W912QR25BA014_Plans-0000.pdf
PDF 2 MB Posted
- Attached to
- Nolin River Lake Hoist Replacement
- Solicitation number
- W912QR25BA014
About this file
These are design and engineering plans for the Nolin River Lake Hoist Replacement project located at 2150 Nolin Dam Road in Mammoth Cave, Kentucky. The comprehensive set of architectural and engineering drawings, prepared by the US Army Corps of Engineers, details the demolition and replacement of an existing hoist system, including structural, mechanical, electrical, and piping modifications. Key elements include a detailed demolition plan for the existing elevator shaft, crane system, and structural components, followed by new framing, crane reference elevations, and electrical system upgrades. The project involves removing existing infrastructure and installing a new hoist system, with specific attention to crane runway rail tolerances, beam splicing, and wall plate connections. The contract number is W912QR25BA014, with an issue date of 02-24-2025, and the project is scheduled to be completed at the Nolin River Lake Control Tower and Service Bridge location.
The technical drawings provide extensive details across multiple disciplines, including demolition plans, framing strategies, crane reference elevations, piping considerations, and electrical system configurations. Specific technical specifications cover structural steel requirements, crane load characteristics, special inspections, and connection methodologies. The plans include precise measurements, tolerances, and installation guidelines for complex components like W-beam connections, wall plates, and crane rail systems. Electrical documentation covers one-line diagrams, motor control center (MCC) elevations, and reflected ceiling plans, ensuring comprehensive infrastructure replacement and upgrade for the hoist system.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Nolin Hoist Replacement Roster.pdf | ||
| W912QR25BA014__ Issued- Nolin Hoist Replacement.zip | ZIP file | |
| W912QR25BA014_Specs-0000.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HORN.ZACHARY.TYLER.1623933152
Digitally signed by HORN.ZACHARY.TYLER.1623933152
DN: CN=HORN.ZACHARY.TYLER.1623933152, OU=USA,
OU=PKI, OU=DoD, O=U.S. Government, C=US Date: 2025.03.18 14:58:10-04'00'
HORN.ZACHARY.TYLER.1623933152
Digitally signed by
HORN.ZACHARY.TYLER.1623933152
DN: CN=HORN.ZACHARY.TYLER.1623933152,
OU=USA, OU=PKI, OU=DoD, O=U.S. Government, C=US
Date: 2025.03.18 14:58:29-04'00'
TIMBAS.JEFFREY.
W.1365057903
Digitally signed by
TIMBAS.JEFFREY.W.1365057903
Date: 2025.03.19 08:38:09 -04'00'
WILSON.MATTHE
W.G.1634055483
Digitally signed by
WILSON.MATTHEW.G.1634055483
Date: 2025.03.19 08:35:36 -04'00'
REDDICK.MATTHEW.NEWTON.1234329150
Digitally signed by
REDDICK.MATTHEW.NEWTON.1234329150
DN: CN=REDDICK.MATTHEW.NEWTON.1234329150,
OU=USA, OU=PKI, OU=DoD, O=U.S. Government, C=US
Date: 2025.04.03 10:03:13+02'00'
HARTMAN.BRETT.E.1548512618
Digitally signed by HARTMAN.BRETT.E.1548512618
DN: CN=HARTMAN.BRETT.E.1548512618, OU=USA,
OU=PKI, OU=DoD, O=U.S. Government, C=US Date: 2025.03.25 07:33:42-04'00'
ALEXANDER.LAND
ON.F.1538722460
Digitally signed by
ALEXANDER.LANDON.F.1538722460
Date: 2025.03.18 15:07:51 -04'00'
ARIMS: 1200 Disposition: Permanent
01 May 2025
W912QR25BA014
W
2Q R
BA
4_
Pl an s-
ARIMS: 1200 Disposition: Permanent
W
2Q R
BA
4_
Pl an s-
2Q R
BA
4_
Pl an s-
2Q R
BA
4_
Pl an s-
2Q R
BA
4_
Pl an s-
2Q R
BA
4_
Pl an s-
2Q R
BA
4_
Pl an s-
2Q R
BA
4_
Pl an s-
2Q R
BA
4_
Pl an s-
2Q R
BA
4_
Pl an s-
2Q R
BA
4_
Pl an s-
OS
DL
LC
J
J
F1
DO
M
OS
SWITCH ID INDICATED BY A LOWERCASE LETTER.
SWITCH IDS ARE UNIQUE PER SPACE. A SWITCH
WITH AN ID "a" CONTROLS ALL DEVICES WITHIN THE SPACE IN WHICH IT IS LOCATED TAGGED WITH "a".
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE
EQUIPMENT NAME AND CIRCUIT NUMBER(S) ARE
INDICATED. HOMERUNS ARE ONLY INTENDED TO
INDICATE PANEL AND CIRCUIT NUMBER. DETERMINE
ACTUAL HOMERUN LOCATION IN THE FIELD.
POWER SYMBOLS
EXIT LIGHT, WALL-MOUNTED. SHADING AND
ARROWS INDICATE FACES AND DIRECTIONAL
CHEVRONS.
WALL-MOUNTED FIXTURES, TYPICAL
(VARIOUS SYMBOLS)
EMERGENCY LIGHTING UNIT, WALL-
MOUNTED, REMOTE BATTERY
EMERGENCY LIGHTING UNIT, WALL
MOUNTED, INTEGRAL BATTERY
EMERGENCY LIGHTING UNIT, CEILING-
MOUNTED, INTEGRAL BATTERY
EMERGENCY LIGHTING UNIT, CEILING-
MOUNTED, REMOTE BATTERY
LIGHTING FIXTURES, TYPICAL,
RECTANGULAR (VARIOUS SYMBOLS) FILLED
CIRCLES INDICATE RECESSED. OPEN
CIRCLES INDICATE SURFACE MOUNTED.
DIAGONAL LINE INDICATES LENSED. OUTER
DOTS INDICATE SUSPENDED.
LIGHTING FIXTURES, TYPICAL, ROUND
(VARIOUS SYMBOLS) CENTER DOT
INDICATES PENDANT. DIAGONAL LINE
INDICATES LENSED. CHEVRON INDICATES
WALL WASH.
STRIP FIXTURE
DIRECTIONAL/TRACK/FLOOD LIGHT
EXIT LIGHT, CEILING-MOUNTED. SHADING
AND ARROWS INDICATE FACES AND
DIRECTIONAL CHEVRONS.
LINEAR LIGHT, TAPE LIGHT
EXIT/ELU COMBO
DIAGONAL HATCH INDICATES LIGHT ON A
CRITICAL CIRCUIT.
SOLID HATCH INDICATES LIGHT ON AN
EMERGENCY OR LIFE SAFETY CIRCUIT.
POLE/AREA LIGHTS
POST-TOP AREA LIGHT
BOLLARD LIGHT
SINGLE-POLE SWITCH
TWO-POLE SWITCH
THREE-POLE SWITCH
SWITCH MODIFIERS:
3: 3-WAY
4: 4-WAY
K: KEYED
D: DIMMING
T: TIMER
OS: OCCUPANCY SENSOR
VS: VACANCY SENSOR
AC: ABOVE-COUNTER
LV: LOW-VOLTAGE
M: MOTOR-RATED
LIGHTING CONTACTOR
LIGHTING CONTROL PANEL
OCCUPANCY SENSOR
DAYLIGHT HARVESTING SENSOR
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
SPECIAL RECEPTACLE, TYPE AS INDICATED
W
AL
L C
EI
LI
N G
FL
O
O R
RECEPTACLE MODIFIERS:
##": HEIGHT AFF OC
AC: ABOVE COUNTER
GFI: GROUND-FAULT CIRCUIT INTERRUPTER
WP: WEATHERPROOF IN-USE COVER
HALF SHADING INDICATES SPLIT (TYPICALLY SWITCHED)
OUTSIDE SHADING INDICATES EMERGENCY CIRCUIT
CENTER SHADING INDICATES ISOLATED GROUND
MULTIOUTLET ASSEMBLY FILLED SQUARES INDICATE
120V OUTLET OPEN SQUARES INDICATE WITH USB
CORD REEL, DEVICE VARIES
DROP CORD, DEVICE VARIES
JUNCTION BOX
FLOOR BOX, SEE SCHEDULE FOR TYPE
EMERGENCY POWER OFF
DOOR OPENER PUSH PLATE
POWER METER
SAFETY SWITCH, FUSED
SAFETY SWITCH, UNFUSED
MOTOR STARTER
COMBINATION STARTER/DISCONNECT
GROUND ROD
GROUND ROD WITH TEST WELL
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CONDUCTOR SPLICE
STATIC GROUND RECEPTACLE
LIGHTING SYMBOLS
CONTACTOR
SINGLE-POLE SWITCH
TWO-POLE SWITCH
THREE-POLE SWITCH
SWITCH MODIFIERS:
K: KEYED
T: TIMER
AC: ABOVE-COUNTER
M: MOTOR-RATED
a
A1
HATCHED FILL INDICATES DISTRIBUTION PANEL OR
SWITCHBOARD. SOLID FILL INDICATES BRANCH PANEL OR
LOAD CENTER. DOOR INDICATES FRONT OF RECESSED PANEL.
DISTRIBUTION EQUIPMENT
HP
1A
(B
LP
1A
(C
MD
P(
A)
SB1(S)
TRANSFORMER: TYPICALLY TRANSFORMER NAMES
BEGIN WITH OR CONTAIN THE LETTER "T". SEE
SINGLE-LINE DIAGRAM FOR DESCRIPTION AND
REQUIREMENTS.
T1
LOWERCASE LETTER: SWITCH ID
LIGHTING TAGS
UPPERCASE LETTER: FIXTURE TYPE ID
(UNDERLINED) - SEE SCHEDULE
a a
LIGHTING LEGEND POWER EQUIPMENT AND DEVICES LEGEND
L4-01
D = DISTRIBUTION
L = LIGHTING
P = GENERAL POWER
M = MECHANICAL POWER
C = IT POWER
1 = 240V, 1-PHASE
2 = 240V. 3-PHASE
3 = 208V, 3-PHASE
4 = 480V, 3-PHASE
01 = PANEL #1
02 = PANEL #2
03 = PANEL #3
ETC
a 1: DENOTES EMERGENCY FIXTURE
PANEL NAMING CONVENTION
LIGHTNING PROTECTION AND GROUNDING LEGEND ONE LINE DIAGRAM LEGEND
POTENTIAL TRANSFORMER
SURGE SUPPRESSOR
CONTACT (NORMALLY OPEN)
CONTACT (NORMALLY CLOSED)
FUSE
GROUND
TRANSFORMER
TRANSFER SWITCH
CIRCUIT BREAKER
DRAW-OUT CIRCUIT BREAKER
DRAW-OUT FUSE
RELAY
CURRENT TRANSFORMER
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
LIGHTNING ARRESTOR
RECEPTACLE
MOTOR (# = HORSEPOWER)
R
GENERAL ELECTRICAL NOTES
1. SYMBOLS, NOTES AND ABBREVIATIONS ON THIS SHEET ARE STANDARD
AND MAY NOT ALL APPEAR ON THIS PROJECT.
2. VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK. THESE
DRAWINGS ARE GENERALLY DIAGRAMMATIC AND DO NOT SHOW ALL
DETAILS REQUIRED FOR THE COMPLETE SYSTEM. THEY SHOULD
HOWEVER BE FOLLOWED AS CLOSELY AS POSSIBLE IN THE GENERAL
ARRANGEMENT AND LOCATION OF EQUIPMENT. CHECK ALL DIMENSIONS
AND INVESTIGATE STRUCTURAL/FINISH CONDITIONS AT THE SITE.
ARRANGE WORK TO MEET THESE CONDITIONS AND PROVIDE SUCH
EQUIPMENT AND ACCESSORIES AS MAY BE REQUIRED. PROVIDE ALL
EQUIPMENT FOR A FULLY FUNCTIONING SYSTEM.
3. BEFORE INSTALLING EQUIPMENT, MAKE FIELD MEASUREMENTS TO
ENSURE THAT ALL ITEMS OF EQUIPMENT FURNISHED WILL FIT INTO THE
SPACE AS SHOWN ON THE DRAWINGS. WHERE EQUIPMENT WILL NOT FIT
AS SHOWN ON THE DRAWINGS, PROVIDE DRAWINGS TO THE
CONTRACTING OFFICER FOR APPROVAL WITH A PROPOSED REVISED
ARRANGEMENT BEFORE INSTALLING THE EQUIPMENT.
4. ADJUST EQUIPMENT AND FIXTURES TO AVOID INTERFERENCES WITH
OTHER EQUIPMENT AND UTILITIES.
5. UPON DISCOVERY OF ANY DISCREPANCY OR POINTS OF CONFLICT IN THE
DRAWINGS OR THE SPECIFICATIONS, IMMEDIATELY NOTIFY THE
CONTRACTING OFFICER IN WRITING. THE CONTRACTING OFFICER WILL
CLARIFY SUCH DISCREPANCY OR POINTS OF CONFLICT IN WRITING PRIOR
TO THE PROGRESS OF THE WORK BEYOND THE POINT CONCERNED.
6. PROPERLY SUPPORT ALL WORK AND EQUIPMENT INSTALLED UNDER THIS
CONTRACT PLUMB AND PARALLEL WITH GRADE OR STRUCTURE LINES.
STUDY ALL DRAWINGS, SHOP DRAWINGS, AND CATALOG DATA TO
DETERMINE HOW EQUIPMENT, ACCESSORIES, PIPING, FIXTURES, AND
RELATED ITEMS ARE TO BE SUPPORTED, MOUNTED, OR SUSPENDED.
PROVIDE ALL BOLTS, INSERTS, PIPE STANDS, BRACKETS, STRUCTURAL
SUPPORTS, AND ACCESSORIES FOR PROPER SUPPORT OF EQUIPMENT
FURNISHED UNDER THIS CONTRACT. COORDINATE THE ELECTRICAL WITH
ALL OTHER CONTRACTORS BEFORE BEGINNING WORK TO INSURE THAT
THE ELECTRICAL WORK DOES NOT INTERFERE WITH OTHER WORK.
7. CUT AND PATCH AS REQUIRED TO COMPLETE WORK.
8. FURNISH AND INSTALL ALL EQUIPMENT FOR THE CONSTRUCTION AND
COMPLETION IN EVERY DETAIL OF THE WORK DESCRIBED, UNLESS
OTHERWISE NOTED. FURNISH ALL LABOR, SUPERVISION,
MATERIALS,EQUIPMENT, TOOLS, TRANSPORTATION, SUPPLIES, TESTING
AND INCIDENTALS REQUIRED TO COMPLETE THE WORK IN ACCORDANCE
WITH THE DRAWINGS (PLANS), SPECIFICATIONS, AND TERMS OF THE
CONTRACT.
9. OBTAIN AND PAY FOR ALL REQUIRED PERMITS, LICENSES, ETC., PRIOR TO
COMMENCEMENT OF WORK. ASSUME ALL COSTS OF PERMITS, LICENSES,
CONNECTIONS, ETC.
10. REPORT ALL DAMAGES TO UTILITIES OR EXISTING STRUCTURES
IMMEDIATELY TO THE CONTRACTING OFFICER. THE CONTRACTING
OFFICER SHALL DETERMINE WHETHER REPAIR OR REPLACEMENT IS
NECESSARY. SUBMIT ALL REPAIR METHODS TO THE CONTRACTING
OFFICER FOR REVIEW AND APPROVAL PRIOR TO INITIATING THE WORK.
11. ATTEND THE CONSTRUCTION MEETINGS FOR THE DURATION OF THE
PROJECT.
12. COMPLETELY REMOVE AND REPLACE ANY ITEMS INSTALLED
INCORRECTLY PER CONTRACT DOCUMENTS AT NO ADDITIONAL EXPENSE
TO THE GOVERNMENT.
13. PERFORM ALL ELECTRICAL WORK IN ACCORDANCE WITH THE MOST
RECENT EDITION OF NFPA 70 - NATIONAL ELECTRICAL CODE.
