About this opportunity
The Bureau of Prisons United States Penitentiary Hazelton is soliciting proposals for four indirect plate and frame water heaters and four pumps to accompany each heater to replace the existing water heating system. The heaters must meet specific dimensional and weight restrictions and include features such as ASME-rated heat exchangers and digital controls. Pumps must achieve defined flow, head, efficiency and operational parameters. Proposals are due by November 27, 2023 and will be evaluated based on compliance with the requirements outlined in the solicitation and attached specifications documents.
There is no set-aside designated for this requirements-based procurement of products only. NAICS 333414 and PSC J060 are applicable for this location of Bruceton Mills, West Virginia. Proposals must include a signed SF1449 and be submitted to the identified contracting and procurement email addresses by the stated deadline. No incumbent is identified for this replacement of four heaters and four associated pumps at the Hazelton federal correctional facility.
Notice text
FCC Hazelton requires a quantity of 4 each indirect plate and frame water heater plus 4 each pumps to accompany the water heaters. Vendors are required to have active SAM.Gov registration and to provide their UEI. A signed SF1449 must be submitted to be considered received. This requirement is for product ONLY. All quotes and bids are required to be submitted to Kelly Brown, Supervisory Contract Specialist with FCC Hazelton at k1roberts@bop.gov (Note: that is a number one after the K) AND HAX-ProcurementProp-S@bop.gov. Quotes must be valid for at least 30 days after close of bids on November 27, 2023 at 2 PM EDT. Specific product requirements below and example spec sheets attached.
Indirect Plate And Frame Water Heater: (4)
Dimensions cannot Exceed: 63” Height Max; 22” Width max; 61” Base Length – MUST FIT THROUGH STANDARD 36” door. Product should not exceed 1200 lbs – Lite Weight Preferred
FEATURES:
ASME DOUBLE WALL HEAT EXCHANGER
• 316L Stainless Steel
• 150 psi Working Pressure
DIGITAL DISPLAY
• DHW Set Point Range 90°F to 180°F
ADVANCED TEMPERATURE CONTROL
MODULATING CONTROL VALVE
SCALE REDUCING PUMP
AUTOMATIC AIR VENT
ASME TEMPERATURE & PRESSURE RELIEF VALVE
• 210°F and 150 psi
ADJUSTABLE HIGH LIMIT
WYE STRAINERS - DOMESTIC PIPING AND
BOILER PIPING
ISOLATION VALVES - DOMESTIC PIPING AND BOILER PIPING
MODBUS COMMUNICATION
WARRANTY
• 5-Year limited warranty/1-Year limited parts
• Warranty for product only without services requirement
SUGGESTED SPECIFICATION
The Indirect Plate and Frame shall be constructed of a 316 stainless steel plate with EPDM gaskets. Maximum unit dimensions shall be: Length ___61_inches, Width ___22___inches and Height __63______ inches.
The Indirect Plate and Frame shall be a double wall. The plate and frame shall be constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements, stamped and registered with the National Board of Boiler and Pressure Vessel Inspectors
The Indirect Plate and Frame shall have a 150 psi working pressure and be supplied with an ASME temperature and pressure relief valve. Standard equipment shall include Wye Strainers, Isolation Valves, Automatic Air Vent, Scale Reduction Pump, Adjustable High Limit and drain valve
The temperature control shall provide + or – 4 degrees Fahrenheit accuracy with up to a 50% change in load. Setpoint range between 90 and 180 F. Modbus communication shall be standard equipment. The modulating valve shall have a 1000 to 1 turndown. The Indirect Plate and Frame shall be suitable for use with polypropylene glycol, up to 50% concentration. The de-rate associated with the glycol will vary per glycol manufacturer.
Pump: (4) Specifications must meet all below requirements for pump withsystem control and monitoring key
Conditions of Service
Flow: 130 US GPM
Head: 32 ft
Efficiency: 68.6 %
Liquid: Water
Temperature: 60 °C
NPSH required: ft
Pump Data
Specific Gravity: 0.985
Maximum operating pressure: 12 bar
Liquid temperature range: -10 .. 110 °C
Maximum ambient temperature: 40 °C
Flange standard: GF
Pipe connection: GF65
Product number: On request
Motor Data
P1 max: 29 .. 1385 W
Mains frequency: 60 Hz
Enclosure class: X4D
Insulation class: F
ADDITIONAL INFORMATION: Domestic inlet temp Set point. DHW set point 90 to 180 degrees. GPH for all units together or for each if separated. GPH is for each unit. Each system will supply at minimum hot water to 64-cells, 10-showers, 2-mop closet and 1-staff restroom. Boiler water entering temp 160-180 degrees. Boiler water Leaving temp 120-140 degrees BTU I am looking for specifics on this. -These units are in use 24/7-365 if that helps.
For singled cell showers, 10 to be used at a time with a maximum of up to 128.
Attachments
| File | Type | Posted |
|---|---|---|
| HW Tank Specs.pdf | ||
| 15B12124Q00000002 WATER HEATER AND PUMPS FCC HAZELTON.pdf | ||
| Pump Specs.pdf | ||
| Specs.pdf |
Notice history
| Notice | Type | Posted |
|---|---|---|
| FCC Hazelton - Water Heating System - PRODUCT ONLY | Award Notice | |
| FCC Hazelton - Water Heating System - PRODUCT ONLY | Solicitation |
On GovTribe
Work this opportunity on GovTribe
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity