1-ELECT SET-TIRE SHREDDER.pdf

PDF 12 MB Posted

Attached to
Electriician Services for New Service and MCC Installation
Solicitation number
ITB 26-011
Issued by
Schleicher County, Texas

About this file

This is an electrical specifications and design document for a tire shredder facility located at 7 County Road 201, Pecos, Texas 79772, prepared for Reeves County. The project encompasses a complete electrical infrastructure installation including a new service connection, motor control centers (MCCs), wiring systems, receptacles, light fixtures, and associated electrical equipment. The scope of work requires installation of high-voltage service distribution panels rated at 2000 amperes at 277/480 volts, a 45-kilowatt step-down transformer, five vendor-furnished motor control centers with ratings of 300 to 400 amperes, underground and overhead electrical conduit systems, high-bay LED lighting fixtures with automatic controls, weatherproof receptacles, and a comprehensive grounding electrode system including ground rods and a copper ground ring around the building perimeter. The contractor must comply with all locally adopted building codes, the National Electric Code (NEC), and requirements of the Authority Having Jurisdiction (AHJ). The project requires pre-construction submittals of manufacturer specifications and shop drawings for approval, performance of commissioning work including testing and startup of all lighting and electrical systems, creation of equipment labels and index cards for all panelboards, and provision of operations and maintenance documentation in a minimum of two binders. The contractor shall provide a minimum one-year warranty on all labor and materials and conduct at least two hours of on-site training for the owner's operational staff upon project completion.

The specifications require all contractors to obtain necessary permits and licenses from the AHJ and pay all permitting fees and utility connection charges. All equipment and materials must be new, commercially-grade merchandise manufactured to comply with the basis of design and free of defects, with a minimum one-year factory warranty. Electrical conductors shall be copper wire with 90-degree Fahrenheit rated insulation, though aluminum conductors may be substituted for sizes number 6 and above with suitable terminal lugs. Specific equipment manufacturers are identified as the basis of design, including Eaton panelboards, Square D disconnect switches, Intermatic lighting controls, and Hubbell receptacles, with equal products acceptable upon approval through the commissioning process. The contractor is responsible for all materials management including delivery, storage, and rigging of equipment, daily and final jobsite cleanup, and immediate notification to the engineer if any site conditions prohibit or negatively impact system installation or performance. Any defective equipment or work found out of compliance with the basis of design or applicable codes must be replaced at no additional cost to the owner.

View the file

Other files

File Type Posted
2-26-011 Electrician Services.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TI

R

E

SH

R

ED

D

ER

F

AC

IL

IT

Y R

EE

VE

S C

O U

N

TY

, T

EX

AS

C O

. R D

. 2

, P

EC

O S, T X

TEXAS FIRM

REGISTRATION:

#F-26227

E8

ELECTRICAL LEGENDS:

ELECTRICAL ABBREVIATIONS:

ELECTRICAL PANELBOARD, LABEL SHOWN

LIGHT SWITCH AT 48" ABOVE FINISHED FLOOR

JUNCTION BOX

WP

ELECTRICAL METER

ELECTRICAL GROUND CONNECTION

DISCONNECT SWITCH, FUSED OR NON-FUSED, SEE SCHEDULES.2

UE

E

S

P1 1,3,5

P1 26,28

P1

A - AMPERES CURRENT

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AFI - ARC FAULT INTERRUPTING

AHJ - AUTHORITY HAVING JURISDICTION

ARCH - ARCHITECTURAL

BFF - BELOW FINISHED FLOOR

BFG - BELOW FINISHED GRADE

BOP - BOTTOM OF PIPE ABOVE FINISHED FLOOR OR GRADE

BTM - BOTTOM

BTU - BRITISH THERMAL UNIT

CB - CIRCUIT BREAKER

CONC - CONCRETE

CU - COPPER

DET - DETAIL

DIA - DIAMETER

DN - DOWN

ENGR - ENGINEER OR ENGINEERING

EXIST - EXISTING

FC - FOOTCANDLES, ILLUMINANCE LEVEL

FT - FEET

GFI - GROUND FAULT INTERRUPTING

GND - GROUND

HZ - HERTZ

IE - INVERT ELEVATION, BELOW FINISHED FLOOR LEVEL

IECC - INTERNATIONAL ENERGY CONSERVATION CODE

IG - ISOLATED GROUND

IN - INCHES

JBX - JUNCTION BOX

KW - KILOWATT

KVA - KILOVOLT AMPS

LBS - POUNDS

MAX - MAXIMUM

MCA - MINIMUM CIRCUIT AMPACITY

MCB - MAIN CIRCUIT BREAKER

MFG - MANUFACTURER

MIN - MINIMUM

MLO - MAIN LUGS ONLY

MOCP - MAXIMUM OVERCURRENT PROTECTION

NA - NOT APPLICABLE

NEC - NATIONAL ELECTRIC CODE

NEMA - NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION

NO - NUMBER

NFDS - NON-FUSED DISCONNECT SWITCH

OE - OVERHEAD ELECTRICAL

O&M - OPERATIONS & MAINTENANCE

P - POLE

PH - PHASE

PLCS - PLACES

SCA - SHORT CIRCUIT CURRENT AVAILABLE

TYP - TYPICAL

V - VOLTS

W - WIRE

WP - WEATHERPROOF

XFMR - TRANSFORMER

YR - YEAR

HOMERUN, 120V/1P/20A CIRCUIT WITH 2 #12 AND #12 GND IN

1/2" CONDUIT, PANEL AND CIRCUIT NUMBER SHOWN.

HOMERUN, 208V/2P CIRCUIT HOME RUN WITH 2 HOTS AND GND,

PANEL AND CIRCUIT NO'S SHOWN.

HOMERUN, 208V/3P CIRCUIT HOME RUN WITH 3 HOTS AND GND,

PANEL AND CIRCUIT NO'S SHOWN.

ELECTRICAL CONDUIT AND WIRE OR CABLES IN WALLS OR ABOVE

CEILINGS

ELECTRICAL CONDUIT AND WIRE UNDERGROUND OR BELOW

FLOOR WITH POWER CIRCUIT, SEE SCHEDULES.

DUPLEX RECEPTACLE, GFI TYPE IN WEATHERPROOF BOX WITH

COVER, MIN. 24" ABOVE GRADE.

OUTDOOR LIGHTING TIMER, SEE SPECS AND LIGHTING CONTROL DETAILS.OT

P PHOTOCELL SWITCH FOR OUTDOOR LIGHTING CONTROL, SEE DETAILS.

ELECTRICAL COMMISSIONING PLANS:

A. PURPOSE: THIS COMMISSIONING PLAN IS REQUIRED FOR PERFORMANCE VERIFICATIONS AND QUALITY

CONTROL. FAILURE TO IMPLEMENT THIS PLAN MAY RESULT IN POOR PERFORMANCE AND QUALITY. THE

DRAWINGS AND SPECIFICATIONS ARE TO BE USED AS THE BASIS OF ALL EVALUATIONS.

B. RESPONSIBILITIES:

1. OWNER/GENERAL CONTRACTOR (GC):

a. IMPLEMENT THE COMMISSIONING PLAN AS PROVIDED

b. REVIEW AND APPROVE ALL SUBMITTALS, TESTING AND WORK DESCRIBED BELOW.

c. MAINTAIN RECORDS OF ALL COMMISSIONING WORK AND FINAL APPROVALS

d. PROVIDE ENGINEER WITH COPY OF RECORDS AS NEEDED

2. MEP CONTRACTOR:

a. COORDINATE, REVIEW AND APPROVE ALL VENDOR EQUIPMENT SUBMITTALS.

b. OBTAIN GC APPROVAL OF ALL SUBMITTALS PRIOR TO ORDERING.

c. PERFORM ALL COMMISSIONING WORK LISTED BELOW.

d. OBTAIN GC APPROVAL OF ALL STARTUP AND TESTING OF MEP SYSTEMS AND EQUIPMENT

e. MAINTAIN AND PROVIDE ALL OPERATIONS AND MAINTENANCE MATERIALS.

f. PROVIDE OWNER TRAINING ON NEW SYSTEMS INSTALLED

C. SUBMITTALS: PRE-CONSTRUCTION SUBMITTALS SHALL INCLUDE MANUFACTURER'S SPECIFICATIONS, SHOP DRAWINGS AND INSTALLATION MANUALS. PROVIDE SUBMITTALS FOR GC AND ARCHITECT

APPROVAL PRIOR TO ORDERING THE FOLLOWING MAJOR COMPONENTS.

1. ELECTRICAL:

a. ELECTRICAL DISTRIBUTION EQUIPMENT

b. LIGHT FIXTURES AND ACCESSORIES

c. AUTOMATIC LIGHTING CONTROLS

D. LIGHTING EQUIPMENT STARTUP: CONTRACTOR SHALL PERFORM THE FOLLOWING:

1. TEST ALL OUTDOOR LIGHTING CONTROLS AFTER INSTALLATION. PROVIDE NAME AND SIGNATURE OF PERSON(S) COMPLETING THE TESTING, DATE PERFORMED, INITIAL AND FINAL SETTINGS OF CONTROLS

ADJUSTMENTS AND THE RESULTING OPERATIONAL PERFORMANCE.

2. ENSURE LIGHT FIXTURES ARE INSTALLED AND OPERATIONAL

3. VERIFY OPERATION OF LIGHTING TIME CLOCKS. ADJUST SETPOINTS ON TIME CLOCK TO ENABLE

OUTDOOR LIGHTING CIRCUIT INDEPENDENT OF SEASONAL CHANGES. PERFORM ALL TESTING PER

MANUFACTURER'S INSTRUCTIONS.

E. ELECTRICAL SYSTEM STARTUP:

1. VERIFY THAT LABELS HAVE BEEN PROPERLY CREATED AND PERMANENTLY ATTACHED TO ALL

PANELBOARDS AND DISCONNECT SWITCHES, AS SHOWN ON DRAWINGS AND SPECIFICATIONS.

2. VERIFY THAT INDEX CARD HAS BEEN PROPERLY FILLED OUT WITH TYPE WRITTEN DESCRIPTION FOR

EACH CIRCUIT INSTALLED IN ALL NEW PANELBOARDS. VERIFY THAT COMPLETED INDEX CARDS ARE

PROPERLY ATTACHED TO EACH PANELBOARD.

F. O&M DOCUMENTATION: MEP CONTRACTOR SHALL PROVIDE A MINIMUM OF 2 SETS OF OPERATIONS AND MAINTENANCE (O&M) BINDERS FOR THE PROJECT. EACH BINDER SHOULD INCLUDE ALL O&M MANUALS, WARRANTIES, STARTUP AND TESTING SHEETS, CONTROL DIAGRAMS AND SETPOINTS FOR THE

FOLLOWING ITEMS:

1. ALL NEW LIGHTING AND CONTROLS, INCLUDING EMERGENCY LIGHTING

G. TRAINING: CONTRACTOR SHALL PROVIDE A MINIMUM OF 2 HOURS ON-SITE TRAINING FOR OWNER'S OPERATIONAL STAFF UPON COMPLETION OF ALL WORK. TRAINING SHALL COVER OPERATIONS AND

MAINTENANCE ON ALL NEW MEP SYSTEMS INCLUDING:

1. LIGHTING AND ELECTRICAL SYSTEMS AND EQUIPMENT

DISC. NO.

SCHEDULED

GENERAL NOTES FOR ELECTRICAL CONTRACTORS:

A. INCIDENTAL WORK:

1. CUTTING AND PATCHING: WHERE CUTTING AND PATCHING ARE REQUIRED TO INSTALL MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS, CONTRACTORS SHALL PROVIDE AS NEEDED. AFTER INSTALLATION, PATCH ALL OPENINGS TO MATCH ADJACENT FINISHED SURFACES. FINISHED PAINTING TO BE PROVIDED BY

OTHERS.

B. EXCAVATIONS:

1. PERFORM EXCAVATIONS CAUTIOUSLY TO AVOID DISRUPTION OR DAMAGE TO UNDERGROUND UTILITIES. HAVE ALL UNDERGROUND UTILITIES LOCATED AND MARKED, PRIOR TO DIGGING. UTILIZE HAND DIGGING WHEN

NEAR BURIED PIPING, CABLES, GAS LINES, ETC.

2. COMBINE UNDERGROUND PIPING AND ELECTRICAL CONDUITS INTO COMMON TRENCHES WHERE POSSIBLE TO MINIMIZE TRENCHING. TRENCH ROUTING SHOWN ON PLANS IS PRELIMINARY ONLY. SEE CIVIL ENGR. PLANS

FOR OUTDOOR ROUTING AND UTILITY CONNECTION DETAILS.

C. ENGINEERING DRAWINGS:

1. SCHEMATIC DRAWINGS: ALL ENGINEERING PLANS AND DETAILS ARE GENERALLY SCHEMATIC IN NATURE. ONLY ITEMS WITH SPECIFIC LOCATIONS AND OR SIZES WILL BE DIMENSIONED. CONTRACTORS ARE RESPONSIBLE FOR COORDINATING FINAL LOCATIONS OF ALL NEW EQUIPMENT. COORDINATE WITH ARCHITECTURAL AND

STRUCTURAL DRAWINGS.

2. ADDED DETAILS: DRAWINGS DO NOT SHOW EVERY DETAIL OR ITEM REQUIRED FOR EQUIPMENT INSTALLATIONS. CONTRACTORS SHALL PROVIDE ALL REQUIRED INSTALLATION WORK AND ACCESSORIES AS

SPECIFIED BY EQUIPMENT MFG'S INSTRUCTIONS.

3. OFFSETS AND ADJUSTMENTS: CONTRACTORS SHALL PROVIDE ALL REQUIRED OFFSETS AND ADJUSTMENTS TO DUCTWORK, CONDUIT AND PIPING SHOWN ON DRAWINGS AS NEEDED TO AVOID INTERFERENCES WITH BUILDING STRUCTURE AND OR OTHER TRADES. ALL FINAL COORDINATION AND DETAILING OF DUCTWORK AND

PIPING SHALL BE PROVIDED BY CONTRACTORS.

4. EQUIPMENT SELECTION: THE CONTRACTOR AND SUPPLIER ARE RESPONSIBLE FOR THE FINAL SELECTION OF ALL EQUIPMENT, BASED ON THE PERFORMANCE AND FEATURES SCHEDULED ON THE DRAWINGS. MODEL NO'S SHOWN ON SCHEDULES ARE BASIS OF DESIGN ONLY AND SHALL BE CONFIRMED BY VENDOR THROUGH PRE-CONSTRUCTION SUBMITTALS. PERFORMANCE AND FEATURE DATA SHOWN SHALL BE EQUIVALENT FOR

ALL SUBSTITUTIONS WHERE ALLOWED.

5. EQUIPMENT WEIGHTS: UTILIZE FINAL EQUIPMENT SUBMITTALS FROM SUPPLIER FOR ALL STRUCTURAL SUPPORT DESIGN. INCLUDE CURB WEIGHTS FOR ALL ROOFTOP MOUNTED EQUIPMENT. WEIGHTS SHOWN ON

SCHEDULES ARE PRELIMINARY ONLY.

D. COORDINATION WITH OWNER:

1. ELECTRICAL SHALL COORDINATE WITH OWNER TO VERIFY:

a. FINAL LOCATION AND MOUNTING HEIGHT OF ALL LIGHT FIXTURES, WALL MOUNTED RECEPTACLES AND

LIGHTING CONTROLS.

b. VENDOR INSTALLATION DATA AND FINAL LOCATIONS FOR ALL OWNER FURNISHED EQUIPMENT REQUIRING

POWER CONNECTIONS, INCLUDING TIRE SHREDDER EQUIPMENT.

c. PANEL AND EQUIPMENT IDENTIFICATION MARKS PRIOR TO ORDERING PERMANENT LABELS. ALL MARKS

SHOWN ON PLANS ARE PRELIMINARY.

E. COORDINATION BETWEEN TRADES:

1. ALL CONTRACTORS SHALL COORDINATE WITH ALL OTHER TRADES TO AVOID INTERFERENCES, PROPERLY SEQUENCE INSTALLATIONS, AND PROVIDE MANUFACTURER'S REQUIRED SERVICE CLEARANCES. WHERE

REQUIRED, CONTRACTOR SHALL MAKE THE REQUIRED ADJUSTMENTS.

2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH LOCAL UTILITY FINAL SPECIFICATIONS AND REQUIREMENTS FOR ALL NEW ELECTRICAL SERVICE EQUIPMENT SHOWN ON PLANS, INCLUDING METER BASE

AND DISCONNECT SWITCH OR SERVICE PANEL BOARD.

