F-FAC SVC Replacement of emergency exit Signs @ COB
Closed Solicitation Posted
- Solicitation number
- PR16062817
- Agency
-
Department of State
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 33995 Sign Manufacturing
- Place of performance
- Frankfurt 60435 Germany
- Points of contact
-
- GSO Procurement einkauf@state.gov +496975352581
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of State seeks replacement and installation of emergency exit signs and emergency egress lighting systems at the U.S. Consulate General Frankfurt, Germany, with proposals due August 9, 2026.
Place of performance is Frankfurt, Germany, at two Consulate facilities: Joachim-Becher-Strasse 19 and Giessener Strasse 30. The contractor must furnish all materials, equipment, labor, supervision, and services for complete replacement, installation, testing, commissioning, and documentation of LED exit signs and emergency luminaires. Work includes site survey and assessment of existing conditions, removal and disposal of existing fixtures, electrical modifications, firestopping of penetrations, functional testing, commissioning, labeling, and final cleanup.
All work must comply with U.S. codes and standards including NEC (NFPA 70), NFPA 101, NFPA 72, OSHA requirements, and UL 924, as well as German and European standards including DIN EN 1838, DIN EN 50172/VDE 0108-100, DIN VDE electrical installation standards, German Workplace Ordinance (ArbStattV), and local building and fire protection requirements. The approved equipment is the GESS Lumina 2000/7 (Part Number: L07W1230L13-PIKSET) or approved equal.
The contractor must demonstrate five years of documented experience in emergency egress lighting systems and completion of at least three comparable projects within the past five years, and must employ qualified, licensed electrical personnel. All personnel require Visit Authorization Requests and vehicle clearances compliant with Consulate security procedures. Period of performance is 365 calendar days. Proposals must be submitted on a firm fixed-price basis. The NAICS code is 33995, Sign Manufacturing; PSC is 9905.
Notice text
The U.S. Consulate General Frankfurt has a requirement to Replacement and Installation of Exit Signs
and Emergency Egress Lighting
A. located at the Joachim-Becher-Straße 19 and AmConGen Frankfurt, Gießener Straße 30.
The Contractor shall furnish all materials, equipment, and labor required to complete the
work. The proposed scope of work includes, but is not limited to, the following:
1. Replacement and Installation of Exit Signs and Emergency Egress Lighting
The project consists of the replacement, installation, testing, commissioning, and documentation
of emergency exit signs and emergency egress lighting systems throughout multiple Consulate
facilities. The Contractor shall provide all labor, materials, equipment, supervision,
transportation, and services necessary to deliver a complete, fully operational, and codecompliant
installation.
The scope includes a detailed site survey, assessment and documentation of existing conditions,
removal and disposal of existing fixtures, installation of new LED exit signs and emergency
luminaires, electrical modifications, firestopping of penetrations, system testing, commissioning,
labeling, and final cleanup. All work shall comply with applicable U.S. codes and standards,
including NEC (NFPA 70), NFPA 101, NFPA 72, OSHA requirements, UL 924, the
International Building Code (IBC), and local Authority Having Jurisdiction (AHJ) requirements.
As the project is located in Germany, the Contractor shall also ensure compliance with all
applicable German and European regulations and standards, including, where applicable, DIN
EN 1838 (Emergency Lighting), DIN EN 50172 / VDE 0108-100 (Emergency Escape Lighting
Systems), DIN VDE electrical installation standards, the German Workplace Ordinance
(ArbStättV), Technical Rules for Workplaces (ASR A2.3 Escape Routes and Emergency
Exits), local building regulations, and fire protection requirements.
The Contractor shall perform functional testing, emergency operation verification, illumination
measurements, and compliance checks to ensure that all installed systems meet life-safety and
emergency egress requirements. Upon completion, comprehensive closeout documentation shall
be provided, including as-built drawings, test reports, circuit schedules, product data sheets,
warranties, maintenance manuals, and an updated asset inventory.
Due to the work being performed within an active Consulate facility, strict security and access
procedures shall apply. The Contractor must demonstrate relevant experience in government,
diplomatic, institutional, or high-security facilities, employ qualified and licensed personnel, and
coordinate all activities with facility management and security representatives. Final acceptance
will be subject to successful completion of all work, testing, documentation, correction of
deficiencies, and written approval by the Contracting Officer or Owner Representative.