AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
Amendment is necessary to post the Site Visit Attendee List, provide answ ers to Requests for Information, and provide a revised set of plans.
Closing w ill be extended until April 26, 2019 at 5:00 PM. All other terms and conditions remain unchanged.
1. CONTRACT ID CODE PAGE OF PAGES
1 3
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 18-Apr-2019
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912WJ19Q0064
X 9B. DATED (SEE ITEM 11)
01-Apr-2019
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
18-Apr-2019
CODE
U S ARMY ENGR DISTRICT, NEW ENGLAND
696 VIRGINIA RD
CONCORD MA 01742-2751
W912WJ 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
ROBERT.C.GARRAHAN@USACE.ARMY.MILEMAIL:978-318-8814TEL:
ROBERT C GARRAHAN / ADDED BY UPASS
W912WJ19Q0064
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE
The following have been added by full text:
REQUESTS FOR INFORMATION
BLACK ROCK ELECTRICAL UPGRADES ATTENDEE LIST (APRIL 16, 2019)
NAME COMPANY
Jon Brida Pro-Electric Inc.
Mike Funaro Mercury Group Janet Patev USACE Richard Doughty USACE Brian Head USACE Jere Masey USACE Michael Green USACE Jennifer Samela USACE
REQUESTS FOR INFORMATION:
1. Who is responisble for the transformer disposal?
Answer: The contractor is responsible for the transformer disposal. Transformers do not contain PCBs.
2. Can wires be crimped rather than spliced?
Answer: No, splice kits are specified; compression kits will not be accepted.
3. Which connectors (feeders) are to remain and which are to be replaced?
Answer: The connector from project office to disconnect at base of dam remains. The connector from disconnect to gatehouse will be replaced.
4. Who originally pulled the feed from the disconnect to the gatehouse?
Answer: The US Army Corps of Engineers did.
5. The disconnect remains at the pole at the base of the dam?
Answer: Yes, it remains.
6. What is the size of the feed from the Project Office to the base of the dam?
Answer: Feed is 3 phase, 480V, ungrounded.
7. Are any new grounding rods to be added at the base of the dam at the disconnect?
Answer: No.
8. The bonding at the pole of the base of the dam is only to the lightning arrestors and doesn’t include the disconnect. Will the disconnect need to be bonded?
Answer: Yes, the contractor will need to bond the disconnect.
9. Is an equipment grounding conductor required?
Answer: Yes, the contractor will need to run an equipment grounding conductor from the disconnect at the base of the dam to the gatehouse.
10. Will additional grounding be required at the gatehouse?
Answer: Yes, an additional ground rod will be installed at the base of the gatehouse.
11. How do we access the base of the gatehouse?
Answer: Access for vehicles to the base of the gatehouse will be provided by the US Army Corps of Engineers.
SECTION A - SOLICITATION/CONTRACT FORM
The required response date/time has changed from 22-Apr-2019 05:00 PM to 26-Apr-2019 05:00 PM.
(End of Summary of Changes)
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
C O
N C
O R
D
M A
-2
V
IR
G
IN
IA
R
O A
D
N E
W E
N G
L A
N D D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
D R
A W
IN
G C
O D
E
S C
A L E
S H
E E
T
F
H
U -B
R -1
T H
O M
A S
T O
N
C O
N N
E C
T
IC
U T
B L
A C
K R
O C
K L
A K
E
E L E
C T
R
IC
A L U
P G
R A
D E
S
SHEET ID
®of Engineers
US Army Corps
W
W J
Q 4 7
DESIGN FILESHEET NO.
G-001
INDEX TO DRAWINGS
SHEET TITLE
HOU-BR-118_G-001.DGN
A N
S I
D
G-001
:1
HOU-BR-118_E-501.DGN
HOU-BR-118_ED-101.DGNED-101
E-501
ED-601 HOU-BR-118_ED-601.DGN
New England District of Engineers
US Army Corps
PROJECT
LOCATION
PROJECT
LOCATION
TORRINGTON
WATERBURY
THOMASTON
NORTHFIELD
BRISTOL
WATERTOWN
MASSACHUSETTS
N E
W Y
O R
K
WATERBURY
THOMASTON
HARTFORD
SPRINGFIELD
CONNECTICUT
B R
A N
C H B
R O
O K
BLACK ROCK LAKE
COVER SHEET AND INDEX TO DRAWINGS
E-101 HOU-BR-118_E-101.DGN
ELECTRICAL DEMOLITION INTAKE STRUCTURE AND PROJECT OFFICE
NEW ELECTRICAL INSTALLATION INTAKE STRUCTURE AND PROJECT OFFICE
B
H E
A D
D
H A
S S
E T
T
J
C L
IN
E
ELECTRICAL ONE LINE DIAGRAM DEMOLITION
E-601 HOU-BR-118_E-601.DGN ELECTRICAL ONE LINE DIAGRAM INSTALLATION7
ELECTRICAL DETAILS
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
THOMASTON, CONNECTICUT
BLACK ROCK LAKE
ELECTRICAL UPGRADES
R
U
TE
109 B
R A N C
H R
D
DAM
T O
P O
F D
A M
E L
OLD BRANCH RD.