F. ELECTRICAL CONDUCTORS AND CABLES:

1. CONDUCTORS: ALL WIRES AND SIZES SHOWN ON PLANS ARE FOR COPPER WIRE WITH PROPER INSULATION, RATED FOR THE ACTUAL CONDITIONS OF THE INSTALLATION. ALUMINUM WIRE CAN BE SUBSTITUTED FOR CONDUCTORS SIZED #6 AND ABOVE. PROVIDE SUITABLE TERMINAL LUGS WHERE ALUMINUM WIRE IS USED.

2. CONDUCTOR SIZES: SEE ELECTRICAL PANEL SCHEDULES FOR ALL WIRE AND CONDUIT SIZES, NOT SHOWN ON PLANS FOR CLARITY. ALL ELECTRICAL CIRCUITS ON PLAN ARE IDENTIFIED AT HOMERUN BY PANEL AND CIRCUIT

NUMBERS.

G. ELECTRICAL CONDUITS AND SUPPORTS:

1. HOLD ALL CONDUITS TIGHT AGAINST STRUCTURE TO AVOID DAMAGE AND INTERFERENCE FROM OTHER TRADES. RUN ALL CONDUITS IN A NEAT AND WORKMAN LIKE MANNER PARALLEL TO BUILDING LINES.

2. PROVIDE ALL REQUIRED CONDUIT HANGERS AND SUPPORTS WITH PROPER SPACING PER CODE REQUIREMENTS.

GROUP PARALLEL RUNS OF CONDUIT TOGETHER ON COMMON HANGERS AND SUPPORTS TO MINIMIZE SPACE

WHEREVER POSSIBLE.

3. INSTALL A GALVANIZED IRON OR PVC SLEEVE FOR THE CONDUIT PASSING THROUGH CONCRETE OR MASONRY

CONSTRUCTION.

4. UTILIZE RIGID PVC CONDUIT FOR INSTALLING ELECTRICAL IN UNDERGROUND EXTERIOR LOCATIONS WHERE ALLOWED AND NOT SUBJECT TO DAMAGE. WHERE EXPOSED CONDUITS ARE RISING OUT OF EXCAVATION

TRENCH, PROVIDE SCHEDULE 80 PVC PIPE RISERS AND LONG-SWEEP ELBOWS IN TRENCH.

5. UTILIZE RIGID STEEL CONDUIT FOR INSTALLING ELECTRICAL CONDUCTORS IN ALL HIGH ABUSE AREAS INDOORS

AND OUTDOORS.

H. AUTOMATIC LIGHTING CONTROLS:

1. PROVIDE ALL REQUIRED OUTDOOR AREA LIGHTING CONTROLS, INCLUDING OUTDOOR LIGHTING TIMER AND PHOTOCELL SWITCH. SEE CONTROLS DETAILS. PROGRAM TIMER WITH ON/OFF TIMES FOR PROPER OPERATION

YEAR-ROUND, USING PHOTOCELL SWITCH AS FINAL SEASONAL ADJUSTMENT CONTROL.

2. INSTALL ALL LIGHTING CONTROLLERS IN ACCESSIBLE LOCATION ON WALL, ABOVE CEILING OR OTHER APPROVED LOCATION. WHEN ABOVE CEILING, PROVIDE PERMANENT MARKER FOR LOCATING CONTROLLER FROM THE

GROUND.

I. APPLIANCE AND EQUIPMENT CONNECTIONS:

1. WHERE REQUIRED FOR EQUIPMENT SERVICE CONNECTIONS, PROVIDE STEEL CHANNEL SUPPORT STANDS FOR MOUNTING OF UNIT DISCONNECT SWITCHES, STARTERS, SPEED CONTROLLERS AND CONDUITS. PROPERLY

SECURE SUPPORTS TO FLOORS OR WALLS.

2. ENSURE THAT SERVICE CLEARANCES ARE NOT BLOCKED BY ROUTING OF CONDUIT OR SUPPORT STRUCTURES AT ALL EQUIPMENT SERVICE CONNECTIONS. COORDINATE WITH EQUIPMENT CONTRACTOR TO DETERMINE

REQUIRED CLEARANCES AND SERVICE WORK AREAS.

J. ELECTRICAL SERVICES AND EQUIPMENT:

1. INSTALL ALL ELECTRICAL SERVICE EQUIPMENT AS REQUIRED BY LOCAL UTILITY SPECIFICATIONS. FIELD VERIFY FINAL LOCATION OF EQUIPMENT TO ENSURE PROPER CLEARANCES ARE AVAILABLE FOR FINAL ENCLOSURES TO BE INSTALLED. PROVIDE STEEL MOUNTING RACK WHERE REQUIRED TO HOLD ALL METERS, DISCONNECT

SWITCHES, BUSSED GUTTERS AND PANELS AS SHOWN.

AutoCAD SHX Text

JOB NO.:

AutoCAD SHX Text

REVISIONS :

AutoCAD SHX Text

SHEET :

AutoCAD SHX Text

OF :

AutoCAD SHX Text

SCALE :

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 5/13/26

AutoCAD SHX Text

SHOWN

AutoCAD SHX Text

WB-112

AutoCAD SHX Text

ELECTRICAL LEGENDS,

AutoCAD SHX Text

NOTES & COMMISSIONING

AutoCAD SHX Text

AutoCAD SHX Text

C.A.PIEPER

AutoCAD SHX Text J

E

SH

R

ED

D

ER

F

AC

IL

IT

Y R

EE

VE

S C

O U

N

TY

, T

EX

AS

C O

. R D

. 2

, P

EC

O S, T X

TEXAS FIRM

REGISTRATION:

#F-26227

E9

ELECTRICAL SPECIFICATIONS:

GENERAL CONDITIONS FOR MEP WORK:

A. CONTRACTOR QUALIFICATIONS:

1. CONTRACTORS SHALL STUDY CONTRACT DOCUMENTS, FULLY UNDERSTAND AND ACCEPT THE BASIS

OF DESIGN AND SCOPE OF WORK. SUBMISSION OF BID INDICATES CONTRACTOR'S COMPLETE

APPROVAL AND ACCEPTANCE OF CONSTRUCTION DOCUMENTS.

2. CONTRACTORS SHALL PROVIDE A MINIMUM 1 YR. WARRANTY ON ALL LABOR AND MATERIALS

INSTALLED. CONTRACTOR SHALL MAKE ALL WARRANTY REPAIRS OR REPLACEMENTS IN A TIMELY

MANNER, AT NO ADDITIONAL COST TO THE OWNER.

B. BASIS OF DESIGN:

1. ALL CONSTRUCTION DOCUMENTS PROVIDED BY OWNER, INCLUDING ENGINEERING DRAWINGS,

NOTES, SCHEDULES, DETAILS, CALCULATIONS AND SPECIFICATIONS PROVIDED, ALONG WITH

EQUIPMENT MANUFACTURER'S DRAWINGS AND SPECIFICATIONS, FORM THE 'BASIS OF DESIGN'.

2. THE BASIS OF DESIGN WILL BE USED FOR ALL INSPECTIONS, TESTING AND ACCEPTANCE OF THE WORK

PERFORMED BY THE CONTRACTOR TO VERIFY SUCCESSFUL COMPLETION OF SCOPE OF WORK.

C. SCOPE OF WORK:

1. INSTALL COMPLETE AND OPERABLE ELECTRICAL SYSTEMS AS DESCRIBED BY THE CONSTRUCTION DOCUMENTS. INCIDENTAL ITEMS NOT SPECIFIED, BUT WHICH ARE ESSENTIAL FOR THE PROPER OPERATION OF SPECIFIED SYSTEMS AND EQUIPMENT, ARE INCLUDED IN THE SCOPE OF WORK AND

SHALL BE PROVIDED BY CONTRACTOR AT NO ADDITIONAL COST.

2. COMPLY WITH COMMISSIONING PLAN SHOWN ON DRAWINGS TO VERIFY FINAL QUALITY AND

PERFORMANCE OF ALL WORK.

D. CODE COMPLIANCE: ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL LOCALLY ADOPTED BUILDING CODES AS LISTED ON THE DRAWINGS, AND ACCORDING TO THE LOCAL AUTHORITY HAVING

JURISDICTION (AHJ).

E. DISCREPANCIES:

1. IN THE CASE OF A DISCREPANCY BETWEEN DRAWINGS, SPECIFICATIONS OR MANUFACTURER'S REQUIREMENTS, THE MOST STRINGENT SHALL APPLY AND BE COMPLIED WITH BY THE CONTRACTOR.

