16510 Mepem UPS OM Manual.pdf

PDF 3 MB Posted

Attached to
Uninterruptible Power Supply Repair Federal contract opportunity
Solicitation number
12505B24Q0067
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Midwest Area

About this file

This is a combined synopsis and solicitation from the Department of Agriculture seeking quotes for uninterruptible power supply repair services. The solicitation will be set aside for small businesses and involves repair of UPS units located at the USDA Agricultural Research Service facility in Ames, Iowa. Quotes are due by February 23, 2024 and the period of performance is from March 1, 2024 through May 31, 2024. The award will be made to the lowest priced technically acceptable quote based on technical specifications and price, including shipping. All contractors must be registered in the System for Award Management and have satisfactory past performance. Inspection and acceptance will occur upon delivery to the specified location.

View the file

Other files for this federal contract opportunity

Other files attached to Uninterruptible Power Supply Repair, newest first.
File Type Posted
RFIs Updated.pdf PDF
IMG_0201.jpg JPG image
IMG_0129.jpg JPG image
SF-30 Amendment 02.pdf PDF
IMG_0197.jpg JPG image
IMG_0199.jpg JPG image
IMG_0128.jpg JPG image
SF-30 Amendment 01.pdf PDF
RFIs.pdf PDF
UPS4 TRANSFORMER2.jpg JPG image
UPS 4 TRANSFORMER1.jpg JPG image
Label A.JPG JPG image
Statement of Work.pdf PDF
Label B.jpg JPG image
Back of Unit.JPG JPG image
Clauses and Provisions.pdf PDF
Wage Determination.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MEPEM

UNINTERRUPTIBLE POWER SYSTEM

20/30/50/75kVA —

3 phase input / 3 phase output

USER HANDBOOK

PART NUMBER UPLIT042 rev.4 page 2 – UPLIT042 rev.4 - 05/2005

IMPORTANT SAFETY INSTRUCTIONS

READ BEFORE INSTALLING

1) SAVE THESE INSTRUCTIONS

This manual contains important instructions for the MEPEM which should be followed during installation and maintenance of the UPS and associated batteries.

2) The installation must be inspected by trained technicians.

The instructions must be followed.

3) When external batteries are provided by the Customer and not Chloride, reference must be made to the installation instructions provided by the battery supplier.

WARNINGS

1) The AC and DC supplies to the MEPEM UPS and the AC output from the UPS MUST be fed through suitably rated circuit breakers or fuses and isolating switches suitable for branch circuit operation.

2) Any external battery cabinet connected to the UPS MUST be provided with an over-current protection device per UL924 Par. No. 25.

3) To reduce the risk of fire or electric shock, the equipment must be installed indoors, in a humidity and temperature controlled environment which is free from conductive contaminants.

SAFETY

1) DO NOT REMOVE COVERS DURING NORMAL OPERATION. The panels will be removed during installation, however this should only be undertaken by qualified technicians. It should be ensured that the UPS is switched off and that all power sources are disconnected (A.C. mains and Battery) before either the rear or side panels are removed.

2) FOREIGN OBJECTS MUST NOT BE INTRODUCED INTO THE VENTILLATION GRILLES.

HAZARDOUS VOLTAGES are present within the MEPEM even when it is switched off.

3) Fuses must ONLY be replaced with the same type and rating.

4) The MEPEM contains a battery which can be DANGEROUS if interfered with. Contact the supplier for replacement.

5) The UPS and/or its components must be disposed of as notifiable waste in accordance with local pollution control (special waste) regulations.

UPLIT042 rev4 - 05/2005-- page 3

WARNING

The UPS contains hazardous voltages, even when all switches are open.

In case of fire in the installation area, do not use water to extinguish fire.

ELECTRICAL PRECAUTIONS:

If the UPS is in By-pass mode and the Output switch is closed, no indications will be displayed;

fans will however function, and hazardous voltages are present downline from the static switches.

EMERGENCY PROCEDURE

In the case of an emergency, the load supply can be interrupted by switching off all the switches fitted in the UPS.

ELECTRIC SHOCK

Switch off power; use dry insulating material for protection when pulling the injured person clear of conductors.

NEVER TOUCH THE INJURED PERSON WITH BARE HANDS UNTIL CLEAR OF

CONDUCTORS. SEEK QUALIFIED ASSISTANCE IMMEDIATELY.

INJURIES CAUSED BY CONTACT WITH CORROSIVE LIQUIDS

In normal conditions, installed batteries are sealed. A damaged battery container may however leak electrolyte, or cause the latter to come into contact with battery parts.

In the event of electrolyte contact with the eyes, rinse eyes thoroughly with a saline solution or fresh water for at least 10 minutes.

In the event of electrolyte contact with skin, rinse the affected area with abundant water. Remove contaminated clothing. Cover affected area with dry gauze.

If electrolyte is swallowed, do not induce vomiting. Administer large quantities of milk or water.

IN ALL CASES, SEEK MEDICAL ATTENTION IMMEDIATELY

page 4 – UPLIT042 rev.4 - 05/2005

Contents

1.0 INTRODUCTION

1.1 Summary of the manual

1.2 Summary of the equipment

1.3 Block diagram

1.4 Functions

1.5 Operational modes

2.0 SAFETY

2.1 General safety

2.2 Symbols

2.3 Electrical precautions

2.4 Battery precautions

2.5 Battery safety equipment

3.0 STORAGE

4.0 INSTALLATION

4.1 Mechanical characteristics

4.2 Installation

Recommended wire sizes

4.4 Ventilation

5.0 CONNECTION

5.1 Electrical connections

5.2 10/15/20kVA

5.3 30kVA

5.3 50/75kVA

5.4 Signal connections

6.0 CONTROLS

6.1 User Controls

6.2 Control Panel

7.0 START UP

UPLIT042 rev4 - 05/2005-- page 5

Figures Figure 1 – Block diagrams – 20/30kVA 9 Figure 2 – Block diagram – 50/75kVA 10 Figure 3 – Normal operation 11 Figure 4 – Utility Supply failure 11 Figure 5 – Re-establishing the Utility Supply 12 Figure 6 – Transferring the Load onto the Reserve Supply 12 Figure 7 – 20 Footprint and cabinet dimensions 16 Figure 8 – 30 Footprint and cabinet dimensions 17 Figure 9 – 50/75 Footprint and cabinet dimensions 18 Figure 10 – “A” Battery Cabinet Drawing for 20/30kVA Ratings 19 Figure 11 – “B” Battery Cabinet Drawing for 20/30kVA Ratings 20 Figure 12 – “E” Battery Cabinet Drawing for 50/75kVA Ratings 21 Figure 13 – “F” Battery Cabinet Drawing for 50/75kVA Ratings 22 Figure 14 – “C” Battery Cabinet Drawing for 30/50/75kVA Ratings 23 Figure 15 – “D” Battery Cabinet Drawing for 30/50/75kVA Ratings 24 Figure 16 – UPS Ratings 25 Figure 17 – Connection diagrams 29 Figure 18 - 10/15/20kVA: Switches and Breakers 32 Figure 19 - 10/15/20kVA: Switches 33 Figure 20 - 10/15/20kVA: Cable Connections 34 Figure 21 - 20/30kVA: Switches and Breakers 35 Figure 22 - 20/30kVA: Connections 36 Figure 23 - 20/30kVA: Cable Connections 37 Figure 20 – 50/75kVA: Switches and Breakers 38 Figure 25 – 50/75kVA: Connections 39 Figure 26 – 50/75kVA: Cable Connections 40 Figure 27 – Control panel 42 page 6 – UPLIT042 rev.4 - 05/2005

EQUIPMENT DELIVERY AND STORAGE

Delivery

The equipment and battery are delivered separately. On receipt, the packaging must be checked for any signs of damage. Any damage or missing parts should be reported to the carrier within 20 hours of delivery.

Unpacking

Care should be taken when unpacking to avoid damaging the equipment or battery; in particular, avoid short circuiting battery terminals. All packing materials should be checked before disposal to ensure that no items are discarded. The equipment panel rating plate should be checked to ensure that supply voltage and output rating correspond to the equipment and load and that the mode of operation is correct.

Handling Keep equipment and battery upright at all times, and handle with care. Either may be damaged if dropped or subject to severe impact. Particular care should be taken to protect the controls and instruments.

a) Leave the equipment in its packaging and transport it with a fork lift.

b) Cut the tapes and remove the packing case by lifting it upwards.

c) Unscrew the screws fastening the pallet to the cubicle feet.

d) Lift the cubicle and remove the pallet.

Storage Store the equipment and battery in a clean, dry place, free from water, condensation, dirt and extremes of temperature.

Sealed lead acid battery cells which are supplied filled and charged must be given a boost charge at least every 3 months.

Sealed Nickel-Cadmium battery cells which are supplied filled and discharged must be charged and discharged before storage.

Sealed Nickel-Cadmium battery cells which are supplied dry must be filled, charged and discharged before storage.

Sealed spare battery cells must be charged at least every 3 months.

Failure to comply with the Manufacturer’s instructions may result in the battery not reaching its rated performance and having a shortened life.

UPLIT042 rev4 - 05/2005-- page 7 a b c d page 8 – UPLIT042 rev.4 - 05/2005

1.0 INTRODUCTION

1.1 Summary of the manual

This handbook provides for the safe installation, startup and use of the MEPEM Uninterruptible Power System (UPS).

The Company recommends that the equipment be installed and regularly maintained by a Chloride Authorized personnel.

DO: - read the User Handbook before operating the MEPEM UPS.

- keep a log of all incidents.

- protect the batteries from damage. Batteries leak acid; avoid contact with skin, clothes or eyes.

DO NOT: - operate the control switches.

- operate the MEPEM UPS with any covers removed.

- obstruct the ventilation grilles.

1.2 Summary of the equipment

The MEPEM Uninterruptible Power System (UPS) totally isolates the load from voltage drops, spikes, transients frequency variations in the utility supply.

In the event of failure or brownout of the AC utility supply, an internal audible alarm sounds and an LED on the control panel illuminates, the MEPEM UPS will continue to provide safe, clean continuous power, without interruption, from the battery, for a duration dependent on battery capacity and output load.

The audible alarm alerts the user to start a safe orderly shutdown of the load. When the AC utility supply returns to normal, the MEPEM UPS automatically recharges the battery ready for any future power failure.

The microprocessor display panel provides access to very detailed information regarding the status of the supplies and MEPEM UPS. Refer to current publication for detailed specification.

The block diagram, shows the main functional sub-assemblies of the MEPEM UPS. The AC three phase utility supply is rectified to provide direct current, which maintains the battery in a fully charged state and also supplies the inverter, which provides the three phase output via an electronic static switch.

Normally the supply of the reserve line is taken from the AC utility input, but special units, with a separate reserve input supply, are available. This allows the inputs to be supplied from independent three phase sources.

Provided the reserve supply is within limits, the inverter will match the output frequency with the reserve supply frequency. The inverter has its own internal crystal control to stabilize the output frequency if the reserve supply frequency is out of limits. The electronic static switch switches the output from the inverter to the reserve supply, without interruption, to meet any load current surges, or to supply the load if the battery is discharged during an AC utility supply failure.

Maintenance and testing can be carried out on the MEPEM UPS without interrupting the output, by switching the load from the reserve supply to the maintenance bypass circuit. This work should only be carried out by Chloride-trained personnel.

UPLIT042 rev4 - 05/2005-- page 9

1.3 Block diagram

Figure 1 – Block diagrams – 20/30kVA page 10 – UPLIT042 rev.4 - 05/2005

Figure 2 – Block diagram – 50/75kVA

The uninterruptible power system consists of the following:

1 - RECTIFIER/INVERTER S1 = Equipment ON/OFF switch 2 - BATTERY S2 = Equipment Reserve switch 3 - BACKFEED PROTECTION S3 = Equipment By-pass switch 4 - INVERTER STATIC SWITCH S4 = Equipment OUTPUT switch 5 - RESERVE STATIC SWITCH (INVERTER OUTPUT switch for 50/75kVA only) S5 = RESERVE OUTPUT switch for 50/75kVA only

1.4 Functions

RECTIFIER / BATTERY CHARGER

The rectifier/battery charger transforms the alternating current of the mains supply to direct voltage to maintain the battery in a fully charged state and also supply the inverter.

BATTERY

The battery is an energy reserve that is used by the inverter and the load whenever the mains supply fails.

INVERTER

The inverter changes the direct voltage from the rectifier or from the battery into a three phase sinusoidal alternating voltage for the external supply.

ELECTRONIC STATIC SWITCH

The function of the electronic static switch is to select one of the two sources of alternating voltage and to supply it to the external load. The two sources of voltage supplied to the static switch are the output of the inverter and the reserve supply. In normal working conditions, the static switch supplies the load from the inverter.

SWITCHES

The switches permits maintenance and repair of the UPS, without interrupting the supply to the load.

UPLIT042 rev4 - 05/2005-- page 11

1.5 Operational modes

Figure 3 – Normal operation During normal operation the load is supplied by the mains through the rectifier and inverter. The rectifier also supplies the current for recharging and maintaining the battery in a fully charged state.

Figure 4 – Utility Supply failure

When the utility supply voltage is absent or outside the allowed tolerances, the battery supplies the inverter. This will be indicated on the UPS front panel display and the Remote Alarm Unit (if fitted). The standby time available depends both on the capacity of the battery and on the size of load. It is possible to extend autonomy by reducing the output power by disconnecting non-important loads. In all cases, the alphanumerical display shows the residual autonomy.

page 12 – UPLIT042 rev.4 - 05/2005

Figure 5 – Re-establishing the Utility Supply When the utility supply returns within acceptable limits, the UPS returns automatically to normal operation mode as previously described. The rectifier now starts to recharge the battery. However, until recharge has been completed, any further mains failure will result in reduced standby times.

Figure 6 – Transferring the Load onto the Reserve Supply Transfer onto the reserve line is caused by two conditions:

a) inverter stop

b) overload In both instances the load is transferred onto the reserve without interruption. If the overload is temporary, the system will re-transfer from reserve to inverter as soon as it ceases. This allows for the initial start-up of loads with high or excessive switch-on currents.

UPLIT042 rev4 - 05/2005-- page 13

2.0 SAFETY

Read all instructions carefully before installing or operating the equipment.

2.1 General safety

The procedure described in these instructions is intended for use by persons experienced in the operation of Uninterruptible Power Systems and ancillary equipment.

Persons unfamiliar with this type of equipment should seek guidance from experienced personnel.

The MEPEM UPS is designed to be operated in accordance with existing safe operating procedures.

These instructions are not intended to replace existing safety practices.

If there are any questions regarding the safe operation of the system, contact a Chloride service representative.

This equipment is designed and built for safe operation when used to supply its rated load, providing it is installed as specified by qualified, licensed and competent electricians.

Electrical energy can be supplied by the equipment and the battery.

2.2 Symbols

The following symbols appear in this book and in the unit:

Warning - Hazardous voltages are present. If the instructions are not heeded, there is a risk of electrical shock and danger to personal safety.

DIRECT CURRENT SUPPLY

ALTERNATING CURRENT SUPPLY

ON position of the switches

OFF position of the switches

Inverter Start Up For explanation see Para. 6.2. of this manual

Inverter Shutdown For explanation see Para. 6.2. of this manual

Audible Alarm Cancel Switch For explanation see Para. 6.2. of this manual page 14 – UPLIT042 rev.4 - 05/2005

Page Right Control For explanation see Para. 6.2. of this manual

Record Up For explanation see Para. 6.2. of this manual

Record Down For explanation see Para. 6.2. of this manual

2.3 Electrical precautions

Never handle a component or assembly without first confirming that no voltage is applied or present. Remove only those protective covers that are essential to perform the repairs or adjustment currently required, and replace them as soon as possible.

. Use only insulated tools.

. Place a rubber insulating mat in front of all equipment doors.

. Keep all door closed and locked at all times during normal operation.

2.4 Battery precautions

Always isolate the load before connecting or disconnecting the batteries or battery cells.

Ensure that batteries are fully isolated by disconnecting the battery connectors, opening circuit breakers, or both.

Remove all jewellery from hands, wrists and neck before working on batteries or battery cells.

Before leaning over batteries, remove any metal object that could fall out of pockets.

Do not place tools or other conductive objects on the batteries.

2.5 Battery safety equipment

When working on or handling batteries, ensure that the following items are worn:

. Eye goggles . Rubber gloves . Rubber apron . Rubber boots

When batteries are being moved or worked on, ensure the following items are available in the immediate vicinity:

. An eye bath, eyewash station or equivalent . A clean water source to wash spilled acids . Absorbent materials to soak up spilled acids . Disposal for contaminated materials.

UPLIT042 rev4 - 05/2005-- page 15

3.0 STORAGE

If the MEPEM UPS cannot be installed within sixty days of delivery, there is a danger of the integral battery becoming discharged thereby sustaining permanent damage and affecting the standby period available and battery life.

The date the battery was last recharged and the date the battery is due for its next recharge are both stamped on the packaging accompanying the unit. If you intend to store the unit, please refer to the recharge date.

When the MEPEM is due to be recharged, refer to the Installation instructions and connect the MEPEM UPS to a temporary AC supply. The battery MUST be recharged for at least 20 hours every 3 months.

4.0 INSTALLATION

4.1 Mechanical characteristics

- Ambient temperature 18°F[-10°C] to 104°F [+40°C ]

- Relative Humidity (w/out condensing @ 68°F[20°C]) < 90%

- Max altitude (w/out derating) 3300 feet [1000 m] above sea-level

- Protection degree (panel fitted)

- Input cables bottom

- Air inlet bottom

- Air outlet rear

UPS model Description u.m. 20 30 50 75

Size width depth height

In [mm]

28-.5 [700]

28.7 [730] 56 [1420]

27.5 [700]

28.7 [730] 56 [1420]

35.4 [900]

28.7 [730] 63 [1600]

35.4 [900]

28.7 [730] 63 [1600]

Total

Weight

(UPS +

Battery) w/out cells 25 Ah cells 30 Ah cells 35 Ah cells

Lbs [kg]

875 [400] 1342 [610] 1456 [662] 1526 [694]

1300 [590] n.a.

n.a.

n.a.

1342 [610] n.a.

n.a.

n.a.

1750 [818] n.a.

n.a.

n.a.

Floor Area In2[m2] 789 [0.511] 789 [0.511] 1019 [0.657] 1019 [0.657]

Floor Loading

(UPS +

Battery) w/out cells 25 Ah cells 30 Ah cells 35 Ah cells

Lbs/in2 [kg/m2]

1.12 [782]

1.70 [1194]

1.85 [1296]

1.93 [1358]

1.65 [1155] n.a.

n.a.

n.a.

1.32 [930] n.a.

n.a.

n.a.

1.77 [1205] n.a.

n.a.

n.a.

Air-Flow cfm [mc/h]

[400]

[1100]

[1975]

[2640]

Acoustic Noise 100% Linear Load dBA 52 55 55 62

Notes: 1) n.a. = not applicable

2) Longer autonomies, and battery for MEPEM above 20 kVA are available with external battery cubicles.

page 16 – UPLIT042 rev.4 - 05/2005

Figure 7 – 20 Footprint and cabinet dimensions

(5.9) (25.39)

30,0

600,0

(1.18) 645,0

260 (10.24) X 66 (2.6)

(23.62)

(ø0,31) N

R 4 X ø8

C

ABLE EN

TR

Y

58,0 (2.28)

(28.5)725,0 1422,0

(56)

ALL MEASUREMENTS ARE IN

MILLIMETERS (AND INCHES)

700,0 (27.56)

(2.64) 67,0

63,0 (2.48)

SPACE REQUIRED

BY THE WHEEL

WHEN ROTATING

(7.87)

730,0 (28.7)

(26.77) 680,0

UPLIT042 rev4 - 05/2005-- page 17

Figure 8 – 30 Footprint and cabinet dimensions

50,0

(7.87)

SPACE REQUIRED

BY THE WHEEL

WHEN ROTATING

600,0

CABLE ENTRY

500 (19.68) X 110 (4.33)

(25.39) (1.18)

645,0 30,0

(23.62)

500 (19.7)

530 (20.9)

(5.9)

700,0

NR 4 X

(ø0,31) ø8

125,0 (4.92)

(27.5)

1422,0 (56)

ALL MEASUREMENTS ARE IN

MILLIMETERS (AND INCHES)

700,0 (27.56)

(1.97)

(3.46) 88,0

730,0 (28.7)

(26.77) 680,0 page 18 – UPLIT042 rev.4 - 05/2005

Figure 9 – 50/75 Footprint and cabinet dimensions

50,0

SPACE REQUIRED

BY THE WHEEL

WHEN ROTATING

800,0

700 (27.56) X 110 (4.33)

CABLE ENTRY

(25.39) (1.18)

645,0 30,0

(31.5)

(7.87)

(5.9)

100,0

NR 4 X

ø8 (ø0,31) (3.94)

(63.0)

ALL MEASUREMENTS ARE IN

MILLIMETERS (AND INCHES)

900,0 (35.4)

(1.97)

(2.68) 68,0

730,0 (28.7)

UPLIT042 rev4 - 05/2005-- page 19

Figure 10 — “A” Battery Cabinet Drawing for 20/30kVA Ratings page 20 – UPLIT042 rev.4 - 05/2005

Figure 11 — “B” Battery Cabinet Drawing for 20/30kVA Ratings

UPLIT042 rev4 - 05/2005-- page 21

Figure 12 — “E” Battery Cabinet Drawing for 50/75kVA Ratings page 22 – UPLIT042 rev.4 - 05/2005

Figure 13 — “F” Battery Cabinet Drawing for 50/75kVA Ratings

UPLIT042 rev4 - 05/2005-- page 23

ALL MEASUREMENTS ARE IN INCHES

MOUNTING

(Terminal Blocks)

Connection

22.70

CABLE

FEET

ENTRY

2.75

FUSE

32.13

Points

32.88

PLATE

ACCESS

Figure 14 — “C” Battery Cabinet Drawing for 30/50/75kVA Ratings page 24 – UPLIT042 rev.4 - 05/2005

ENTRY

MOUNTING

ALL MEASUREMENTS ARE IN INCHES

CABLE

FEET

Points Connection

(Terminal Blocks)

5.33

40.16

28.35

FUSE

32.68

ACCESS

PLATE

Figure 15 — “D” Battery Cabinet Drawing for 50/75kVA Ratings

UPLIT042 rev4 - 05/2005-- page 25

4.2 Installation

Check the rating label on the rear of the front panel of the MEPEM UPS to ensure the input/output voltages, frequency and load are all within the rating of the UPS.

MEPEM is designed to operate in an office environment with an optimum temperature of 68°F [20 C].

A gap of at least 4 in [ 10cm. ] must be maintained at rear of the UPS to ensure adequate ventilation.

Nothing should be placed around the equipment which might restrict the airflow.

Ensure the interconnecting cables do not cause a hazard to the user.

A gap of at least 32 in [ 812 mm] must be maintained above the UPS to ensure adequate space for maintenance.

The appropriate lifting equipment must be used to move the MEPEM UPS.

Figure 16 – UPS Ratings UPS ratings

Description U.M. 20

10kVA

15kVA

20kVA

30kVA Output power kVA 10 15 20 30

Nominal Load kW 10 15 20 30

Maximum input power (with unit @ nominal Load & battery recharge) kVA 15 21 28 35

Maximum dissipation (with inverter @ nominal Load)

BTU/H 3750 5460 6800 9500

Number of battery cells n 144 240

Battery voltage range V 238-327 396-545

Battery end-discharge current

A 37 55 74 67

UPS ratings

Description U.M. 50

40kVA

50kVA

65kVA

75kVA

Output power kVA 40 50 65 75

Nominal Load kW 40 50 65 75

Maximum input power (with unit @ nominal Load & battery recharge) kVA 57 71 91 112

Maximum dissipation (with inverter @ nominal Load)

BTU/H 11700 14300 18600 22100

Number of battery cells n 240

Battery voltage range V 396-545

Battery end-discharge current

A 88 110 140 173 page 26 – UPLIT042 rev.4 - 05/2005

Recommended wire sizes

1) It is recommended that the external cables and protection be selected for the highest rated unit of the model in use.

2) Reserve (or primary) input and output Neutral cable size should be greater than that of the line cables in order to be able to supply non-linear loads having a Crest Factor of up to 3:1 (i.e.

where neutral current = 1.7 x line current).

If non-linear loads are not to be supplied from the Installation, the Neutral can be of the same size as the load cable.

3) Recommended AC input overcurrent protection represents 125% of nominal full load current (continuous) plus the short duration input current (non-continuous) for battery re-charging per NEC 215.2.

4) UPS output cables should be run in separate conduits from input cables.

5) Grounding conductors are sized per NEC 250.122.

6) Cable sizes are based upon NEC.

Refer to local codes applying to your installation prior to choosing appropriate cable size.

Refer to UPS ampacity table on following page.

UPLIT042 rev4 - 05/2005-- page 27

A.C. Supply Reserve Supply UPS Type

Vin/Vout

Rated current (A)

Protection device (A)

Output

Nominal current (A)

Nominal current (A)

Protection device (A)

20/10kVA 42 50 33 33 50 20/15kVA 60 80 50 50 75 20/20kVA

208/120- 208/120

78 100 67 67 100 20/10kVA 19 30 33 33 45 20/15kVA 26 40 50 50 70 20/20kVA

480-208/120

34 50 67 67 90 20/10kVA 19 30 14 14 20 20/15kVA 26 40 22 22 30 20/20kVA

480-480/277

34 50 29 29 40

30/30kVA 208/120- 208/120 97 150 83 83 125

30/30kVA 480-208/120 42 60 83 83 125

30/30kVA 480/277- 480/277 42 60 36 36 45

50/40kVA 152 200 111 111 150 50/50kVA

208-208/120 192 250 138 138 175

50/40kVA 66 90 111 111 150 50/50kVA

480-208/120 83 125 139 139 175

50/40kVA 66 90 48 48 60 50/50kVA

480-480/277 83 125 60 60 75

75/65kVA 254 350 180 180 225 75/75kVA

208-208/120 311 400 222 222 300

75/65kVA 110 150 180 180 225 75/75kVA

480-208/120 135 175 222 222 300

75/65kVA 110 150 78 78 100 75/75kVA

480-480/277 135 175 96 96 125 page 28 – UPLIT042 rev.4 - 05/2005

4.4 Ventilation

UPS can work in a continuous environment within 18°F[-10°C] to 104°F [+40°C ] temperature range, although, ideally the ambient temperature should be below 78°F [25°C].

The heat, dissipated by the UPS (indicated on figure 7), is extracted by internal fans and then dissipated into the air.

The heat can be removed from the UPS room by a forced cooling ventilation system or, alternatively, an air conditioning system.

The required air changes per hour will depend on the UPS rating and this heat loss and on the cooling air temperature.

