Amendment_1.pdf

PDF 175 KB Posted

Attached to
Electrical Upgrade in Building 13 Federal contract opportunity
Solicitation number
1232SDS18JC06
Issued by
Department of Agriculture Agricultural Research Service Central Program Planning Coordination and Support

View the file

Other files for this federal contract opportunity

Other files attached to Electrical Upgrade in Building 13, newest first.
File Type Posted
SF-30_Amendment_03.pdf PDF
SF-30_Amendment_02.pdf PDF
Attachment_I_-_Specifications_for_base.pdf PDF
Solicitation_-_1232SDS18JC06.pdf PDF
Attachment_V_-_Payment_and_Performance_Bond_Forms.pdf PDF
Attachment_III_-_Option_1_-_SOW_with_photos.pdf PDF
Attachment_IV_-_DBA_Wage_Rates.pdf PDF
Attachment_II_-_Drawings_for_base.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1232SDS18JC06 - Amendment 1

The purpose of this amendment is to provide the following information:

1. In addition to Sheet E100, General Note B – In addition to providing temporary power to subzero freezers, provide temporary power to feed exterior packaged AC unit located on the north side of B13 that supplies cooling to RM #307, which houses the subzero freezers. AC is estimated to be 10 tons, contactor to verify electrical requirements of AC unit and subzero freezers.

2. Clarification to SOW, Construction, 1b – there is an existing 3” conduit under driveway between B11 and B13 that may be utilized for installation of new feeders. Conduit extends width of driveway only, it does not extend from B13 panel to B11 panel.

File details come from the government source that posted it.