2. IN THE CASE OF A DISCREPANCY BETWEEN BY CODES AND THE CONSTRUCTION DOCUMENTS OR MANUFACTURER'S REQUIREMENTS, THE AHJ SHALL DETERMINE WHICH SHOULD BE COMPLIED WITH

BY THE CONTRACTOR.

F. JOBSITE CONDITIONS: CONTRACTOR SHALL EXAMINE THE JOBSITE PRIOR TO BIDDING AND FULLY UNDERSTAND THE CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED. BY SUBMITTING BID

FOR WORK CONTRACTOR ACCEPTS ALL JOB CONDITIONS AS-IS.

G. PERMITS AND FEES: CONTRACTOR SHALL OBTAIN THE NECESSARY PERMITS, LICENSES, AND

CERTIFICATIONS REQUIRED BY THE AHJ AND PAY FOR ALL PERMITTING FEES.

H. UTILITY CONNECTIONS:

1. SEE CIVIL PLANS FOR CONTINUATION OF ELECTRICAL, WATER AND SEWER SERVICE CONNECTIONS

OUTSIDE OF BUILDING.

2. COORDINATE WITH LOCAL UTILITIES TO PROVIDE NEW SERVICES AS SHOWN ON PLANS. INSTALL ALL REQUIRED SERVICE CONNECTIONS PER UTILITY SPECIFICATIONS. PAY ALL UTILITY REQUIRED FEES FOR

SERVICE CONNECTIONS OR MODIFICATIONS SHOWN ON PLANS.

I. CONTRACTOR FURNISHED EQUIPMENT & MATERIALS: SHALL BE NEW, COMMERCIAL GRADE,

MANUFACTURED AND CERTIFIED TO COMPLY WITH THE BASIS OF DESIGN, FREE OF DEFECT, MINIMUM

1-YEAR FACTORY WARRANTY. ALL SUBSTITUTIONS MUST BE 'APPROVED' THROUGH THE

COMMISSIONING PROCESS TO BE ACCEPTABLE.

J. DELIVERY, STORAGE AND PROTECTION: CONTRACTOR SHALL INCLUDE ALL REQUIRED MATERIALS MANAGEMENT AS PART OF THE SCOPE OF WORK, INCLUDING DELIVERY, STORAGE AND RIGGING OF ALL

EQUIPMENT AND MATERIALS TO BE FURNISHED. DAMAGED ITEMS SHOULD BE IDENTIFIED AND

RETURNED TO THE FACTORY FOR REPLACEMENTS AT NO ADDITIONAL COST TO THE OWNER.

K. JOBSITE CLEANUP AND SAFETY: CONTRACTOR SHALL INCLUDE DAILY AND FINAL CLEANUP OF JOBSITE AS PART OF SCOPE OF WORK. CONTRACTOR SHALL COMPLY WITH ALL SAFETY REQUIREMENTS AS DIRECTED

BY OWNER AND AHJ.

L. CORRECTIONS REQUIRED:

1. IF CONTRACTOR IDENTIFIES ANY ACTUAL SITUATION OR SITE CONDITION THAT WILL PROHIBIT OR NEGATIVELY IMPACT THE INSTALLATION OR PERFORMANCE OF THE SYSTEMS AS DESIGNED, STOP ALL

WORK AND NOTIFY THE ENGINEER IMMEDIATELY.

2. ANY EQUIPMENT THAT IS FOUND TO BE DEFECTIVE, OR OUT OF COMPLIANCE WITH BASIS OF DESIGN OR CODE, CONTRACTOR SHALL REPLACE AT NO ADDITIONAL COST. ALL NEW WORK SHALL COMPLY

WITH THE BASIS OF DESIGN.

3. IF CONTRACTOR DAMAGES ADJACENT PROPERTY WHILE PERFORMING SCOPE OF WORK, HE SHALL

MAKE PROMPT REPAIR AT OWN EXPENSE, PRIOR TO COMPLETING PROJECT.

ELECTRICAL EQUIPMENT & MATERIALS

A. CONDUIT AND WIREWAYS:

1. EMT: HOT GALVANIZED STEEL, INTERIOR COATING, UL LISTED, AS MANUFACTURED BY ALLIED, E-Z PULL EMT, OR EQUAL. ALL FACTORY COUPLINGS AND FITTINGS SHALL BE OF SAME MATERIAL AS

CONDUIT.

2. RIGID STEEL: HOT DIPPED GALVANIZED STEEL, CORROSION RESISTANT, UL LISTED, AS MANUFACTURED BY ALLIED, GRC, OR EQUAL. ALL FACTORY COUPLINGS AND FITTINGS SHALL BE OF SAME MATERIAL AS

CONDUIT.

3. PVC: SCHEDULE 40 OR 80 ELECTRICAL CONDUIT, UL LISTED, SLIP BELL FITTING ON ONE END, AS

MANUFACTURED BY ALLIED OR EQUAL. SUNLIGHT RESISTANT WHERE USED EXPOSED OUTSIDE.

B. WIRE AND CABLE:

1. CONDUCTORS: PROVIDE COPPER CONDUCTORS OF STANDARD AMERICAN GAGES FOR ALL WIRING SHOWN ON DRAWINGS. MINIMUM 90°F RATED INSULATION FOR ALL CONDUCTORS USED, SUCH AS

THHN, THHW, THW OR EQUAL.

2. ALUMINUM CONDUCTORS OF EQUIVALENT AMPACITY CAN BE SUBSTITUTED FOR SIZES #6 AND

ABOVE.

3. MC CABLE: METAL CLAD CABLE WITH COPPER CONDUCTORS, RATED FOR WET OR DRY LOCATIONS, 90⁰C TEMPERATURE RATING, WITH GREEN INSULATED GROUNDING CONDUCTOR. ALL CONDUCTORS

CABLED TOGETHER WITH SEPARATOR TAPE, INTERLOCKED ALUMINUM ARMOR, FLAME RETARDANT

BLACK PVC JACKET OVER THE ARMOR.

4. SPLICE CONNECTORS: INSUL-TAP CONNECTORS, UV RATED, COPPER OR ALUMINUM RATED, AS

MANUFACTURED BY POLARIS, IT SERIES OR EQUAL.

C. BOXES AND ENCLOSURES:

1. JUNCTION BOXES: PROVIDE STEEL OR PVC, WEATHERPROOF BOXES AND GASKETED COVERS FOR ALL

CONTROLS WIRING CIRCUITS AT EQUIPMENT SWITCH RACK STANDS AS SHOWN ON PLANS.

D. RECEPTACLES AND COVER PLATES:

1. INDOORS:

a. DUPLEX RECEPTACLES: 120V, DUPLEX, 15A 125V, NEMA 5-15R, AS MANUFACTURED BY HUBBELL

MODEL #BR15I OR EQUAL.

b. GFI RECEPTACLES: 120V, DUPLEX, TEST BUTTON, LED INDICATOR LIGHT, 15A 125V, NEMA 5-15R, AS

MANUFACTURED BY HUBBELL MODEL #GF15IL OR EQUAL.

2. OUTDOORS:

a. GFI RECEPTACLES: 120V, WEATHER RESISTANT, DUPLEX, TEST BUTTON, LED INDICATOR LIGHT, 15A

125V, NEMA 5-15R, AS MANUFACTURED BY HUBBELL MODEL #GF15ILWR OR EQUAL. PROVIDE

WITH WEATHERPROOF, LOCKING COVER, EQUAL TO HUBBELL BELL #MX105OS.

E. WALL SWITCHES:

1. LIGHT SWITCH: 1P/15A/120V TOGGLE SWITCH, SINGLE GANG BOX MOUNTED, AS MANUFACTURED BY

LEVITON MODEL # 5501-LHW OR EQUAL.

F. LIGHT FIXTURES: AS SCHEDULED ON PLANS, OR APPROVED EQUAL.

G. AUTOMATIC LIGHTING CONTROLS:

1. LIGHTING TIMER: 24-HOUR ELECTRONIC TYPE, MIN. 2P/20A CONTACTS, 120V POWER SUPPLY, NEMA

1 ENCLOSURE, AS MANUFACTURED BY INTERMATIC #ET1125C OR EQUAL.

2. PHOTOCELL SWITCH: 1P/120V, 1800 W RATING, WEATHERPROOF, SLIDE ADJUSTMENT, DELAY

ACTION, AS MANUFACTURED BY INTERMATIC, MODEL # K4121C OR EQUAL.

