1-ELECT SET-TIRE SHREDDER.pdf
PDF 12 MB Posted
- Solicitation number
- ITB 26-011
- Issued by
- Schleicher County, Texas
About this file
This is an electrical specifications and design document for a tire shredder facility located at 7 County Road 201, Pecos, Texas 79772, prepared for Reeves County. The project encompasses a complete electrical infrastructure installation including a new service connection, motor control centers (MCCs), wiring systems, receptacles, light fixtures, and associated electrical equipment. The scope of work requires installation of high-voltage service distribution panels rated at 2000 amperes at 277/480 volts, a 45-kilowatt step-down transformer, five vendor-furnished motor control centers with ratings of 300 to 400 amperes, underground and overhead electrical conduit systems, high-bay LED lighting fixtures with automatic controls, weatherproof receptacles, and a comprehensive grounding electrode system including ground rods and a copper ground ring around the building perimeter. The contractor must comply with all locally adopted building codes, the National Electric Code (NEC), and requirements of the Authority Having Jurisdiction (AHJ). The project requires pre-construction submittals of manufacturer specifications and shop drawings for approval, performance of commissioning work including testing and startup of all lighting and electrical systems, creation of equipment labels and index cards for all panelboards, and provision of operations and maintenance documentation in a minimum of two binders. The contractor shall provide a minimum one-year warranty on all labor and materials and conduct at least two hours of on-site training for the owner's operational staff upon project completion.
The specifications require all contractors to obtain necessary permits and licenses from the AHJ and pay all permitting fees and utility connection charges. All equipment and materials must be new, commercially-grade merchandise manufactured to comply with the basis of design and free of defects, with a minimum one-year factory warranty. Electrical conductors shall be copper wire with 90-degree Fahrenheit rated insulation, though aluminum conductors may be substituted for sizes number 6 and above with suitable terminal lugs. Specific equipment manufacturers are identified as the basis of design, including Eaton panelboards, Square D disconnect switches, Intermatic lighting controls, and Hubbell receptacles, with equal products acceptable upon approval through the commissioning process. The contractor is responsible for all materials management including delivery, storage, and rigging of equipment, daily and final jobsite cleanup, and immediate notification to the engineer if any site conditions prohibit or negatively impact system installation or performance. Any defective equipment or work found out of compliance with the basis of design or applicable codes must be replaced at no additional cost to the owner.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2-26-011 Electrician Services.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TI
R
E
SH
R
ED
D
ER
F
AC
IL
IT
Y R
EE
VE
S C
O U
N
TY
, T
EX
AS
C O
. R D
. 2
, P
EC
O S, T X
TEXAS FIRM
REGISTRATION:
#F-26227
E8
ELECTRICAL LEGENDS:
ELECTRICAL ABBREVIATIONS:
ELECTRICAL PANELBOARD, LABEL SHOWN
LIGHT SWITCH AT 48" ABOVE FINISHED FLOOR
JUNCTION BOX
WP
ELECTRICAL METER
ELECTRICAL GROUND CONNECTION
DISCONNECT SWITCH, FUSED OR NON-FUSED, SEE SCHEDULES.2
UE
E
S
P1 1,3,5
P1 26,28
P1
A - AMPERES CURRENT
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AFI - ARC FAULT INTERRUPTING
AHJ - AUTHORITY HAVING JURISDICTION
ARCH - ARCHITECTURAL
BFF - BELOW FINISHED FLOOR
BFG - BELOW FINISHED GRADE
BOP - BOTTOM OF PIPE ABOVE FINISHED FLOOR OR GRADE
BTM - BOTTOM
BTU - BRITISH THERMAL UNIT
CB - CIRCUIT BREAKER
CONC - CONCRETE
CU - COPPER
DET - DETAIL
DIA - DIAMETER
DN - DOWN
ENGR - ENGINEER OR ENGINEERING
EXIST - EXISTING
FC - FOOTCANDLES, ILLUMINANCE LEVEL
FT - FEET
GFI - GROUND FAULT INTERRUPTING
GND - GROUND
HZ - HERTZ
IE - INVERT ELEVATION, BELOW FINISHED FLOOR LEVEL
IECC - INTERNATIONAL ENERGY CONSERVATION CODE
IG - ISOLATED GROUND
IN - INCHES
JBX - JUNCTION BOX
KW - KILOWATT
KVA - KILOVOLT AMPS
LBS - POUNDS
MAX - MAXIMUM
MCA - MINIMUM CIRCUIT AMPACITY
MCB - MAIN CIRCUIT BREAKER
MFG - MANUFACTURER
MIN - MINIMUM
MLO - MAIN LUGS ONLY
MOCP - MAXIMUM OVERCURRENT PROTECTION
NA - NOT APPLICABLE
NEC - NATIONAL ELECTRIC CODE
NEMA - NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NO - NUMBER
NFDS - NON-FUSED DISCONNECT SWITCH
OE - OVERHEAD ELECTRICAL
O&M - OPERATIONS & MAINTENANCE
P - POLE
PH - PHASE
PLCS - PLACES
SCA - SHORT CIRCUIT CURRENT AVAILABLE
TYP - TYPICAL
V - VOLTS
W - WIRE
WP - WEATHERPROOF
XFMR - TRANSFORMER
YR - YEAR
HOMERUN, 120V/1P/20A CIRCUIT WITH 2 #12 AND #12 GND IN
1/2" CONDUIT, PANEL AND CIRCUIT NUMBER SHOWN.
HOMERUN, 208V/2P CIRCUIT HOME RUN WITH 2 HOTS AND GND,
PANEL AND CIRCUIT NO'S SHOWN.
HOMERUN, 208V/3P CIRCUIT HOME RUN WITH 3 HOTS AND GND,
PANEL AND CIRCUIT NO'S SHOWN.
ELECTRICAL CONDUIT AND WIRE OR CABLES IN WALLS OR ABOVE
CEILINGS
ELECTRICAL CONDUIT AND WIRE UNDERGROUND OR BELOW
FLOOR WITH POWER CIRCUIT, SEE SCHEDULES.
DUPLEX RECEPTACLE, GFI TYPE IN WEATHERPROOF BOX WITH
COVER, MIN. 24" ABOVE GRADE.
OUTDOOR LIGHTING TIMER, SEE SPECS AND LIGHTING CONTROL DETAILS.OT
P PHOTOCELL SWITCH FOR OUTDOOR LIGHTING CONTROL, SEE DETAILS.
ELECTRICAL COMMISSIONING PLANS:
A. PURPOSE: THIS COMMISSIONING PLAN IS REQUIRED FOR PERFORMANCE VERIFICATIONS AND QUALITY
CONTROL. FAILURE TO IMPLEMENT THIS PLAN MAY RESULT IN POOR PERFORMANCE AND QUALITY. THE
DRAWINGS AND SPECIFICATIONS ARE TO BE USED AS THE BASIS OF ALL EVALUATIONS.
B. RESPONSIBILITIES:
1. OWNER/GENERAL CONTRACTOR (GC):
a. IMPLEMENT THE COMMISSIONING PLAN AS PROVIDED
b. REVIEW AND APPROVE ALL SUBMITTALS, TESTING AND WORK DESCRIBED BELOW.
c. MAINTAIN RECORDS OF ALL COMMISSIONING WORK AND FINAL APPROVALS
d. PROVIDE ENGINEER WITH COPY OF RECORDS AS NEEDED
2. MEP CONTRACTOR:
a. COORDINATE, REVIEW AND APPROVE ALL VENDOR EQUIPMENT SUBMITTALS.
b. OBTAIN GC APPROVAL OF ALL SUBMITTALS PRIOR TO ORDERING.
c. PERFORM ALL COMMISSIONING WORK LISTED BELOW.
d. OBTAIN GC APPROVAL OF ALL STARTUP AND TESTING OF MEP SYSTEMS AND EQUIPMENT
e. MAINTAIN AND PROVIDE ALL OPERATIONS AND MAINTENANCE MATERIALS.
f. PROVIDE OWNER TRAINING ON NEW SYSTEMS INSTALLED
C. SUBMITTALS: PRE-CONSTRUCTION SUBMITTALS SHALL INCLUDE MANUFACTURER'S SPECIFICATIONS, SHOP DRAWINGS AND INSTALLATION MANUALS. PROVIDE SUBMITTALS FOR GC AND ARCHITECT
APPROVAL PRIOR TO ORDERING THE FOLLOWING MAJOR COMPONENTS.
1. ELECTRICAL:
a. ELECTRICAL DISTRIBUTION EQUIPMENT
b. LIGHT FIXTURES AND ACCESSORIES
c. AUTOMATIC LIGHTING CONTROLS
D. LIGHTING EQUIPMENT STARTUP: CONTRACTOR SHALL PERFORM THE FOLLOWING:
1. TEST ALL OUTDOOR LIGHTING CONTROLS AFTER INSTALLATION. PROVIDE NAME AND SIGNATURE OF PERSON(S) COMPLETING THE TESTING, DATE PERFORMED, INITIAL AND FINAL SETTINGS OF CONTROLS
ADJUSTMENTS AND THE RESULTING OPERATIONAL PERFORMANCE.
2. ENSURE LIGHT FIXTURES ARE INSTALLED AND OPERATIONAL
3. VERIFY OPERATION OF LIGHTING TIME CLOCKS. ADJUST SETPOINTS ON TIME CLOCK TO ENABLE
OUTDOOR LIGHTING CIRCUIT INDEPENDENT OF SEASONAL CHANGES. PERFORM ALL TESTING PER
MANUFACTURER'S INSTRUCTIONS.
E. ELECTRICAL SYSTEM STARTUP:
1. VERIFY THAT LABELS HAVE BEEN PROPERLY CREATED AND PERMANENTLY ATTACHED TO ALL
PANELBOARDS AND DISCONNECT SWITCHES, AS SHOWN ON DRAWINGS AND SPECIFICATIONS.
2. VERIFY THAT INDEX CARD HAS BEEN PROPERLY FILLED OUT WITH TYPE WRITTEN DESCRIPTION FOR
EACH CIRCUIT INSTALLED IN ALL NEW PANELBOARDS. VERIFY THAT COMPLETED INDEX CARDS ARE
PROPERLY ATTACHED TO EACH PANELBOARD.
F. O&M DOCUMENTATION: MEP CONTRACTOR SHALL PROVIDE A MINIMUM OF 2 SETS OF OPERATIONS AND MAINTENANCE (O&M) BINDERS FOR THE PROJECT. EACH BINDER SHOULD INCLUDE ALL O&M MANUALS, WARRANTIES, STARTUP AND TESTING SHEETS, CONTROL DIAGRAMS AND SETPOINTS FOR THE
FOLLOWING ITEMS:
1. ALL NEW LIGHTING AND CONTROLS, INCLUDING EMERGENCY LIGHTING
G. TRAINING: CONTRACTOR SHALL PROVIDE A MINIMUM OF 2 HOURS ON-SITE TRAINING FOR OWNER'S OPERATIONAL STAFF UPON COMPLETION OF ALL WORK. TRAINING SHALL COVER OPERATIONS AND
MAINTENANCE ON ALL NEW MEP SYSTEMS INCLUDING:
1. LIGHTING AND ELECTRICAL SYSTEMS AND EQUIPMENT
DISC. NO.
SCHEDULED
GENERAL NOTES FOR ELECTRICAL CONTRACTORS:
A. INCIDENTAL WORK:
1. CUTTING AND PATCHING: WHERE CUTTING AND PATCHING ARE REQUIRED TO INSTALL MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS, CONTRACTORS SHALL PROVIDE AS NEEDED. AFTER INSTALLATION, PATCH ALL OPENINGS TO MATCH ADJACENT FINISHED SURFACES. FINISHED PAINTING TO BE PROVIDED BY
OTHERS.
B. EXCAVATIONS:
1. PERFORM EXCAVATIONS CAUTIOUSLY TO AVOID DISRUPTION OR DAMAGE TO UNDERGROUND UTILITIES. HAVE ALL UNDERGROUND UTILITIES LOCATED AND MARKED, PRIOR TO DIGGING. UTILIZE HAND DIGGING WHEN
NEAR BURIED PIPING, CABLES, GAS LINES, ETC.
2. COMBINE UNDERGROUND PIPING AND ELECTRICAL CONDUITS INTO COMMON TRENCHES WHERE POSSIBLE TO MINIMIZE TRENCHING. TRENCH ROUTING SHOWN ON PLANS IS PRELIMINARY ONLY. SEE CIVIL ENGR. PLANS
FOR OUTDOOR ROUTING AND UTILITY CONNECTION DETAILS.
C. ENGINEERING DRAWINGS:
1. SCHEMATIC DRAWINGS: ALL ENGINEERING PLANS AND DETAILS ARE GENERALLY SCHEMATIC IN NATURE. ONLY ITEMS WITH SPECIFIC LOCATIONS AND OR SIZES WILL BE DIMENSIONED. CONTRACTORS ARE RESPONSIBLE FOR COORDINATING FINAL LOCATIONS OF ALL NEW EQUIPMENT. COORDINATE WITH ARCHITECTURAL AND
STRUCTURAL DRAWINGS.
2. ADDED DETAILS: DRAWINGS DO NOT SHOW EVERY DETAIL OR ITEM REQUIRED FOR EQUIPMENT INSTALLATIONS. CONTRACTORS SHALL PROVIDE ALL REQUIRED INSTALLATION WORK AND ACCESSORIES AS
SPECIFIED BY EQUIPMENT MFG'S INSTRUCTIONS.
3. OFFSETS AND ADJUSTMENTS: CONTRACTORS SHALL PROVIDE ALL REQUIRED OFFSETS AND ADJUSTMENTS TO DUCTWORK, CONDUIT AND PIPING SHOWN ON DRAWINGS AS NEEDED TO AVOID INTERFERENCES WITH BUILDING STRUCTURE AND OR OTHER TRADES. ALL FINAL COORDINATION AND DETAILING OF DUCTWORK AND
PIPING SHALL BE PROVIDED BY CONTRACTORS.
4. EQUIPMENT SELECTION: THE CONTRACTOR AND SUPPLIER ARE RESPONSIBLE FOR THE FINAL SELECTION OF ALL EQUIPMENT, BASED ON THE PERFORMANCE AND FEATURES SCHEDULED ON THE DRAWINGS. MODEL NO'S SHOWN ON SCHEDULES ARE BASIS OF DESIGN ONLY AND SHALL BE CONFIRMED BY VENDOR THROUGH PRE-CONSTRUCTION SUBMITTALS. PERFORMANCE AND FEATURE DATA SHOWN SHALL BE EQUIVALENT FOR
ALL SUBSTITUTIONS WHERE ALLOWED.
5. EQUIPMENT WEIGHTS: UTILIZE FINAL EQUIPMENT SUBMITTALS FROM SUPPLIER FOR ALL STRUCTURAL SUPPORT DESIGN. INCLUDE CURB WEIGHTS FOR ALL ROOFTOP MOUNTED EQUIPMENT. WEIGHTS SHOWN ON
SCHEDULES ARE PRELIMINARY ONLY.
D. COORDINATION WITH OWNER:
1. ELECTRICAL SHALL COORDINATE WITH OWNER TO VERIFY:
a. FINAL LOCATION AND MOUNTING HEIGHT OF ALL LIGHT FIXTURES, WALL MOUNTED RECEPTACLES AND
LIGHTING CONTROLS.
b. VENDOR INSTALLATION DATA AND FINAL LOCATIONS FOR ALL OWNER FURNISHED EQUIPMENT REQUIRING
POWER CONNECTIONS, INCLUDING TIRE SHREDDER EQUIPMENT.
c. PANEL AND EQUIPMENT IDENTIFICATION MARKS PRIOR TO ORDERING PERMANENT LABELS. ALL MARKS
SHOWN ON PLANS ARE PRELIMINARY.
E. COORDINATION BETWEEN TRADES:
1. ALL CONTRACTORS SHALL COORDINATE WITH ALL OTHER TRADES TO AVOID INTERFERENCES, PROPERLY SEQUENCE INSTALLATIONS, AND PROVIDE MANUFACTURER'S REQUIRED SERVICE CLEARANCES. WHERE
REQUIRED, CONTRACTOR SHALL MAKE THE REQUIRED ADJUSTMENTS.
2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH LOCAL UTILITY FINAL SPECIFICATIONS AND REQUIREMENTS FOR ALL NEW ELECTRICAL SERVICE EQUIPMENT SHOWN ON PLANS, INCLUDING METER BASE
AND DISCONNECT SWITCH OR SERVICE PANEL BOARD.
F. ELECTRICAL CONDUCTORS AND CABLES:
1. CONDUCTORS: ALL WIRES AND SIZES SHOWN ON PLANS ARE FOR COPPER WIRE WITH PROPER INSULATION, RATED FOR THE ACTUAL CONDITIONS OF THE INSTALLATION. ALUMINUM WIRE CAN BE SUBSTITUTED FOR CONDUCTORS SIZED #6 AND ABOVE. PROVIDE SUITABLE TERMINAL LUGS WHERE ALUMINUM WIRE IS USED.
2. CONDUCTOR SIZES: SEE ELECTRICAL PANEL SCHEDULES FOR ALL WIRE AND CONDUIT SIZES, NOT SHOWN ON PLANS FOR CLARITY. ALL ELECTRICAL CIRCUITS ON PLAN ARE IDENTIFIED AT HOMERUN BY PANEL AND CIRCUIT
NUMBERS.
G. ELECTRICAL CONDUITS AND SUPPORTS:
1. HOLD ALL CONDUITS TIGHT AGAINST STRUCTURE TO AVOID DAMAGE AND INTERFERENCE FROM OTHER TRADES. RUN ALL CONDUITS IN A NEAT AND WORKMAN LIKE MANNER PARALLEL TO BUILDING LINES.
2. PROVIDE ALL REQUIRED CONDUIT HANGERS AND SUPPORTS WITH PROPER SPACING PER CODE REQUIREMENTS.
GROUP PARALLEL RUNS OF CONDUIT TOGETHER ON COMMON HANGERS AND SUPPORTS TO MINIMIZE SPACE
WHEREVER POSSIBLE.
3. INSTALL A GALVANIZED IRON OR PVC SLEEVE FOR THE CONDUIT PASSING THROUGH CONCRETE OR MASONRY
CONSTRUCTION.
4. UTILIZE RIGID PVC CONDUIT FOR INSTALLING ELECTRICAL IN UNDERGROUND EXTERIOR LOCATIONS WHERE ALLOWED AND NOT SUBJECT TO DAMAGE. WHERE EXPOSED CONDUITS ARE RISING OUT OF EXCAVATION
TRENCH, PROVIDE SCHEDULE 80 PVC PIPE RISERS AND LONG-SWEEP ELBOWS IN TRENCH.
5. UTILIZE RIGID STEEL CONDUIT FOR INSTALLING ELECTRICAL CONDUCTORS IN ALL HIGH ABUSE AREAS INDOORS
AND OUTDOORS.
H. AUTOMATIC LIGHTING CONTROLS:
1. PROVIDE ALL REQUIRED OUTDOOR AREA LIGHTING CONTROLS, INCLUDING OUTDOOR LIGHTING TIMER AND PHOTOCELL SWITCH. SEE CONTROLS DETAILS. PROGRAM TIMER WITH ON/OFF TIMES FOR PROPER OPERATION
YEAR-ROUND, USING PHOTOCELL SWITCH AS FINAL SEASONAL ADJUSTMENT CONTROL.
2. INSTALL ALL LIGHTING CONTROLLERS IN ACCESSIBLE LOCATION ON WALL, ABOVE CEILING OR OTHER APPROVED LOCATION. WHEN ABOVE CEILING, PROVIDE PERMANENT MARKER FOR LOCATING CONTROLLER FROM THE
GROUND.
I. APPLIANCE AND EQUIPMENT CONNECTIONS:
1. WHERE REQUIRED FOR EQUIPMENT SERVICE CONNECTIONS, PROVIDE STEEL CHANNEL SUPPORT STANDS FOR MOUNTING OF UNIT DISCONNECT SWITCHES, STARTERS, SPEED CONTROLLERS AND CONDUITS. PROPERLY
SECURE SUPPORTS TO FLOORS OR WALLS.
2. ENSURE THAT SERVICE CLEARANCES ARE NOT BLOCKED BY ROUTING OF CONDUIT OR SUPPORT STRUCTURES AT ALL EQUIPMENT SERVICE CONNECTIONS. COORDINATE WITH EQUIPMENT CONTRACTOR TO DETERMINE
REQUIRED CLEARANCES AND SERVICE WORK AREAS.
J. ELECTRICAL SERVICES AND EQUIPMENT:
1. INSTALL ALL ELECTRICAL SERVICE EQUIPMENT AS REQUIRED BY LOCAL UTILITY SPECIFICATIONS. FIELD VERIFY FINAL LOCATION OF EQUIPMENT TO ENSURE PROPER CLEARANCES ARE AVAILABLE FOR FINAL ENCLOSURES TO BE INSTALLED. PROVIDE STEEL MOUNTING RACK WHERE REQUIRED TO HOLD ALL METERS, DISCONNECT
SWITCHES, BUSSED GUTTERS AND PANELS AS SHOWN.
AutoCAD SHX Text
JOB NO.:
AutoCAD SHX Text
REVISIONS :
AutoCAD SHX Text
SHEET :
AutoCAD SHX Text
OF :
AutoCAD SHX Text
SCALE :
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 5/13/26
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
WB-112
AutoCAD SHX Text
ELECTRICAL LEGENDS,
AutoCAD SHX Text
NOTES & COMMISSIONING
AutoCAD SHX Text
AutoCAD SHX Text
C.A.PIEPER
AutoCAD SHX Text J
E
SH
R
ED
D
ER
F
AC
IL
IT
Y R
EE
VE
S C
O U
N
TY
, T
EX
AS
C O
. R D
. 2
, P
EC
O S, T X
TEXAS FIRM
REGISTRATION:
#F-26227
E9
ELECTRICAL SPECIFICATIONS:
GENERAL CONDITIONS FOR MEP WORK:
A. CONTRACTOR QUALIFICATIONS:
1. CONTRACTORS SHALL STUDY CONTRACT DOCUMENTS, FULLY UNDERSTAND AND ACCEPT THE BASIS
OF DESIGN AND SCOPE OF WORK. SUBMISSION OF BID INDICATES CONTRACTOR'S COMPLETE
APPROVAL AND ACCEPTANCE OF CONSTRUCTION DOCUMENTS.
2. CONTRACTORS SHALL PROVIDE A MINIMUM 1 YR. WARRANTY ON ALL LABOR AND MATERIALS
INSTALLED. CONTRACTOR SHALL MAKE ALL WARRANTY REPAIRS OR REPLACEMENTS IN A TIMELY
MANNER, AT NO ADDITIONAL COST TO THE OWNER.
B. BASIS OF DESIGN:
1. ALL CONSTRUCTION DOCUMENTS PROVIDED BY OWNER, INCLUDING ENGINEERING DRAWINGS,
NOTES, SCHEDULES, DETAILS, CALCULATIONS AND SPECIFICATIONS PROVIDED, ALONG WITH
EQUIPMENT MANUFACTURER'S DRAWINGS AND SPECIFICATIONS, FORM THE 'BASIS OF DESIGN'.
2. THE BASIS OF DESIGN WILL BE USED FOR ALL INSPECTIONS, TESTING AND ACCEPTANCE OF THE WORK
PERFORMED BY THE CONTRACTOR TO VERIFY SUCCESSFUL COMPLETION OF SCOPE OF WORK.
C. SCOPE OF WORK:
1. INSTALL COMPLETE AND OPERABLE ELECTRICAL SYSTEMS AS DESCRIBED BY THE CONSTRUCTION DOCUMENTS. INCIDENTAL ITEMS NOT SPECIFIED, BUT WHICH ARE ESSENTIAL FOR THE PROPER OPERATION OF SPECIFIED SYSTEMS AND EQUIPMENT, ARE INCLUDED IN THE SCOPE OF WORK AND
SHALL BE PROVIDED BY CONTRACTOR AT NO ADDITIONAL COST.
2. COMPLY WITH COMMISSIONING PLAN SHOWN ON DRAWINGS TO VERIFY FINAL QUALITY AND
PERFORMANCE OF ALL WORK.
D. CODE COMPLIANCE: ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL LOCALLY ADOPTED BUILDING CODES AS LISTED ON THE DRAWINGS, AND ACCORDING TO THE LOCAL AUTHORITY HAVING
JURISDICTION (AHJ).
E. DISCREPANCIES:
1. IN THE CASE OF A DISCREPANCY BETWEEN DRAWINGS, SPECIFICATIONS OR MANUFACTURER'S REQUIREMENTS, THE MOST STRINGENT SHALL APPLY AND BE COMPLIED WITH BY THE CONTRACTOR.
2. IN THE CASE OF A DISCREPANCY BETWEEN BY CODES AND THE CONSTRUCTION DOCUMENTS OR MANUFACTURER'S REQUIREMENTS, THE AHJ SHALL DETERMINE WHICH SHOULD BE COMPLIED WITH
BY THE CONTRACTOR.
F. JOBSITE CONDITIONS: CONTRACTOR SHALL EXAMINE THE JOBSITE PRIOR TO BIDDING AND FULLY UNDERSTAND THE CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED. BY SUBMITTING BID
FOR WORK CONTRACTOR ACCEPTS ALL JOB CONDITIONS AS-IS.
G. PERMITS AND FEES: CONTRACTOR SHALL OBTAIN THE NECESSARY PERMITS, LICENSES, AND
CERTIFICATIONS REQUIRED BY THE AHJ AND PAY FOR ALL PERMITTING FEES.
H. UTILITY CONNECTIONS:
1. SEE CIVIL PLANS FOR CONTINUATION OF ELECTRICAL, WATER AND SEWER SERVICE CONNECTIONS
OUTSIDE OF BUILDING.
2. COORDINATE WITH LOCAL UTILITIES TO PROVIDE NEW SERVICES AS SHOWN ON PLANS. INSTALL ALL REQUIRED SERVICE CONNECTIONS PER UTILITY SPECIFICATIONS. PAY ALL UTILITY REQUIRED FEES FOR
SERVICE CONNECTIONS OR MODIFICATIONS SHOWN ON PLANS.
I. CONTRACTOR FURNISHED EQUIPMENT & MATERIALS: SHALL BE NEW, COMMERCIAL GRADE,
MANUFACTURED AND CERTIFIED TO COMPLY WITH THE BASIS OF DESIGN, FREE OF DEFECT, MINIMUM
1-YEAR FACTORY WARRANTY. ALL SUBSTITUTIONS MUST BE 'APPROVED' THROUGH THE
COMMISSIONING PROCESS TO BE ACCEPTABLE.
J. DELIVERY, STORAGE AND PROTECTION: CONTRACTOR SHALL INCLUDE ALL REQUIRED MATERIALS MANAGEMENT AS PART OF THE SCOPE OF WORK, INCLUDING DELIVERY, STORAGE AND RIGGING OF ALL
EQUIPMENT AND MATERIALS TO BE FURNISHED. DAMAGED ITEMS SHOULD BE IDENTIFIED AND
RETURNED TO THE FACTORY FOR REPLACEMENTS AT NO ADDITIONAL COST TO THE OWNER.
K. JOBSITE CLEANUP AND SAFETY: CONTRACTOR SHALL INCLUDE DAILY AND FINAL CLEANUP OF JOBSITE AS PART OF SCOPE OF WORK. CONTRACTOR SHALL COMPLY WITH ALL SAFETY REQUIREMENTS AS DIRECTED
BY OWNER AND AHJ.
L. CORRECTIONS REQUIRED:
1. IF CONTRACTOR IDENTIFIES ANY ACTUAL SITUATION OR SITE CONDITION THAT WILL PROHIBIT OR NEGATIVELY IMPACT THE INSTALLATION OR PERFORMANCE OF THE SYSTEMS AS DESIGNED, STOP ALL
WORK AND NOTIFY THE ENGINEER IMMEDIATELY.
2. ANY EQUIPMENT THAT IS FOUND TO BE DEFECTIVE, OR OUT OF COMPLIANCE WITH BASIS OF DESIGN OR CODE, CONTRACTOR SHALL REPLACE AT NO ADDITIONAL COST. ALL NEW WORK SHALL COMPLY
WITH THE BASIS OF DESIGN.
3. IF CONTRACTOR DAMAGES ADJACENT PROPERTY WHILE PERFORMING SCOPE OF WORK, HE SHALL
MAKE PROMPT REPAIR AT OWN EXPENSE, PRIOR TO COMPLETING PROJECT.
ELECTRICAL EQUIPMENT & MATERIALS
A. CONDUIT AND WIREWAYS:
1. EMT: HOT GALVANIZED STEEL, INTERIOR COATING, UL LISTED, AS MANUFACTURED BY ALLIED, E-Z PULL EMT, OR EQUAL. ALL FACTORY COUPLINGS AND FITTINGS SHALL BE OF SAME MATERIAL AS
CONDUIT.
2. RIGID STEEL: HOT DIPPED GALVANIZED STEEL, CORROSION RESISTANT, UL LISTED, AS MANUFACTURED BY ALLIED, GRC, OR EQUAL. ALL FACTORY COUPLINGS AND FITTINGS SHALL BE OF SAME MATERIAL AS
CONDUIT.
3. PVC: SCHEDULE 40 OR 80 ELECTRICAL CONDUIT, UL LISTED, SLIP BELL FITTING ON ONE END, AS
MANUFACTURED BY ALLIED OR EQUAL. SUNLIGHT RESISTANT WHERE USED EXPOSED OUTSIDE.
B. WIRE AND CABLE:
1. CONDUCTORS: PROVIDE COPPER CONDUCTORS OF STANDARD AMERICAN GAGES FOR ALL WIRING SHOWN ON DRAWINGS. MINIMUM 90°F RATED INSULATION FOR ALL CONDUCTORS USED, SUCH AS
THHN, THHW, THW OR EQUAL.
2. ALUMINUM CONDUCTORS OF EQUIVALENT AMPACITY CAN BE SUBSTITUTED FOR SIZES #6 AND
ABOVE.
3. MC CABLE: METAL CLAD CABLE WITH COPPER CONDUCTORS, RATED FOR WET OR DRY LOCATIONS, 90⁰C TEMPERATURE RATING, WITH GREEN INSULATED GROUNDING CONDUCTOR. ALL CONDUCTORS
CABLED TOGETHER WITH SEPARATOR TAPE, INTERLOCKED ALUMINUM ARMOR, FLAME RETARDANT
BLACK PVC JACKET OVER THE ARMOR.
4. SPLICE CONNECTORS: INSUL-TAP CONNECTORS, UV RATED, COPPER OR ALUMINUM RATED, AS
MANUFACTURED BY POLARIS, IT SERIES OR EQUAL.
C. BOXES AND ENCLOSURES:
1. JUNCTION BOXES: PROVIDE STEEL OR PVC, WEATHERPROOF BOXES AND GASKETED COVERS FOR ALL
CONTROLS WIRING CIRCUITS AT EQUIPMENT SWITCH RACK STANDS AS SHOWN ON PLANS.
D. RECEPTACLES AND COVER PLATES:
1. INDOORS:
a. DUPLEX RECEPTACLES: 120V, DUPLEX, 15A 125V, NEMA 5-15R, AS MANUFACTURED BY HUBBELL
MODEL #BR15I OR EQUAL.
b. GFI RECEPTACLES: 120V, DUPLEX, TEST BUTTON, LED INDICATOR LIGHT, 15A 125V, NEMA 5-15R, AS
MANUFACTURED BY HUBBELL MODEL #GF15IL OR EQUAL.
2. OUTDOORS:
a. GFI RECEPTACLES: 120V, WEATHER RESISTANT, DUPLEX, TEST BUTTON, LED INDICATOR LIGHT, 15A
125V, NEMA 5-15R, AS MANUFACTURED BY HUBBELL MODEL #GF15ILWR OR EQUAL. PROVIDE
WITH WEATHERPROOF, LOCKING COVER, EQUAL TO HUBBELL BELL #MX105OS.
E. WALL SWITCHES:
1. LIGHT SWITCH: 1P/15A/120V TOGGLE SWITCH, SINGLE GANG BOX MOUNTED, AS MANUFACTURED BY
LEVITON MODEL # 5501-LHW OR EQUAL.