C O
N N E C T
IC
U T R
IV
E R
STRUCTURE
INTAKE
NOT TO SCALE NOT TO SCALE
NOT TO SCALE
SITE PLAN
VICINITY MAPLOCATION PLAN
J S
W A
L L E
Y
FROM RT. 109
CONTRACTOR'S ACCESS
OUTLET CHANNEL
SPILLWAY
PROJECT OFFICE
ACCESS ROAD
FUSIBLE DISCONNECT
APPROXIMATE LOCATION OF
100' X 50'
STORAGE AREA
CONTRACTOR'S
C O
V E
R S
H E
E T A
N D I
N D
E X T
O D
R A
W
IN
G S
A P
R
IL
HOU-BR-118_E-502.DGNE-5026 GATE TOWER GROUNDING SCHEMATIC INSTALLATION
APRIL 2019
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
C O
N C
O R
D
M A
-2
V
IR
G
IN
IA
R
O A
D
N E
W E
N G
L A
N D D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
D R
A W
IN
G C
O D
E
S C
A L E
S H
E E
T
U -B
R -1
T H
O M
A S
T O
N
C O
N N
E C
T
IC
U T
B L
A C
K R
O C
K L
A K
E
E L E
C T
R
IC
A L U
P G
R A
D E
S
SHEET ID
®of Engineers
US Army Corps
W
W J
Q
SERVICE
BRIDGE
BALCONY
ELEVATOR
FLOAT
LADDER
LADDER
DOWNVALVES
PUMPS
HATCHWAY
EXTERIOR WALL
GATE TOWER
TRANSFORMER
GATE TOWER RAILING
TRANSFORMER
PHASE GENERATOR
EXISTING SINGLE
LOCATION
WEATHERHEAD
OFFICE GENSET
208V PANEL B
PANEL LP-1
PANEL
INSTRUMENT
PANEL RP-1
480V PANEL A
PANEL MDP-1
TO BE REPLACED
CIRCUIT BREAKER
MANUAL TRANSFER SWITCH
ES
ES
POLE 1
POLE 2
C1 C5
N N
0 4' 8'2' 0 4' 8'2'SCALE: 1/4" = 1'- 0"SCALE: 1/4" = 1'- 0"
KEYED NOTES FOR INTAKE STRUCTURE: KEYED NOTES FOR PROJECT OFFICE:
B
H E
A D
D
H A
S S
E T
T
A N
S I
D
ED-101
E L E
C T
R
IC
A L D
E M
O L
IT
IO
N
IN
T
A K
E S
T R
U C
T U
R E A
N D
P R
O J E
C T O
F F
IC
E :1
PROJECT OFFICE ELECTRICAL FLOOR PLAN DEMOLITION
J
C L
IN
E
INTAKE STRUCTURE ELECTRICAL FLOOR PLAN DEMOLITION
J S
W A
L L E
Y
REQUIRED TO RESTORE FEEDER TO PANEL-A.
DEMOLISH INSTRUMENT PANEL. PROVIDE CONDUIT, WIRE, AND JUNCTION BOX AS
BREAKERS AND ASSOCIATED CONDUCTORS TO REMAIN.
DEMOLISH MAIN CIRCUIT BREAKER IN EXISTING PANELBOARD B. PANELBOARD, BRANCH
RETAIN CONDUITS FOR REUSE.
CONDUCTORS BACK TO DISCONNECT AT THE BASE OF THE DAM AND OUT TO THE MTS.
DEMOLISH SERVICE ENTRANCE ENCLOSED CIRCUIT BREAKER AND ASSOCIATED
D E
C
10 SEE CONDUIT AND CABLE SCHEDULE ON E-501 FOR ESTIMATED LENGTHS.
RUNNING FROM TRANSFORMER TO INTAKE STRUCTURE.
DEMOLISH TAP ON SECONDARY SIDE OF THE TRANSFORMER AND RETAIN POLE MOUNTED LOW VOLTAGE CONDUCTORS
DEMOLISH LOW VOLTAGE CONDUCTORS FROM TRANSFORMER TO SERVICE ENTRANCE PANEL MDP-1.
9 DEMOLISH POLE MOUNTED TRANSFORMERS AND ASSOCIATED FUSED CUT-OUT AND CONDUCTORS SEE SHEET ED-601.
BACK TO UTILITY METER, LOCATED AT POLE 2.
8 DEMOLISH OVERHEAD MEDIUM VOLTAGE CABLES FROM POLE MOUNTED TRANSFORMER, LOCATED ON POLE 1, 7 NOT USED.
FOR REFEEDING FROM NEW PANEL.
6 DEMOLISH PANELBOARD RP-1, RETAIN CONDUIT AND WIRE SUPPLYING BRANCH CIRCUIT LOADS
5 DEMOLISH DOUBLE THROUGH SAFETY SWITCH.
4 DEMOLISH ENCLOSED CIRCUIT BREAKER. RETAIN CONDUIT AND WIRE FOR REUSE.
A P
R
IL
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
C O
N C
O R
D
M A
-2
V
IR
G
IN
IA
R
O A
D
N E
W E
N G
L A
N D D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
D R
A W
IN
G C
O D
E
S C
A L E
S H
E E
T
U -B
R -1
T H
O M
A S
T O
N
C O
N N
E C
T
IC
U T
B L
A C
K R
O C
K L
A K
E
E L E
C T
R
IC
A L U
P G
R A
D E
S
SHEET ID
®of Engineers
US Army Corps
W
W J
Q 4 7
B
H E
A D
B
H E
A D
A N
S I
D
ED-601
:1
UTILITY BUS
S.E. XFMR PRI
S.E. XFMR SEC
OFFICE XFMR PRI
OFFICE XFMR SEC
CAMPER FDR TAP
RV HOOKUP 2
MTS-OFFICE
OFF GENSET
G.T. SERVICE FDR
G.T. GENSET BUS
G.T. XFMR SEC
RV HOOKUP 1
HDP 1 HDP 2 BUS-2
HOIST BUS
G.T. XFMR PRI
AERIAL END
UTILITY
S.E. XFMR
150 kVA
4.8 - 0.48 kV
2.3%
OFFICE XFMR
45 kVA
0.48 - 0.208 kV
6.3%
15 kVA
0.48 - 0.208 kV
2.45%
OFF LTS RCPTS RV HOOK UP 2 LD
HYDRAULIC PMP 1 HYDRAULIC PUMP 2 ELEVATOR
HOIST
RV HOOK UP 1 LD
G.T. PUMP-1
C-H FD
225/20
OFFICE S.E.
SIEMENS FXD6
250/200
S.E. PNL BRANCH
SIEMENS BQD
100/100
OFFICE FEEDER
GE THQL
125/60
RV FEEDER
GE THQL
125/100
RV-2 CB
GE THQL
125/50
OFFICE GENSET CB
C-H FG
150/35
OFFICE GEN CB-2
GE TEF
100/50
OFFICE MAIN
GE TE
100/70
G.T. GENSET
GE TED (480V)
150/40
G.T. XFMR FDR
C-H FD
225/50
OFFICE BRANCH
GE TE
100/50
RV-2 LOADS
GE THQL
125/20
G.T. PUMP-2
C-H FD
225/20
G.T. SPARE
C-H FD
225/70
G.T. ELEVATOR
C-H FD
225/20
G.T. HOIST
C-H FD
225/30
RV-1 CB
GE THQL
125/50
RV-1 LOADS
GE THQL
125/20
8 8
ABBREVIATIONS:
J
C L
IN
E
E L E
C T
R
IC
A L O
N E L
IN
E D
IA
G R
A M D
E M
O L
IT
IO
N
FS-1
BUSS FRS-R(RK5)
200A
225/200
GE THQD
OFF 208V PNL MN
150/50
GE TED (480V) OLD
G.T. S.E. CB
G.T. GENSET (EXISTING)
OFFICE GENSET (EXISTING)
MDP-1
RP-1
ELECTRICAL CONDUCTOR DEMOLITION
ELECTRICAL CONDUCTOR EXISTING
ELECTRICAL BUS
EQUIPMENT ENCLOSURE
LINE TYPES:
LP-1
PANEL-A
PANEL-B
100/70
GE THQB
PANEL-B
(INTAKE STRUCTURE)
S.E. GATE TOWER
MTS-GATE TOWER (INTAKE STRUCTURE)
STRUCTURE) XFMR
GATE TOWER (INTAKE
J S
W A
L L E
Y
KEYED NOTES:
XFMR TRANSFORMER
THQL GENERAL ELECTRIC MODEL THQB CIRCUIT BREAKER
TEF GENERAL ELECTRIC MODEL TEF CIRCUIT BREAKER
TED GENERAL ELECTRIC MODEL TED CIRCUIT BREAKER
TE GENERAL ELECTRIC BREAKER TYPE TE
SEC SECONDARY
S.E. SERVICE ENTRANCE
RV RECREATIONAL VEHICLE
RCPTS RECEPTACLES
PRI PRIMARY
PNL PANEL
MTS MANUAL TRANSFER SWITCH ALSO CALLED DOUBLE THROW SAFETY SWITCH
MN PANEL NAME
LD LOAD
kV KILOVOLT
GE GENERAL ELECTRIC
G.T. GATE TOWER
FDR FEEDER
C-H FG CUTTLER-HAMMER TYPE FG FUSE
C-H FD CUTTLER-HAMMER TYPE FD FUSE
CB CIRCUIT BREAKER
BKR BREAKER
SWITCH AND PANEL MDP-1.
DEMOLISH MANUAL TRANSFER SWITCH AND ASSOCIATED CONDUIT AND WIRE BETWEEN MANUAL TRANSFER
CONDUCTORS TO THE PROJECT OFFICE.
GATE TOWER DISCONNECT AT BASE OF THE DAM TO BE RETAINED FOR REUSE. DEMOLISH SERVICE
DEMOLISH SPLICE ON THE SECONDARY OF POLE MOUNTED TRANSFORMER. CONDUCTORS RUNNING TO THE
PER KEYED NOTE 9.
POINT OF DEMARCATION TO TRANSFORMER AND FROM TRANSFORMER TO MANUAL DISCONNECT DEMOLISHED
DEMOLISH POLE MOUNTED TRANSFORMER, ASSOCIATED FUSED CUTOUT, AERIAL CONDUCTORS FROM UTILITY
CONTRACTOR SHALL MAINTAIN PHASE ROTATION.
CONTRACTOR SHALL LABEL THE CONDUCTORS FEEDING EACH BRANCH CIRCUIT PRIOR TO DEMOLITION.
DEMOLISH PANELBOARD. PANELBOARD TO BE REPLACED IN SAME LOCATION PER SHEETS E-101 AND E-601.
DEMOLISH ENCLOSED CIRCUIT BREAKER. RETAIN CONDUIT AND WIRE FOR REUSE.
DEMOLISH EXISTING MANUAL TRANSFER SWITCH IN PROJECT OFFICE. RETAIN CONDUIT AND WIRE FOR REUSE.
ASSOCIATED CONDUIT AND WIRE TO REMAIN.
DEMOLISH MAIN CIRCUIT BREAKER IN EXISTING PANELBOARD. PANELBOARD, BRANCH BREAKERS AND
THE LINE AND LOAD SIDE.
DEMOLISH SERVICE ENTRANCE ENCLOSED CIRCUIT BREAKER. DEMOLISH ASSOCIATED CONDUIT AND WIRE ON
INTAKE STRUCTURE. DISCONNECT AND CONDUIT TO REMAIN.
DEMOLISH 200A FUSES IN EXISTING DISCONNECT AND ASSOCIATED CONDUCTORS FROM DISCONNECT TO
A P
R
IL
480V PANEL A
O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
C O
N C
O R
D
M A
-2
V
IR
G
IN
IA
R
O A
D
N E
W E
N G
L A
N D D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
D R
A W
IN
G C
O D
E
S C
A L E
S H
E E
T
U -B
R -1
T H
O M
A S
T O
N
C O
N N
E C
T
IC
U T
B L
A C
K R
O C
K L
A K
E
E L E
C T
R
IC
A L U
P G
R A
D E
S
SHEET ID
®of Engineers
US Army Corps
W
W J
Q
SERVICE
BRIDGE
BALCONY
ELEVATOR
FLOAT
LADDER
LADDER
DOWNVALVES
PUMPS
HATCHWAY
EXTERIOR WALL
GATE TOWER
TRANSFORMER
GATE TOWER RAILING
TRANSFORMER
PHASE GENERATOR
EXISTING SINGLE
LOCATION
WEATHERHEAD
OFFICE GENSET
208V PANEL B
PANEL LP-1
PANEL RP-1
480V PANEL A
PANEL MDP-1
DEVICE
PROTECTIVE
SURGE
TO BE REPLACED
CIRCUIT BREAKER
ES
ES
POLE 1
POLE 2
C1 C5
N
N
0 4' 8'2' 0 4' 8'2'SCALE: 1/4" = 1'- 0"SCALE: 1/4" = 1'- 0"
KEYED NOTES FOR INTAKE STRUCTURE: KEYED NOTES FOR PROJECT OFFICE:
D
H A
S S
E T
T
E-101
P R
O J E
C T O
F F
IC
E :1
PROJECT OFFICE ELECTRICAL FLOOR PLAN INSTALLATION
J
C L
IN
E
B
H E
A D
A N
S I
D
N E
W E
L E
C T
R
IC
A L I
N S
T A
L L
A T
IO
N
IN
T
A K
E S
T R
U C
T U
R E A
N D
J S
W A
L L E
Y
DOUBLE THROW SAFETY SWITCH
INTAKE STRUCTURE ELECTRICAL FLOOR PLAN INSTALLATION
SPECIFICATION 26 20 00.
2 PROVIDE NEW MAIN CIRCUIT BREAKER IN EXISTING PANELBOARD B PER SHEET E-601 AND
KEYED NOTE 1 BACK TO AERIAL END (DISCONNECT AT BASE OF DAM) AND OUT TO THE MTS.
SPECIFICATION 26 20 00. PROVIDE CONDUCTORS IN CONDUITS RETAINED PER SHEET ED-101
1 PROVIDE SERVICE ENTRANCE ENCLOSED CIRCUIT BREAKER PER SHEET E-601 AND
12. SEE CONDUIT AND CABLE SCHEDULE ON E-501 FOR ESTIMATED LENGTHS.
PROVIDE 20A 3-POLE BREAKER IN PANEL MDP-1 AS SPECIFIED IN 26 20 00.
11 PROVIDE SURGE PROTECTIVE DEVICE AS SPECIFIED IN 26 20 00, CONDUIT AND WIRE BACK TO PANEL MDP-1.
PER KEYED NOTE 8 ON SHEET ED-601. SEE DETAIL SHEET E-501.
SPLICE CONDUCTORS INSTALLED PER KEYED NOTE 8 SHEET E-601 TO CONDUCTORS RETAINED
10 PROVIDE TAP KIT PER SPECIFICATION 26 20 00 IN A NEMA-3R ENCLOSURE MOUNTED ON EXTERIOR POLE.
PROVIDE ASSOCIATED SUPPORTS AND INSULATORS. REUSE EXISTING WEATHERHEAD.
9 PROVIDE AERIAL CONDUCTORS FROM METER SOCKET TO SERVICE ENTRANCE PANEL MDP-1 PER SPECIFICATION 33 71 01.
ON THIS DRAWING) AND CONDUCTORS FROM UTILITY OWNED POLE TO METER SOCKET.
UTILITY TO PROVIDE POLE MOUNTED TRANSFORMERS ON UTILITY OWNED POLE ON OLD BRANCH ROAD (NOT SHOWN
8 PROVIDE GALVANIZED RIGID STEEL RISER ON EXISTING POLE.
AS REQUIRED TO MAKE THE INSTALLATION COMPLETE.
TO RISER INSTALLED PER KEYED NOTE 8, MOUNT METER SOCKET TO EXISTING POLE USING BOLTS, ANCHORS, STRUT, ETC.
7 PROVIDE METER SOCKET AS SPECIFIED IN 26 20 00 AND CONDUIT FROM METER SOCKET
IN EXISTING PANELBOARD MDP-1.
6 PROVIDE CIRCUIT BREAKER AS INDICATED ON SHEET E-601 AND PER SPECIFICATION 26 20 00
SPECIFICATION 26 20 00. REUSE EXISTING CONDUIT AND WIRE RETAINED PER SHEET ED-601 KEYED NOTE 6.
5 PROVIDE 240V 1-PHASE, 60A SINGLE THROW NONFUSED SAFETY SWITCH PER SHEET E-601 AND
PROVIDE CONDUIT AND WIRE BACK TO DOUBLE THROW SAFETY SWITCH INSTALLED PER KEYED NOTE 3.
4 PROVIDE 120/240V 100A 1-PHASE PANELBOARD RP-1 PER SPECIFICATION 26 20 00.
WIRE FROM SINGLE PHASE GENERATOR RETAINED PER SHEET ED-101 AND ED-601.
PER SPECIFICATION 26 20 00. PROVIDE CONDUIT AND WIRE BACK TO PANEL LP-1 AND RECONNECT CONDUIT AND
3 PROVIDE 240V 60A 1-PHASE NON FUSED DOUBLE THROW SAFETY SWITCH WITH SOLID NEUTRAL
A P
R
IL
E-501
E1
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
C O
N C
O R
D
M A
-2
V
IR
G
IN
IA
R
O A
D
N E
W E
N G
L A
N D D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
D R
A W
IN
G C
O D
E
S C
A L E
S H
E E
T
U -B
R -1
T H
O M
A S
T O
N
C O
N N
E C
T
IC
U T
B L
A C
K R
O C
K L
A K
E
E L E
C T
R
IC
A L U
P G
R A
D E
S
SHEET ID
®of Engineers
US Army Corps
W
W J
Q
R
IA
N H
E A
D
B R
IA
N H
E A
D
A N
S I
D
E L E
C T
R
IC
A L D
E T
A
IL
S
E1
POLE MOUNTED J-BOX DETAIL
E-101
C5
CONDUIT AND CABLE SCHEDULE
VOLTAGE
CONDUCTORS
OF
NUMBER
(AWG)
SIZE
WIRE
(AWG)
SIZE
GROUND
SIZE -TYPE
CONDUIT
LENGTH
APPROX.
CONDUIT AND CABLE SCHEDULE NOTES
SOURCE LOAD
25'
480/277V 850'
480/277V
480/277V
4/0
1/0
EXISTING
4.0"-RGS
1/0 1.5"-RGS 10'
208 22.8 1.7
208 85.4 11.9
52.3 5.8
6.1 0.2
480 4.9 0.2
VOLTAGE
(INCHES)
BOUNDARY
APPROACH
(CAL/cm2_
ENERGY
INCIDENT
51.1 5.6
EQUIPMENT
NOTE:
480/277V 130'AERIAL4 4/0 2
MDP-1
TRANSFER SWITCH
AERIAL
3.0"-RGS/
AERIAL END (DISC AT BASE OF DAM)
MDP-1
G.T. SERVICE FEEDER DISCONNECT
MTS GATE TOWER
208 20.3 1.4
21.9 1.6
39.3 3.8
28.7 2.4
208 28.8 2.4
VOLTAGE
(INCHES)
BOUNDARY
APPROACH
(CAL/cm2_
ENERGY
INCIDENT
25.8 2.0
EQUIPMENT
NOTE:
480 20.8 1.5
480 12.6 0.7
480 12.6 0.7
480 12.6 0.7
HOIST DISCONNECT
HDP-1
HDP-2
ELEVATOR
OFFICE TRANSFORMER
LP-1
MTS-OFFICE
RP-1
RV HOOKUP 1
RV HOOKUP 2
119.3 19.4
PANEL-A
PANEL-B
SERVICE ENTRANCE
GATE TOWER (INTAKE STRUCTURE)
SERVICE ENTRANCE
GATE TOWER (INTAKE STRUCTURE)
J
C L
IN
E
:1
E-501
(INTAKE STRUCTURE)
SERVICE ENTRANCE GATE TOWER
TRANSFORMER
GATE TOWER (INTAKE STRUCTURE)
EXISTING POLE
JUNCTION BOX
TO GATE TOWER
EXISTING CONDUCTORS RUNNING
TO PROJECT OFFICE
CONDUCTORS RUNNING
ANCHOR BOLT
CONTRACTOR PROVIDED
SUPPORT CABLE
CONDUCTORS RUNNING TO PROJECT OFFICE
BUSHING ON J-BOX PENETRATION
ABOVE GRADE
JUNCTION BOX 15'
NOT TO SCALE
FRONT VIEW SIDE VIEW
J S
W A
L L E
Y
UTILITY, POLE 2 MDP-1, VIA POLE 1
JUNCTION BOX ON POLE 1 (SEE DETAIL ABOVE)
AND NOTE 3
SEE SPEC. 33 71 01
480/277VAERIAL END (DISC AT BASE OF DAM)
(SEE DETAIL ABOVE)
JUNCTION BOX ON POLE 1
(EXISTING)
400'
(EXISTING)
4/0
AERIAL
AND NOTE 5
SEE SPEC. 33 71 01
5. PHASE CONDUCTORS ARE EXISTING. PROVIDE GROUND CONDUCTOR AS INDICATED.
GROUND CONDUCTOR WHICH MUST ALSO BE PROVIDED.
4. THE NUMBER OF CONDUCTORS IN THE ABOVE SCHEDULE IS THE NUMBER OF CURRENT CARRYING CONDUCTORS, IT DOES NOT INCLUDE THE
3. 130' LENGTH INCLUDES 40' FOR VERTICAL POLE HEIGHT.
2. REFEED CIRCUITS SHOWN ON PANEL SCHEDULE, SEE SHEET E-601.
1. LENGTH ON THIS SCHEDULE IS APPROXIMATE, CONTRACTOR SHALL CONFIRM LENGTH IN THE FIELD.
A P
R
IL
LABELS.
RISK ASSESSMENT AND SUBMIT RESULTS FOR REVIEW PRIOR TO PLACING
CONTRACTOR SHALL SUBMIT AN RFI OR CONDUCT AN INDEPENDENT ARC FLASH
USED OTHER THAN THOSE SPECIFICALLY IDENTIFIED IN THE SPECS,
DIFFERENT WIRE OR OVERCURRENT PROTECTIVE DEVICES ARE APPROVED AND
PROVIDE ARC FLASH LABELS ON EACH PIECE OF EQUIPMENT PER THIS TABLE. IF
LABELS.
RISK ASSESSMENT AND SUBMIT RESULTS FOR REVIEW PRIOR TO PLACING
CONTRACTOR SHALL SUBMIT AN RFI OR CONDUCT AN INDEPENDENT ARC FLASH
USED OTHER THAN THOSE SPECIFICALLY IDENTIFIED IN THE SPECS,
DIFFERENT WIRE OR OVERCURRENT PROTECTIVE DEVICES ARE APPROVED AND
PROVIDE ARC FLASH LABELS ON EACH PIECE OF EQUIPMENT PER THIS TABLE. IF
CONDUCTOR TO JUNCTION BOX
BOND EQUIPMENT GROUNDING
N/A
A
P R
C
O R
R E
C T
E D E
Q U
IP
M E
N T G
R O
U N
D
IN
G C
O N
D U
C T
O R I
N S
T A
L L
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
C O
N C
O R
D
M A
-2
V
IR
G
IN
IA
R
O A
D
N E
W E
N G
L A
N D D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
D R
A W
IN
G C
O D
E
S C
A L E
S H
E E
T
U -B
R -1
T H
O M
A S
T O
N
C O
N N
E C
T
IC
U T
B L
A C
K R
O C
K L
A K
E
E L E
C T
R
IC
A L U
P G
R A
D E
S
SHEET ID
®of Engineers
US Army Corps
W
W J
Q 4 7
B R
IA
N H
E A
D
B R
IA
N H
E A
D
A N
S I
D
E-502
G A
T E T
O W
E R
G R
O U
N D
IN
G S
C H
E M
A T
IC
IN
S
T A
L L
A T
IO
N N .T .S
SCALE: N.T.S.
A1
#2 MIN.
A B C
A B C
20 KW GENERATOR SET
A B C
G
PHASE AND NEUTRAL #4/0
125A FUSE
CONDUCTOR
GROUNDING
#2 EQUIPMENT
N G
CBA
CONDUCTOR
GROUNDING
#3 EQUIPMENT
(PROJECT OFFICE)
TO PANEL MDP
(EXISTING)
PHASE AND NEUTRAL #2
A B C
G
S.E. GATE TOWER
CONDUCTOR
GROUNDING
#2 EQUIPMENT
CONDUCTOR
GROUNDING
#3 EQUIPMENT
100A BREAKER
PHASE AND NEUTRAL #2
CONDUCTOR
GROUNDING
#2 EQUIPMENTPHASE AND NEUTRAL #2
#2 MIN.
N G
CBA
#2 MIN
SYSTEM BONDING JUMPER
#4/0 BARE CU.