H. PANELS, SWITCHGEAR & DISTRIBUTION EQUIPMENT

1. ELECTRICAL PANELS: AS MANUFACTURED BY EATON OR EQUAL. PROVIDE SUBMITTALS FROM

VENDOR PRIOR TO ORDERING PANELS AND BREAKERS. VERIFY PANELS MEET THE FAULT CURRENT

RMS VALUES AS SHOWN ON THE PLANS.

a. 1000A OR HIGHER, 480V: PROVIDE WITH GROUND-FAULT PROTECTION AS REQUIRED BY NEC.

2. CIRCUIT BREAKERS: AS SPECIFIED BY PANELBOARD MANUFACTURER. RATINGS AS SHOWN ON PLANS.

a. 1200A OR HIGHER: PROVIDE CIRCUIT BREAKER WITH FACTORY ENERGY-REDUCING SWITCHING OR

ACTIVE ARC FLASH MITIGATION SYSTEM.

3. TRANSFORMERS: SEE SCHEDULES FOR PERFORMANCE REQUIREMENTS, MAKE AND MODEL NO

REQUIRED, OR EQUAL.

a. DRY-TYPE: 600V OR LESS PRIMARY AND SECONDARY, 15 KVA THROUGH 750 KVA, CLASS 220

INSULATION, LOW LOSS TYPE, VENTILATED STEEL ENCLOSURE, AS SCHEDULED ON PLANS OR

EQUAL. PROVIDE ALL REQUIRED MOUNTING SUPPORTS FOR WALL INSTALLATIONS OR CONCRETE

HOUSEKEEPING PAD FOR GRADE MOUNTED INSTALLATIONS.

4. DISCONNECT SWITCHES: HEAVY DUTY SAFETY SWITCH AS MANUFACTUED BY SQUARE D, OR EQUAL.

PROVIDE NEMA 1 OR 3R ENCLOSURE AS REQUIRED. PROVIDE CLASS R, L OR J FUSES AND SPRING

REINFORCED PLATED COPPER FUSE CLIPS WHERE SPECIFIED.

5. ELECTRICAL CAUTION TAPE: 6" WIDE HEAVY-DUTY POLYETHYLENE TAPE, RED WITH BLACK LETTERS, "CAUTION, ELECTRIC LINE BELOW" TEXT, AS MANUFACTURED BY BRADY #91296 OR EQUAL.

6. EQUIPMENT LABELS: PROVIDE EQUIPMENT LABELS FOR ALL DISCONNECT SWITCHES, PANELBOARDS, MOTOR CONTROL CENTERS AND OTHER MARKED ENCLOSURES. LABELS SHALL BE PERMANENTLY

FASTENED TO EXTERIOR OF ENCLOSURE IN VISIBLE LOCATION AND SHALL MATCH EQUIPMENT

IDENTIFICATION MARKS SHOWN ON PLANS.

a. INTERIOR LABELS SHALL BE BLACK PLASTIC WITH WHITE LETTERS, MINIMUM ¾” HIGH.

b. EXTERIOR LABELS SHALL BE METALLIC, SUITABLE FOR EXTERIOR LOCATIONS WITH BLACK LETTERS

MINIMUM ¾” HIGH.

AutoCAD SHX Text

JOB NO.:

AutoCAD SHX Text

REVISIONS :

AutoCAD SHX Text

SHEET :

AutoCAD SHX Text

OF :

AutoCAD SHX Text

SCALE :

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 5/13/26

AutoCAD SHX Text

SHOWN

AutoCAD SHX Text

WB-112

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

SPECIFICATIONS

AutoCAD SHX Text

C.A. PIEPER

PARTIAL PLAN - ELECTRICAL

SCALE: 1/4"=1'-0"

KEYNOTES:#

1. PROVIDE BARE 3/0 CU BONDING JUMPER, WELDED TO STEEL COLUMN,

BONDED TO BARE #3/0 CU GROUND RING AROUND FOOTINGS. TYPICAL

ALL COLUMNS.

2. PROVIDE FIELD FABRICATED UNITSTRUT RACK STAND TO HOLD GROUP

OF DISCONNECT SWITCHES, SEE TYPICAL DETAIL FOR REQUIREMENTS.

COORDINATE WITH OWNER FOR FINAL LOCATIONS OF ALL RACK STANDS,

LOCATIONS SHOWN ARE PRELIMINARY ONLY.

3. PROVIDE BARE #3/0 CU GROUND RING AROUND BUILDING FOOTINGS.

BOND TO BUILDING GROUNDING ELECTRODE SYSTEM PER NEC. 250, SEE

DETAILS.

E1

TI

R

E

SH

R

ED

D

ER

F

AC

IL

IT

Y R

EE

VE

S C

O U

N

TY

, T

EX

AS

C O

. R D

. 2

, P

EC

O S, T X

TEXAS FIRM

REGISTRATION:

#F-26227

E1

KEY PLAN

WORK AREA

PAVILLION

8 40 41 42

2 35 739 3811 3736 45 9

11.F

11.E

11.A

11.B

24.B

24.A

36.C 36.B 36.A

35.A

35.B

51.B

51.A

10 64 17 80

60 59 43 12 58 16

66 67 65 68 69 70

26 77

50.A50.B 50.A50.B 50.A50.B

38.B 38.B

38.A

38.A

18 19 61 62

NOTES

1. COORDINATE WITH OWNER, FINAL RECEPTACLE LOCATIONS AND MOUNTING

HEIGHTS, PRIOR TO ROUGH-IN. LOCATIONS SHOWN ON PLANS ARE

PRELIMINARY.

2. COORDINATE WITH OWNER, FINAL LOCATION OF ALL DISCONNECT SWITCHES

AND MOUNTING STANDS. LOCATIONS SHOWN ABOVE ARE PRELIMINARY

ONLY.

3. GROUP MULTIPLE MOTOR FEEDERS INTO LARGER CONDUITS AND ROUTE

OVERHEAD FROM MCC IN OFFICE TO SWITCH RACK LOCATIONS SHOWN

ABOVE. VERIFY FINAL MOTOR FEEDER REQUIREMENTS WITH OWNER PRIOR

TO SIZING FEEDER CONDUITS. FEEDER CIRCUITS FROM MCC TO THE SWITCH

RACKS ARE NOT SHOWN ABOVE FOR CLARITY. SEE TYPICAL RACK STAND

DETAILS 3/E7.

WP

36" WP36" WP36" WP36" WP36"

LV1

WP

36"

LV1

WP 36"

WP

36" WP 36"

WP

36"

1 1 1 1 1

2 2

MCC1

MCC2

27 78 28 79

1 44

MCC4

MCC4

MCC4

MCC4

MCC4

MCC4

MCC4

MCC4

MCC415

MCC416

MCC4

MCC4

MCC4

MCC4

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5 40

MCC5

MCC5

MCC5

24D

MCC5

MCC4

MCC4

MCC4

MCC4

1 SEE 1/E2 FOR

CONTINUATION OF

GROUND RING

SEE 1/E2 FOR

CONTINUATION OF

GROUND RING

3 3

AutoCAD SHX Text

JOB NO.:

AutoCAD SHX Text

REVISIONS :

AutoCAD SHX Text

SHEET :

AutoCAD SHX Text

OF :

AutoCAD SHX Text

SCALE :

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 5/13/26

AutoCAD SHX Text

SHOWN

AutoCAD SHX Text

WB-112

AutoCAD SHX Text

ELECTRICAL PLANS

AutoCAD SHX Text

AND NOTES

AutoCAD SHX Text

NAME

PARTIAL PLAN - ELECTRICAL

SCALE: 1/4"=1'-0"

KEYNOTES:#

E2

TI

R

E

SH

R

ED

D

ER

F

AC

IL

IT

Y R

EE

VE

S C

O U

N

TY

, T

EX

AS

C O

. R D

. 2

, P

EC

O S, T X

TEXAS FIRM

REGISTRATION:

#F-26227

E2

32 31 30 34

5 29 4 3 33

2.B 2.A

2.C

33.A 33.B

34.A 34.B

34.A 34.B

49.A 49.B

48.A 48.B

48.A 48.B

49.A 49.B

49.A 49.B

71 74 72 75 73 76

WP36"

WP 36"

WP36"

WP 36"

WP36"

WP 36"

1. PROVIDE BARE 3/0 CU BONDING JUMPER, WELDED TO STEEL COLUMN,

BONDED TO BARE #3/0 CU GROUND RING AROUND FOOTINGS. TYPICAL

ALL COLUMNS.

2. PROVIDE FIELD FABRICATED UNITSTRUT RACK STAND TO HOLD GROUP

OF DISCONNECT SWITCHES, SEE TYPICAL DETAIL FOR REQUIREMENTS.

COORDINATE WITH OWNER FOR FINAL LOCATIONS OF ALL RACK STANDS,

LOCATIONS SHOWN ARE PRELIMINARY ONLY.

3. NEW UNDERGROUND ELECTRICAL SERVICE LATERAL BY LOCAL UTILITY

CO. COORDINATE REQUIREMENTS WITH UTILITY. SEE RISER DIAGRAM.

SEE CIVIL PLANS FOR CONTINUATION.

4. HIGH-VOLTAGE SERVICE PANEL, PROVIDE NEMA 3R ENCLOSURE AND

MIN. 3” CONCRETE HOUSEKEEPING PAD FOR BASE MOUNTING.

5. STEPDOWN TRANSFORMER, PAD MOUNTED, PROVIDE MIN. 3”

CONCRETE HOUSEKEEPING PAD FOR BASE MOUNTING.

6. LOW-VOLTAGE BRANCH PANEL, MOUNTED TO CONNEX BUILDING.

7. MOTOR CONTROL CENTER BY EQUIPMENT VENDOR, COORDINATE FINAL

INSTALLATION AND CONNECTION REQUIREMENTS WITH EQUIP VENDOR,

PRIOR TO ROUGH-IN, TYPICAL 5 PLACES.

8. OVERHEAD FEEDER FROM SERVICE PANEL TO MOTOR CONTROL CENTER,

TYPICAL 5 PLACES. HOLD CONDUIT TIGHT TO STRUCTURE ABOVE. SEE

RISER DIAGRAM FOR CONDUIT AND WIRE SIZES

9. PROVIDE BARE #3/0 CU GROUND RING AROUND BUILDING FOOTINGS.

BOND TO BUILDING GROUNDING ELECTRODE SYSTEM PER NEC. 250, SEE

DETAILS.

1 1 1

MCC3

MCC3

MCC4

MCC4

MCC4

MCC4

MCC4

MCC4

MCC4

MCC4

MCC4

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5

MCC5 47

MCC5

MCC5

MCC5

MCC5

OFFICE

MCC1 MCC2 MCC3 MCC4 MCC5

HV1

LV1

T1

UE

FROM UTILITY

TRANSFORMER

CONNEX BUILDING

BY OWNER

7 7 7 7 7

3" C.

3" C.

4" C.

4" C.

4" C.

8 8

WP

36"

LV1

MCC4

MCC4

MCC4

SEE 1/E1 FOR

CONTINUATION OF

GROUND RING

SEE 1/E1 FOR

CONTINUATION OF

CIRCUIT

SEE 1/E1 FOR

CONTINUATION OF

CIRCUIT

SEE 1/E1 FOR

CONTINUATION OF

GROUND RING

9 9

NOTES

1. COORDINATE WITH OWNER, FINAL RECEPTACLE LOCATIONS AND MOUNTING

HEIGHTS, PRIOR TO ROUGH-IN. LOCATIONS SHOWN ON PLANS ARE

PRELIMINARY.

2. COORDINATE WITH OWNER, FINAL LOCATION OF ALL DISCONNECT SWITCHES

AND MOUNTING STANDS. LOCATIONS SHOWN ABOVE ARE PRELIMINARY

ONLY.

3. GROUP MULTIPLE MOTOR FEEDERS INTO LARGER CONDUITS AND ROUTE

OVERHEAD FROM MCC IN OFFICE TO SWITCH RACK LOCATIONS SHOWN

ABOVE. VERIFY FINAL MOTOR FEEDER REQUIREMENTS WITH OWNER PRIOR

TO SIZING FEEDER CONDUITS. FEEDER CIRCUITS FROM MCC TO THE SWITCH

RACKS ARE NOT SHOWN ABOVE FOR CLARITY. SEE TYPICAL RACK STAND

DETAILS 3/E7.

4. COORDINATE FINAL DIMENSIONS, LOCATION AND POWER REQUIREMENTS

FOR OFFICE STRUCTURE WITH OWNER, PRIOR TO STARING WORK. OFFICE

AND MCC INSTRALLATION SHOWN ABOVE IS PRELIMINARY ONLY.

AutoCAD SHX Text

JOB NO.:

AutoCAD SHX Text

REVISIONS :

AutoCAD SHX Text

SHEET :

AutoCAD SHX Text

OF :

AutoCAD SHX Text

SCALE :

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 5/13/26

AutoCAD SHX Text

SHOWN

AutoCAD SHX Text

WB-112

AutoCAD SHX Text

ELECTRICAL PLANS

AutoCAD SHX Text

AND NOTES

AutoCAD SHX Text

PARTIAL PLAN - LIGHTING

SCALE: 1/4"=1'-0"E3

KEYNOTES:#

1. HIGH-BAY LED LIGHT FIXTURE, TYPICAL. COORDINATE FINAL MOUNTING

HEIGHT WITH OWNER PRIOR TO ROUGH-IN.

TI

R

E

SH

R

ED

D

ER

F

AC

IL

IT

Y R

EE

VE

S C

O U

N

TY

, T

EX

AS

C O

. R D

. 2

, P

EC

O S, T X

TEXAS FIRM

REGISTRATION:

#F-26227

E3NOTES:

1. COORDINATE WITH OWNER, FINAL MOUNTING HEIGHT FOR ALL PENDANT

MOUNTED LIGHT FIXTURES, PRIOR TO INSTALLATION. HEIGHTS SHOWN ON

SCHEDULE ARE PRELIMINARY ONLY.

2. COORDINATE WITH OWNER, ALL LIGHT SWITCH LOCATIONS PRIOR TO

ROUGH-IN. LOCATIONS SHOWN ARE PRELIMINARY ONLY. KEY PLAN

S WP

HB1 HB1 HB1 HB1

HB1

HB1

HB1 HB1 HB1

HB1 HB1 HB1

LV1

S WP

LV1

WP

WP

WP WP WP

WPWPWP

SEE 1/E2 FOR

CONTINUATION

SEE 1/E2 FOR

CONTINUATION

AutoCAD SHX Text

JOB NO.:

AutoCAD SHX Text

REVISIONS :

AutoCAD SHX Text

SHEET :

AutoCAD SHX Text

OF :

AutoCAD SHX Text

SCALE :

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 5/13/26

AutoCAD SHX Text

SHOWN

AutoCAD SHX Text

WB-112

AutoCAD SHX Text

LIGHTING PLANS

AutoCAD SHX Text

AND NOTES

AutoCAD SHX Text

PARTIAL PLAN - LIGHTING

SCALE: 1/4"=1'-0"E4

KEYNOTES:#

TI

R

E

SH

R

ED

D

ER

F

AC

IL

IT

Y R

EE

VE

S C

O U

N

TY

, T

EX

AS

C O

. R D

. 2

, P

EC

O S, T X

TEXAS FIRM

REGISTRATION:

#F-26227

E4

NOTES:

1. COORDINATE WITH OWNER, FINAL MOUNTING HEIGHT FOR ALL PENDANT

MOUNTED LIGHT FIXTURES, PRIOR TO INSTALLATION. HEIGHTS SHOWN ON

SCHEDULE ARE PRELIMINARY ONLY.

2. COORDINATE WITH OWNER, ALL LIGHT SWITCH LOCATIONS PRIOR TO

ROUGH-IN. LOCATIONS SHOWN ARE PRELIMINARY ONLY.

HB1

HB1

HB1

HB1

HB1

HB1

HB1

HB1 HB1

HB1

S

WP

SEE 1/E3 FOR

CONTINATION

LV1

1. HIGH-BAY LED LIGHT FIXTURE, TYPICAL. COORDINATE FINAL MOUNTING

HEIGHT WITH OWNER PRIOR TO ROUGH-IN.

2. OUTDOOR LIGHTING TIMER, INSTALLED IN ACCESSIBLE LOCATION FOR

ADJUSTMENT, COORDINATE FINAL LOCATION WITH OWNER PRIOR TO

ROUGH-IN. SEE DETAILS FOR WIRING.

3. PROVIDE PHOTOCELL SWITCH FOR OUTDOOR LIGHTING CONTROLS,

INSTALLED IN ACCESSIBLE LOCATION FOR SERVICE AND ADJUSTMENT.

ENSURE CLEAR VIEW OF AMBIENT LIGHTING AT LOCATION INSTALLED.

SEE 1/E2 FOR

CONTINUATION

SEE 1/E3 FOR

CONTINUATION

HV1

LV1

T1

LV1

OT

P

WP

WPWP

WP

WP

OFFICE

LIGHTING THIS

AREA BY OWNER

AutoCAD SHX Text

JOB NO.:

AutoCAD SHX Text

REVISIONS :

AutoCAD SHX Text

SHEET :

AutoCAD SHX Text

OF :

AutoCAD SHX Text

SCALE :

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 5/13/26

AutoCAD SHX Text

SHOWN

AutoCAD SHX Text

WB-112

AutoCAD SHX Text

LIGHTING PLANS

AutoCAD SHX Text

AND NOTES

AutoCAD SHX Text

E

SH

R

ED

D

ER

F

AC

IL

IT

Y R

EE

VE

S C

O U

N

TY

, T

EX

AS

C O

. R D

. 2

, P

EC

O S, T X

TEXAS FIRM

REGISTRATION:

#F-26227

E5

NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY. NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY.

NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY.NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY.

NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO STARTING WORK. CIRCUITS SHOWN ABOVE ARE PRELIMINARY ONLY.

AutoCAD SHX Text

JOB NO.:

AutoCAD SHX Text

REVISIONS :

AutoCAD SHX Text

SHEET :

AutoCAD SHX Text

OF :

AutoCAD SHX Text

SCALE :

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 5/13/26

AutoCAD SHX Text

SHOWN

AutoCAD SHX Text

WB-112

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

SCHEDULES

AutoCAD SHX Text

E

SH

R

ED

D

ER

F

AC

IL

IT

Y R

EE

VE

S C

O U

N

TY

, T

EX

AS

C O

. R D

. 2

, P

EC

O S, T X

TEXAS FIRM

REGISTRATION:

#F-26227

E6

NOTE: COORDINATE FINAL EQUIP IDENTIFICATION AND CIRCUIT REQUIREMENTS WITH EQUIP MFG, PRIOR TO

STARTING WORK. SWITCHES SHOWN ABOVE ARE PRELIMINARY ONLY.

AutoCAD SHX Text

JOB NO.:

AutoCAD SHX Text

REVISIONS :

AutoCAD SHX Text

SHEET :

AutoCAD SHX Text

OF :

AutoCAD SHX Text

SCALE :

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 5/13/26

AutoCAD SHX Text

SHOWN

AutoCAD SHX Text

WB-112

AutoCAD SHX Text

ELECTRICAL SCHEDULES

AutoCAD SHX Text

AND NOTES

AutoCAD SHX Text

E

SH

R

ED

D

ER

F

AC

IL

IT

Y R

EE

VE

S C

O U

N

TY

, T

EX

AS

C O

. R D

. 2

, P

EC

O S, T X

TEXAS FIRM

REGISTRATION:

#F-26227

E7

ELECTRICAL RISER DIAGRAM

NO SCALEE7

GRADE

UTILITY

POLE

UE

1500 KVA POLE

MOUNTED

TRANSFORMER

HV1

2000A

MCB

277/480V 3P/4W

NEMA 3R

LV1

100A

MLO

120/208V 3P/4W

NEMA 3R

T1

45 KVA

NEMA 3R

1. UTILITY TRANSFORMER: PROPOSED TRANSFORMER BY LOCAL ELECT

UTILITY AS SHOWN, COORDINATE NEW SERVICE INSTALLATION AS

SHOWN. COORDINATE FINAL TRANSFORMER SIZE AND LOCATION WITH

UTILITY.

2. SERVICE CONDUCTORS: SIX SETS OF 4 #500 MCM IN 4" CONDUITS,

COORDINATE ROUGH-IN REQUIREMENTS WITH UTILITY.

3. ELECTRIC METER: UTILITY FURNISHED ENCLOSURE, POLE MOUNTED AT

TRANSFORMER LOCATION, SERVICE CAPABILITY AS SHOWN, TO BE

INSTALLED BY CONTRACTOR, COORDINATE ROUGH-IN WITH UTILITY.

4. SERVICE PANEL HV1: SERVICE DISTRIBUTION PANEL, RATINGS AS

SHOWN. SEE SCHEDULES. COORDINATE FINAL LOCATION AND

REQUIREMENTS WITH OWNER PRIOR TO ROUGH-IN.

5. TRANSFORMER PRIMARY FEEDER: 3 #4 AWG AND #8 GND IN 1"

CONDUIT.

6. TRANSFORMER T1: LOW-VOLTAGE STEP DOWN, KVA RATING AND

ENCLOSURE AS SHOWN ABOVE, 480V/30 PRIMARY, 120/208V

SECONDARY, DRY TYPE, WALL OR PAD MOUNTED, VERIFY FINAL

LOCATION WITH OWNER PRIOR TO ROUGH-IN. SEE SCHEDULES AND

GROUNDING DETAILS.

7. SECONDARY PANEL FEEDER: 4 #1 AWG AND #6 GND IN 1 1/2" CONDUIT.

8. BRANCH PANEL LV1: LOW-VOLTAGE, RATINGS AS SHOWN ABOVE.

SERVING OFFICE EQUIPMENT, HVAC, LIGHTING AND RECEPTACLES.

9. MOTOR CONTROL PANEL FEEDER: ROUTE TO VENDOR FURNISHED MCC

ENCLOSURE, 3 #350 MCM AND #3 GND IN 3" CONDUIT. COORDINATE

FINAL REQUIREMENTS WITH MCC EQUIPMENT VENDOR PRIOR TO

ROUGH-IN, TYPICAL 2 PLACES.

10. MOTOR CONTROL PANEL FEEDER: ROUTE TO VENDOR FURNISHED MCC

ENCLOSURE, 3 #600 MCM AND #2 GND IN 4" CONDUIT. COORDINATE

FINAL REQUIREMENTS WITH MCC EQUIPMENT VENDOR PRIOR TO

ROUGH-IN, TYPICAL 3 PLACES.

11. MOTOR CONTROL CENTER (MCC): VENDOR FURNISHED, AMP RATINGS

AS SHOWN ABOVE. SERVING VENDOR FURNISHED TIRE SHREDDER

EQUIPMENT, TYPICAL 5 PLACES. COORDINATE WITH VENDOR FOR FINAL

INSTALLATION AND CONNECTION REQUIREMENTS, PRIOR TO ROUGH IN.

12. TRANSFORMER GROUND: ROUT BARE #6 CU CONDUCTOR FROM

GROUND LUG ON TRANSFORMER TO GROUND ROD AND BUILDING

GROUNDING ELECTRODE SYSTEM AS SHOWN. SEE DETAILS FOR

TRANSFORMER GROUND REQUIREMENTS.

13. GROUNDING ELECTRODE CONDUCTOR: PROVIDE BARE #3/0 AWG

COPPER CONDUCTOR FROM GROUND BUS ON SERVICE PANEL TO

GROUND ROD AND GROUNDING ELECTRODE SYSTEM.

14. GROUND ROD: PROVIDE MIN. 1 GROUND RODS TO PROVIDE MAXIMUM

OF 25 OHMS RESISTANCE TO GROUND PER NEC 250 BETWEEN SERVICE

PANEL BOND AND EARTH. IF NEEDED, PROVIDE AND BOND A SECOND

GROUND ROD, MIN. 6FT APART, TO LOWER RESISTANCE TO EARTH.

E

POLE MOUNTED

ELECT METER

MCC1

300A

MCB

480V

3P/3W

NEMA 3R

MCC2

300A

MCB

480V

3P/3W

NEMA 3R

MCC3

400A

MCB

480V

3P/3W

NEMA 3R

MCC4

400A

MCB

480V

3P/3W

NEMA 3R

MCC5

400A

MCB

480V

3P/3W

NEMA 3R

FLOOR

SERVICE

PANEL

VENDOR FURNISHED

MOTOR CONTROL

PANELS

11 11 11 11

NOTES:

1. DIAGRAM SHOWN ABOVE IS GENERAL ARRANGEMENT ONLY. ELECTRICAL CONTRACTOR SHALL DETERMINE ACTUAL TYPES AND LOCATIONS OF GROUNDING ELECTRODES AND BONDING JUMPER CONNECTIONS BASED UPON SITE CONDITIONS AND SHALL COORDINATE THE INSTALLATION OF ALL REQUIRED GROUND CONNECTORS WITH THE LOCAL UTILITY AND OTHER TRADES.

