About this forecast
Navy NAVFAC Southwest is procuring design-build services to replace and upgrade HVAC systems in building PM53 at Point Mugu, California, bringing existing systems into building code and life safety compliance. The base scope covers complete HVAC system replacement and upgrades for the second floor, including demolition, abatement, HVAC, electrical, plumbing, structural modifications, interior and exterior repairs, fire protection modifications, and security modifications, with a Variable Refrigerant Flow (VRF) system paired with an independent Dedicated Outside Air System (DOAS) per ASHRAE 62.1 standards and temporary supplemental cooling during installation. A contract option covers identical work for the third floor. The solicitation release and award dates are both estimated for April 1, 2026, with an 18-month period of performance.
The estimated award value ranges from $2 million to $7.5 million under a fixed-price delivery order instrument. This is a competitive multiple award IDIQ do/to vehicle. Work is performed at Point Mugu Naval Base Ventura County, California. The contracting office is NAVFAC Southwest (UIC N62473), and clearance requirements are unclassified for both facilities and personnel.
Forecast text
SCOPE OF WORK
This is a Design-Build RFP in support of NAVAIR Sea Range Operations at building PM53 Proper, Point Mugu, NBVC. The goal is to bring this existing HVAC systems into building code and life safety compliance for a complete and useable system. This scope of work is primary focus in Phase IIIB at PM53 Building. It shall require a complete HVAC System replacement and upgrades in PM53 Proper serving the 2nd Floor and 3rd Floor.
The following one (1) project is the base bid for this contract:
BASE SOW -
Design and provide full replacement and upgrades to the second floor HVAC system served by AHU-4 (ONLY) located in Mechanical Room (Third Floor) next to staircase. The work includes (but not limited to) demolition and abatement, HVAC, electrical, plumbing, structural modifications, interior and exterior repairs, mechanical room repairs, fire protection modifications and security modifications in particular secured spaces impacted by this project.
The new VRF System shall be provided with independent Dedicated Outside Air System (DOAS) for proper direct ventilation in each room via supply diffuser per ASHRAE 62.1 Ventilation for Acceptable Indoor Quality. For pre-heating DOAS requirements, the existing HHW system shall be re-utilized and connected.
Temporary Supplemental Cooling shall be provided during the performance of the new HVAC System installations in the 2nd floor.
Provide dedicated Cooling System in the Server Room per UFC NMCI Requirements.
The following project will be listed as option for this contract:
OPTION 1 SOW –
Design and provide full replacement and upgrades to the third floor HVAC system served by AHU-6 (ONLY) located in Mechanical Room (Third Floor). The work includes (but not limited to) demolition and abatement, HVAC, electrical, plumbing, structural modifications, interior and exterior repairs, mechanical room repairs, fire protection modifications and security modifications in particular secured spaces impacted by this project.
The new VRF System shall be provided with independent Dedicated Outside Air System (DOAS) for proper direct ventilation in each room via supply diffuser per ASHRAE 62.1 Ventilation for Acceptable Indoor Quality. For pre-heating DOAS requirements, the existing HHW system shall be re-utilized and connected.
Provide dedicated Cooling System in the Server Room per UFC NMCI Requirements.
Option(s) to be included in the solicitation: FAR 52.217-5, Evaluation of Options will be included in the solicitation.
Option clauses to be included in the contract: Per NFAS 17.208-100, clause 52.217-7, Option for Increased Quantity – Separately Priced Line Items is included for the construction contract with options for additional work.
Method of evaluation of option(s): Each option item will be evaluated independently through a technical analysis, which shall compare the proposed line items in RS Means to those in the Government Estimate.