Generator ATS Information (Run Hrs).pdf

PDF 59 KB Posted

Attached to
Replace 400KW Generator Federal contract opportunity
Solicitation number
12405B23Q0465
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery

About this file

This document contains technical specifications for a 400KW generator and associated automatic transfer switch to be replaced under a federal solicitation. The generator is a Generac model 5118530600 with serial number 2083309, rated for 400KW at 480V/277V 3-phase power. Running hours and fuel consumption rates are provided for various loads. The automatic transfer switch is a Cutler Hammer CTVIMGC3 1000XSU with GO number KDO1342, rated for 120/600V 1000A 3-phase power. The related solicitation is number 12405B23Q0465 from the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery to replace the existing 400KW generator. Specifications include voltage and load tolerance ranges for the new generator.

View the file

Other files for this federal contract opportunity

Other files attached to Replace 400KW Generator, newest first.
File Type Posted
Connect Generator-ATS Design.pdf PDF
Service Provisions 1106524.docx DOCX document
SOW 400KW Generator USHRL Ft Pierce FL.pdf PDF
FAR 13 Single Source or Brand Name Justification Less Than SAT VA CO.pdf PDF
Wage Rates.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERATOR (GENERAC)

Model: 5118530600 Serial No: 2083309

400 KW 480V /277V 3 phase 0.8 pf

Gal/hr Running hrs Days

700 gal (693 gal actual)

Voltage tolerance 551 Volts Hi Delta 71 Volts l00KW 8.3 83.5 3.5

200KW

14.3 48.5

300KW

21.3 32.5

1.4

383 Volts Lo 97 Volts

400KW

23.9

Double wall fuel tank protection in case of fuel leak.

ATS (CUTLER HAMMER)

Cat No: CTVIMGC3 l 000XSU GO No: KDO1342

120/600 V 1000 Amps 3 Phase 3 poles

File details come from the government source that posted it. Updated .