F. LIGHT FIXTURES: AS SCHEDULED ON PLANS, OR APPROVED EQUAL.
G. AUTOMATIC LIGHTING CONTROLS:
1. LIGHTING TIMER: 24-HOUR ELECTRONIC TYPE, MIN. 2P/20A CONTACTS, 120V POWER SUPPLY, NEMA
1 ENCLOSURE, AS MANUFACTURED BY INTERMATIC #ET1125C OR EQUAL.
2. PHOTOCELL SWITCH: 1P/120V, 1800 W RATING, WEATHERPROOF, SLIDE ADJUSTMENT, DELAY
ACTION, AS MANUFACTURED BY INTERMATIC, MODEL # K4121C OR EQUAL.
H. PANELS, SWITCHGEAR & DISTRIBUTION EQUIPMENT
1. ELECTRICAL PANELS: AS MANUFACTURED BY EATON OR EQUAL. PROVIDE SUBMITTALS FROM
VENDOR PRIOR TO ORDERING PANELS AND BREAKERS. VERIFY PANELS MEET THE FAULT CURRENT
RMS VALUES AS SHOWN ON THE PLANS.
a. 1000A OR HIGHER, 480V: PROVIDE WITH GROUND-FAULT PROTECTION AS REQUIRED BY NEC.
2. CIRCUIT BREAKERS: AS SPECIFIED BY PANELBOARD MANUFACTURER. RATINGS AS SHOWN ON PLANS.
a. 1200A OR HIGHER: PROVIDE CIRCUIT BREAKER WITH FACTORY ENERGY-REDUCING SWITCHING OR
ACTIVE ARC FLASH MITIGATION SYSTEM.
3. TRANSFORMERS: SEE SCHEDULES FOR PERFORMANCE REQUIREMENTS, MAKE AND MODEL NO
REQUIRED, OR EQUAL.
a. DRY-TYPE: 600V OR LESS PRIMARY AND SECONDARY, 15 KVA THROUGH 750 KVA, CLASS 220
INSULATION, LOW LOSS TYPE, VENTILATED STEEL ENCLOSURE, AS SCHEDULED ON PLANS OR
EQUAL. PROVIDE ALL REQUIRED MOUNTING SUPPORTS FOR WALL INSTALLATIONS OR CONCRETE
HOUSEKEEPING PAD FOR GRADE MOUNTED INSTALLATIONS.
4. DISCONNECT SWITCHES: HEAVY DUTY SAFETY SWITCH AS MANUFACTUED BY SQUARE D, OR EQUAL.
PROVIDE NEMA 1 OR 3R ENCLOSURE AS REQUIRED. PROVIDE CLASS R, L OR J FUSES AND SPRING
REINFORCED PLATED COPPER FUSE CLIPS WHERE SPECIFIED.
5. ELECTRICAL CAUTION TAPE: 6" WIDE HEAVY-DUTY POLYETHYLENE TAPE, RED WITH BLACK LETTERS, "CAUTION, ELECTRIC LINE BELOW" TEXT, AS MANUFACTURED BY BRADY #91296 OR EQUAL.
6. EQUIPMENT LABELS: PROVIDE EQUIPMENT LABELS FOR ALL DISCONNECT SWITCHES, PANELBOARDS, MOTOR CONTROL CENTERS AND OTHER MARKED ENCLOSURES. LABELS SHALL BE PERMANENTLY
FASTENED TO EXTERIOR OF ENCLOSURE IN VISIBLE LOCATION AND SHALL MATCH EQUIPMENT
IDENTIFICATION MARKS SHOWN ON PLANS.
a. INTERIOR LABELS SHALL BE BLACK PLASTIC WITH WHITE LETTERS, MINIMUM ¾” HIGH.
b. EXTERIOR LABELS SHALL BE METALLIC, SUITABLE FOR EXTERIOR LOCATIONS WITH BLACK LETTERS
MINIMUM ¾” HIGH.
AutoCAD SHX Text
JOB NO.:
AutoCAD SHX Text
REVISIONS :
AutoCAD SHX Text
SHEET :
AutoCAD SHX Text
OF :
AutoCAD SHX Text
SCALE :
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 5/13/26
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
WB-112
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
SPECIFICATIONS
AutoCAD SHX Text
C.A. PIEPER
PARTIAL PLAN - ELECTRICAL
SCALE: 1/4"=1'-0"
KEYNOTES:#
1. PROVIDE BARE 3/0 CU BONDING JUMPER, WELDED TO STEEL COLUMN,
BONDED TO BARE #3/0 CU GROUND RING AROUND FOOTINGS. TYPICAL
ALL COLUMNS.
2. PROVIDE FIELD FABRICATED UNITSTRUT RACK STAND TO HOLD GROUP
OF DISCONNECT SWITCHES, SEE TYPICAL DETAIL FOR REQUIREMENTS.
COORDINATE WITH OWNER FOR FINAL LOCATIONS OF ALL RACK STANDS,
LOCATIONS SHOWN ARE PRELIMINARY ONLY.
3. PROVIDE BARE #3/0 CU GROUND RING AROUND BUILDING FOOTINGS.
BOND TO BUILDING GROUNDING ELECTRODE SYSTEM PER NEC. 250, SEE
DETAILS.
E1
TI
R
E
SH
R
ED
D
ER
F
AC
IL
IT
Y R
EE
VE
S C
O U
N
TY
, T
EX
AS
C O
. R D
. 2
, P
EC
O S, T X
TEXAS FIRM
REGISTRATION:
#F-26227
E1
KEY PLAN
WORK AREA
PAVILLION
8 40 41 42
2 35 739 3811 3736 45 9
11.F
11.E
11.A
11.B
24.B
24.A
36.C 36.B 36.A
35.A
35.B
51.B
51.A
10 64 17 80
60 59 43 12 58 16
66 67 65 68 69 70
26 77
50.A50.B 50.A50.B 50.A50.B
38.B 38.B
38.A
38.A
18 19 61 62
NOTES
1. COORDINATE WITH OWNER, FINAL RECEPTACLE LOCATIONS AND MOUNTING
HEIGHTS, PRIOR TO ROUGH-IN. LOCATIONS SHOWN ON PLANS ARE
PRELIMINARY.
2. COORDINATE WITH OWNER, FINAL LOCATION OF ALL DISCONNECT SWITCHES
AND MOUNTING STANDS. LOCATIONS SHOWN ABOVE ARE PRELIMINARY
ONLY.
3. GROUP MULTIPLE MOTOR FEEDERS INTO LARGER CONDUITS AND ROUTE
OVERHEAD FROM MCC IN OFFICE TO SWITCH RACK LOCATIONS SHOWN
ABOVE. VERIFY FINAL MOTOR FEEDER REQUIREMENTS WITH OWNER PRIOR
TO SIZING FEEDER CONDUITS. FEEDER CIRCUITS FROM MCC TO THE SWITCH
RACKS ARE NOT SHOWN ABOVE FOR CLARITY. SEE TYPICAL RACK STAND
DETAILS 3/E7.
WP
36" WP36" WP36" WP36" WP36"
LV1
WP
36"
LV1
WP 36"
WP
36" WP 36"
WP
36"
1 1 1 1 1
2 2
MCC1
MCC2
27 78 28 79
1 44
MCC4
MCC4
MCC4
MCC4
MCC4
MCC4
MCC4
MCC4
MCC415
MCC416
MCC4
MCC4
MCC4
MCC4
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5 40
MCC5
MCC5
MCC5
24D
MCC5
MCC4
MCC4
MCC4
MCC4
1 SEE 1/E2 FOR
CONTINUATION OF
GROUND RING
SEE 1/E2 FOR
CONTINUATION OF
GROUND RING
3 3
AutoCAD SHX Text
JOB NO.:
AutoCAD SHX Text
REVISIONS :
AutoCAD SHX Text
SHEET :
AutoCAD SHX Text
OF :
AutoCAD SHX Text
SCALE :
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 5/13/26
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
WB-112
AutoCAD SHX Text
ELECTRICAL PLANS
AutoCAD SHX Text
AND NOTES
AutoCAD SHX Text
NAME
PARTIAL PLAN - ELECTRICAL
SCALE: 1/4"=1'-0"
KEYNOTES:#
E2
TI
R
E
SH
R
ED
D
ER
F
AC
IL
IT
Y R
EE
VE
S C
O U
N
TY
, T
EX
AS
C O
. R D
. 2
, P
EC
O S, T X
TEXAS FIRM
REGISTRATION:
#F-26227
E2
32 31 30 34
5 29 4 3 33
2.B 2.A
2.C
33.A 33.B
34.A 34.B
34.A 34.B
49.A 49.B
48.A 48.B
48.A 48.B
49.A 49.B
49.A 49.B
71 74 72 75 73 76
WP36"
WP 36"
WP36"
WP 36"
WP36"
WP 36"
1. PROVIDE BARE 3/0 CU BONDING JUMPER, WELDED TO STEEL COLUMN,
BONDED TO BARE #3/0 CU GROUND RING AROUND FOOTINGS. TYPICAL
ALL COLUMNS.
2. PROVIDE FIELD FABRICATED UNITSTRUT RACK STAND TO HOLD GROUP
OF DISCONNECT SWITCHES, SEE TYPICAL DETAIL FOR REQUIREMENTS.
COORDINATE WITH OWNER FOR FINAL LOCATIONS OF ALL RACK STANDS,
LOCATIONS SHOWN ARE PRELIMINARY ONLY.
3. NEW UNDERGROUND ELECTRICAL SERVICE LATERAL BY LOCAL UTILITY
CO. COORDINATE REQUIREMENTS WITH UTILITY. SEE RISER DIAGRAM.
SEE CIVIL PLANS FOR CONTINUATION.
4. HIGH-VOLTAGE SERVICE PANEL, PROVIDE NEMA 3R ENCLOSURE AND
MIN. 3” CONCRETE HOUSEKEEPING PAD FOR BASE MOUNTING.
5. STEPDOWN TRANSFORMER, PAD MOUNTED, PROVIDE MIN. 3”
CONCRETE HOUSEKEEPING PAD FOR BASE MOUNTING.
6. LOW-VOLTAGE BRANCH PANEL, MOUNTED TO CONNEX BUILDING.
7. MOTOR CONTROL CENTER BY EQUIPMENT VENDOR, COORDINATE FINAL
INSTALLATION AND CONNECTION REQUIREMENTS WITH EQUIP VENDOR,
PRIOR TO ROUGH-IN, TYPICAL 5 PLACES.
8. OVERHEAD FEEDER FROM SERVICE PANEL TO MOTOR CONTROL CENTER,
TYPICAL 5 PLACES. HOLD CONDUIT TIGHT TO STRUCTURE ABOVE. SEE
RISER DIAGRAM FOR CONDUIT AND WIRE SIZES
9. PROVIDE BARE #3/0 CU GROUND RING AROUND BUILDING FOOTINGS.
BOND TO BUILDING GROUNDING ELECTRODE SYSTEM PER NEC. 250, SEE
DETAILS.
1 1 1
MCC3
MCC3
MCC4
MCC4
MCC4
MCC4
MCC4
MCC4
MCC4
MCC4
MCC4
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5
MCC5 47
MCC5
MCC5
MCC5
MCC5
OFFICE
MCC1 MCC2 MCC3 MCC4 MCC5
HV1
LV1
T1
UE
FROM UTILITY
TRANSFORMER
CONNEX BUILDING
BY OWNER
7 7 7 7 7
3" C.
3" C.
4" C.
4" C.
4" C.
8 8
WP
36"
LV1
MCC4
MCC4
MCC4
SEE 1/E1 FOR
CONTINUATION OF
GROUND RING
SEE 1/E1 FOR
CONTINUATION OF
CIRCUIT
SEE 1/E1 FOR
CONTINUATION OF
CIRCUIT
SEE 1/E1 FOR
CONTINUATION OF
GROUND RING
9 9
NOTES
1. COORDINATE WITH OWNER, FINAL RECEPTACLE LOCATIONS AND MOUNTING
HEIGHTS, PRIOR TO ROUGH-IN. LOCATIONS SHOWN ON PLANS ARE
PRELIMINARY.
2. COORDINATE WITH OWNER, FINAL LOCATION OF ALL DISCONNECT SWITCHES
AND MOUNTING STANDS. LOCATIONS SHOWN ABOVE ARE PRELIMINARY
ONLY.
3. GROUP MULTIPLE MOTOR FEEDERS INTO LARGER CONDUITS AND ROUTE
OVERHEAD FROM MCC IN OFFICE TO SWITCH RACK LOCATIONS SHOWN
ABOVE. VERIFY FINAL MOTOR FEEDER REQUIREMENTS WITH OWNER PRIOR
TO SIZING FEEDER CONDUITS. FEEDER CIRCUITS FROM MCC TO THE SWITCH
RACKS ARE NOT SHOWN ABOVE FOR CLARITY. SEE TYPICAL RACK STAND
DETAILS 3/E7.
4. COORDINATE FINAL DIMENSIONS, LOCATION AND POWER REQUIREMENTS
FOR OFFICE STRUCTURE WITH OWNER, PRIOR TO STARING WORK. OFFICE
AND MCC INSTRALLATION SHOWN ABOVE IS PRELIMINARY ONLY.
AutoCAD SHX Text
JOB NO.:
AutoCAD SHX Text
REVISIONS :
AutoCAD SHX Text
SHEET :
AutoCAD SHX Text
OF :
AutoCAD SHX Text
SCALE :
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 5/13/26
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
WB-112
AutoCAD SHX Text
ELECTRICAL PLANS
AutoCAD SHX Text
AND NOTES
AutoCAD SHX Text
PARTIAL PLAN - LIGHTING
SCALE: 1/4"=1'-0"E3
KEYNOTES:#
1. HIGH-BAY LED LIGHT FIXTURE, TYPICAL. COORDINATE FINAL MOUNTING
HEIGHT WITH OWNER PRIOR TO ROUGH-IN.
TI
R
E
SH
R
ED
D
ER
F
AC
IL
IT
Y R
EE
VE
S C
O U
N
TY
, T
EX
AS
C O
. R D
. 2
, P
EC
O S, T X
TEXAS FIRM
REGISTRATION:
#F-26227
E3NOTES:
1. COORDINATE WITH OWNER, FINAL MOUNTING HEIGHT FOR ALL PENDANT
MOUNTED LIGHT FIXTURES, PRIOR TO INSTALLATION. HEIGHTS SHOWN ON
SCHEDULE ARE PRELIMINARY ONLY.
2. COORDINATE WITH OWNER, ALL LIGHT SWITCH LOCATIONS PRIOR TO
ROUGH-IN. LOCATIONS SHOWN ARE PRELIMINARY ONLY. KEY PLAN
S WP
HB1 HB1 HB1 HB1
HB1
HB1
HB1 HB1 HB1
HB1 HB1 HB1
LV1
S WP
LV1
WP
WP
WP WP WP
WPWPWP
SEE 1/E2 FOR
CONTINUATION
SEE 1/E2 FOR
CONTINUATION
AutoCAD SHX Text
JOB NO.:
AutoCAD SHX Text
REVISIONS :
AutoCAD SHX Text
SHEET :
AutoCAD SHX Text
OF :
AutoCAD SHX Text
SCALE :
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 5/13/26
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
WB-112
AutoCAD SHX Text
LIGHTING PLANS
AutoCAD SHX Text
AND NOTES
AutoCAD SHX Text
PARTIAL PLAN - LIGHTING
SCALE: 1/4"=1'-0"E4
KEYNOTES:#
TI
R
E
SH
R
ED
D
ER
F
AC
IL
IT
Y R
EE
VE
S C
O U
N
TY
, T
EX
AS
C O
. R D
. 2
, P
EC
O S, T X
TEXAS FIRM
REGISTRATION:
#F-26227
E4
NOTES:
1. COORDINATE WITH OWNER, FINAL MOUNTING HEIGHT FOR ALL PENDANT
MOUNTED LIGHT FIXTURES, PRIOR TO INSTALLATION. HEIGHTS SHOWN ON
SCHEDULE ARE PRELIMINARY ONLY.
2. COORDINATE WITH OWNER, ALL LIGHT SWITCH LOCATIONS PRIOR TO
ROUGH-IN. LOCATIONS SHOWN ARE PRELIMINARY ONLY.
HB1
HB1
HB1
HB1
HB1
HB1
HB1
HB1 HB1
HB1
S
WP
SEE 1/E3 FOR
CONTINATION
LV1
1. HIGH-BAY LED LIGHT FIXTURE, TYPICAL. COORDINATE FINAL MOUNTING
HEIGHT WITH OWNER PRIOR TO ROUGH-IN.
2. OUTDOOR LIGHTING TIMER, INSTALLED IN ACCESSIBLE LOCATION FOR
ADJUSTMENT, COORDINATE FINAL LOCATION WITH OWNER PRIOR TO
ROUGH-IN. SEE DETAILS FOR WIRING.
3. PROVIDE PHOTOCELL SWITCH FOR OUTDOOR LIGHTING CONTROLS,
INSTALLED IN ACCESSIBLE LOCATION FOR SERVICE AND ADJUSTMENT.
ENSURE CLEAR VIEW OF AMBIENT LIGHTING AT LOCATION INSTALLED.
SEE 1/E2 FOR
CONTINUATION
SEE 1/E3 FOR
CONTINUATION
HV1
LV1
T1
LV1
OT
P
WP
WPWP
WP
WP
OFFICE
LIGHTING THIS
AREA BY OWNER
AutoCAD SHX Text
JOB NO.:
AutoCAD SHX Text
REVISIONS :
AutoCAD SHX Text
SHEET :
AutoCAD SHX Text
OF :
AutoCAD SHX Text
SCALE :
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 5/13/26
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
WB-112
AutoCAD SHX Text
LIGHTING PLANS
AutoCAD SHX Text
AND NOTES
AutoCAD SHX Text
E
SH
R
ED
D
ER
F
AC
IL
IT
Y R
EE
VE
S C
O U
N
TY
, T
EX
AS
C O
. R D
. 2
, P
EC
O S, T X
TEXAS FIRM
REGISTRATION:
#F-26227
E5
NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY. NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY.
NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY.NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY.
NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY.
AutoCAD SHX Text
JOB NO.:
AutoCAD SHX Text
REVISIONS :
AutoCAD SHX Text
SHEET :
AutoCAD SHX Text
OF :
AutoCAD SHX Text
SCALE :
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 5/13/26
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
WB-112
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
SCHEDULES
AutoCAD SHX Text
E
SH
R
ED
D
ER
F
AC
IL
IT
Y R
EE
VE
S C
O U
N
TY
, T
EX
AS
C O
. R D
. 2
, P
EC
O S, T X
TEXAS FIRM
REGISTRATION:
#F-26227
E6
NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO
STARTING WORK. SWITCHES SHOWN ABOVE ARE PRELIMINARY ONLY.
AutoCAD SHX Text
JOB NO.:
AutoCAD SHX Text
REVISIONS :
AutoCAD SHX Text
SHEET :
AutoCAD SHX Text
OF :
AutoCAD SHX Text
SCALE :
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 5/13/26
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
WB-112
AutoCAD SHX Text
ELECTRICAL SCHEDULES
AutoCAD SHX Text
AND NOTES
AutoCAD SHX Text
E
SH
R
ED
D
ER
F
AC
IL
IT
Y R
EE
VE
S C
O U
N
TY
, T
EX
AS
C O
. R D
. 2
, P
EC
O S, T X
TEXAS FIRM
REGISTRATION:
#F-26227
E7
ELECTRICAL RISER DIAGRAM
NO SCALEE7
GRADE
UTILITY
POLE
UE
1500 KVA POLE
MOUNTED
TRANSFORMER
HV1
2000A
MCB
277/480V 3P/4W
NEMA 3R
LV1
100A
MLO
120/208V 3P/4W
NEMA 3R
T1
45 KVA
NEMA 3R
1. UTILITY TRANSFORMER: PROPOSED TRANSFORMER BY LOCAL ELECT
UTILITY AS SHOWN, COORDINATE NEW SERVICE INSTALLATION AS
SHOWN. COORDINATE FINAL TRANSFORMER SIZE AND LOCATION WITH
UTILITY.
2. SERVICE CONDUCTORS: SIX SETS OF 4 #500 MCM IN 4" CONDUITS,
COORDINATE ROUGH-IN REQUIREMENTS WITH UTILITY.
3. ELECTRIC METER: UTILITY FURNISHED ENCLOSURE, POLE MOUNTED AT
TRANSFORMER LOCATION, SERVICE CAPABILITY AS SHOWN, TO BE
INSTALLED BY CONTRACTOR, COORDINATE ROUGH-IN WITH UTILITY.
4. SERVICE PANEL HV1: SERVICE DISTRIBUTION PANEL, RATINGS AS
SHOWN. SEE SCHEDULES. COORDINATE FINAL LOCATION AND
REQUIREMENTS WITH OWNER PRIOR TO ROUGH-IN.
5. TRANSFORMER PRIMARY FEEDER: 3 #4 AWG AND #8 GND IN 1"
CONDUIT.
6. TRANSFORMER T1: LOW-VOLTAGE STEP DOWN, KVA RATING AND
ENCLOSURE AS SHOWN ABOVE, 480V/30 PRIMARY, 120/208V
SECONDARY, DRY TYPE, WALL OR PAD MOUNTED, VERIFY FINAL
LOCATION WITH OWNER PRIOR TO ROUGH-IN. SEE SCHEDULES AND
GROUNDING DETAILS.
7. SECONDARY PANEL FEEDER: 4 #1 AWG AND #6 GND IN 1 1/2" CONDUIT.
8. BRANCH PANEL LV1: LOW-VOLTAGE, RATINGS AS SHOWN ABOVE.
SERVING OFFICE EQUIPMENT, HVAC, LIGHTING AND RECEPTACLES.
9. MOTOR CONTROL PANEL FEEDER: ROUTE TO VENDOR FURNISHED MCC
ENCLOSURE, 3 #350 MCM AND #3 GND IN 3" CONDUIT. COORDINATE
FINAL REQUIREMENTS WITH MCC EQUIPMENT VENDOR PRIOR TO
ROUGH-IN, TYPICAL 2 PLACES.
10. MOTOR CONTROL PANEL FEEDER: ROUTE TO VENDOR FURNISHED MCC
ENCLOSURE, 3 #600 MCM AND #2 GND IN 4" CONDUIT. COORDINATE
FINAL REQUIREMENTS WITH MCC EQUIPMENT VENDOR PRIOR TO
ROUGH-IN, TYPICAL 3 PLACES.
11. MOTOR CONTROL CENTER (MCC): VENDOR FURNISHED, AMP RATINGS
AS SHOWN ABOVE. SERVING VENDOR FURNISHED TIRE SHREDDER
EQUIPMENT, TYPICAL 5 PLACES. COORDINATE WITH VENDOR FOR FINAL
INSTALLATION AND CONNECTION REQUIREMENTS, PRIOR TO ROUGH IN.
12. TRANSFORMER GROUND: ROUT BARE #6 CU CONDUCTOR FROM
GROUND LUG ON TRANSFORMER TO GROUND ROD AND BUILDING
GROUNDING ELECTRODE SYSTEM AS SHOWN. SEE DETAILS FOR
TRANSFORMER GROUND REQUIREMENTS.
13. GROUNDING ELECTRODE CONDUCTOR: PROVIDE BARE #3/0 AWG
COPPER CONDUCTOR FROM GROUND BUS ON SERVICE PANEL TO
GROUND ROD AND GROUNDING ELECTRODE SYSTEM.
14. GROUND ROD: PROVIDE MIN. 1 GROUND RODS TO PROVIDE MAXIMUM
OF 25 OHMS RESISTANCE TO GROUND PER NEC 250 BETWEEN SERVICE
PANEL BOND AND EARTH. IF NEEDED, PROVIDE AND BOND A SECOND
GROUND ROD, MIN. 6FT APART, TO LOWER RESISTANCE TO EARTH.
E
POLE MOUNTED
ELECT METER
MCC1
300A
MCB
480V
3P/3W
NEMA 3R
MCC2
300A
MCB
480V
3P/3W
NEMA 3R
MCC3
400A
MCB
480V
3P/3W
NEMA 3R
MCC4
400A
MCB
480V
3P/3W
NEMA 3R
MCC5
400A
MCB
480V
3P/3W
NEMA 3R
FLOOR
SERVICE
PANEL
VENDOR FURNISHED
MOTOR CONTROL
PANELS
11 11 11 11
NOTES:
1. DIAGRAM SHOWN ABOVE IS GENERAL ARRANGEMENT ONLY. ELECTRICAL CONTRACTOR SHALL DETERMINE ACTUAL TYPES AND LOCATIONS OF GROUNDING ELECTRODES AND BONDING JUMPER CONNECTIONS BASED UPON SITE CONDITIONS AND SHALL COORDINATE THE INSTALLATION OF ALL REQUIRED GROUND CONNECTORS WITH THE LOCAL UTILITY AND OTHER TRADES.
2. CONTRACTOR SHALL BOND TOGETHER AS SHOWN ALL GROUNDING ELECTRODES PRESENT AT THE BUILDING OR STRUCTURE. A MINIMUM OF TWO ELECTRODES IS REQUIRED AT ALL BUILDINGS OR STRUCTURES UNLESS SINGLE ELECTRODE HAS MEASURED RESISTANCE TO EARTH OF 25 OHMS OR LESS. CONTRACTOR SHALL PROVIDE ELECTRODES AS NEEDED TO COMPLY WITH NEC ARTICLE 250.
3. WHERE MULTIPLE RODS ARE USED AS ELECTRODES THEY SHALL BE SPACED A MINIMUM OF 6' APART. GROUND CLAMPS SHALL BE
BELOW GRADE AS SHOWN OR ABOVE GRADE WITH APPROVED PROTECTIVE COVERING.
4. ALL GROUNDING CONNECTORS USED SHALL BE INSTALLED IN ACCESSIBLE LOCATIONS AND LISTED FOR SUCH USE AS GROUNDING CONNECTOR. THE ELECTRICAL CONTRACTOR SHALL ENSURE MATERIALS ARE COMPATIBLE TO AVOID CORROSION AT CONNECTIONS.
5. ALL BONDING JUMPERS AND GROUNDING ELECTRODE CONDUCTOR SHALL BE SECURELY FASTENED TO STRUCTURE AND PROTECTED FROM PHYSICAL DAMAGE PER NEC REQUIREMENTS. WHERE INSTALLED IN METALLIC CONDUIT OR RACEWAY, PROVIDE EQUAL SIZED BONDING JUMPER BETWEEN RACEWAY AND GROUNDING JUMPER OR ELECTRODE, USING LISTED CLAMPS AND FITTINGS.
GROUNDING ELECTRODE SYSTEM
NO SCALE
MIN. 5/8" DIA. X 8' GROUND ROD OF
STAINLESS OR GALV. STEEL OR
COPPER.
BUILDING STEEL
STRUCTURE
COPPER GROUNDING ELECTRODE CONDUCTOR TO GROUND
BUS OR LUGS AT MAIN SERVICE SWITCH OR PANELBOARD
FLOOR
CLAMP SUITABLE FOR
DIRECT BURIAL
ALL BONDING JUMPERS SHOWN SHALL
BE COPPER AND SIZED EQUAL TO THE
GROUNDING ELECTRODE CONDUCTOR
SHOWN
5' M
AX
E7
TYPICAL RACK STAND DETAILS
SCALE: 1/4"=1'-0"E7
FACTORY
MOUNTING
FEET
AUX
GUTTER
SMALLER MOTOR
DISCONNECTS
INCOMING
FEEDER CIRCUITS
LARGER MOTOR
DISCONNECTS
12x12 JBOX FOR LV
CONTROL WIRING
TO MOTORSCONCRETE
FLOOR
UNISTRUT STAND
NOTES
1. DIAGRAM ABOVE IS GENERAL ARRANGEMENT AS A GUIDE ONLY. CUSTOM
FABRICATE EACH RACK STAND BASED ON THE SWITCH REQUIREMENTS AT EACH
LOCATION. USE DIAGRAM ABOVE AS A GUIDE TO LAYING OUT RACK STANDS AT
ALL LOCATIONS.
2. ROUTE INCOMING FEEDER CIRCUITS AND LV CONTROL CIRCUITS OVERHEAD AS
SHOWN. COORDINATE WITH OWNER TO VERIFY MIN. HEIGHT OF OVERHEAD
CONDUITS. VERIFY FINAL SWITCH RACK LOCATIONS WITH OWNER PRIOR TO
ROUGH-IN OF FEEDER CONDUITS.
3. COORDINATE WITH OWNER ON REQUIRED SIZE OF LV CONTROL WIRING JBOX TO
BE LOCATED AT ALL RACK STANDS. BOX SHOWN ABOVE IS PRELIMINARY SIZE
ONLY.
4. FABRICATE ALL UNISTRUT STANDS USING FACTORY FITTINGS AND ACCESSORIES,
AND SECURELY FASTEN TO FINISHED FLOOR WITH MOUNTING FEET AS SHOWN.
PROVIDE ALL ADDITIONAL SUPPORTS AND BRACES AS NEEDED FOR STURDY
INSTALLATION OF ALL SWITCHES AND CONNECTING CONDUITS.
5. PROVIDE UNISTRUT SUPPORT STANDS AND BRACING AS REQUIRED, SPACED
MAX. 4' APART, TO ROUTE FEEDER CONDUITS FROM RACK STANDS TO MOTOR
CONNECTIONS AT PRODUCTION EQUIPMENT.
6. SIZE ALL AUX. GUTTERS BASED ON NUMBER OF CONDUCTORS TO BE ENCLOSED,
PER NEC REQUIREMENTS.
LV WIRING TO
CONTROLS
NOTES:
1. DIAGRAM SHOWN ABOVE IS GENERAL ARRANGEMENT ONLY. PHASE CONDUCTORS NOT
SHOWN FOR CLARITY.
2. SEE RISER DIAGRAM FOR EQUIPMENT GROUNDING CONDUCTOR SIZE.
3. SEE RISER DIAGRAM FOR GROUNDING ELECTRODE CONDUCTOR SIZE.
4. SEE NEC TABLE 250.102(C)(1) FOR MIN. BONDING JUMPER SIZES REQD.
TRANSFORMER GROUNDING DETAILS
NO SCALE
NEUTRAL CONDUCTOR, ROUT WITH
PHASE CONDUCTORS
TRANSFORMER GROUNDED
TERMINAL CONNECTION
SYSTEM BONDING
JUMPER
TRANSFORMER GROUND
BUS OR LUGS, BONDED
TO ENCLOSURE
GROUNDING ELECTRODE CONDUCTOR
TO GROUNDING SYSTEM, SEE RISER
DIAGRAM
X0 N
G G
TRANSFORMER
G
EQUIP. GROUNDING CONDUCTOR
FROM PRIMARY FEEDER, SEE RISER
DIAGRAM
E7
HV1
GN
NEW SERVICE
DISTRIBUTION
PANEL
SERVICE GROUNDING DETAIL
NO SCALEE7
GROUNDING ELECTRODE
CONDUCTOR TO GROUNDING
ELECTRODE SYSTEM, INCLUDING
GROUND ROD(S), BUILDING STEEL
FRAME, BURIED METAL WATER PIPE,
ETC.
G
N
KEEP ISOLATED TO
ALL SUBPANELS
NOTES:
1. DIAGRAM ABOVE IS GENERAL ARRANGEMENT ONLY. PHASE CONDUCTORS NOT SHOWN
FOR CLARITY.
2. SEE RISER DIAGRAM FOR NEUTRAL AND GROUND CONDUCTOR SIZES NOT SHOWN
ABOVE.
3. GROUNDING SHOWN IS TYPICAL FOR ALL SUB-PANELS NOT SHOWN FOR CLARITY.
4. ALL EQUIPMENT GROUNDS IN NEW SYSTEM SHALL BE ISOLATED FROM NEUTRAL
CONDUCTORS AS SHOWN.
N
GROUNDED CONDUCTOR
FROM UTILITY SERVICE
DROP
MIN. 20' OF #3/0 COPPER WIRE GROUND RING
AROUND BUILDING PERIMETER, IN DIRECT
CONTACT WITH THE EARTH, MIN. 30" BELOW
FINISHED GRADE.
UNISTRUT FRAME
' M
IN
AutoCAD SHX Text
JOB NO.:
AutoCAD SHX Text
REVISIONS :
AutoCAD SHX Text
SHEET :
AutoCAD SHX Text
OF :
AutoCAD SHX Text
SCALE :
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 5/13/26
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
WB-112
AutoCAD SHX Text
ELECTRICAL SCHEDULES
AutoCAD SHX Text
AND NOTES
AutoCAD SHX Text