2. CONTRACTOR SHALL BOND TOGETHER AS SHOWN ALL GROUNDING ELECTRODES PRESENT AT THE BUILDING OR STRUCTURE. A MINIMUM OF TWO ELECTRODES IS REQUIRED AT ALL BUILDINGS OR STRUCTURES UNLESS SINGLE ELECTRODE HAS MEASURED RESISTANCE TO EARTH OF 25 OHMS OR LESS. CONTRACTOR SHALL PROVIDE ELECTRODES AS NEEDED TO COMPLY WITH NEC ARTICLE 250.

3. WHERE MULTIPLE RODS ARE USED AS ELECTRODES THEY SHALL BE SPACED A MINIMUM OF 6' APART. GROUND CLAMPS SHALL BE

BELOW GRADE AS SHOWN OR ABOVE GRADE WITH APPROVED PROTECTIVE COVERING.

4. ALL GROUNDING CONNECTORS USED SHALL BE INSTALLED IN ACCESSIBLE LOCATIONS AND LISTED FOR SUCH USE AS GROUNDING CONNECTOR. THE ELECTRICAL CONTRACTOR SHALL ENSURE MATERIALS ARE COMPATIBLE TO AVOID CORROSION AT CONNECTIONS.

5. ALL BONDING JUMPERS AND GROUNDING ELECTRODE CONDUCTOR SHALL BE SECURELY FASTENED TO STRUCTURE AND PROTECTED FROM PHYSICAL DAMAGE PER NEC REQUIREMENTS. WHERE INSTALLED IN METALLIC CONDUIT OR RACEWAY, PROVIDE EQUAL SIZED BONDING JUMPER BETWEEN RACEWAY AND GROUNDING JUMPER OR ELECTRODE, USING LISTED CLAMPS AND FITTINGS.

GROUNDING ELECTRODE SYSTEM

NO SCALE

MIN. 5/8" DIA. X 8' GROUND ROD OF

STAINLESS OR GALV. STEEL OR

COPPER.

BUILDING STEEL

STRUCTURE

COPPER GROUNDING ELECTRODE CONDUCTOR TO GROUND

BUS OR LUGS AT MAIN SERVICE SWITCH OR PANELBOARD

FLOOR

CLAMP SUITABLE FOR

DIRECT BURIAL

ALL BONDING JUMPERS SHOWN SHALL

BE COPPER AND SIZED EQUAL TO THE

GROUNDING ELECTRODE CONDUCTOR

SHOWN

5' M

AX

E7

TYPICAL RACK STAND DETAILS

SCALE: 1/4"=1'-0"E7

FACTORY

MOUNTING

FEET

AUX

GUTTER

SMALLER MOTOR

DISCONNECTS

INCOMING

FEEDER CIRCUITS

LARGER MOTOR

DISCONNECTS

12x12 JBOX FOR LV

CONTROL WIRING

TO MOTORSCONCRETE

FLOOR

UNISTRUT STAND

NOTES

1. DIAGRAM ABOVE IS GENERAL ARRANGEMENT AS A GUIDE ONLY. CUSTOM

FABRICATE EACH RACK STAND BASED ON THE SWITCH REQUIREMENTS AT EACH

LOCATION. USE DIAGRAM ABOVE AS A GUIDE TO LAYING OUT RACK STANDS AT

ALL LOCATIONS.

2. ROUTE INCOMING FEEDER CIRCUITS AND LV CONTROL CIRCUITS OVERHEAD AS

SHOWN. COORDINATE WITH OWNER TO VERIFY MIN. HEIGHT OF OVERHEAD

CONDUITS. VERIFY FINAL SWITCH RACK LOCATIONS WITH OWNER PRIOR TO

ROUGH-IN OF FEEDER CONDUITS.

3. COORDINATE WITH OWNER ON REQUIRED SIZE OF LV CONTROL WIRING JBOX TO

BE LOCATED AT ALL RACK STANDS. BOX SHOWN ABOVE IS PRELIMINARY SIZE

ONLY.

4. FABRICATE ALL UNISTRUT STANDS USING FACTORY FITTINGS AND ACCESSORIES,

AND SECURELY FASTEN TO FINISHED FLOOR WITH MOUNTING FEET AS SHOWN.

PROVIDE ALL ADDITIONAL SUPPORTS AND BRACES AS NEEDED FOR STURDY

INSTALLATION OF ALL SWITCHES AND CONNECTING CONDUITS.

5. PROVIDE UNISTRUT SUPPORT STANDS AND BRACING AS REQUIRED, SPACED

MAX. 4' APART, TO ROUTE FEEDER CONDUITS FROM RACK STANDS TO MOTOR

CONNECTIONS AT PRODUCTION EQUIPMENT.

6. SIZE ALL AUX. GUTTERS BASED ON NUMBER OF CONDUCTORS TO BE ENCLOSED,

PER NEC REQUIREMENTS.

LV WIRING TO

CONTROLS

NOTES:

1. DIAGRAM SHOWN ABOVE IS GENERAL ARRANGEMENT ONLY. PHASE CONDUCTORS NOT

SHOWN FOR CLARITY.

2. SEE RISER DIAGRAM FOR EQUIPMENT GROUNDING CONDUCTOR SIZE.

3. SEE RISER DIAGRAM FOR GROUNDING ELECTRODE CONDUCTOR SIZE.

4. SEE NEC TABLE 250.102(C)(1) FOR MIN. BONDING JUMPER SIZES REQD.

TRANSFORMER GROUNDING DETAILS

NO SCALE

NEUTRAL CONDUCTOR, ROUT WITH

PHASE CONDUCTORS

TRANSFORMER GROUNDED

TERMINAL CONNECTION

SYSTEM BONDING

JUMPER

TRANSFORMER GROUND

BUS OR LUGS, BONDED

TO ENCLOSURE

GROUNDING ELECTRODE CONDUCTOR

TO GROUNDING SYSTEM, SEE RISER

DIAGRAM

X0 N

G G

TRANSFORMER

G

EQUIP. GROUNDING CONDUCTOR

FROM PRIMARY FEEDER, SEE RISER

DIAGRAM

E7

HV1

GN

NEW SERVICE

DISTRIBUTION

PANEL

SERVICE GROUNDING DETAIL

NO SCALEE7

GROUNDING ELECTRODE

CONDUCTOR TO GROUNDING

ELECTRODE SYSTEM, INCLUDING

GROUND ROD(S), BUILDING STEEL

FRAME, BURIED METAL WATER PIPE,

ETC.

G

N

KEEP ISOLATED TO

ALL SUBPANELS

NOTES:

1. DIAGRAM ABOVE IS GENERAL ARRANGEMENT ONLY. PHASE CONDUCTORS NOT SHOWN

FOR CLARITY.

2. SEE RISER DIAGRAM FOR NEUTRAL AND GROUND CONDUCTOR SIZES NOT SHOWN

ABOVE.

3. GROUNDING SHOWN IS TYPICAL FOR ALL SUB-PANELS NOT SHOWN FOR CLARITY.

4. ALL EQUIPMENT GROUNDS IN NEW SYSTEM SHALL BE ISOLATED FROM NEUTRAL

CONDUCTORS AS SHOWN.

N

GROUNDED CONDUCTOR

FROM UTILITY SERVICE

DROP

MIN. 20' OF #3/0 COPPER WIRE GROUND RING

AROUND BUILDING PERIMETER, IN DIRECT

CONTACT WITH THE EARTH, MIN. 30" BELOW

FINISHED GRADE.

UNISTRUT FRAME

' M

IN

AutoCAD SHX Text

JOB NO.:

AutoCAD SHX Text

REVISIONS :

AutoCAD SHX Text

SHEET :

AutoCAD SHX Text

OF :

AutoCAD SHX Text

SCALE :

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 5/13/26

AutoCAD SHX Text

SHOWN

AutoCAD SHX Text

WB-112

AutoCAD SHX Text

ELECTRICAL SCHEDULES

AutoCAD SHX Text

AND NOTES

AutoCAD SHX Text

Sheets and Views
MEP-MEP1
MEP-MEP2