2. SOW-Q0116.pdf

PDF 512 KB Posted

Attached to
Passenger Elevator Modernization Federal contract opportunity
Solicitation number
12505B24Q0116
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Midwest Area

About this file

This document is a Statement of Work (SOW) for the modernization of a passenger elevator located at the National Laboratory of Agriculture and the Environment (NLAE) in Ames, Iowa. The key requirements include upgrading the elevator controls, mechanicals, and fixtures to meet the latest ANSI A17.1 Code, ADA, and fire service regulations. The work includes installing a new controller, power unit, door equipment, and various other components. Contractor requirements include a minimum of 10 years of elevator modernization experience and providing references.

The related federal contract opportunity is a solicitation (RFP) issued by the U.S. Department of Agriculture (USDA) Agricultural Research Service for the passenger elevator modernization project at NLAE. This is a 100% small business set-aside with a NAICS code of 238290 and size standard of $22 million. The magnitude of construction is estimated between $100,000 and $250,000, with a 450-day period of performance. Site visits are scheduled for April 10-11, 2024, and all questions must be submitted by April 18, 2024. Offerors must be registered in SAM.gov to submit proposals.

View the file

Other files for this federal contract opportunity

Other files attached to Passenger Elevator Modernization, newest first.
File Type Posted
12505B24Q0116 -0001.pdf PDF
8. Site Visit Sign-in.pdf PDF
1. SF 1442 - 12505B24Q0116.pdf PDF
3. Wage Determination IA20240074 03-01-2024.pdf PDF
4. Material Submittal Form.pdf PDF
7. Past Performance Questionnaire.pdf PDF
5. ARS-371.pdf PDF
6. ARS-372.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work (SOW)

Project: NLAE Passenger Elevator Update

GENERAL INFORMATION

1.0 Scope of Work: Modernization of elevator controls and mechanicals for the passenger elevator at the National Laboratory of Agriculture and the Environment (NLAE), Ames, IA. 1015 North University Blvd, 50011. Include latest modern VVVF power and logic controller with full ADA and 2017ANSI A17.1 Code compliancy. Electronic controller shall be non-proprietary open source units with on board diagnostics. New controller will support all current codes regarding fire service and handicap accessibility. New power unit. All push button controls (in car and out) shall be brought up to ADA and fire service specifications. Site visit/inspection is required. Available drawings will be provided. Inspection was performed in 2017. Statement of Work is based off those findings. Other discrepancies found during Update will be addressed if any should arise.

Work outside of the specifications below may be noted. They may be considered as optional work. They will not affect the awarding of the project.

2.0 Background: Elevator was installed in 1989 and have had some updates/repairs made since then. Elevator services a basement floor, 1st (ground), 2nd and 3rd (top) floor. Control panel is displaying signs of heat damage and dip switches are stiff and brittle feeling when operated. Light bars have been upgraded, the cab interior lighting could be improved. Unit has had the power units serviced in 2017 but mostly the elevator is operating as installed. Our concerns are with travel cables, parts availability for now components and to provide a safe elevator for the passengers.

CONTRACTOR REQUIREMENTS

3.0 Technical Requirements/Tasks: Existing fixtures do not meet ANSI Code and shall be replaced with the following but not limited to:

Controller Specification

• Selective Collective Operation

• NEII Handicap Package

• Emergency Power Capabilities

• Digital Position indicator

• Fire Service Features Compliant with the current Code of your AHJ

• Solid State Starter

• On Board Diagnostics

• Programmable car homing

• Reverse phase protection

• Pump Run Timer

Power Unit shall include the following features:

• Maxton Valve

• Pump

• Motor

• Oil level site gauge

• Shut off valve kit for the pit and the machine room

• Necessary sheaves, bushings and belts

• Pump/Valve manifold

• Tank with new hydraulic fluid

• Muffler

• New hydraulic fluid

Main Car

• Signage for Capacity, Fire Service instructions and Elevator Designator

• All pushbuttons and key switches necessary for the features

• Built-in emergency light

• New 6v alarm bell

• Phase II Fire Service in locked cabinet per current Code

• Independent Service, Fan, Light & Hoistway Enable in locked cabinet

• Permanently mounted Braille

• Brushed stainless steel face plate

• ADA push to talk phone

• Certificate Window

• Digital Position Indicator in Car Station

• Fixture Type: PB1 – Universal

• New stainless-steel wall panels or any other recommended option for wall panels

Hall Push Button Stations & Accessories

• One terminal station with hoistway access at lowest landing

• One terminal station with hoistway access at top landing

• Intermediate hall stations at all other landings

• Phase I Fire Service to be located at the main egress

• Fire Service plates with instructions will be located at each landing per

Code

• #4 brushed stainless steel face plates will cover each station

• Hoistway jamb Braille will be installed at Code height for each elevator

Digital Hall Position Indicators with Lanterns

• A hall position indicator will be installed at each landing above the elevator door indicating the landing which the elevator resides and the direction of travel when the elevator leaves a landing

• A chime will announce arrival

Door Equipment

• New master gearless solid-state door operator, cushioned at both limits of travel

• Electro-mechanical interlock provided at each hoistway, door operator arranged in case of power failure the doors can be opened by hand from within car in accordance with applicable code

• Door operator

• Clutch with restrictor

• Interlocks

• Mounting brackets

• Car and Hoistway door hangers and tracks complete

• Gate switch

• Long lever, crank arm and split link

• Door retainers with Fire tabs per code

• Door edge detector/light curtain

• New stainless-steel car door

Miscellaneous Items

• Hoistway switch package will be installed

• A Car top exit switch will be installed per Code

• Pit ladder to be extended or replaced per Code

• Car top inspection stations, pit stop switch and alarm bell

• New travel cable and wiring will be provided to meet the needs of the new controller and fixtures

• The toe guard will be extended per Code as required and to the extent it is able

• Stenciling of floor numbers will be done on the inside of each landing door per Code

• Painting of machine room and pit floor will be performed upon completion

• Drawings will be provided along with three sets of owner’s manuals upon completion of the modernization

• All necessary permits, data tags, testing and one State inspection upon

Security

• Elevator is tied into Lenel building access system. New controller will need to be tied into existing Lenel building access system. (After hours and weekend card access)

The end goal is to have modernized passenger elevator for NLAE satisfying Handicap Code/ADA, the Fire Service Code and the current ANSI Codes.

Contractor must have minimum documentable ten (10) years elevator experience.

Quote shall include minimum of 3 references related to recently completed work.

4.0 Government Furnished: On-Site Work Hours: Limit work in the existing building to normal business working hours of 7:30 a.m. to 4:30 p.m., Monday through

Friday, unless otherwise approved. 1. Weekend Hours: Must be coordinated with Owner’s site representative. 2. Early Morning Hours: Must be coordinated with Owner’s site representative. 3. Hours for Utility Shutdowns: Must be coordinated with Owner’s site representative. 4. Hours of extreme noise activities must be coordinated with the Owner’s site representative. Contractors will have a limited background investigation to provide unescorted access to the elevator spaces and building. Contractor shall remove all old/replaced materials to be recycled or disposed of. Contractor shall keep a clean and orderly work area and leave the work area as clean or cleaner than when starting work.

5.0 Deliverables / Schedule: The contractor is required to provide written progress reports monthly for the period of the project duration. The original and two electronic copies are required. The progress report shall cover all work completed during the specified period and shall present the work to be accomplished during the subsequent period. This report shall also identify any problems that arose and a statement explaining how the problem was resolved. This report shall also identify any problems that have arisen but have not been completely resolved and provide an explanation.

6.0 Contractor’s Key Personnel: Certified elevator contractors with 10 years of experience with upgrading with modernization projects

7.0 Security Requirements: Requirements for limited background investigation listed above.

8.0 Place of Performance: National Laboratory for Agriculture and the Environment, 1015 N. University Blvd, Ames, IA 50011

9.0 Period of Performance: Anticipated completion within 450 days of award

10.0 Evaluation Factors: Technical acceptability, references, delivery, price.

11.0 Technical Point of Contact: Patrick Quance, 515-203-1447 patrick.quance@usda.gov

Attachment: Pictures below

Passenger

CONTRACTOR REQUIREMENTS
6.0 Contractor’s Key Personnel: Certified elevator contractors with 10 years of experience with upgrading with modernization projects
7.0 Security Requirements: Requirements for limited background investigation listed above.
8.0 Place of Performance: National Laboratory for Agriculture and the Environment, 1015 N. University Blvd, Ames, IA 50011
9.0 Period of Performance: Anticipated completion within 450 days of award