11. PMs-Pittsburgh.docx
DOCX document 84 KB Posted
- Attached to
- Request for Information: NIOSH Facilities Operations and Maintenance Support Federal contract opportunity
- Solicitation number
- Not on record
About this file
This is a Request for Information issued by the Centers for Disease Control and Prevention to identify contractors capable of performing operations and maintenance requirements at National Institute for Occupational Safety and Health campuses in Pittsburgh, Pennsylvania; Spokane, Washington; Morgantown, West Virginia; and Cincinnati, Ohio. Key requirements include facilities and physical plant operations, maintenance, repair, and select support services for all buildings, utilities, roadways and grounds at the referenced NIOSH facilities to maintain continuous operations. An 8(a) set aside is being considered. Respondents are requested to provide contact information, business size classification, confirmation of GSA schedule use and site visit ability, descriptive literature demonstrating ability to meet performance work statement requirements, and experience with commercial, federal, state and local government contracts illustrating capability to meet specific performance work statement requirements. Feedback on the draft performance work statement is also requested.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 1. O&M DRAFT Performance Work Statement_Feb 2024_v3.docx | DOCX document | |
| 4. Campus Map - Cincinnati.pdf | ||
| 7. Floor plans-Pittsburgh.pdf | ||
| 9. Floor plans-Cincinnati.pdf | ||
| 12. PMs-Cincinnati.xlsx | XLSX spreadsheet | |
| 14. PMs-Spokane.docx | DOCX document | |
| 15. AssetsEquipment-Pittsburgh.xlsx | XLSX spreadsheet | |
| 3. Campus Map - Morgantown.pdf | ||
| 5. Campus Map - Spokane.pdf | ||
| 10. Floor plans-Spokane.pdf | ||
| 18. AssetsEquipment-Spokane.xlsx | XLSX spreadsheet | |
| 13. PMs-Morgantown.xlsx | XLSX spreadsheet | |
| 16. AssetsEquipment-Morgantown.xlsx | XLSX spreadsheet | |
| 19. Government Furnished Equipment_Pittsburgh.pdf | ||
| 2. Campus Map - Pittsburgh.pdf | ||
| 6. Building Gross Square Footage for all Campuses.pdf | ||
| 8. Floor plans-Morgantown.pdf | ||
| 17. AssetsEquipment-Cincinnati.xlsx | XLSX spreadsheet | |
| 20. Historical Positions Data.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NAME
| SHOP |
| SERVICE/DESCRIPTION |
| ASSET/LOCATION |
| ESTIMATE |
| IS ACTIVE |
| LAST COMPLETED DATE |
PMI 300 MONTHLY AIR DRYER
1 Task
| HVAC |
| PM |
PMI 300 MONTHLY AIR DRYER
NOTE TO WORK CONTROL PRINT ATTACHMENT
COMPLETE THE FOLLOWING FOR THE AIR DRYER:
1. INSPECT THE CONDENSER COILS AND CLEAN AS REQUIRED WITH A SOFT BRUSH OR BLOW OFF...
PITT-SITE-WIDE
PITT-SITE-WIDE
B151 WATER FILTER CHANGE
| Plumbing |
| PM |
B151 - CHANGE MAIN WATER FILTER ON 152 SIDE OF BUILDING
FILTER - RBG5A29.3
B152 B152
PMI 181 SEMIANNUAL SULLAIR AIR COMPRESSOR B040 OIL SAMPLE ANALYSIS
| Mechanic |
| PM |
PMI 181 SEMIANNUAL SULLAIR AIR COMPRESSOR B040 OIL SAMPLE ANALYSIS
B040 B040
B013 BACNET SYSTEM
| HVAC |
| PM |
CHECK BACNET SYSTEM FOR PROPER OPERATION
CHECK BUILDING TEMP AND RECORD
B013 B013
MONTHLY PEST CONTROL REPORT
| GMW |
| PM |
MONTHLY PEST CONTROL REPORT
NOTE- PRINT ATTACHMENT
PITT-SITE-WIDE
MONTHLY MECHANIC PMI 074 EMERGENCY GENERATOR BUILDING 141
| Mechanic |
| PM |
MONTHLY MECHANIC PMI 074 EMERGENCY GENERATOR BUILDING 141
EMERGENCY GENERATOR
1. CHECK OIL FILTER, CHANGE IF NECESARY
2. CHECK AIR FILTER, CHANGE IF NECESARY
B141 B141
MONTHLY ELECTRICIAN PMI 074 EMERGENCY GENERATOR (EBM)
| Electrical |
| PM |
Monthly ELECTRICIAN PMI 074 EMERGENCY GENERATOR (EBM) BUILDING 141
Emergency Generator
1. Blow out with clean, dry compressed air:
a. Engine generator control panel.
b. Automatic trans...
B141
ESC FIRE PANEL BATTERY ANNUAL PMI 008
| Electrical |
| PM |
FIRE PANEL BATTERY ANNUAL
NOTE TO WORK CONTROL PRINT ATTACHMENT
CHECK BATTERIES. IF BATTERIES ARE BELOW 65% CAPACITY REPLACE BATTERY
PITT-SITE-WIDE
SEMI ANNUAL HALON SYSTEMS
2 Tasks
| Work Control |
| PM |
SEMI ANNUAL HALON SYSTEMS
FIRE FIGHTERS
724-720-6000
CONTRACT NUMBER 146883
B004 ,B003 - L1 - R109 B004 ; B003 - L1 - R109
PMI 142 MECHANIC AIR COMPRESSOR QUARTERLY ECA AND ACP
| Mechanic |
| PM |
PMI 142 AIR COMPRESSOR QUARTERLY ECA AND ACP
MECHANIC
NOTE TO WORK CONTROL PRINT ATTACHMENT
THE FOLLOWING TASK IS TO BE PERFORMED ON EACH COMPRESSOR.
Q 1. Check the compressor and tubing ...
PITT-SITE-WIDE
PMI 142 MECHANIC AIR COMPRESSORS ACP AND ECA MONTHLY
| Mechanic |
| PM |
MONTHLY AIR COMPRESSORS
MECHANIC
NOTE TO WORK CONTROL PRINT ATTACHMENT
ACP AND ECA
PMI 142
COMPLETE THE FOLLOWING FOR THE AIR COMPRESSORS:
INSPECT THE INLET AIR FILTER ELEMENT. C...
PITT-SITE-WIDE
PMI 015 GEO THERMAL HEAT PUMPS EAC HHP ANNUAL
| HVAC |
| PM |
PMI 015 GEO THERMAL HEAT PUMPS EAC HHP ANNUAL
NOTE TO WORK CONTROL PRINT ATTACHMENTS
A 1. Repair or replace flexible duct connections as necessary.
A 2. Report damage or deterioration not re...
B144 B144
PMI 015 GEO THERMAL HEAT PUMPS EAC HHP QUARTERLY
| HVAC |
| PM |
PMI 015 GEO THERMAL HEAT PUMPS EAC HHP QUARTERLY
NOTE TO WORK CONTROL PRINT ATTACHMENT
HVAC
S 1. Request permission from area supervisor/foreman to take unit "out of service". Provide him o...
B144 B144
PMI 015 CENTRAL AIR CONDITIONING EQUIPMENT SEMI ANNUAL EAC
| HVAC |
| PM |
PMI 015 CENTRAL AIR CONDITIONING EQUIPMENT SEMI ANNUAL EAC
NOTE TO WORK CONTROL PRINT ATTACHMENT
HVAC
S 1. Request permission from area supervisor/foreman to take unit "out of service". Pro...
PITT-SITE-WIDE
PMI 013 CENTRAL AIR CONDITIONING EQUIPMENT SEMI ANNUAL EAC
| HVAC |
| PM |
PMI 013 CENTRAL AIR CONDITIONING EQUIPMENT SEMI ANNUAL EAC
NOTE TO WORK CONTROL PRINT ATTACHMENT
CENTRAL AIR CONDITIONING EQUIPMENT
S 1. Repair or replace flexible duct connections as necess...
PITT-SITE-WIDE
PMI 013 CENTRAL AIR CONDITIONING EQUIPMENT QUARTERLY EAC
| HVAC |
| PM |
PMI 013 CENTRAL AIR CONDITIONING EQUIPMENT QUARTERLY EAC
NOTE TO WORK CONTROL PRINT ATTACHMENT
HVAC
Q 1. Request permission from area supervisor/foreman to take unit "out of service." Prov...
PITT-SITE-WIDE
PMI 085 ICE MAKING MACHINE ANNUAL ECB
| HVAC |
| PM |
PMI 085 ICE MAKING MACHINE ANNUAL ECB
NOTE TO WORK CONTROL PRINT ATTACHMENT
Disassemble ice cuber water system and clean in accordance with instructions in the Hashizaki Instruction Manual,...
PITT-SITE-WIDE
PMI 085 ICE MAKING MACHINE QUARTERLY ECB
| HVAC |
| PM |
PMI 085 ICE MAKING MACHINE QUARTERLY ECB
NOTE TO WORK CONTROL PRINT ATTACHMENT
Complete in-place cleaning of the ice cuber water system in accordance with typical cleaning instructions in th...
PITT-SITE-WIDE
PMI 170 PORTABLE LADDER INSPECTION ANNUAL
| Work Control |
| PM |
PMI 170 PORTABALE LADDER INSPECTION ANNUAL
1. Inspect all portable ladders for the following items:
• Free of sharp edges, splinters; solidly constructed and decay free
• Joints between the ...
B019 B019
PMI 171 FALL ARREST SYSTEM INSPECTION ANNUAL
| Work Control |
| PM |
PMI 171 FALL ARREST SYSTEM INSPECTION ANNUAL
TOTAL SAFETY 725-745-1919
PITT-SITE-WIDE
PMI 142 HVAC AIR DRYER AND AIR COMPRESSOR QUARTERLY ECA AND ACP
| HVAC |
| PM |
PMI 142 AIR DRYER AND AIR COMPRESSOR QUARTERLY ECA AND ACP
HVAC
NOTE TO WORK CONTROL PRINT ATTACHMENT
THE FOLLOWING TASK IS TO BE PERFORMED ON EACH COMPRESSOR.
Q 1. Check the compressor a...
PITT-SITE-WIDE
PMI 104 HEATING SYSTEM WATER PUMPS EPA SEMIANNUAL
| HVAC |
| PM |
PMI 104 HEATING SYSTEM WATER PUMPS EPA SEMIANNUAL
NOTE TO WORK CONTROL PRINT ATTACHMENT
EPA0007, EPA0008, EPA0009
S 1. Check pump shaft packing for excessive leakage and tighten if requir...
PITT-SITE-WIDE
PMI 104 HEATING SYSTEM WATER PUMPS EPA ANNUAL
| HVAC |
| PM |
PMI 104 HEATING SYSTEM WATER PUMPS EPA ANNUAL
NOTE TO WORK CONTROL PRINT ATTACHMENT
EPA0007, EPA0008, EPA0009
A 1. Change pump shaft packing. Clean out packing box sumps.
A 2. Grease pum...
PITT-SITE-WIDE
ANNUAL GENERATOR TESTING
| Work Control |
| PM |
ANNUAL GENERATOR TESTING
DO BE DONE IN HOUSE- FILTER AND OIL CHANGES
REGULAR MOTOR OIL
PLEASE CONTACT KELLY GENERATORS
410-257-5225
JENNA WINDSOR EXT 126
PITT-SITE-WIDE
ARC Flash Study
| Electrical |
| PM |
ARC FLASH STUDY
COMPLETE ARC FLASH STUDY FOR SITE
PITT-SITE-WIDE
B019 BREAKROOM SINK FILTER
| Plumbing |
| PM |
B019 - INSPECT FILTER IN BREAKROOM SINK, ON PUMP
B019
DAYLIGHT SAVINGS TIME CHANGE CLOCKS
| Electrical |
| PM |
DAYLIGHT SAVINGS TIME - TURN CLOCKS BACK ONE HOUR
PITT-SITE-WIDE
SEMI ANNUAL ICE MACHINE FILTER CHANGES
3 Tasks
| Plumbing |
| PM |
SEMI ANNUAL ICE MACHINE FILTER CHANGES
CHECK/CHANGE FILTERS IN ICE MACHINES
BUILDINGS 001, 140, 143
ECB0003,ECB0002,ECB0001
B140; B001; B143
PLUMBER BOILER START UP
| Plumbing |
| PM |
PLUMBER BOILER START UP
LUBRICATE PUMP
37, 141, 140
PITT-SITE-WIDE
ELECTRICAN ELECTRIC HEATER START UP AND SHUT DOWN
| Electrical |
| PM |
ELECTRICIAN ELECTRIC HEATERS START UP AND SHUT DOWN
NOTE TO WORK CONTROL PRINT ATTACHMENT
turn on the breakers in the hallways for start up of the heaters
Turn off breakers in hallways fo...
PITT-SITE-WIDE
BOILER START UP AND SHUT DOWN
| HVAC |
| PM |
HVAC BOILER START UP AND SHUT DOWN.
NOTE TO WORK CONTROL - TURN BOILER PMS BACK ON
PITT-SITE-WIDE
MONTHLY GENERATOR REPORT
| Mechanic |
| PM |
MONTHLY GENERATOR REPORT
NOTE TO WORK CONTROL PRINT ATTACHMENT
PITT-SITE-WIDE
PMI 182 SEMIANNUAL HOSEBIBS
| Plumbing |
| PM |
PMI 182 SEMIANNUAL HOSEBIBS
NOTE TO WORK CONTROL PRINT ATTACHMENT
1. Shut the valve off to the outside hose bib.
2. Locate the inside shut off valve.
3. Turn the valve on inside.
PITT-SITE-WIDE
PMI 121 FIRE PROTECTION SPRINKLER SYSTEMS ESA ANNUAL
| Plumbing |
| PM |
ANNUAL FIRE PROTECTION SPRINKLER SYSTEMS (ESA) PMI 121
NOTE TO WORK CONTROL PRINT ATTACHMENT
1. Close shutoff valve in the 2" alarm line
2. Open the 2" drain valve until the discharge wate...
PITT-SITE-WIDE
HEAVY EQUIPMENT MONTHLY ENGINE RUN
| Heavy Equipment |
| PM |
HEAVY EQUIPMENT MONTHLY ENGINE RUN
NOTE TO WORK CONTROL - PRINT ATTACHMENT
MONTHLY - RUN ALL PORTABLE GENERATORS AND SMALL GAS ENGINES
THIS PM IS FOR ANY SMALL EQUIPMENT, GENERATOR, ETC
B019
GMW MONTHLY ENGINE RUN
| GMW |
| PM |
GMW MONTHLY ENGINE RUN
NOTE TO WORK CONTROL - PRINT ATTACHMENT FOR 10-15 MINUTES EACH
MONTHLY - RUN ALL PORTABLE GENERATORS AND SMALL GAS ENGINES
THIS PM IS FOR ANY SMALL EQUIPMENT, GENER...
B019
MONTHLY PMI 136 EXHAUST FAN FOR RADON BUILDING 003 EHF0092
| HVAC |
| PM |
MONTHLY PMI136 EXHAUST FAN FOR RADON
BUILDING 003
EHF0092
ADD 4 PUMPS OF NLGI GRADE 2 LITHIUM BASED GREASE TO BEARINGS. WRITE THE DATE THE BEARINGS WERE GREASED ON THE INSPECTION TAG.
EHF0092
B003 - L2
PMI 004 AIR CONDITIONING WINDOW UNITS ANNUAL EAW
| HVAC |
| PM |
ANNUAL PM AIR CONDITIONING WINDOW UNITS EAW
NOTE TO WORK CONTROL - PRINT ATTACHMENT
PMI 004
HOUSING AND BRACING
Check for Cleanliness and Corrosion Protection.
1. Inspect housing and b...
PITT-SITE-WIDE
BIMONTHLY BUILDING INSPECTIONS
| GMW |
| Rounds |
BIMONTHLY BUILDING INSPECTIONS
PITT-SITE-WIDE
DAILY BOILER INSPECTION EBW0002 BUILDING 140
| HVAC |
| Rounds |
DAILY BOILER INSPECTION
EBW0002
BUILDING 140
Rounds - Any regularly pre-scheduled rounds style inspection
EBW0002
B140 - L1 - R106
DAILY BOILER INSPECTION EBW0001 BUILDING 037
| HVAC |
| Rounds |
DAILY BOILER INSPECTION
EBW0001
BUILDING 037
Rounds - Any regularly pre-scheduled rounds style inspection
EBW0001
B037 - L1 - R110
MECHANIC MONTHLY ENGINE RUN
| Mechanic |
| PM |
MECHANIC MONTHLY ENGINE RUN
NOTE TO WORK CONTROL - PRINT ATTACHMENT
MONTHLY - RUN ALL PORTABLE GENERATORS AND SMALL GAS ENGINES
THIS PM IS FOR ANY SMALL EQUIPMENT, GENERATOR, ETC. THAT US...
PITT-SITE-WIDE ,B019
B019 ; PITT-SITE-WIDE
PMI 181 ANNUAL SULLAIR AIR COMPRESSOR B040
| Mechanic |
| PM |
ANNUAL SULLAIR AIR COMPRESSOR B040
PMI 181
SAFETY INSTRUCTIONS
1. Notify building Supervisor prior to commencing work, post warning signs or barricades as needed to restrict work area acce...
B040 B040
ANNUAL DOCK LEVELER ECL
| Work Control |
| PM |
ANNUAL DOCK LEVELER
TO BE DONE BY OUTSIDE CONTRACTOR
ECL
ECL0001
Timbers Covar 412-781-4000 to schedule B166 B166
ANNUAL CRANE INSPECTION PM
| Work Control |
| PM |
ANNUAL CRANE INSPECTION PM - AFM
TO BE DONE BY OUTSIDE CONTRACTOR
KONE CRANES
TO SCHEDULE
MAXWELL SESSIONS
630-288-0140 EXT. 17567
INSPECTOR
CASEY MCEWAN
412-514-0230
PITT-SITE-WIDE
MONTHLY B166 FORKLIFT
| Mechanic |
| PM |
MONTHLY B166 FORKLIFT
B166
MONTHLY SCISSOR LIFT
| Mechanic |
| PM |
MONTHLY SCISSOR LIFT/ JLG ARTICULATING LIFT
Check integrity of tires Check water level of battery Check function operation and controls for proper use Check chain is intact and latched B159 ,B019 B019 ; B159
SEMI ANNUAL DOCK LEVELER 113 ECL
| Mechanic |
| PM |
SEMI ANNUAL DOCK LEVELER 113
ECL
ECL0001
1. Inspect hydraulic cylinders, rods, linkages, hydraulic piping and hoses for signs or wear or leakage.
2. Lubricate all moving connections on...
B166
MONTHLY GAS MILEAGE REPORT
| Mechanic |
| ADMIN |
MONTHLY GAS MILEAGE REPORT
B019
PMI 128 QUARTERLY OIL FILLED TRANSFORMER INSPECTIONS
| Electrical |
| PM |
PMI 128 QUARTERLY OIL FILLED TRANSFORMER INSPECTIONS
NOTE TO WORK CONTROL PRINT ATTACHMENT
PREVENTIVE MAINTENANCE – Self explanatory
1. Electricians are to visually inspect perimeter of eac...
PITT-SITE-WIDE
| NAME |
| SHOP |
| SERVICE/DESCRIPTION |
| ASSET/LOCATION |
| ESTIMATE |
| IS ACTIVE |
| LAST COMPLETED DATE |
PMI 081ELECTRIC OPERATED SUMP PUMP WEEKLY EBP
| Plumbing |
| PM |
Weekly PMI 081 Electric Operated Sump Pump (EBP)
NOTE TO WORK CONTROL PRINT ATTACHMENT
M 1. Check Plug
BUILDINGS 062 (4), 004, 141(2), 019 (2), Cochran's Mill Rd Pit
M 2. Check level of...
PITT-SITE-WIDE ,EBP0006
Annual PMI 073 1500 KVA Unit Substation - Sylvania (EBL)
| Electrical |
| PM |
Annual PMI 073 1500 KVA Unit Substation - Sylvania (EBL)
EBL0004
Load Interrupter Switch, Fuses and holders A 1. blow out with clean dry compressed air.
A 2. Wipe all insulation and ins...
PITT-SITE-WIDE ,EBL0004
Semi-Annual PMI 168 Solar Panel
| Electrical |
| PM |
SEMI ANNUAL PMI 168 SOLAR PANEL
S 1. Note and Report special operating problems.
S 2. Visually inspect wiring for any hanging wires. Ensure meter on side of building 140 is operating.
S ...
PITT-SITE-WIDE
Quarterly PMI 174 Gem Vehicle Inspection
| Mechanic |
| PM |
1. Check for deterioration or corrosion on lines, wires, and other parts of the vehicle.
Q 2. The mechanic will visually inspect:
Break Lines Tires Wiring
PMI 018 STEAM UNIT HEATERS ANNUAL EHE
| HVAC |
| PM |
Annual PMI 018 Steam Unit Heaters (EHE)
NOTE TO WORK CONTROL PRINT ATTACHMENT
HVAC
A 1. Check the unit's supply valve to make sure steam delivery is shut off.
A 2. Inspect unit for adeq...
PITT-SITE-WIDE
PMI 016 ZONE AIR CONDITIONING UNITS ANNUAL EAZ
| HVAC |
| PM |
Annual EAZ Zone Air Conditioning Units
NOTE TO WORK CONTROL PRINT ATTACHMENT
PMI 016
A 1. Request permission from area supervisor/foreman for "out of service" time on unit (include "down"...
PITT-SITE-WIDE
PMI 015 CENTRAL AIR CONDITIONING EQUIPMENT ANNUAL EAC
| HVAC |
| PM |
PMI 015 CENTRAL AIR CONDITIONING EQUIPMENT ANNUAL EAC
NOTE TO WORK CONTROL PRINT ATTACHMENT
CENTRAL AIR CONDITIONING EQUIPMENT
A 1. Repair or replace flexible duct connections as necessary.
A...
PITT-SITE-WIDE
PMI 009 BUILDING EXTERIOR INSPECTIONS ANNUAL
| Carpentry |
| PM |
Annual PMI 009 Building Exterior
NOTE: Following sections of this instruction are to be performed semi-annually
S STEPS, PORCHES, RAMPS, LOADING PLATFORMS, WALKWAYS, DRIVEWAYS, COLUMNS, FACA...
PITT-SITE-WIDE
Semi-Annual PMI 006 Building Interiors
| Carpentry |
| PM |
Semi-Annual PMI 006 Building Interiors
NOTE TO WORK CONTROL PRINT ATTACHMENT
OFFICES
S 1. Inspect the floor for worn, damaged, or missing material.
S 2. Inspect walls, including wainscotin...
PITT-SITE-WIDE
PMI 005 BUILDING ROOFS ANNUAL
| Carpentry |
| PM |
Annual PMI 005 Building Roofs
NOTE TO WORK CONTROL- PRINT ATTACHMENT
ROOFING MATERIALS
A 1. Examine roofing material for physical damage.
A 2. Examine roof surface for deterioration cond...
PITT-SITE-WIDE
Semi-Annual PMI 003 Overhead Doors
| Work Control |
| PM |
To be done by an outside contractor.
Semi-Annual PMI 003 Overhead Doors
THIS IS THE OVERHEAD DOOR REPORT BY INSTALLATION SERVICES
1412 PARKWAY VIEW DR
PITTSBURGH 15205 PA
412-809-8999
PITT-SITE-WIDE
Annual PMI 001 Fire Extinguisher
| Work Control |
| PM |
Annual PMI 001 Fire Extinguisher Annual Testing is done by a certified 3rd party in accordance with NFPA Standards
Maura Huggins Dale Scheaffer PFE Corporation 412-323-9774
PITT-SITE-WIDE
Quarterly PMI 011 GFCI Testing PM
| Electrical |
| PM |
Quarterly PMI 011 GFCI Testing PM Main,B098 - L1 B098 - L1; Main
Monthly Fire Extinguisher PM 77 Tasks
PM
Monthly Fire Extinguisher PM
GENERAL REMARKS
1. The approved inspector RWD shall perform all inspections in accordance with NFPA codes and standards and OSH...
EXVS-08, EXVS-07 +75 other(s) Main - B - R3; Main - B - R4; Main - B - R8; Main ...
Annual Forklift Inspection PM 4 Tasks
| Heavy Equipment - Spokane |
| PM |
Annual Forklift Inspection PM
SAFETY INSTRUCTIONS
1. Inspectors shall observe all safety procedures.
Annual Inspection is done by a certified 3rd party in accordance OSHA standards
INSTRUCTIO...
LFTS-01,FKLS-03,FKLS-02,FKLS-01
Main - L1 - R145; Main - L1 - R145; R - Hill Build...
Daily Building Inspection
| GMW |
| Rounds |
Daily Building Inspection
PITT-SITE-WIDE
WEEKLY GAS PUMP REPORT
Monthly PMI 037 Water Boiler (EBW)
| HVAC |
| PM |
Monthly PMI 037 Water Boiler (EBW)
1. MAKE VISUAL INSPECTION FOR PROPER OPERATION OF FLUE, VENT, STACK, OR OUTLET DAMPERS. CHECK DRAFT AS SPECIFIED IN SECTION 2 OF THE INSTRUCTION MANUAL.
2. CH...
B140 ,B037 B037 ; B143; B140
WATER BOILER ANNUAL
| Work Control |
| PM |
WATER BOILER ANNUAL
TO BE COMPLETED BY THIRD PARTY
Chris Mough Service Manager Delval Equipment Corporation 295 Meadowlands Blvd.
Washington, PA 15301 P: (724) 743-0410 x217 C: (724) 25...
PITT-SITE-WIDE
PMI 087 VARIABLE AIR VOLUME TERMINAL REHEAT BOX ANNUAL EHR
| HVAC |
| PM |
VARIABLE AIR VOLUME TERMINAL REHEAT BOX (EHR) ANNUAL PMI 087
NOTE TO WORK CONTROL PRINT ATTACHMENT
It is essential that office occupants be notified in advance of equipment servicing to minimiz...
PITT-SITE-WIDE
Annual PMI 126 VARIABLE AIR VOLUME TERMINAL ELECTRIC REHEAT BOX (EHR)
1. Identify energy sources and follow proper lock-out procedures for this unit prior to servicing.
2. Clean air distribution outlet and air control damper of any dust accumulation using vacuum o...
ANNUAL VACUUM PUMP EVP0001
| HVAC |
| PM |
ANNUAL VACUUM PUMP
EVP0001
PMI 108
Clean the intake air filter and the gas ballast valve filter.
Inspect the coupling for wear. Replace as required.
Change the oil using Gardner Den...
EVP0001,PITT-SITE-WIDE
PITT-SITE-WIDE; B037
PMI 140 ANNUAL PMI STEAM BOILER AT B037 AND B140
| Work Control |
| PM |
THIRD PARTY PM
CONTACT DELVAL
PMI 140 ANNUAL PMI STEAM BOILER AT B037 AND B140
STEAM BOILER ANNUAL
1. VERIFY THE SHUT OFF VALVES OPERATE PROPERLY AND DO NOT LEAK THROUGH WHEN CLOSED. IF AN...
EBS MONTHLY STEAM BOILER
| HVAC |
| PM |
MONTHLY STEAM BOILER
NOTE TO WORK CONTROL PRINT ATTACHMENT
EBS
1. CHECK THE RELIEF VALVE, VERIFY IT IS NOT LEAKING THROUGH.
2. TEST THE LOW WATER CUTOFF. BLOW DOWN THE DEVICE TO REMOVE ...
PITT-SITE-WIDE
B156 - L1 - R108; B141 - L1 - R170; B141 - L1 - R1...
PMI 007 EMERGENCY LIGHTING UNITS SEMI ANNUAL EEA
| Electrical |
| PM |
SEMI ANNUAL PMI 007 EMERGENCY LIGHTING UNITS (EEA)
NOTE TO WORK CONTROL PRINT ATTACHMENT
BATTERY
Check each battery cell using a hydrometer. If cell variation is 30 points or more, it sha...
PITT-SITE-WIDE
QUARTERLY EMERGENCY LIGHTING UNITS (EEA)
BATTERY
Check each battery cell using a hydrometer. If cell variation is 30 points or more, it shall be recorded for replacement.
Check water level in batteries. Add distilled water if nece...
QUARTERLY PMI 014 EMERGENCY EYE WASH STATIONS/SHOWERS (ESG,ESH & ESI)
| Plumbing |
| PM |
NOTE TO WORK CONTROL PRINT ATTACHMENT
QUARTERLY EYE WASH STATIONS / SHOWERS
ESG, ESH, ESI
PMI 014
QUARTERLY EMERGENCY EYE WASH STATIONS
1. ACTIVATE THE UNIT TO FLUSH LINES CLEAN AND VE...
PITT-SITE-WIDE
B004 - L1 - R102; B004 - L2 - R204; B155 - L1 - R1...
PMI 089 POLE LINE AND OTHER HIGH VOLTAGE FUSIBLE DISCONNECT SWITCHES ANNUAL UEB
| Electrical |
| PM |
POLE LINE AND OTHER HIGH VOLTAGE FUSIBLE DISCONNECT SWITCHES (UEB) ANNUAL
SARGENT ELECTRIC SUBCONTRACT
NOTE TO WORK CONTROL - PRINT ATTACHMENT
1. Inspect for physical damage or signs of he...
PITT-SITE-WIDE
ANNUAL PMI 093 MOTOR CONTROL CENTER SQUARE D (EBL)
| Electrical |
| PM |
MOTOR CONTROL CENTER SQUARE D (EBL) ANNUAL PMI 093
NOTE TO WORK CONTROL - PRINT ATTACHMENT
'1. Remove top wireway covers and inner sliding doors to expose the 480 volt horizontal bus runs, as...
PITT-SITE-WIDE
MONTHLY VOLT METER INSPECTIONS
| Electrical |
| PM |
MONTHLY VOLT METER INSPECTIONS
NOTE TO WORK CONTROL PRINT ATTACHMENT
B019 - L1 B019 - L1
MONTHLY GAS ENDING AND GAS REPORT
Monthly PMI 001 Fire Extinguisher
| Work Control |
| PM |
1.Check extinguisher area for items obstructing view.
2.Check all seals. Replace if broken or missing.
3.Check tamper device and/or "Pull Pin". If tampering has occurred, remove unit for ...
PITT-SITE-WIDE
MONTHLY FIRE EXTINGUISHER MAINTAINANCE (ESF)
1.Check extinguisher area for items obstructing view.
2.Check all seals. Replace if broken or missing.
3.Check tamper device and/or "Pull Pin". If tampering has occurred, remove unit for ...
MONTHLY PM EIA CRANES OVERHEAD AND GANTRY PMI 002
| Electrical |
| PM |
MONTHLY PM EIA CRANES OVERHEAD AND GANTRY
PMI 002
NOTE TO WORK CONTROL: PRINT ATTACHMENT
1. Check all functional operating mechanisms for maladjustment interfering with proper operation a...
PITT-SITE-WIDE
MONTHLY CFC REPORT
| HVAC |
| ADMIN |
NOTE TO WORK CONTROL PRINT ATTACHMENT
MONTHLY CFC REPORT
SUBMIT TOTAL USED OR RECYCLED CFCS TO WORK CONTROL
B019 - L1 - R112 B019 - L1 - R112
QUARTERLY PMI 123 LABORATORY FUME HOOD TESTING AND MAINTENANCE ESD
| HVAC |
| PM |
QUARTERLY PMI 123 LABORATORY FUME HOOD TESTING AND MAINTENANCE (ESD)
NOTE TO WORK CONTROL PRINT ATTACHMENT
1. Turn fan ON and check for unusual vibrations and noises. If these conditions exi...
PITT-SITE-WIDE
LABORATORY FUME HOOD TESTING AND MAINTENANCE (ESD)
FUMEHOOD TESTING
1. Test should be performed with the hood sash opened to three positions: 1) normal operating position, 2) 25% opening, 3) 50% opening. Tests should be done with the usual amoun...
Monthly PMI 124 ISCO SIGNATURE WATER FLOW METER (EPB)
| Plumbing |
| PM |
ISCO WATER FLOW METER PMI 124
1. Get the reading from the outside meter.
a. Volume – Gallons ___________________________
b. Flow Rate Units – GPM _______________________
c. 310 Lev...
B100 - L1 - R103 B100 - L1 - R103
ISCO MODEL 4210 WATER FLOW METER (EPB) ANNUAL PM
| Work Control |
| PM |
ISCO MODEL 4210 WATER FLOW METER ANNUAL PM
TO BE DONE BY OUTSIDE CONTRACTOR
ANNUAL done in February please call outside vendor to schedule. RWD to assist outside vendor. Please call David Sh...
B100 - L1 - R103 B100 - L1 - R103
Quarterly PMI 023 Ingersol Rand Air Compressor Up Series
| Mechanic |
| PM |
Quarterly PMI 023 Ingersol-Rand Air Compressor Up Series ECA
NOTE TO WORK CONTROL - PRINT ATTACHMENT
-REMOVE AND INSPECT THE PACKAGE PRE-FILTER. CLEAN OR REPLACE AS REQUIRED.
-INSPECT THE CO...
PITT-SITE-WIDE
INGERSOL RAND AIR COMPRESSOR SS5
Drain water out of the Air Receiver Tank.
Check the drive belt tension, adjust or replace the belt as required.
Inspect the air filter, clean it as required.
Check the system for air lea...
INGERSOL RAND AIR COMPRESSOR SS5
Change the oil. Requires 1 quart of IR T30 select.
Change the air filter element. Part Number 32170979.
INGERSOL RAND AIR COMPRESSOR SS5
Change the oil. Requires 1 quart of IR T30 select.
Change the air filter element. Part Number 32170979.
PMI 096 HOT WATER HEATERS ANNUAL EHW
| Plumbing |
| PM |
Annual PMI 096 HOT WATER HEATERS (EHW)
NOTE TO WORK CONTROL PRINT ATTACHMENT
ELECTRIC WATER HEATERS
1.Clean exterior of heater.
2.Exercise cold water inlet valve and check for leaks
PITT-SITE-WIDE
; B100 - L1 - R014; B029 - L1 - R110A; B151 - L1; ...
PMI 137 HOT AND CHILLED WATER CIRCULATING PUMPS EPA SEMIANNUAL
| Plumbing |
| PM |
SEMIANNUAL HOT AND CHILLED WATER CIRCULATING PUMPS PMI137
EPA
NOTE TO WORK CONTROL: PRINT ATTACHMENT
1. Inspect the pump for leakage.
2. Grease motor and pump.
3. Wipe excessive grease B037 B037
Annual PMI 088 HIGH VOLTAGE UNIT SUBSTATION (UEA)
| Electrical |
| PM |
HIGH VOLTAGE UNIT SUBSTATION (UEA) ANNUAL
NOTE TO WORK CONTROL - PRINT ATTACHMENT
LOAD INTERRUPTER SWITCH, FUSES AND HOLDERS
1.Blow out with clean dry compressed air.
2. Wipe all insula...
PITT-SITE-WIDE
HIGH VOLTAGE UNIT SUBSTATION (UEA)
LOAD INTERRUPTER SWITCH, FUSES AND HOLDERS
1.Blow out with clean dry compressed air.
2. Wipe all insulation and insulators free of dust with a clean dry rag.
3. If insulators will not cle...
PMI 143 HEAT/COOL UNITS FOR B141 VUH SEMI ANNUAL
| HVAC |
| PM |
Semi-Annual PMI 143 HEAT/COOL UNITS FOR B141
NOTE TO WORK CONTROL PRINT ATTACHMENT
INSPECT THE COILS FOR LEAKS AND REPAIR ANY FOUND.
INSPECT THE COILS FOR CLEANLINESS AND CLEAN AS REQUIRED
B141
Annual PMI 144 GLASS LINED STORAGE TANK SACRIFICIAL ANODE
| Plumbing |
| PM |
Annual PMI 144 GLASS LINED STORAGE TANK SACRIFICIAL ANODE
REMOVE AND INSPECT THE SACRIFICIAL ANODE. REPLACE AS REQUIRED.
PM - PREVENTIVE MAINTENANCE – Self explanatory B144
PITT-SITE-WIDE; B144
SEMIANNUAL GFCI TESTING PMI 011
| Electrical |
| PM |
SEMIANNUAL GFCI TESTING
PMI 011
1. PUSH THE RESET BUTTON.
2. PLUG IN A DEVICE THAT CAN INDICATE THAT POWER IS ON OR OFF.
3. THE POWER SHOULD BE ON. IF NOT INVESTIGATE UNTIL PROBLEM IS FIXED...
PITT-SITE-WIDE
| NAME |
| SHOP |
| SERVICE/DESCRIPTION |
| ASSET/LOCATION |
| ESTIMATE |
| IS ACTIVE |
| LAST COMPLETED DATE |
GFCI TESTING
1. PUSH THE RESET BUTTON.
2. PLUG IN A DEVICE THAT CAN INDICATE THAT POWER IS ON OR OFF.
3. THE POWER SHOULD BE ON. IF NOT INVESTIGATE UNTIL PROBLEM IS FIXED.
4. PRESS THE TEST BUTTON ON THE GFC...
MONTHLY PM ECA0003 GARDNER DENVER AIR COMPRESSOR
| Mechanic |
| PM |
MONTHLY PM ECA0003 GARNDER DENVER AIR COMPRESSOR
ECA0003
PMI158
Check the oil level and add oil as required.
Drain any moisture in the tank by opening the drain valve. Do not open t...
ECA0003
B152 - L1
ANNUAL PM ECA0003 GARDNER DENVER AIR COMPRESSOR PMI 158
| Mechanic |
| PM |
ANNUAL PM ECA0003 GARDNER DENVER AIR COMPRESSOR
PMI 158
Change the crankcase oil.
Check the entire system for air leakage around fittings, connections and gaskets.
Check all nuts and ca...
ECA0003
PITT-SITE-WIDE; B152 - L1
PMI 121 FIRE PROTECTION SPRINKLERS SYSTEM ESA SEMI ANNUAL
| Plumbing |
| PM |
SEMI ANNUAL FIRE PROTECTION SPRINKLERS SYSTEMS ESA PMI 121
NOTE TO WORK CONTROL - PRINT ATTACHMENT
1. Check the system to ensure there are no leaks.
2. Wipe down the stand pipe.
3. Reco...
PITT-SITE-WIDE
Quarterly PMI 121 FIRE PROTECTION SPRINKLER SYSTEMS (ESA)
Check the system to ensure there are no leaks.
Wipe down the stand pipe.
Record the water pressure read on the gauge.
Record anything out of the ordinary that needs addressed.
PMI 010 FIRE AND POTABLE WATER VALVES ANNUAL UFV UPV
| Plumbing |
| PM |
Annual PMI 010 FIRE AND POTABLE WATER VALVES (UFV, UPV)
NOTE TO WORK CONTROL PRINT ATTACHMENT
Remove the nozzle caps from both 2½" hose outlets on the hydrant. Re-lubricate the threads on bot...
PITT-SITE-WIDE
SEMIANNUAL PMI 108 EXIT SIGNS
| Electrical |
| PM |
Semi-Annual PMI 108 EXIT SIGNS
NOTE: PLEASE PRINT ATTACHMENT
1. Check status of lighting in each exit sign by switching off power to emergency lighting circuit in the associated lighting pan...
PITT-SITE-WIDE
PMI 117 EXHAUST FANS (EHF) (REQ JLG / LIFT FOR ACCESS) ANNUAL
| HVAC |
| PM |
EXHAUST FANS (EHF) (REQ JLG / LIFT FOR ACCESS) ANNUAL
NOTE TO WORK CONTROL PRINT ATTACHMENT
1. Turn fan ON and check for unusual vibrations and noises. If these conditions exist, try to ide...
PITT-SITE-WIDE
PMI 019 EXHAUST FANS ANNUAL EHF
| HVAC |
| PM |
NOTE TO WORK CONTROL - PRINT CHECKLIST
ANNUAL PMI 019
EXHAUST FANS (EHF)
VENT/EXHAUST FANS
1. Turn fan ON and observe how it operates, Note any items and repairs required.
The rem...
PITT-SITE-WIDE
PMI 139 EXHAUST FANS B037 AND B141 EHF QUARTERLY
| HVAC |
| PM |
QUARTERLY EXHAUST FANS B037
NOTIFY LAB FIVE DAYS IN ADVANCE OF WORK
EHF
PMI139
Q 1. Turn fan ON and check for unusual vibrations and noises. If these conditions exist, try to identify...
EHF0001
B037 - L1 - R110
MONTHLY PMI 136 EXHAUST FAN FOR RADON BUILDING 001 EHF0091
| HVAC |
| PM |
MONTHLY PMI136 EXHAUST FAN FOR RADON
BUILDING 001
EHF0091
ADD 4 PUMPS OF NLGI GRADE 2 LITHIUM BASED GREASE TO BEARINGS. WRITE THE DATE THE BEARINGS WERE GREASED ON THE INSPECTION TAG.
EHF0091
; B001 - L1
SEMI ANNUAL PMI 134 ELECTRICAL EXTENSION CORDS AND POWER HAND TOOL CORDS
| Electrical |
| PM |
SEMIANNUAL ELECTRICAL EXTENSION CORDS AND POWER HAND TOOL CORDS PMI 134
NOTE TO WORK CONTROL PRINT ATTACHMENT
01 Electricians
1.Contact each craft, group supervisor or personnel before th...
PITT-SITE-WIDE
SEMIANNUAL PMI 115 DOMESTIC WATER FILTERS (EFW)
| Plumbing |
| PM |
SEMIANNUAL PMI 115 DOMESTIC WATER FILTERS (EFW)
NOTE TO WORK CONTROL - PRINT ATTACHMENT
1. Shut off water valve(s) to isolate filter from main supply.
2. Check condition of the filter elem...
PITT-SITE-WIDE
PITT-SITE-WIDE; PITT-SITE-WIDE
Monthly PMI 113 DOCK LEVELER ECL
| Mechanic |
| PM |
MONTHLY PMI 113 DOCK LEVELER
ECL
ECL0001
1. Inspect hydraulic cylinders, rods, linkages, hydraulic piping and hoses for signs or wear or leakage.
2. Lubricate all moving connections on ...
B166 ; B166
MONTHLY PMI 130 FUEL TANK INSPECTIONS (EGT)
| Mechanic |
| PM |
Monthly PMI 130 DIESEL FUEL TANK INSPECTIONS (EGT)
NOTE TO WORK CONTROL PRINT ATTACHMENT
Fuel Tanks at BL 159 [2]
1. Clean all debris, vegetation, weeds, and/or tall grass, from around the...
B159 ; B159
Quarterly PMI 157 DAYTON SPEEDAIRE AIR COMPRESSOR ECA0004
| Mechanic |
| PM |
Quarterly PMI 157 DAYTON SPEEDAIRE AIR COMPRESSOR
ECA0004
1. CHECK THE OIL AND OIL FILTER. USE 10W30 SYNTHETIC OIL.
2. INSPECT THE AIR FILTER. CLEAN OR REPLACE AS REQUIRED.
3. INSPECT T...
ECA0004
PITT-SITE-WIDE; B143 - L1
Monthly PMI 160 COMPUTER ROOM HVAC, BLDG 003, RM 109
| HVAC |
| PM |
Monthly PMI 160 COMPUTER ROOM HVAC, BLDG 003, RM 109
1. Request permission from area supervisor/foreman to take unit "out of service." Provide him or her with down time estimate.
2. Visually...
B003 - L1 - R109 B003 - L1 - R109
COMPUTER ROOM HVAC, BLDG 003, RM 109
COMPUTER ROOM HVAC, BLDG 003, RM 109
1. Request permission from area supervisor/foreman to take unit "out of service." Provide him or her with down time estimate.
2. Visually inspect the uni...
Monthly PMI 140 BOILER IN BUILDING 37
Inspect the vent system.
Check all joint and connections for tightness, corrosion or deterioration.
Clean any screens that are in the air inlet system.
Flush the condensate drain hose wi...
BOILER IN BUILDING 37 MONTHLY
| HVAC |
| PM |
Boiler in building 37 monthly With the Boiler Operating
1.Inspect the burner flame, if an improper flame is observed or there is any yellow color in the flame;
Inspect the venting system f...
B037
Semi-Annual PMI 159 BOILER IN BUILDING 37
| HVAC |
| PM |
Inspect the air inlet and flue vent piping for tightness and obstructions. Correct as required.
Inspect the screens on the air inlet and flue piping on the outside of the building correct any...
B037
PMI 120 BACKFLOW PREVENTERS EVB ANNUAL
| Plumbing |
| PM |
ANNUAL BACKFLOW PREVENTERS EVB PMI120
NOTE TO WORK CONTROL PRINT CHECKLIST
1. Perform inspection and test of the backflow preventer system in accordance with manufacturer's test procedures
PITT-SITE-WIDE
B156 STEAM BOILER MONTHLY
| HVAC |
| PM |
MONTHLY B156 STEAM BOILER
1. VERIFY THE SHUT OFF VALVES OPERATE PROPERLY AND DO NOT LEAK THROUGH WHEN CLOSED. IF ANY LEAKAGE IS DETECTED, INSPECT AND REPAIR THE VALVE AS REQUIRED.
2. INSPECT IN...
B156 B156
Annual PMI 156 B156 STEAM BOILER
| Work Control |
| PM |
ANNUAL IS DONE BY DELVAL, RWD ASSISTS
FOR 2020 HAVE DELVAL COMPLETE CAPACITY TEST ON NEWLY INSTALLED RELIEF VALVE ON BOILER.
1. CHECK THE FLAME SAFEGUARD COMPONENTS INCLUDING THE SCANNER.
2...
B156 B156
Quarterly PMI 112 AUTOMATIC GATE OPERATOR EID0108
| Electrical |
| PM |
Quarterly PMI 112 AUTOMATIC GATE OPERATOR
EID0108
BUILDING 100
1. Note and report special operating problems.
2. Inspect and lubricate (as required) external operating linkages.
3. Che...
PITT-SITE-WIDE
ANNUAL FIRE EXTINGUISHER MAINTAINANCE (ESF)
1.Check extinguisher area for items obstructing view.
2.Check all seals. Replace if broken or missing.
3.Check tamper device and/or "Pull Pin". If tampering has occurred, remove unit for ...
PMI 008 FIRE ALARMS ANNUAL ESC
| Electrical |
| PM |
ANNUAL PM FIRE ALARMS
NOTE TO WORK CONTROL PRINT ATTACHMENT
ESC
PMI 008
ALL DETECTOR TYPES
1.Notify the building supervisor that the fire alarm system is being serviced and that this ...
PITT-SITE-WIDE
PMI 017 FIN TUBE HEATERS, RADIATORS ANNUAL EHD
| HVAC |
| PM |
NOTE TO WORK CONTROL, PRINT ATTACHMENT
ANNUAL PMI 017 FIN TUBE HEATERS, RADIATORS (EHD)
1. Close supply valve.
2. Remove trap and clean out any loose debris.
3. If repair or replacement ...
PITT-SITE-WIDE
PMI 007 EMERGENCY LIGHTING UNITS ANNUAL EEA
| Electrical |
| PM |
ANNUAL EMERGENCY LIGHTING UNITS (EEA)
PMI 007
De-energize the A/C circuit to which the unit is connected. Let unit lights operate for 1 1/2 hours. Reconnect A/C circuit and note charger ind...
PITT-SITE-WIDE
B001 ; PITT-SITE-WIDE
PMI 142 AIR COMPRESSORS ACP AND ECA MONTHLY
| HVAC |
| PM |
MONTHLY AIR DRYERS
HVAC
NOTE TO WORK CONTROL PRINT ATTACHMENT
ACP AND ECA
PMI 142
COMPLETE THE FOLLOWING FOR THE AIR DRYER:
1. INSPECT THE CONDENSER COILS AND CLEAN AS REQUIRED WI...
B141
PMI 040 AIR COMPRESSORS ANNUAL ECA
| Mechanic |
| PM |
ANNUAL PMI 040 AIR COMPRESSORS
NOTE TO WORK CONTROL PRINT ATTACHMENT
ECA
A 1. Replace the coolant filter.
A 2. Inspect the scavenge screen and clean if required.
A 3. Replace the separa...
PITT-SITE-WIDE
AIR COMPRESSOR PM (INGERSOL-RAND)
1. REPLACE THE COOLANT FILTER.
2. INSPECT THE SCAVENGE SCREEN AND CLEAN IF REQUIRED.
3. REPLACE THE SEPARATOR ELEMENT/CARTRIDGE.
4. REPLACE THE AIR FILTER ELEMENT.
5. REPLACE THE PACKAGE PREFIL...