Y1DA--526-22-207 - AHU's Coil Replacement

Closed Solicitation Posted

This opportunity was awarded. See the award notice from .

Solicitation number
36C24222Q0599
Agency
Veterans Integrated Service Network 2 Veterans Health Administration, Department of Veterans Affairs
Responses due
Set-aside
No set-aside

Opportunity facts

NAICS code
238220 Plumbing, Heating, and Air-Conditioning Contractors
PSC
Y1DA Construction Of Hospitals And Infirmaries

Notice details come from SAM.gov. Updated .

Notice text

2 versions

Update #2 · Latest ·

The RFP shows four (4) coils but there are really five (5) coils found during last week s site visit. Are all five being replaced?

Answer: Yes, all five coils are to be replaced. The SOW was updated to demonstrate the new coil count.

Expedited fabrication charges were requested. 10 days fabrication?

Answer: The POP is to complete all work 45 days from Notice to proceed. The contractor shall determine the appropriate amount of expedited time needed to support his schedule.

For AHU-1, are we insulating piping that is not insulated currently? The RFP says replace any damaged insulation. It doesn t specify missing insulation.

Answer: The contractor shall replace only the missing sections of the insulation. New insulation shall match existing or close and equal to performance.

The RFP does not bring attention replacing coil drip pans. Is there anything to be done to the current drip pans? Sealing, etc.?

Answer: Drip pans for cooling coils is standard and shall be included part of the system. Please ensure to include this with the newly installed cooling coils.

Area 2F, AHU-15 the scope calls to replace 1 of 2 coils in the AHU. Is the coil to be replaced the top or bottom coil? Replacing one coil may involve completely removing the other, especially if the bottom coil is to be replaced.

Answer: All five coils are to be replaced. The SOW was updated to demonstrate the new coil count.

The scope calls for vibration checks, and coil pressure drop testing. Please clarify if this is to be performed by a certified third-party testing and balancing contractor?

Answer: Vibration checks are specific to ensuring contractor did not cause the blower fan out of alignment or specifications. Pressure drop test can be demonstrated with the newly installed gauges. Contractor will be in charge for ensuring flow is present in the new coil.

Can you please provide the StartUpChecklist document it was not provided with the rest of the solicitation documents, or we were unable to find it.

Answer: See attachment StartUpChecklist

AHU-1 GF piping is partially insulated with ½ ArmaFlex and partially uninsulated above an adjacent AHU. Please specify the insulation type for replacement insulation.

Answer: The contractor shall replace only the missing sections of the insulation. New insulation shall match existing or close and equal to performance.

Coils are available with lead time options that have considerable and differing associated costs. For example, a 10-day, 25-day or 45-day lead time may be available. Please give guidance as to the desired lead time for coil production.

Answer: The POP is to complete all work 45 days from Notice to proceed. The contractor shall determine the appropriate amount of expedited time needed to support his schedule.

Update #1 ·

526-22-207 - AHU's Coil Replacement

Attachments

Files attached to this notice, newest first
File Type Posted
36C24222Q0599 0001.docx DOCX document
StartUpChecklist.docx DOCX document
Site Visit Sign in Sheet.pdf PDF
A-1_100-H156 Schedules.pdf PDF
A-1_100-H155 Schedules.pdf PDF
36C24222Q0599_1.docx DOCX document
A-1_100-HVAC Schedules.pdf PDF
A-1_100-H32 3rd Floor Plan-Area-B.pdf PDF
A-1_100-H158 Schedules.pdf PDF
A-1_CHW Coil Replacement GF Research Redline 1.pdf PDF
A-1_100-H157 Schedules 2F 3B CHW Cooling Coil.pdf PDF
A-1_100-H113 2F Mechanical Service Bay Plans.pdf PDF
Show all 12

Notice history

Notices posted for this opportunity, newest first
Notice Type Posted
Y1DA--526-22-207 - AHU's Coil Replacement Award Award Notice
Y1DA--526-22-207 - AHU's Coil Replacement This notice · Latest solicitation Solicitation
Y1DA--526-22-207 - AHU's Coil Replacement Original Pre-Solicitation

On GovTribe

Work this opportunity on GovTribe

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity