W911XK20B0012 FY20 sault magazine feeder 4 repair

Closed Solicitation Posted

Solicitation number
W912P5
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
Sault Sainte Marie MI 49783 USA

Notice details come from SAM.gov. Updated .

About this opportunity

This solicitation seeks a firm fixed-price construction contract to perform repair work on Magazine Feeder 4 located in Sault Ste. Marie, Michigan. The U.S. Army Corps of Engineers, Detroit District is procuring the removal and replacement of approximately 1,200 lineal feet of 15kV cable. Offerors must meet all requirements and qualifications specified in the solicitation documentation. The evaluation criteria include price, technical approach, and past performance. The response deadline was extended to June 12, 2020 at 1:00 PM Central Time per Amendment 02.

This opportunity is set aside 100% for small businesses under NAICS code 238210, Electrical Contractors and Other Wiring Installation Contractors. The estimated value is between $100,000 to $250,000 to restore the magazine feeder to full operational capacity by splicing a new MV cable and installing new cable from Manhole 013 to the Cloverland Electric Cooperative substation. The place of performance is Sault Ste. Marie, Michigan and the contractor must complete all work within 100 calendar days of award. Bids were received from four contractors including DVT Electric Inc., BBA Construction LLC, Keweenaw Power & Lite, and Addon Services LLC.

Notice text

2 versions

Update #2 · Latest ·

The contractor will be required to provide all labor, equipment, and additional materials necessary for the removal and replacement of approximately 1,200 lineal feet of 15kV 500 kcmil Compact Sector, Paper Insulated Lead Covered (PILC) low pressure nitrogen filled cable.  The cable is located between Manhole 13 and the Magazine Street Substation in an underground duct bank. A replacement cable shall be installed in the existing duct back and shall be rated 15kV URD and be of 500 kcmil copper. Splice kits shall be provided to connect the existing cable to the newly installed cable. Cable termination and testing from the Magazine substation to the North Power Plant will be conducted.

See Solicitation.

Update #1 ·

See Solicitation.

Files

Similar open opportunities

Opportunity Agency Set-aside Responses due
Dike B Generator Installation, Mansfield Hollow Dam, Mansfield Center, CT Mansfield Center, Connecticut, United States · NAICS 238290 ENDIST New England Total Small Business
CSSC Utility Feed Transformer Replacement 790 East Old Romeo Road, Lockport, IL 60441 60441 · NAICS 237130 ENDIST Chicago No set-aside
W912EK27BA003 - Detroit Project Office Detroit, MI Wayne County Roads, Parking, and Grounds Renovation NAICS 237310 ENDIST Rock Island Competitive 8(a)
Fernan Ranger Station lift station electrical repair Coeur d Alene, Idaho, United States · NAICS 238210 Region 1 - Northern Region Total Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity