Repair Pilot’s Briefing Room ACA- W912SV-16-B-0004
Questions and Answers
15 September 2016
Q On Drawing Sheet M-101 Detail A2 Duct mounted noise generator detail Note # 5 says see Electrical for Noise Generator System. Drawing E-101 Note # 10 there is no information on the required system. There is nothing in the specs on further detail. What size, model number ext of required system.
A The noise generator is a device mounted to the duct work. The only thing required is for electrical to power it and keyed Note 9 on E-101 identifies the mechanical device and Panelboard Schedules on E-701 (circuit 12 in SP1 and circuit 11 in SP2) takes care of the circuiting.
Q Do you have the manufacture or model No. of the Duct Mounted Noise Generator to be installed???
A We do not have a manufacturer or make/model. The requirements for the product may be found within the document Technical Specifications For Construction And Management Of Sensitive Compartmented Information Facilities Version 1.3 IC Tech Spec‐for ICD/ICS 705, page 70, paragraph (e). https://fas.org/irp/dni/icd/ics-705-ts.pdf https://fas.org/irp/dni/icd/ics-705-ts.pdf