To calculate the required air flow for the dissipated power, the altitude and the cooling air temperature, the following equation can be used:

• Pd

V = 2770 - - - - - - • e (0.125 h T k / T

Tr - Tk with: V = air flow [mc/h]

Pd = total dissipated power [kW]

Tr = max. temperature allowed into the room [104°F = 40°C = 313°K]

Tk = Temperature of input cooling air

T0 = 273 °K h = altitude above the sea level [km]

UPLIT042 rev4 - 05/2005-- page 29

5.0 CONNECTION

Figure 17 – Connection diagrams THE AC AND DC SUPPLIES TO THE MEPEM UPS, AND THE AC OUTPUT FROM THE UPS, SHOULD BE FED THROUGH SUITABLY RATED CIRCUIT BREAKER OR FUSE(S) AND ISOLATING SWITCH SUITABLE FOR BRANCH CIRCUIT

PROTECTION.

NOTE: INTERRUPTING THE NEUTRAL FEED MAY CAUSE THE CHANGE IN GROUND-NEUTRAL VOLTAGE TO AFFECT

THE LOAD.

NOTE: ALL CIRCUIT BREAKERS OR FUSES AND ISOLATING SWITCHES SHOULD BE FITTED AS CLOSE TO THE MEPEM

UPS AS POSSIBLE AND MARKED WITH THE LABELS PROVIDED WITH THE UNIT.

IT IS ALSO RECOMMENDED A LABEL AS FOLLOWS

UNINTERRUPTIBLE POWER SYSTEM

NO UNAUTHORIZED OPERATION

Protection devices to be installed by the customer

Protection devices to be installed by the customer according to the information shown on page 23 according to the information shown on page 23

Neutral not present on 50 and 80kVA ratings

RESERVE

INPUT L3 W

GROUND

G

L3

UTILITY

INPUT

L1 L2

N

L1 L2

W1 N

U V

U1 V1

Neutral not present on 50 and 80kVA ratings

GROUND

G

UTILITY

INPUT

L1 L2 L3 N N

U V W

(Neutral separately derived on 50 and 80kVA ratings)

BATTERIES

Remove link to connect remote E.P.O.

Battery Charge Inhibit

W2 N

U2

V2 OUTPUTL3

EXTERNAL

N

L1 L2

(Neutral separately derived on 50 and 80kVA ratings)

Remove link to connect remote E.P.O.

Battery Charge Inhibit

W2 N

U2 V2

L3

EXTERNAL

BATTERIES

N

OUTPUT

L1 L2 page 30 – UPLIT042 rev.4 - 05/2005

CAUTION!

WARNING!

All power connection must carried out by qualified licensed personnel experienced in wiring this type of equipment

The safety ground wire must be connected before the power input cables

The correct phase rotation (phase A leads B leads C) must be observed on the UPS terminals.

In maintenance by-pass operation, the UPS components are de-energized, with the exception of input/output terminals, battery cabinet, input matching voltage transformer (for 475/208 configuration) and isolating transformer (for 50 and 75kVA).

All input power (AC and DC) must be disconnected to ensure complete isolation

UPLIT042 rev4 - 05/2005-- page 31

5.1 Electrical connections

WARNING!

All electrical connections must be made by a qualified electrician and meet local electrical code standards

Before attempting to connect the mains supply, the reserve/bypass supply or the load, ensure that all supplies, including the battery, are isolated and that all the equipment switches are in their »OFF» position.

Open UPS front access panel and remove internal panel over main switches and terminal blocks.

NOTES:

1) Installation must be performed by a qualified electrician. The terminals require the use of the proper crimp tools and terminals in order to perform an installation in accordance with the National Electrical Code (NEC). The recommended crimp tools, terminals and torque are shown in the following tables:

2) Use Copper Conductors Only

Table 1 – T&B’s Cat. N°s. for terminals and crimp tools

Terminals Hole for screw

Wire Size

(AWG) M6 M10

Toggle hand

Nest (stationary) tool

Indentor (Moveable)

8 D10711 D975 11753 6 E10711 E975 11753 4 F10711 F975 11755 3 F10711 F975 11755 2 G971 G974 11756 1 G671 G974 11756

1/0 H971 H974 11757 2/0 J971 J974 11758 3/0 K971 K974 11759 4/0 L971 L974

WT117

11810

11752

Table 2 – Recommended torque

Torque Type Screw Wrench

(mm) (Nm) (lb.in)

Used ON

Entrelec

M 35/26.FF

M6

4.5

39 MEPEM70Plus up to 20kVA

------- M10 17 39 340 MEPEM70Plus above 20kVA page 32 – UPLIT042 rev.4 - 05/2005

5.2 20 – 10/15/20kVA

Ensure the AC supplies and load are switched OFF. Check that all the MEPEM UPS Switches (behind the front panel) are switched OFF, see Figure 18 .

The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure the AC supply voltage at the MEPEM UPS terminals is within +/- 10% of nominal.

The MEPEM UPS should be connected to the main/reserve supplies and output load via a wall mounted junction box.

Installation and connection should only be carried out by qualified electrical personnel.

Figure 18 - 20 – 10/15/20kVA: Switches and Breakers

Battery Compartment

S2 = Equipment Reserve Switch

S1 = Equipment ON/OFF Breaker

S3 = Equipment By-pass Switch

S4 = Equipment OUTPUT Breaker

UPLIT042 rev4 - 05/2005-- page 33

Figure 19 - 20 – 10/15/20kVA: Switches Access to the terminals for electrical connections is as follows:

a) Remove front panel see Figure 18.

b) Remove the two securing screws for the hinged front panel.

c) This exposes the electrical terminal rail, see Figure 20

d) Remove the screws securing the access plate.

e) Push the interconnection cables up through the cable channel and the access plate.

f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with the correct size lugs and connected on the bottom side terminals as marked.

g) Install or start-up batteries see section 13.1

h) Replace and tighten the terminal securing screws fully clockwise and refit the access plate.

i) Replace the terminal board compartment panel and the front cover.

OBSERVE POLARITIES AND ORIENTATIONS.

See Remote Alarms and Computer Interface for connections to these facilities. For optional battery cubicles, refer to section 13.2.

Output, Reserve, Input and External Battery Terminals

Hinged panel security screws

Cable channel

Cable support page 34 – UPLIT042 rev.4 - 05/2005

Figure 20 - 20 – 10/15/20kVA: Cable Connections

Modem and Multicom power supplies sec. max 14 AWG

U2

FRONT

R

ES

ER

VE

IN

P U

T

M6

G R

O U

N D

P R

IM

A R Y

IN

PU

T

W1V1U1 N PE U V W N

Ba tte ry

C ha rg e r

In hi b i te dE.

P.

O

O U

TP

U

T

EX

TE

R N

AL

B A

TT

ER

IE

S

V2 NW2

Label

REAR

Computer relay interface - FEMALE

RAU - FEMALE

RS232 - MALE

UPLIT042 rev4 - 05/2005-- page 35

5.3 30 – 30/30kVA

Ensure the AC supplies and load are switched OFF. Check that all the MEPEM UPS Switches (behind the front panel) are switched OFF, see figure 13.

The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure the AC supply voltage at the MEPEM UPS terminals is within +/- 10% of nominal.

The MEPEM UPS should be connected to the main/reserve supplies and output load via a wall mounted junction box.

Figure 21 - 30 – 30/30kVA: Switches and Breakers

Terminal board compartment

S2 = Equipment Reserve switch

S3 = Equipment By-pass switch

S1 = Equipment ON/OFF Breaker page 36 – UPLIT042 rev.4 - 05/2005

Figure 22 - 30 – 30/30kVA: Connections

Access to the terminals for electrical connections is as follows:

a) Remove front panel see Figure 22.

b) Remove the terminal board compartment panel by unscrewing the fixing screws at the front.

c) This exposes the electrical terminal rail, see Figure 23

d) Remove the screws securing the access plate.

e) Push the interconnection cables up through the access plate.

f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with the correct size lugs and connected on the bottom side terminals as marked.

g) Install or start-up batteries see section 13.3 and 13.4.

h) Replace and tighten the terminal securing screws fully clockwise and refit the access plate.

i) Replace the terminal board compartment panel and the front cover.

OBSERVE POLARITIES AND ORIENTATIONS.

See Remote Alarms and Computer Interface for connections to these facilities.

Output, Input, Reserve and External Battery Terminals

Access plate

S3 = Equipment By-pass switch

S2 = Equipment Reserve switch

UPLIT042 rev4 - 05/2005-- page 37

Figure 23 - 30 – 30/30kVA: Cable Connections

QS4

Modem and Multicom power supplies

G R

O U

N D

N

EU

TR

A L

(R

ES

/O U

T )

PR

IM

AR

Y

IN

PU

T

E X

TE

R N

AL

B A

TT

ER

IE

S

R

ES

ER

VE

IN

P U

T

O U

T P U

T

UPE

QS1

W2U1V W N U2 V2V1W1

FRONT

QS2

E.

P.

O

B a tte ry c ha rg e in hi bi te d

QS3

RAU - FEMALE

RS232 - FEMALE

Computer relay interface - FEMALE

REAR

page 38 – UPLIT042 rev.4 - 05/2005

5.3 MEPEM 50/75kVA

Ensure the AC supplies and load are switched OFF. Check that all the MEPEM UPS Switches (behind the front panel) are switched OFF, see figure 16.

The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure the AC supply voltage at the MEPEM UPS terminals is within +/- 10% of nominal.

The MEPEM UPS should be connected to the main/reserve supplies and output load via a wall mounted junction box.

Figure 24 – 50/75kVA: Switches and Breakers

Terminal board compartment

S5 = RESERVE OUTPUT switch

S3 = BY-PASS switch

S2 = Equipment RESERVE switch

S4 = INVERTER OUTPUT Breaker

UPLIT042 rev4 - 05/2005-- page 39

Figure 25 – 50/75kVA: Connections

Access to the terminals for electrical connections is as follows:

a) Remove front panel see Figure 22.

b) Remove the terminal board compartment panel by unscrewing the fixing screws at the front.

e) This exposes the electrical terminal rail, see Figure 23.

f) Remove the screws securing the access plate.

e) Push the interconnection cables up through the access plate.

f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with the correct size lugs and connected on the bottom side terminals as marked.

g) Install or start-up batteries see section 13.3 and 13.4.

h) Replace and tighten the terminal securing screws fully clockwise and refit the access plate.

i) Replace the terminal board compartment panel and the front cover.

OBSERVE POLARITIES AND ORIENTATIONS.

See Remote Alarms and Computer Interface for connections to these facilities.

Output, Input, Reserve and External Battery Terminals

Access plate

S5 = RESERVE OUTPUT switch

S3 = BY PASS switch

S2 = Equipment RESERVE switch

S4 = INVERTER OUTPUT Breaker page 40 – UPLIT042 rev.4 - 05/2005

Figure 26 – 50/75kVA: Cable Connections

Modem and Multicom power supplies

RAU - FEMALE

Computer relay interface - FEMALE

RS232 - MALE

QS3

R

ES

ER

VE

IN

P U

T

PR

IM

AR

Y

IN

PU

T

EX

TE

R N

AL

BA

TT

E R

IE

S

QS1

U U1 V1 W1V W

QS2

FRONT

E.

P.

O

O U

TP

U

T

Ba tte ry c ha rg e in hi bi te d

Th er m os tic k co nt a c ts

QS5

1 2 3 4 5 6W2 N NU2 V2 PE

QS4

REAR

UPLIT042 rev4 - 05/2005-- page 41

5.4 Signal connections

a) Battery charge inhibited

By removing the link between terminals 3 and 4, the battery charge will be inhibited, and a warning message will be displayed.

Possible uses of this could be one, or more, of the following:

• connect the above terminals to a contact which will be opened if there is Hydrogen within the battery compartment(s).

In this way the cause of hydrogen generation will be stopped, and a warning about the operating status of the system will be displayed.

• connect the above terminals to a contact which will be opened when the UPS is supplied by a Generator (it should be an auxiliary contact of the Line <-> Generator changeover).

In this way it will be possible to limit the power supplied by the Generator to the only value required to supply the critical loads, and not to charge the battery until the mains supply returns.

In this way it is possible to use a Generator having a power rating less than the maximum input power of the UPS.

Also in this case a warning about the operating status of the system will be displayed.

b) Thermostick connector (50/75kVA only)

This connection provides the customer with remote control over the output transformer Overtemperature Alarm (TCORE = 175°C).

NOTE: If more than one of the above applications (or similar) are installed, the contacts MUST be connected in series.

page 42 – UPLIT042 rev.4 - 05/2005

6.0 CONTROLS

6.1 User Controls

The user controls are situated on the front panel, see Figure 27.

Access to the Equipment Power Switches can be obtained by removing the front cover.

Figure 27 – Control panel

Illuminated Liquid Crystal Display

User Switches Audible Alarm

Cancel Switch Inverter

Start Inverter

Stop

R ~

B

I ~

1 2 3 4 5

S

Display indicators

1) Utility Supply Indicator (Green)

2) Battery Indicator (Green)

3) Inverter Indicator (Green)

4) Static Switch indicator (Green)

5) Reserve Supply Indicator (Green)

6) Warning Indicator (Red)

UPLIT042 rev4 - 05/2005-- page 43

6.2 Control Panel

Inverter Start Up

This allows the user to turn on and reset the inverter. This is normally only used when starting the UPS.

Inverter Shutdown

The switch incorporates a safety feature to prevent inadvertent operation yet still allow rapid shutdown in the event of an emergency. This is achieved by the requirement that the switch be depressed for 2 seconds before the inverter stops during which time the audible alarm will be heard.

Audible Alarm Cancel Switch

This switch cancels the audible alarm. When pressed the red warning light goes from continuous illumination to flashing on and off.

Page Right Control

This switch changes the page headings displayed on the LCD. It also allows the alarm and measurement statuses to be stepped through when examining the power history (refer to section 10.6)

Record Up

This switch changes the record displayed on the LCD to the previous message displayed. When the top of the page has been reached the display will no longer scroll.

Record Down

This switch changes the record displayed on the LCD to the next record on the page. When the bottom of the page has been reached the display will no longer scroll.

page 44 – UPLIT042 rev.4 - 05/2005

7.0 START UP

1. Switch on the AC reserve and the main AC Utility supply to the UPS.

2. Turn on the Utility supply Input, Reserve Input (if fitted) and UPS Output switches located behind the front panel, see figure 18 for 20kVA, figure 21 for 30kVA or figure 20 for 50/75kVA.

3. Replace the front panel.

4. Press the CANCEL AUDIBLE ALARM switch (see section 6.2)

5. Initially, all the green indicators will flash on the display mimic. After about 30 seconds the supply and battery indicators should stop flashing.

6. Press the Inverter On push button (I).

7. The inverter should now start and after a delay of approximately 30 seconds the message ‘SYSTEM NORMAL’, in English, will appear on the liquid crystal display.

8. Select the required language by pressing page right control until the ‘SELECT LANGUAGE’ message appears on the liquid crystal display. Press the page down control until the required language is selected. Press the page right control once more confirm the language selection.

Thereafter, all messages will appear in the selected language.

8.0 MAINTENANCE BYPASS

The MEPEM UPS is equipped with Manual Maintenance Bypass systems. If a unit requires servicing, the Manual Maintenance Bypass allows the load to be connected directly to the AC supply so that the unit may be serviced in safety.

The following instructions must be followed:

1. Ensure that ‘SYSTEM NORMAL’ is displayed on the LCD. (Note: If ‘SYSTEM NORMAL’ is not displayed check that the inverter is not ‘OUT OF SYNC’, see section 10.7. Turning the inverter off under this fault condition will interrupt the load supply.)

2. Turn off the inverter by pressing the inverter shutdown button for more than 2 seconds

3. Turn the Maintenance Bypass Switch (located behind front panel, see figure 18, 21 or 20) to ON.

4. Turn off the Primary Input, Reserve Input and UPS Output Switches, see figure 18, 21 or 20.

THE LOAD IS NOW SUPPLIED DIRECTLY FROM THE AC UTILITY SUPPLY AND IS NO LONGER

PROTECTED BY THE UPS

CAUTION: Some components in the UPS will retain a static voltage even after the switches have been opened. Also, on the 50/75kVA ratings, the isolating transformer and the relative cooling fans are still supplied from the Bypass.

To return to the normal operating mode, follow the above procedure in reverse.

Note: The MEPEM UPS must not be left operating with the Maintenance Bypass Switch in the ON position.

UPLIT042 rev4 - 05/2005-- page 45

9.0 SHUT-DOWN

1. Close down the load in an orderly manner.

2. Push the (inverter shutdown) button for more than 2 seconds.

3. Turn the main switch to OFF.

Note: If the electricity supply to the site is switched off outside normal working hours, the MEPEM should be shut down each evening by using the shutdown procedure.

This will prevent the battery from discharging.

If, on the other hand, the supply to the site is continuous, the MEPEM should be operated 20 hours a day.

page 46 – UPLIT042 rev.4 - 05/2005

10.0 VISUAL AND AUDIBLE ALARMS

The MEPEM UPS is equipped with visual and audible alarms which indicate the status of the UPS to the operator. The visual alarms are displayed on the LCD and the mimic panel.

10.1 Silencing Audible Alarm

The audible alarm sounds when the UPS is in an alarm condition. The sound is silenced by pressing the button marked

When pressed, the red warning light which is illuminated continuously starts to flash, providing an even clearer indication of the alarm condition, even though the audible alarm has been silenced.

10.2 Mimic

The display mimic consists of a pictorial representation of the functional blocks in the MEPEM UPS. When the system is in NORMAL OPERATING CONDITION the green indicators are illuminated continuously.

In the event of an ALARM condition the indicators start to flash identifying the part (or parts) of the system in alarm (see figure 19).

Further information on the alarms can be obtained from the LCD by scrolling through the page headings using the button (page right control) until the message on the display describes the functional block in the UPS identified by the flashing LED(s).

The alarms can then be accessed using the (scrolling up) and (scrolling down) record buttons. This procedure is described in detail in section 10.4.

10.3 Liquid Crystal Display

The display is a 40-character (2 line x 20 character) module which is back lit.

The messages describing the functioning of the system are accessed via the user switches (see figure 18).

UPLIT042 rev4 - 05/2005-- page 47

10.4 Display Page Headings

After initial power up, under normal operating conditions, the main page heading will be displayed:

UPS xx KVA

SYSTEM NORMAL

The first line displays the power rating of the MEPEM UPS, the second line is the system status.

During normal operating conditions, the display reading always returns to this page heading whenever the user switches are not operated for at least 5 minutes.

By pressing the button marked once, the battery rectifier heading is displayed:

RECT/BATT ALARMS

NO ALARMS ACTIVE

The second line of the display confirms that the rectifier and battery are functioning correctly.

By pressing the button marked again, the inverter heading is shown on the display:

INVERTER ALARMS

NO ALARMS ACTIVE

The second line of the display confirms that the inverter is functioning correctly.

By pressing the button marked again, the load output and reserve supply heading is displayed:

LOAD/RES ALARMS

NO ALARMS ACTIVE

The second line of the display indicates that the UPS load output and reserve supply input are correct.

page 48 – UPLIT042 rev.4 - 05/2005

By pressing the button marked again, the selected battery test period appears on the display:

BATTERY TEST

WEEKLY

The button marked is pressed to scroll through the 4 battery test period available (WEEKLY, FORTNIGHTLY, MONTHLY and NONE).

The button marked is pressed to scroll through the list in reverse order.

When the required battery test period appears, press the button marked to select the battery test period and the selected language heading appears on the display.

SELECTED LANGUAGE

ENGLISH

The button marked is pressed to scroll through the languages available (English, French, German, Italian and Spanish).

The button marked is pressed to scroll through the list in reverse order.

When the required language appears, press the button marked to select the language and to return the display to the main UPS status message.

UPLIT042 rev4 - 05/2005-- page 49

If at any time the inverter is blocked then the power history heading appears:

POWER HISTORY

DOWN TO ACCESS

The power history page is described in detail in section 10.6.

The machine measurement signals are accessed from the main page heading as follows:

UPS xx kVA

SYSTEM NORMAL

press once

RECTIFIER

Vdc xxx V Idc xxx A

Displays the output voltage and current supplied by the rectifier.

BATTERY

Vb xxx V Ib xxx A

Displays the battery voltage and the charge or discharge current of the battery (ve = charge, - ve = discharge)

INVERTER F xx.x Hz A xxx V B xxx V C xxx V

Displays the frequency and phase-neutral voltage at which the inverter is running.

AB xxx V BC xxx V CA xxx V

Displays the frequency and phase-phase voltage at

RESERVE F xx.x Hz

Displays the frequency and the phase-neutral voltage of the reserve supply.

RESERVE F xx.x Hz

Displays the frequency and the phase-phase voltage of the reserve supply.

page 50 – UPLIT042 rev.4 - 05/2005

LOAD F xx.x Hz A xxx V B xxx V C xxxV

Displays the frequency and phase-neutral voltage supplied to the load.

LOAD F xx.x Hz AB xxx V BC xxx V CA xxxV

Displays the frequency and phase-phase voltage

LOAD

A xxx A B xxx A C xxx A

Displays the current supplied to the load.

A x% B x% C x%

Displays the load capacity percentage of the UPS rated value.

LOAD P.F. 0.99

P = 80kW s = 80kVA

Displays the Peak Factor of the load current.

TIME ON INVERTER

xxg: xxh: xxm: xxs

Displays the total time the load has been supplied by the inverter since the machine was last switched off.

TIME ON RESERVE

Displays the total time the load has been supplied by the reserve since the machine was last switched off.

UPLIT042 rev4 - 05/2005-- page 51

LAST MAINS FAILURE

xxd: xxh: xxm: xxs

Displays the duration time of the most recent Mains Failure

MAINS FAILURE yy xxgg: xxh: xxm: xxs

Displays the number of mains failures and the total duration of these failures since the machine was last switched off.

TOTAL MAINS FAILURE yy

Displays the total number of mains failures and their total duration since the machine was installed.

REV A. XX xx-xx-xx 10h00yyy

Displays the code for the version of software resident (and relevant data) within the MEPEM UPS system page 52 – UPLIT042 rev.4 - 05/2005

The measurement signals are accessed from the battery rectifier page as follows:

RECT/BATT ALARMS

Normal operating mode

RECTIFIER

Vdc xxx V Idc xxx A

Displays the output voltage and current supplied by the rectifier.

BATTERY

Vdc xxx V Ib xxxx A

Displays the battery voltage and the charge or discharge current of the battery (ve = charge, - ve = discharge)

The measurement signals are accessed from the inverter page as follows:

INVERTER ALARMS

Displays the frequency and phase-neutral voltage at

Displays the frequency and phase-phase voltage at

INVERTER

Displays the current at which the inverter is running.

UPLIT042 rev4 - 05/2005-- page 53

The measurement signals are accessed from the load output - reserve supply page as follows:

LOAD/RES ALARMS

LOAD f xx.x Hz

LOAD f xx.x Hz

Displays the current supplied to the load.

A x% B x% C x%

Displays the load capacity percentage of the UPS rated value.

LOAD P.F. 0.99

P = 80kW s = 80kVA

Displays the Peak Factor of the load current.

RESERVE F xx.xHz A xxx V B xxx V Cxxx V supplied to the reserve line.

RESERVE F xx.xHz supplied to the reserve line.

page 54 – UPLIT042 rev.4 - 05/2005

10.5 Abnormal operating mode messages

Under abnormal operating conditions, the normal functioning heading on the main page UPS xx KVA

SYSTEM NORMAL

is replaced with the alarm page:

UPS xx KVA

SYSTEM ALARM

If at least 1 alarm is activated for each block; the »NO ALARMS ACTIVE» message in the second line on the display is replaced with the first active alarm. Whenever there is more than one active alarm, they can be scrolled through using the and keys.

Each message is associated with one of the following conditions:

NORMAL

Conditions which do not adversely affect the normal functioning of the machine are identified under this heading.

No action is required on the part of the operator.

WARNING

Transitory conditions which can either return to normal condition or result in a permanent fault are identified under this heading. No action is required on the part of the operator.

FAULT

Faults are identified under this heading. The intervention of a qualified technician is required.

Alarms which do not come under any of these headings do not require any action if arising separately.

MAIN PAGE HEADING ALARMS

MESSAGE CONDITION

TESTING BATTERY NORMAL

NOT CALIBRATED FAULT

TESTING AUTONOMY WARNING

SYSTEM TEST MODE FAULT

UPLIT042 rev4 - 05/2005-- page 55

a) When the battery is discharging, the machine displays the residual autonomy and the discharging time information.

1. If no information on autonomy is available, then the following message is displayed:

BATTERY DISCHARGING

AUT calc DIS xx min where xx represents the discharging time

2. Where AUTONOMY information is available, the following message will appear:

BATTERY DISCHARGING

AUT yy min DIS xx min where yy represents the residual autonomy of the batteries.

b) In overload condition, the machine calculates the time remaining before the inverter is switched off.

Under this condition, the following message is displayed:

OVERLOAD

INV STOP xx min: yy:s

If the inverter is inhibited due to overloading, the time at which the inverter will be reactivated is displayed, with the following message:

STOP DUE TO OVERLOAD

RESTART IN xx min: yy: s page 56 – UPLIT042 rev.4 - 05/2005

RECTIFIER/BATTERY ALARMS

NOT CALIBRATED FAULT

DC FEEDBACK FAULT FAULT

VERIFY DC FEEDBACK NORMAL

PRIMARY SUPPLY FAULT WARNING

PHASE SEQUENCE ERROR FAULT

BATTERY FAULT FAULT

PCB SUPPLY FAULT FAULT

BATT CONTACTOR OPEN -

BATTERY DISCHARGING WARNING

SHUTDOWN IMMINENT WARNING

DC VOLTAGE HIGH FAULT

DC VOLTAGE LOW WARNING

INPUT SWITCH OPEN FAULT

HARMONIC FILTER OPEN FAULT

RECTIFIER ALARM FAULT

RECTIFIER INHIBITED WARNING

RECTIFIER BLOCKED FAULT

BATT. CHARGE INHIBIT WARNING

UPLIT042 rev4 - 05/2005-- page 57

INVERTER ALARMS

PCB SUPPLY FAULT FAULT

OUT OF SYNC WARNING

DESATURATION FAULT

OVER TEMPERATURE FAULT

BYPASS SWITCH CLOSED FAULT

SHUTDOWN IMMINENT WARNING

DC VOLTAGE HIGH FAULT

DC VOLTAGE LOW WARNING

INVERTER NOT RUNNING FAULT

INVERTER INHIBITED FAULT

INVERTER BLOCKED FAULT

INVERTER VOLTS HIGH FAULT

INVERTER VOLTS LOW FAULT

OVERLOAD WARNING

STOP DUE TO OVERLOAD FAULT

CURRENT LIMIT WARNING

INV.ST. SWITCH FAULT FAULT

INV.FREQ.OUT RANG. 8% FAULT

INV. FEEDBACK FAULT FAULT

VERIFYING INV. FREQ. -

VERIFYING BATT. CONT. -

INV.FREQ.OUT 1% FAULT

page 58 – UPLIT042 rev.4 - 05/2005

LOAD/RESERVE ALARMS

LOAD ON RESERVE WARNING

LOAD NOT SUPPLIED…