-WAY VALVE DETAIL

M-501

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

MECHANICAL DETAILS, SCHEDULES, AND CONTROLS

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

FINAL TURNOVERRLP06/22/18

M501

TYPICAL CLEVIS HANGER DETAIL

D

A

A-E FIRM USDA

NO. DATE BY DESCRIPTION

REVISIONS

Agricultural

Research

Service

DWG. NO.

SHEET OF

PROJECT MANAGER EPM

DESIGNER

CHECKED BY

DRAWN BY REAL PROPERTY

SAFETY & HEALTH

PPM

SPECIFICATION NO.

DATE

8201 NORMAN CENTER DRIVE

SUITE #300

BLOOMINGTON, MN 55437

952-656-6003

PROJECT #103129

M601

HOT WATER HEATING DIAGRAM

ISOLATION

VALVE (TYP)

CAP EXISTING

PIPE (TYP)

M-601

12/08/17

R. PEARSON

R. DARNELL

-R. PEARSON

B. A'HEARNJ. LOUVIERE

HOT WATER HEATING PIPING DIAGRAM

NCAH BUILDING 7

HVAC ZONE CONTROL MODIFICATIONS

AG-32SC-D-17-0278

FINAL TURNOVERRLP06/22/18

GENERAL NOTES:

1. FOR MECHANICAL GENERAL NOTES, LEGENDS,

AND ABBREVIATIONS, SEE M-001.

2. FOR CONSTRUCTION PHASING REQUIREMENTS,

SEE M-001.

3. SEE M-501 FOR DUCT COIL PIPING DETAIL.

4. NEW COILS AND PIPING SHALL BE CLEANED AND

FLUSHED TO THE OUTDOORS. SEE M-001, AND

SPECIFICATION SECTION 23 21 13 FOR

REQUIREMENTS.

KEYED NOTES:

INSTALL NEW 1" 3-WAY CONTROL VALVE IN

PIPING UPSTREAM OF DC-5-1 DUCT COILS

(8.8 GPM)

103129M001-M001
Sheets and Views
103129M001-M001
103129M002-Layout1
Sheets and Views
103129M002-Layout1
103129MD101-Layout1
Sheets and Views
103129MD101-Layout1
103129MD102-Layout1
Sheets and Views
103129MD102-Layout1
103129MD201-Layout1
Sheets and Views
103129MD201-Layout1
103129MD202-Layout1
Sheets and Views
103129MD202-Layout1
103129MH101-Layout1
Sheets and Views
103129MH101-Layout1
103129MH102-Layout1
Sheets and Views
103129MH102-Layout1
103129MP101-Layout1
Sheets and Views
103129MP101-Layout1
103129MP102-Layout1
Sheets and Views
103129MP102-Layout1
103129M501-Layout1
Sheets and Views
103129M501-Layout1
103129M601-Layout1
Sheets and Views
103129M601-Layout1
2018-06-27T14:48:26-0500
Darnell, Rober
2018-06-27T14:48:52-0500
Darnell, Rober

File details come from the government source that posted it.