00017613 - Exhibit 6 - Prineville_Ceiling_Drawings.pdf

PDF 3 MB Posted

Attached to
ESB Prineville MS - Storage Bldg Ceiling Installation - Rebid
Solicitation number
S-73000-00017613
Issued by
Oregon

About this file

This is a ceiling installation drawing set for the Oregon Department of Transportation (ODOT) Prineville Maintenance Station Storage Building located at 3571 NE 3rd Street, Prineville, Oregon 97754. The project requires installation of a new ceiling system including framing, 29-gauge metal panels, attic ventilation louvers, and an attic access panel in the existing 1,728 square-foot storage building (occupancy classification S-1, construction type V-B). The base bid scope includes installing new 2x6 ceiling joists at 3-foot on-center spacing, metal ceiling panels fastened with #10 x 1½-inch screws at 9-inch on-center spacing, four ventilation louvers (two at 1'-6" x 1'-6" and two at 2'-6" x 1'-6") positioned between truss webs at each end of the building, and a 2'-10" by 2'-0" attic access panel centered on the roof ridge. Contractors must conduct a mandatory site visit to examine existing conditions prior to bidding and submit any discrepancies or clarifications in writing to ODOT before installation. All work must conform to applicable codes and regulations, with gaps in ceiling installation not to exceed ¼ inch, and the completed work area must be cleaned to the satisfaction of the ODOT project manager.

Add Alternate #1 includes removal of existing building lighting and installation of new lighting fixtures comprising three Lithonia Lighting CSS L96 AL04 MVOLT SWW3 80 CRI fixtures mounted in a row centered on the trusses in three separate locations, along with a Lithonia Lighting CRM 10 occupancy sensor switch mounted on the ceiling. This electrical work must be performed by a licensed electrician using MC cable with copper conductors, with all new wiring runs sealed at ceiling penetrations. The basis of design specifies maximum light output and 3500K color temperature settings for the fixtures. If Add Alternate #1 is not selected by ODOT, removal of existing lighting becomes the responsibility of others outside the contract. The agency notes that limited funding is available, with one additive alternate being utilized to maximize work completion within available budget constraints. The contract award will be based on bid pricing as described in the Invitation to Bid Attachment C - Bid Pricing Form.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WALLOWA

UNION

UMATILLA

MORROW

GILLIAM

SHERMANWASCO

HOOD

RIVER

CLACKAMAS

MULTNOMAH

COLUMBIA

CLATSOP

TILLAMOOK

WASHINGTON

YAMHILL

POLK

LINCOLN

BENTON

LINN

MARION

LANE

DOUGLAS

COOS

CURRY

JOSEPHINE

JACKSON

KLAMATH

LAKE

HARNEY

MALHEUR

CROOK

JEFFERSON WHEELER

GRANT

BAKER

DESCHUTES

26 JOHN

DAY

THE

DALLES

PENDLETON

LA

GRANDE

BAKER

CITY

ONTARIO

BURNS

BEND

KLAMATH

FALLS

PORTLAND

SALEM

EUGENE

ROSEBURG

MEDFORD

COOS

BAY

NEWPORT

ASTORIA

FLORENCE

CORVALLIS

ALBANY

ASHLAND

LAKEVIEW

STORAGE

F4070306

ENCLOSED

STORAGE

F4070303

OPEN STORAGE

F4070304

OFFICE

F4070307

SHOP BUILDING

F4070301

FUEL BUILDING

F4070302

O

HP

O

HP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

NE OCHOCO HWY 26

REDUCED 50%

WHEN PRINTED

AT 11" x 17"

TH

IS

D R

AW

IN

G

IS

R

ED

U C

ED

IF

B O

R D

ER

IS

N O

T

/2

" x

2"

F4070306

ODOT PRINEVILLE MAINTENANCE STATION

STORAGE BUILDING CEILING INSTALLATION

3571 NE 3rd ST, PRINEVILLE, OR 97754 4 04/15/26

FRANCO

JON DOUGHTON S T R U C T U R A L

J A

N U A R Y 1 3 , 2

0 0

ODOT PRINEVILLE MAINTENANCE STATION

STORAGE BUILDING CEILING

INSTALLATION

3571 NE 3rd ST, PRINEVILLE, OR 97754

1. ALL WORK SHALL CONFORM TO APPLICABLE CODES, LAWS AND ORDINANCES OF THE

JURISDICTION HAVING AUTHORITY.

2. DO NOT SCALE THE DRAWINGS.

3. CONTRACTOR SHALL MAKE A SITE VISIT AND EXAMINE EXISTING CONDITIONS PRIOR TO

PROVIDING A BID. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF ODOT

THROUGH A REQUEST FOR CLARIFICATION AS SET FORTH IN THE BID DOCUMENTS.

4. CLARIFICATIONS SHALL BE REQUESTED IN WRITING PRIOR TO ANY INSTALLATION. INCORRECT

INSTALLATIONS SHALL BE CORRECTED AT NO ADDITIONAL COST TO ODOT.

5. ALL WORK SHOWN IS TO BE BY THE CONTRACTOR UNLESS SPECIFICALLY NOTED AS BEING BY

ODOT OR BY OTHERS. ALL MATERIALS SHOWN ARE TO BE PROVIDED BY THE CONTRACTOR

UNLESS SPECIFICALLY NOTED AS EXISTING OR PROVIDED BY ODOT.

6. DRAWINGS ARE SCHEMATIC IN NATURE. MAJOR COMPONENTS ARE SHOWN ON THE DRAWINGS.

CONTRACTOR SHALL SUPPLY AND INSTALL ALL MINOR COMPONENTS AND MATERIALS

NECESSARY TO PROVIDE A COMPLETE AND FUNCTIONAL PROJECT WHETHER OR NOT ALL SUCH

COMPONENTS ARE NOTED IN THE DRAWINGS AND SPECIFICATIONS.

7. ALL MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED

INSTALLATION INSTRUCTIONS AND RECOMMENDATIONS.

8. INSTALL CEILING TIGHT WITH NO GAPS GREATER THAN 1/4". INSTALL BLOCKING AS REQUIRED.

9. CLEAN ENTIRE WORK AREA AT CONCLUSION OF PROJECT TO THE SATISFACTION OF THE ODOT

PROJECT MANAGER.

GENERAL CONSTRUCTION NOTES

T101 TITLE SHEET

A101 FLOOR PLAN AND REFLECTED CEILING PLAN

A102 SECTIONS AND ELEVATIONS

A103 DETAILS

SHEET INDEX

STATE VICINITY MAP

SCALE: N.T.S.

TITLE SHEET T101

PRINEVILLE

0 100'

SITE PLAN

SCALE: 1" = 100''

OCCUPANCY: STORAGE S-1

CONSTRUCTION TYPE: V-B

AREA: 1,728 SF

CODE DATA:

1 06/30/26 NO CHANGE THIS SHEET JD

ADD ALTERNATES:

AGENCY HAS LIMITED FUNDING AVAILABLE FOR THE CONSTRUCTION OF THIS PROJECT AND THE FUNDING MAY NOT BE ADEQUATE TO CONSTRUCT THE ENTIRE PROJECT. ONE ADDITIVE ALTERNATE IS BEING USED TO MAXIMIZE THE WORK THAT CAN BE COMPLETED WITHIN THE AVAILABLE FUNDING LIMITS. THE CONTRACT AWARD WILL BE AS DESCRIBED IN

THE INVITATION TO BID ATTACHMENT C - BID PRICING FORM.

BASE BID - INSTALL NEW CEILING IN EXISTING STORAGE BUILDING, ATTIC VENTILATION, AND ATTIC ACCESS AS SHOWN ON DRAWINGS.

ADD ALTERNATE #1 - REMOVE EXISTING BUILDING LIGHTING AND INSTALL NEW LIGHTING AS SHOWN ON DRAWING A101.

NOTE: IF ADD ALTERNATE #1 IS NOT SELECTED BY ODOT, THE REMOVAL OF EXISTING LIGHTING IS BY OTHERS (NOT IN CONTRACT).

2 07/13/26 INCLUDE ADD ALTERNATE #1 JD

±36'-0"

±48'-0"

OPEN STORAGE

A102

A102

A103

A103

ATTIC ACCESS IN NEW

CEILING, CENTER ON

RIDGE, SEE DETAIL

A103

A103

A103

A103

A102

A102

A103

TYP.

LINE OF TRUSSES

ABOVE CEILING, TYP.

TYPICAL NEW

CEILING, SEE DETAIL 2

A103

(3) NEW LIGHT FIXTURES IN A

ROW, CENTERED ON TRUSSES,

TYPICAL (3) PLACES

(INCLUDED IN ADD ALTERNATE #1)NEW OCCUPANCY SENSOR

SWITCH MOUNTED ON CEILING

(INCLUDED IN ADD ALTERNATE #1)

TH

IS

D R

AW

IN

G

IS

R

ED

U C

ED

IF

B O

R D

ER

IS

N O

T

/2

" x

2"

F4070306

ODOT PRINEVILLE MAINTENANCE STATION

STORAGE BUILDING CEILING INSTALLATION

3571 NE 3rd ST, PRINEVILLE, OR 97754 4 04/15/26

FRANCO

JON DOUGHTON S T R U C T U R A L

J A

N U A R Y 1 3 , 2

0 0

FLOOR PLAN AND REFLECTED CEILING PLAN A101

EXISTING FLOOR PLAN

SCALE: 1/4" = 1'-0"

REFLECTED CEILING PLAN

SCALE: 1/4" = 1'-0"

REDUCED 50%

WHEN PRINTED

AT 11" x 17"

1 06/30/26 ADD LIGHT FIXTURES AND ELECTRICAL

NOTES

JD

ELECTRICAL NOTES (INCLUDED IN ADD

ALTERNATE #1):

1. ALL ELECTRICAL WORK SHALL BE PERFORMED BY A

LICENSED ELECTRICIAN IN ACCORDANCE WITH

APPLICABLE CODES.

2. BASIS OF DESIGN LIGHT FIXTURE IS LITHONIA

LIGHTING MODEL NUMBER CSS L96 ALO4 MVOLT

SWW3 80 CRI. SET TO MAXIMUM LIGHT OUTPUT AND

3500K COLOR TEMPERATURE. MOUNT TO CEILING IN

APPROXIMATE LOCATION SHOWN.

3. BASIS OF DESIGN OCCUPANCY SENSOR IS LITHONIA

LIGHTING CRM 10. MOUNT TO CEILING IN

APPROXIMATE LOCATION SHOWN TO MAXIMIZE

DETECTION.

4. REMOVE EXISTING LIGHTING AND RETURN TO ODOT.

MODIFY EXISTING ELECTRICAL SYSTEM AS

REQUIRED TO SUPPLY NEW LIGHTING FIXTURES.

PROVIDE OCCUPANCY SENSOR BETWEEN EXISTING

MANUAL SWITCH AND NEW LIGHTING.

5. USE MC CABLE WITH COPPER CONDUCTORS FOR

NEW WIRING RUNS. SEAL PENETRATIONS IN CEILING.

2 07/13/26 INCLUDE ADD ALTERNATE REFERENCES JD

EXISTING METAL

ROOFING

EXISTING ENGINEERED

TRUSS

EXISTING POST

COLUMN

TYPICAL NEW CEILING, APPLY NEW METAL

PANELS TO NEW 2x6 CEILING JOISTS AT 3'-0"

ON CENTER, SEE DETAIL

A103

A103

A103

EXISTING CONCRETE

FLOOR SLAB

OPEN OPEN OPEN OPEN

FOUR LOUVERS AT EACH END OF BUILDING,

(2) 1'-6"x1'-6" AND (2) 2'-6"x1'-6" POSITION TO

FIT BETWEEN TRUSS WEBS, TYP.

A103 TYP.

TH

IS

D R

AW

IN

G

IS

R

ED

U C

ED

IF

B O

R D

ER

IS

N O

T

/2

" x

2"

F4070306

ODOT PRINEVILLE MAINTENANCE STATION

STORAGE BUILDING CEILING INSTALLATION

3571 NE 3rd ST, PRINEVILLE, OR 97754 4 04/15/26

FRANCO

JON DOUGHTON S T R U C T U R A L

J A

N U A R Y 1 3 , 2

0 0

SECTIONS AND ELEVATIONS A102

EXISTING BUILDING SECTION

SCALE: 3/8" = 1'-0"

A102

PROPOSED BUILDING SECTION

SCALE: 3/8" = 1'-0"

A102

WEST ELEVATION

SCALE: 1/8" = 1'-0"

EAST ELEVATION

SCALE: 1/8" = 1'-0"

EXISTING NORTH / SOUTH ELEVATION

SCALE: 1/8" = 1'-0"

PROPOSED NORTH / SOUTH ELEVATION

SCALE: 1/8" = 1'-0"

REDUCED 50%

WHEN PRINTED

AT 11" x 17"

1 06/30/26 NO CHANGE THIS SHEET JD

2 07/13/26 NO CHANGE THIS SHEET JD

METAL CEILING PANEL IS TO BE 29 GAUGE

WITH A NOMINAL WIDTH OF 3 FEET.

FASTENERS ARE TO BE #10 x 1 1/2" SCREWS

WITH NEOPRENE AND COLOR MATCHED

WASHERS. PLACE FASTENERS NEXT TO

MAJOR RIBS AT 9" ON CENTER.

29 GAUGE METAL PANEL

#10 x 1 1/2" SCREWS AT 9" ON

CENTER ALONG EACH JOIST

INSTALL SCREW THROUGH BOTH

SHEETS AT JOINT, TYPICAL

EXTENDED LEG

ON SHEET

SHEET OVERLAP #14 x 3/4" STITCH SCREWS

AT 24" ON CENTER

NEW 2x6 CEILING JOIST

AT 3'-0" ON CENTER

PRE-FINISHED METAL "J" CHANNEL

EDGE TRIM AROUND OPENING, TYP.

TYPICAL 2x2 PERIMETER

WITH 1/4" GAP TO FRAMING

NEW 1/2" THICK 5-PLY ACX

PLYWOOD ACCESS PANEL

#9x1-1/2" SCREWS AT 6"

ON CENTER AROUND

PERIMETER

TYPICAL 2x6

PERIMETER FRAMING

NEW PRE-FINISHED

METAL CEILING PANEL

ACCESS NOTES:

1. CLEAR ACCESS OPENING IS 2'-10" BY 2'-0".

2. PROVIDE 2x6 FRAMING BETWEEN CEILING

JOIST TO FRAME OPENING.

TYPICAL NEW

CEILING JOIST

EXISTING TRUSS

BOTTOM CHORDS

NEW SIMPSON LUS26 HANGER TO

SUPPORT CEILING JOIST WITH ALL

MFGR. SPECIFIED FASTENERS, TYP.

CEILING PANEL

NEW SIMPSON LUS26 HANGER TO

SUPPORT CEILING JOIST WITH ALL

MFGR. SPECIFIED FASTENERS, USE

1-1/2" NAILS INTO TRUSS CHORD, TYP. EXISTING TRUSS

CHORD

EXISTING METAL

SIDING

CEILING PANEL

PRE-FINISHED METAL "J"

CHANNEL EDGE TRIM, TYP.

NEW LIGHT FIXTURE MOUNTED

UNDER TRUSS

(INCLUDED IN ADD ALTERNATE #1)

NEW 2x6 EDGE JOIST

EXISTING METAL

ROOFING

EXISTING

METAL SIDING

NEW METAL CEILING, BUTT

TIGHT TO METAL SIDING PANEL

NEW 2x10 EDGE JOIST

EXISTING METAL

ROOFING

NEW METAL

CEILING PANEL

EXISTING

POST

CONNECT EDGE JOIST TO EXISTING

TRUSS WITH SIMPSON A35 ANGLE

WITH (12) 8dx1-1/2" NAILS

CONNECT EDGE JOIST TO EXISTING

TRUSS WITH SIMPSON A35 ANGLE

WITH (12) 8dx1-1/2" NAILS

CUT EXISTING METAL

SIDING TO FIT NEW

LOUVER, TYP.

NEW PRE-FINISHED METAL "J"

CHANNEL TRIM AROUND

LOUVER PERIMETER

INSTALL NEW 2x4 BLOCKING AROUND ALL

SIDES OF OPENING BETWEEN TRUSS

WEBS, INSTALL 2x4 FRAMING AROUND ALL

SIDES OF OPENING TO SUPPORT LOUVER

NEW VENTILATION LOUVER,

SEE ELEVATION VIEW FOR SIZE

SHIM AND FASTEN

LOUVER SECURELY

INSTALL BACKER ROD AND

SEALANT AROUND PERIMETER TO

SEAL OPENING WEATHER TIGHT

TH

IS

D R

AW

IN

G

IS

R

ED

U C

ED

IF

B O

R D

ER

IS

N O

T

/2

" x

2"

F4070306

ODOT PRINEVILLE MAINTENANCE STATION

STORAGE BUILDING CEILING INSTALLATION

3571 NE 3rd ST, PRINEVILLE, OR 97754 4 04/15/26

FRANCO

JON DOUGHTON S T R U C T U R A L

J A

N U A R Y 1 3 , 2

0 0

DETAILS A103

TYPICAL METAL CEILING

SCALE: 1-1/2" = 1'-0"

2ATTIC ACCESS

SCALE: 1-1/2" = 1'-0"

NEW CEILING CONNECTION AT TRUSSES

SCALE: 3" = 1'-0"

4 NEW CEILING CONNECTION AT END TRUSS

SCALE: 3" = 1'-0"

REAR CEILING DETAIL

SCALE: 1-1/2" = 1'-0"

6 FRONT CEILING DETAIL

SCALE: 1-1/2" = 1'-0"

ATTIC VENTILATION LOUVER DETAIL

SCALE: 1-1/2" = 1'-0"

A103

A103A103

A103

A103 A103

A103

REDUCED 50%

WHEN PRINTED

AT 11" x 17"

1 06/30/26 ADD LIGHT FIXTURES TO DETAIL 4/A103 JD

2 07/13/26 INCLUDE ADD ALTERNATE #1 ON DETAIL 4 JD

F4070306 - 04_PRINEVILLE STORAGE CEILING INSTALL_REV2 PLAN t101.pdf
F4070306 - 04_PRINEVILLE STORAGE CEILING INSTALL_REV2 PLAN 07.13.26.pdf
F4070306 - 04_PRINEVILLE STORAGE CEILING INSTALL_PLAN A101.pdf
F4070306 - 04_PRINEVILLE STORAGE CEILING INSTALL_PLAN A102.pdf
F4070306 - 04_PRINEVILLE STORAGE CEILING INSTALL_PLAN A103.pdf
2026-07-13T10:32:17-0700
DOUGHTON Jonathan S
2026-07-13T10:33:40-0700
DOUGHTON Jonathan S
2026-07-13T10:34:36-0700
DOUGHTON Jonathan S
2026-07-13T10:35:21-0700
DOUGHTON Jonathan S

File details come from the government source that posted it. Updated .