(EXISTING)
CONDUCTOR
DOWN
LIGHTNING
GATE TOWER GROUNDING DETAIL
(EXISTING)
TRANSFORMER 15 KVA
(EXISTING)
480V
PANEL-A
(EXISTING)
208V
PANEL-B
(EXISTING)
PHASE AND NEUTRAL #4
(EXISTING)
PHASE AND NEUTRAL #2
(EXISTING)
SWITCH
TRANSFER
MANUAL
(EXISTING)
STEEL COLUMN
(EXISTING)
STEEL COLUMN
G
(EXISTING)
G.T. SERVICE FDR
#4/0 CONDUCTORS
PHASE AND NEUTRAL
KEYED NOTES:
#2 EQUIPMENT GROUNDING CONDUCTOR
(EXISTING)
PHASE #6
CONDUCTOR
GROUNDING
#10 EQUIPMENT
STRUCTURE NEAR THE BASE OF THE GATE TOWER. MARK THE LOCATION.
PROVIDE GROUNDING ELECTRODE AS SPECIFIED IN 26 20 00. INSTALL GROUNDING ELECTRODE OUTSIDE
(TWO TOTAL).
CADWELD GROUNDING ELECTRODE TO BUILDING STEEL AND TO LIGHTNING PROTECTION DOWN CONDUCTORS
PROVIDE GROUNDING ELECTRODE CONDUCTOR FROM BUILDING STEEL TO GROUNDING ELECTRODE.
PROVIDE SYSTEM BONDING JUMPER IN PANEL B.
PROVIDE EQUIPMENT GROUNDING CONDUCTOR FROM PANEL A TO TRANSFORMER.
PROVIDE EQUIPMENT GROUNDING CONDUCTOR FROM GENERATOR TO MANUAL TRANSFER SWITCH.
PROVIDE EQUIPMENT GROUNDING CONDUCTOR FROM MANUAL TRANSFER SWITCH TO PANEL A.
PROVIDE GROUND BUS IN EXISTING MANUAL TRANSFER SWITCH.
EXISTING MANUAL TRANSFER SWITCH.
PROVIDE CONDUIT AND CONDUCTORS FROM ENCLOSED CIRCUIT BREAKER INSTALLED PER KEYED NOTE 4 TO
ELECTRODE CONDUCTOR TO BUILDING STEEL.
AND GROUNDING ELECTRODE CONDUCTOR FROM ENCLOSURE TO BUILDING STEEL. CAD WELD GROUNDING
PROVIDE ENCLOSED SERVICE ENTRANCE CIRCUIT BREAKER AS SPECIFIED IN 26 20 00. PROVIDE GROUND BUS
PROVIDE GROUND BUS AND ASSOCIATED GROUNDING AND BONDING IN EXISTING DISCONNECT.
PROVIDE FUSES IN EXISTING DISCONNECT PER SPECIFICATION 26 20 00.
PROVIDE EQUIPMENT GROUNDING CONDUCTOR, SEE SHEETS E-601 AND E-101.
A P
R
IL
J
C L
IN
E
J S
W A
L L E
Y
(EXISTING)
TO LIGHTNING ARRESTOR
GROUND CONDUCTOR
SPLICE TO EXISTING
EXISTING AT POLE
GROUNDING ELECTRODE
A
P R
C
O R
R E
C T
E D I
N S
T A
L L O
F E
Q U
IP
M E
N T G
R O
U N
D
IN
G C
O N
D U
C T
O R
(EXISTING OVERHEAD)
#4/0 CONDUCTORS
PHASE AND NEUTRAL
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
C O
N C
O R
D
M A
-2
V
IR
G
IN
IA
R
O A
D
N E
W E
N G
L A
N D D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
D R
A W
IN
G C
O D
E
S C
A L E
S H
E E
T
U -B
R -1
T H
O M
A S
T O
N
C O
N N
E C
T
IC
U T
B L
A C
K R
O C
K L
A K
E
E L E
C T
R
IC
A L U
P G
R A
D E
S
SHEET ID
®of Engineers
US Army Corps
W
W J
Q
H E
A D
B
H E
A D
A N
S I
D
E-601
:1
OFFICE XFMR PRI
OFFICE XFMR SEC
CAMPER FDR TAP
RV HOOKUP 2
OFF GENSET
G.T. SERVICE FDR
G.T. GENSET BUS
G.T. XFMR SEC
RV HOOKUP 1
HDP 1 HDP 2 BUS-2HOIST BUS
AERIAL END
MTS-OFFICE
HYDRAULIC PMP 1
5 HP
INDUCTION
16.7%
HYDRAULIC PUMP 2
5 HP
INDUCTION
16.7%
ELEVATOR
5 HP
INDUCTION
16.7%
HOIST
3 HP
INDUCTION
16.7%
UTILITY
UNKNOWN
RV HOOK UP 2 LDRV HOOK UP 1 LD
S.E. XFMR
75 kVA
4.8 - 0.48 kV
2.3%
OFFICE XFMR
45 kVA
0.48 - 0.208 kV
6.3%
15 kVA
0.48 - 0.208 kV
2.45%
C-4
C-5
C-RV'S
C-RV2C-RV1
C-OFF FDR
C-OFF GENSET
C-OFF PNL
C-12
C-13
C-14
C-15
C-16
C-HDP1 C-HDP2
C-ELEVC-HOIST
C-XFMR
C-19
G.T. PUMP-1
C-H FD
225/20
OFFICE S.E.
SIEMENS FXD6
250/200
S.E. PNL BRANCH
SIEMENS BQD
100/100
OFF 208V PNL MN
GE THQD
225/150
OFFICE FEEDER
GE THQL
125/60
RV FEEDER
GE THQL
125/100
RV-2 CB
GE THQL
125/50
OFFICE GENSET CB
C-H FG
150/35
OFFICE MAIN
GE TE
100/70
G.T. S.E. CB
C-H KD
400/100
G.T. GENSET
GE TED (480V)
150/40
G.T. XFMR FDR
C-H FD
225/50
OFFICE BRANCH
GE TE
100/50
RV-2 LOADS
GE THQL
125/20
G.T. PUMP-2
C-H FD
225/20
G.T. SPARE
C-H FD
225/70
G.T. ELEVATOR
C-H FD
225/20
G.T. HOIST
C-H FD
225/30
RV-1 CB
GE THQL
125/50
G.T. 208V MAIN
GE THQB
100/60
RV-1 LOADS
GE THQL
125/20
G.T. FEEDER
SIEMENS NEB
125/125
UTILITY BUS
S.E. XFMR PRI
S.E. XFMR SEC
S.E. CABLE
KEYED NOTES:
G.T. XFMR PRI
J
C L
IN
E
E L E
C T
R
IC
A L O
N E L
IN
E D
IA
G R
A M I
N S
T A
L L
A T
IO
N
125A~
BUSS FRS-R(RK5)
FS-1 G.T. GENSET (EXISTING)
OFFICE GENSET (EXISTING)
RP-1
MDP-1
SIEMENS BQD
100/20
SPD LINE TYPES:
SPD
LP-1
PANEL-A
PANEL-B
MTS-GATE TOWER (INTAKE STRUCTURE)
(INTAKE STRUCTURE)
S.E. GATE TOWER
(INTAKE STRUCTURE)
GATE TOWER XFMR
ELECTRICAL CONDUCTOR EXISTING
ELECTRICAL BUS
EQUIPMENT ENCLOSURE
J S
W A
L L E
Y
PROVIDE SURGE PROTECTIVE DEVICE AS SPECIFIED IN 26 20 00. PROVIDE CONDUIT AND WIRE BACK TO SOURCE.
PROVIDE MAIN CIRCUIT BREAKER IN EXISTING PANEL AS INDICATED.
SPECIFICATION 26 20 00.
CONTRACTOR SHALL HIRE THE LOCAL UTILITY EVERSOURCE TO PROVIDE POLE MOUNTED TRANSFORMER SEE
CONDUCTORS INSTALLED PER KEYED NOTE 8 TO CONDUCTORS RETAINED PER KEYED NOTE 9 ON SHEET ED-601.
PROVIDE TAP KIT PER SPECIFICATION 26 20 00 IN A NEMA-3R ENCLOSURE MOUNTED ON EXTERIOR POLE. SPLICE
WIRE INSTALLED OUTSIDE MUST BE AERIAL PER SPECIFICATION 33 71 01.
PROVIDE CONDUIT AND WIRE, (3) 4/0 & #3G, FROM PANEL MDP-1 TO JUNCTION BOX INSTALLED PER KEYED NOTE 9.
PROVIDE CIRCUIT BREAKER AS INDICATED AND PER SPECIFICATION 26 20 00 IN EXISTING PANELBOARD MDP-1.
PANELBOARD. PROVIDE PANEL SCHEDULE.
PER SHEET ED-601. EACH LOAD MUST BE FED FROM THE SAME BREAKER DESIGNATION AS THE PREVIOUS
PROVIDE PANELBOARD PER SPECIFICATION 26 20 00. CONTRACTOR SHALL REFEED LOADS ON PANEL DEMOLISHED
EXISTING CONDUIT AND WIRE RETAINED PER SHEET ED-601 KEYED NOTE 6.
PROVIDE 240V 1-PHASE, 100A SINGLE THROW NONFUSED SAFETY SWITCH PER SPECIFICATION 26 20 00. REUSE
AND WIRE RETAINED PER SHEET ED-601 KEYED NOTE 4.
PROVIDE 240V 1-PHASE, 60A MANUAL TRANSFER SWITCH PER SPECIFICATION 26 20 00. REUSE EXISTING CONDUIT
PROVIDE MAIN CIRCUIT BREAKER IN EXISTING PANELBOARD AS INDICATED AND AS SPECIFIED IN 26 20 00.
EXISTING CONDUITS BACK TO DISCONNECT AT THE BASE OF THE DAM AND OUT TO THE MTS.
PROVIDE ENCLOSED CIRCUIT BREAKER IN NEMA-12 ENCLOSURE AS SPECIFIC IN 26 20 00. PROVIDE CONDUCTORS IN
PROVIDE FUSES IN EXISTING DISCONNECT AS INDICATED AND AS SPECIFIED IN SPECIFICATION 26 20 00.
A P
R
IL
| Amendment W912WJ19Q0064-0001 |
| Plans REVISED |
| HOU-BR-118_G-001 |
| HOU-BR-118_ED-101 |
| HOU-BR-118_ED-601 |
| HOU-BR-118_E-101 |
| HOU-BR-118_E-501 |
| HOU-BR-118_E-502 |
| HOU-BR-118_E-601 |