This document outlines specifications for an indirect plate and frame water heater system and pump procurement for the Federal Correctional Complex in Hazelton, West Virginia. The Bureau of Prisons requires four indirect plate and frame water heaters no larger than 63" height, 22" width, and 61" base length that can pass through a standard 36" door and weigh no more than 1200 pounds each. The heaters must have ASME-certified double wall heat exchangers, 316L stainless steel construction, digital displays, modulating control valves, and 5-year limited warranties. An additional four pumps are required that meet specified flow, head, efficiency, pressure, and temperature parameters. Bids are due by November 27, 2023 at 2:00 PM EDT and must be submitted to the identified contracting and procurement email addresses. The award is for products only without associated services.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| HW Tank Specs.pdf | ||
| 15B12124Q00000002 WATER HEATER AND PUMPS FCC HAZELTON.pdf | ||
| Pump Specs.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FCC Hazelton requires a quan�ty of 4 each indirect plate and frame water heater plus 4 each pumps to accompany the water heaters. Vendors are required to have ac�ve SAM.Gov registra�on and to provide their UEI. This requirement is for product ONLY. All quotes and bids are required to be submited to Kelly Brown, Supervisory Contract Specialist with FCC Hazelton at k1roberts@bop.gov (Note: that is a number one a�er the K) AND HAX-ProcurementProp-S@bop.gov.
Quotes must be valid for at least 30 days a�er close of bids on November 27, 2023 at 2 PM EDT. Specific product requirements below and example spec sheets atached.
Indirect Plate And Frame Water Heater: (4)
Dimensions cannot Exceed: 63” Height Max; 22” Width max; 61” Base Length – MUST FIT THROUGH STANDARD 36” door. Product should not exceed 1200 lbs – Lite Weight Preferred
FEATURES:
ASME DOUBLE WALL HEAT EXCHANGER
• 316L Stainless Steel
• 150 psi Working Pressure
DIGITAL DISPLAY
• DHW Set Point Range 90°F to 180°F
ADVANCED TEMPERATURE CONTROL
MODULATING CONTROL VALVE
SCALE REDUCING PUMP
AUTOMATIC AIR VENT
ASME TEMPERATURE & PRESSURE RELIEF
VALVE
• 210°F and 150 psi
ADJUSTABLE HIGH LIMIT
WYE STRAINERS - DOMESTIC PIPING AND
BOILER PIPING
ISOLATION VALVES - DOMESTIC PIPING
AND BOILER PIPING
MODBUS COMMUNICATION
WARRANTY
• 5-Year limited warranty/1-Year limited parts
• Warranty for product only without services requirement
Pump: (4) Specifica�ons must meet all below requirements for pump withsystem control and monitoring key
Conditions of Service Pump Data Motor Data Flow: 130 US GPM Head: 32 ft Efficiency: 68.6 % Liquid: Water Temperature: 60 °C NPSH required: ft
Maximum operating pressure: 12 bar Liquid temperature range: -10 .. 110 °C Maximum ambient temperature: 40 °C Flange standard: GF Pipe connection: GF65 Product number: On request
P1 max: 29 .. 1385 W Mains frequency: 60 Hz Enclosure class: X4D Insulation class: F
SUGGESTED SPECIFICATION
The Indirect Plate and Frame shall be constructed of a 316 stainless steel plate with EPDM gaskets. Maximum unit dimensions shall be: Length ___61_inches, Width ___22___inches and Height __63______ inches.
The Indirect Plate and Frame shall be a double wall. The plate and frame shall be constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements, stamped and registered with the Na�onal Board of Boiler and Pressure Vessel Inspectors .
The Indirect Plate and Frame shall have a 150 psi working pressure and be supplied with an ASME temperature and pressure relief valve. Standard equipment shall include Wye Strainers, Isola�on Valves, Automa�c Air Vent, Scale Reduc�on Pump, Adjustable High Limit and drain valve The temperature control shall provide + or – 4 degrees Fahrenheit accuracy with up to a 50% change in load. Setpoint range between 90 and 180 F. Modbus communica�on shall be standard equipment. The modula�ng valve shall have a 1000 to 1 turndown. The Indirect Plate and Frame shall be suitable for use with polypropylene glycol, up to 50% concentra�on. The de-rate associated with the glycol will vary per glycol manufacturer.
mailto:k1roberts@bop.gov mailto:HAX-ProcurementProp-S@bop.gov
Specific Gravity: 0.985 ADDITIONAL INFORMATION: Domes�c inlet temp Set point. DHW set point 90 to 180 degrees. GPH for all units together or for each if separated. GPH is for each unit. Each system will supply at minimum hot water to 64-cells, 10-showers, 2-mop closet and 1-staff restroom. Boiler water entering temp 160-180 degrees. Boiler water Leaving temp 120-140 degrees BTU I am looking for specifics on this. -These units are in use 24/7-365 if that helps.
For singled cell showers, 10 to be used at a �me with a maximum of up to 128.