This is a structural engineering drawing and specification document for the City of Minneapolis Department of Public Works, specifically for the PS6 Boiler Room Crane project located at 4100 Marshall Street NE, Minneapolis, Minnesota. The project involves the installation of a new one-ton capacity crane beam system within the existing boiler room roof structure. The scope of work includes fabrication and erection of new structural steel members, including a W10x30 crane beam, associated bracing, stiffeners, and connection details to integrate with existing structural elements. The drawing was issued for construction on May 22, 2026, with the design prepared by Brandon Clark, a licensed Professional Engineer in Minnesota (Registration No. 60507), and reviewed by project team members Andrew Atkins and Maxwell Ludington. The structural design incorporates specific load criteria including a 20 PSF non-reducible roof live load, a 1-ton crane capacity live load, and a 35 PSF flat roof snow load based on Minnesota Building Code standards.
The project specifications require adherence to the 2020 Minnesota Building Code, IBC 2018, ASCE 7-16, ACI 318-14, AISC 360-10, and AWS D1.1 welding standards. All structural steel must be prime painted in the shop with touch-up following erection. Shop drawings require submission for engineer review with a two-week turnaround time prior to fabrication. The contractor has the option to provide steel shim plates to achieve level crane beam installation, with maximum thickness not to exceed three-eighths inch without engineer coordination. Special inspections by an approved agency are required for steel construction in accordance with Chapter 17 of the IBC. Field verification of all existing dimensions and elevations is mandatory prior to steel fabrication to account for potential camber or deflection in existing structural elements that could affect crane beam installation elevation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| COM_MWW_PS6BoilerRoomCraneBeam_Spec_2605_V2_0730.pdf | ||
| BID_-_PW_PS6_Boiler_Room_Crane_Beam.pdf | ||
| Call_for_Bids.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(E) JOIST GIRDER
(E
W x1 9w
1/
2" x8
B
T M
P
LA
T E
(E
W x2 w
1/ 2" x8
B T
M P
LA
T
E
(E
W x2 w
1/ 2" x8
B T
M P
LA
T
E
(E
W x2
(E
W x2
(E
W x1
(E
W x1
(E
W x2
(E
W x2
(E
W x1
NEW W
10x30 CRANE BEAM
2'-0"
(E) W18X50(E) W16X45
(E
W x2
(E
W x1 6.
(E) X-BRACING
NEW ANGLE BRACE
(4 TOTAL)
S-102
7'-4" VIF 7'-4" VIF 7'-4" VIF 6'-5 1/2" VIF
VIF
6'-5 1/2"
W8X18
1' -0
2' -0
CANTILEVER CRANE BEAM
12" PAST HSS TUBE
'-4
V
IF
S-102
S-102
S-102
S-102
OUTLINE OF EXISTING
PLATFORM BELOW
OUTLINE OF EXISTING
PLATFORM BELOW
CRANE BEAM (SEE PLAN)
NEW 3/8" STIFFENER EACH
SIDE OF BEAM CENTERED
ABOVE HSS TUBE1/4"x4"x4" PLATE
(E) ROOF DECK
(E) BEAM (SEE PLAN)
(E) BEAM (SEE PLAN)
L3x3x1/4 BRACE
3/16
3/16
TYP
1/4 1 1/2"
EA END
1/2"x8" BTM PLATE
1/2"x8" BTM PLATE
1/4 3-12
TYP
3" STD PIPE x 6" LG
1/2"x6"x9" PLATE w/
(4) 3/4" DIA BOLTS
1/4
EA END
TACK WELD NUT OR
DAMAGE THREADS
AFTER INSTALL
*CONTRACTOR HAS THE OPTION TO PROVIDE STEEL
SHIM PLATES BTWN CRANE BEAM & BTM PLATE,
MATCHING BTM PLATE SIZE TO ALLOW FOR LEVEL
CRANE BEAM INSTALLATION. MAXIMUM SHIM PLATE
THICKNESS SHALL BE 3/8". COORDINATE w/ EOR IF
THICKER SHIM IS REQUIRED.
1/4 8
ABOVE HSS
BEAM (SEE PLAN)
3" STD PIPE x 8-1/2" LG
CRANE BEAM (SEE PLAN)
1/2"x6"x9" PLATE w/
(4) 3/4" DIA BOLTS
1/4
EA END
2"
(E) ROOF DECK
(E) BEAM (SEE PLAN)
L4x3x5/16 x 5" LG EA
SIDE AT EA END 1/4
3-SIDES
TYP
(E) BRICK WALL
(E) BEAM INSET INTO
EXISTING BRICK WALL
PROVIDE L3x3x5/16 x 4"
LG CRANE STOPS EA
SIDE OF BM WEB AT EA
END OF CRANE BEAM
(COORD w/ HOIST
MANUFACTURER)
TACK WELD NUT OR
DAMAGE THREADS
AFTER INSTALL
*CONTRACTOR HAS THE OPTION TO PROVIDE STEEL
SHIM PLATES BTWN CRANE BEAM & BTM PLATE,
MATCHING BTM PLATE SIZE TO ALLOW FOR LEVEL
CRANE BEAM INSTALLATION. MAXIMUM SHIM PLATE
THICKNESS SHALL BE 3/8". COORDINATE w/ EOR IF
THICKER SHIM IS REQUIRED.
NEW 3/8" STIFFENER EACH
SIDE OF BEAM CENTERED
ABOVE HSS TUBE
CRANE BEAM (SEE PLAN)
1/2"x8" BTM PLATE
3" STD PIPE x 6-1/2" LG
1/2"x6"x8" PLATE w/
(4) 3/4" DIA BOLTS
1/4
EA END
(E) BEAM (SEE PLAN)
L3x3x1/4 BRACE
3/16
1/4 3-12
TYP
1/4 1 1/2"
EA END
PROVIDE L3x3x5/16 x 4"
LG CRANE STOPS EA
SIDE OF BM WEB AT EA
END OF CRANE BEAM
1/4
3-SIDES
TACK WELD NUT OR
DAMAGE THREADS
AFTER INSTALL
*CONTRACTOR HAS THE OPTION TO PROVIDE STEEL
SHIM PLATES BTWN CRANE BEAM & BTM PLATE,
MATCHING BTM PLATE SIZE TO ALLOW FOR LEVEL
CRANE BEAM INSTALLATION. MAXIMUM SHIM PLATE
THICKNESS SHALL BE 3/8". COORDINATE w/ EOR IF
THICKER SHIM IS REQUIRED.
8"
6"
(E) STL BEAM
1/2
1/2" PLATE REINFORCEMENT
1/4 6 AT PLATE ENDS Project Number
Original Issue
Sheet Number
Sheet Name
Project Status
Project Designer
Project Manager
Structural Engineer
A
B
C
D
12345
A
B
C
D
I hereby certify that this plan, specifications, or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota.
DATE: REG NO:
PRINT NAME:
SIGNATURE:
BRANDON CLARK
5-22-2026 60507
5/
/2
1:
:0
P
M A ut od es k
D oc s:
//1
7_
C ity of M pl s_
P S
6_ B oi le r_ R m _C ra ne
/1
7_ M
P
LS
P S
B oi le r R oo m
C ra ne _R
.r vt
S-102
ROOF FRAMING PLAN
AND DETAILS
City of Minneapolis Department of Public Works PS6 Boiler Room Crane
ISSUED FOR CONSTRUCTION
4100 Marshall St. NE
Minneapolis, MN 55421
10463327
05/22/2026
1601 Utica Avenue South, Suite 600 St. Louis Park, MN 55416
(763) 591-5400
Andrew Atkins
Maxwell Ludington
Brandon Clark
1/4" = 1'-0"
PARTIAL BOILER ROOM ROOF FRAMING PLAN
3/4" = 1'-0" 2
DETAIL
ABBREVIATIONS
@ AT
AB ANCHOR BOLTS
ADDL ADDITIONAL
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
ARCH ARCHITECTURAL
BKT BRACKET
BL BASE LINE
BM BEAM
BN BOUNDARY NAILING
BOF BOTTOM OF FOOTING
BOT BOTTOM
BP BASE PLATE
BRG BEARING
BSMT BASEMENT
BTWN BETWEEN
CANT CANTILEVER
CG CENTER OF GRAVITY
CIP CAST IN PLACE
CJ CONSTRUCTION OR CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTER LINE
CLR CLEARANCE, OR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS OR CONTINUED
CTR CENTER
C TO C CENTER TO CENTER
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
D DEAD LOAD
DO DITTO
DWG DRAWING
DWL DOWEL
EA EACH
EE EACH END
EF EACH FACE
EFF EFFECTIVE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
EMB EMBEDMENT, EMBEDDED
EN EDGE NAILING
EOS EDGE OF SLAB
EQ EQUAL
ES EACH SIDE
EW EACH WAY
EXP EXPANSION
EXIST EXISTING
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FLR FLOOR
FN FIELD NAILING
FS FAR SIDE
FT FEET
FTG FOOTING
FUT FUTURE
FV FIELD VERIFY
GA GAGE OR GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GR GRADE
HK HOOK
HORIZ HORIZONTAL
HS HEADED STUD
HSB HIGH STRENGTH BOLT
HSS HOLLOW STRUCTURAL SECTION
ID INSIDE DIAMETER
IF INSIDE FACE
IJ ISOLATION JOINT
IN INCHES
INFO INFORMATION
INT INTERIOR
JT JOINT
K KIPS
KSF KIPS PER SQUARE FOOT
ABBREVIATIONS (CONTINUED)
L LIVE LOAD
LE LEFT END
LF LINEAR FEET
LLH LONG LEG HORIZ
LLV LONG LEG VERT
LOC LOCATION
LONG LONGITUDINAL
LWT LIGHTWEIGHT
MATL MATERIAL
MAX MAXIMUM
MEP MECHANICAL, ELECTRICAL, PLUMBING
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTL METAL
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
NWT NORMALWEIGHT
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
OSL OUTSTANDING LEG
PAF POWER ACTUATED FASTENER
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PR PAIR
PREFAB PREFABRICATED
PRL PARALLEL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PVMT PAVEMENT
R RADIUS
RD ROOF DRAIN
RE RIGHT END
REF REFER TO
REV REVISION
REINF REINFORCEMENT
REQD REQUIRED
RO ROUGH OPENING
SCH SCHEDULE
SECT SECTION
SEOR STRUCTURAL ENGINEER OF RECORD
SEPN SEPARATION
SF SQUARE FEET
SIM SIMILAR
SMS SHEET METAL SCREW
SOG SLAB ON GRADE
SOMD SLAB ON METAL DECK
SPA SPACING, SPACES
SPEC SPECIFICATION
SQ SQUARE
SSL SHORT SLOTTED HOLES
STD STANDARD
STIFF STIFFENER
STRUCT STRUCTURAL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
TEMP TEMPERATURE
TO TOP OF
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W WIND LOAD
WLD WELDED
W/O WITHOUT
WT WEIGHT
WWF WELDED WIRE FABRIC
GENERAL
A. SCOPE
THE NOTES ON THIS SHEET AND THE STANDARD STRUCTURAL DETAILS ARE GENERAL AND APPLY TO THE ENTIRE PROJECT WHETHER SPECIFICALLY CALLED OUT OR NOT, EXCEPT WHERE THERE ARE SPECIFIC INDICATIONS TO THE CONTRARY ON STRUCTURAL SHEETS. IF THERE ARE QUESTIONS, THEY SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER AND ANSWERED IN
WRITING PRIOR TO CONSTRUCTION.
B. APPLICABLE SPECIFICATIONS AND CODES
A. 2020 MINNESOTA BUILDING CODE, IBC 2018 WITH APPLICABLE EDITIONS OF THE CODE REFERENCED STANDARDS.
B. ASCE 7-16
C. ACI 318-14
D. AISC 360-10
E. AWS D1.1
F. LOCAL JURISDICTION AMENDMENTS
C. DESIGN CRITERIA
A. DEAD LOAD:
a. ACTUAL TRIBUTARY STRUCTURE WEIGHT
b. SUPERIMPOSED DEAD LOAD: 40 PSF
B. LIVE LOAD:
a. ROOF: 20 PSF (NOT REDUCIBLE)
b. CRANE CAPACITY: 1 TON
C. SNOW:
a. GROUND SNOW LOAD; Pg: 50 PSF
b. [FLAT ROOF SNOW LOAD; Pf: 35 PSF
c. EXPOSURE FACTOR; Ce: 1.0
d. IMPORTANCE FACTOR; Is: 1.0
e. THERMAL FACTOR; Ct: 1.0
D. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS OF EXISTING CONSTRUCTION AS REQUIRED TO
COORDINATE NEW CONSTRUCTION. SUBMIT REQUIRED CHANGES FOR APPROVAL.
E. THE CONTRACT STRUCTURAL DRAWINGS REPRESENT THE FINISHED STRUCTURE. MEANS AND METHODS ARE THE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR TO PROVIDE ALL BRACING AND SHORING AS REQUIRED TO PROTECT THE
STRUCTURE, WORKMEN OR OTHER PERSONS DURING CONSTRUCTION.
F. STRUCTURAL DRAWINGS MUST NOT BE SCALED. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED DRAWINGS AND LARGE
SCALE OVER SMALL SCALED DRAWINGS.
STEEL
1. DESIGN STRENGTHS:
WIDE FLANGE AND TEES: Fy= 50 KSI HSS SQUARE OR RECTANGULAR: Fy= 46 KSI PIPE: Fy= 35 KSI ALL OTHER PLATES AND SHAPES: Fy= 36 KSI BOLTS Fu = 120,000 ASTM325 w/ ASTM A563 NUTS WELD ELECTRODE Fu = 70,000 PSI
2. DIMENSIONS:
TO CENTERLINES OF COLUMNS AND BEAMS, TOP SURFACES OF BEAMS AND TUBES AND BACKS OF CHANNELS AND ANGLES UNO.
3. FABRICATION & ERECTION OF STRUCTURAL STEEL MEMBERS ARE TO BE IN ACCORDANCE WITH AISC CODE OF STANDARD
PRACTICE.
4. WHEN FILLET WELD SIZE IS NOT INDICATED, PROVIDE MAXIMUM WELD SIZE BASED ON MATERIAL THICKNESS IN ACCORDANCE
WITH AISC SPECIFICATIONS.
5. ALL WELDING MUST BE PERFORMED IN ACCORDANCE WITH AWS REQUIREMENTS.
6. ALL BOLTED STRUCTURAL CONNECTIONS ARE BEARING TYPE CONNECTIONS UNLESS OTHERWISE SPECIFIED TO BE SLIP-
CRITICAL. PROVIDE LOAD INDICATING WASHERS AT SLIP-CRITICAL CONNECTIONS.
7. CONFORM TO AISC 360, STEEL CONSTRUCTION MANUAL.
8. ALL STEEL TO BE PRIME PAINTED IN THE SHOP. TOUCH UP ALL DISTURBED AREAS AFTER ERECTION.
9. CUTTING OF EXISTING STRUCTURAL STEEL IS PROHIBITED WITHOUT THE APPROVAL FROM THE ENGINEER.
10. SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW PRIOR TO FABRICATION. PRIOR TO SUBMITTAL, THE CONTRACTOR SHALL REVIEW THE SHOP DRAWINGS AND MAKE ANY CORRECTIONS REQUIRED. THE CONTRACTOR SHALL STAMP AND SIGN THE DRAWINGS AS EVIDENCE OF REVIEW. THE TURN AROUND TIME FOR SHOP DRAWINGS SHALL BE TWO WEEKS FROM DATE
RECEIVED IN THE ENGINEER'S OFFICE.
SPECIAL INSPECTION
1. THE OWNER MUST EMPLOY ONE OR MORE APPROVED AGENCIES TO PERFORM INSPECTIONS DURING CONSTRUCTION ON THE
TYPES OF WORK LISTED UNDER SECTION 1705 OF THE IBC REQUIRING VERIFICATION AND INSPECTION. THESE INSPECTIONS ARE IN ADDITION TO THE INSPECTIONS DEFINED IN SECTION 110. THE INSPECTING AGENCY MUST PROVIDE REPORTS OF THE SPECIAL
INSPECTIONS DIRECTLY TO THE OWNER.
THE FOLLOWING IS A LIST OF INSPECTIONS THAT SHALL BE PERFORMED IN ACCORDANCE WITH CHAPTER 17 OF THE IBC.
A. STEEL CONSTRUCTION: 1705.2
N
3/4" = 1'-0" 3
DETAIL
3/4" = 1'-0" 4
DETAIL
NOTE: CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND
ELEVATION OF THE EXISTING STRUCTURE PRIOR TO STEEL
FABRICATION. EXISTING STEEL BEAMS MAY HAVE CAMBER OR EXISTING
DEFLECTION THAT NEEDS TO BE ACCOUNTED FOR TO ENSURE THE
CRANE BEAM GETS INSTALLED AT A CONSTANT ELEVATION.
3D AERIAL IMAGE OF PROJECT LOCATION
1 1/2" = 1'-0"
BOTTOM PLATE SPLICE DETAIL
VICINITY MAP
PROJECT LOCATION
MARK DATE DESCRIPTION
| Sheets |
| S-102 - ROOF FRAMING PLAN AND DETAILS |