14. ROUTE CIRCUITS IN EMT EXCEPT WHERE THE USE OF EMT IS PROHIBITED
BY NFPA 70. HAZARDOUS LOCATIONS AND AREAS SUBJECT TO PHYSICAL
DAMAGE ARE NOTED ON THE DRAWINGS.
15. DO NOT WORK ON ENERGIZED ELECTRICAL CIRCUITS UNLESS PROOF IS
PROVIDED THAT NO OTHER MEANS EXIST. IF IT IS DETERMINED THAT
EQUIPMENT MUST BE WORKED ON IN AN ENERGIZED CONDITION, SUBMIT
AN ENERGIZED WORK REQUEST TO THE GOVERNMENT VIA THE
CONTRACTING OFFICER FOR ACCEPTANCE. THE ENERGIZED WORK
REQUEST SHALL CONTAIN INFORMATION REQUIRED BY USACE EM 385-1-1
PARAGRAPH 11.A.02.C REFERENCE NFPA 70E.
16. ENERGIZED CIRCUITS: WHEN ENERGIZED WORK IS DEEMED ABSOLUTELY
NECESSARY, IT SHOULD BE ACCOMPLISHED WITH EXTREME CAUTION AND
ONLY WHEN THE BASIC ENERGIZED WORK PROCEDURES LISTED IN AFI
32-1064 ARE FOLLOWED AND REVIEWED WITH ALL PERSONNEL
IMMEDIATELY BEFORE STARTING. ENERGIZED WORK SHALL NOT BE
ALLOWED WITHOUT MEETING THE FOLLOWING REQUIREMENTS:
A. SAFETY OFFICER MUST APPROVE ENERGIZED WORK IN ADVANCE.
B. USE TWO-PERSON TEAMS TO PERFORM WORK.
C. A QUALIFIED SUPERVISOR MUST BE CONSULTED AND MUST APPROVE
ANY PLAN TO WORK ON ENERGIZED EQUIPMENT AND ENSURE
PROPER USE OF PERSONAL PROTECTIVE EQUIPMENT.
D. THE ENERGIZED WORK REQUEST MUST BE PREPARED IN ADVANCE.
E. PLACE SPECIAL EMPHASIS ON PERSONAL PROTECTIVE EQUIPMENT
AND APPROPRIATE SUPERVISION. PROPER SUPERVISION, TRAINING,
AND PLANNING ARE PARAMOUNT TO ENSURE SAFETY.
F. CONVENTIONAL CIRCUIT DE-ENERGIZING/RE-ENERGIZING METHODS
(I.E., TURNING OFF/ON A SWITCH, OPENING AND CLOSING SWITCHES,
OR OPERATING CIRCUIT BREAKERS/DISCONNECTS) FOR THE
PURPOSE OF ISOLATING CIRCUITS IS CONSIDERED PERFORMING
"ENERGIZED WORK" AND ALL THE PROCEDURES ABOVE SHALL BE
FOLLOWED; HOWEVER, FOR THE PURPOSES OF THIS
PARAGRAPH,BASE CIVIL ENGINEER APPROVAL IS GRANTED THROUGH
A WRITTEN SAFE CLEARANCE FORM.
G. WHILE THE JOB IS IN PROGRESS, AN ON-SITE SUPERVISOR MUST
CLOSELY SUPERVISE THE WORKERS, CHECKING THEM CONSTANTLY
TO MAKE SURE THEY ARE IN SAFE WORKING POSITIONS, HANDLING
TOOLS SAFELY, AND COMPLYING WITH THE ENERGIZED WORK
PERMIT.
1P 1 POLE (2P, 3P, 4P, ETC.)
AMP AMPERE
AC ABOVE COUNTER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
AMP AMPERE
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BJ BONDING JUMPER
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CONT CONTINUATION OR CONTINUOUS
CT CURRENT TRANSFORMER
CU COPPER
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
EGC EQUIPMENT GROUNDING CONDUCTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EWC ELECTRIC WATER COOLER
EXP EXPLOSION PROOF
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FLR FLOOR
FLUOR FLUORESCENT
GA GAUGE
GALV GALVANIZED
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
HOA HANDS-OFF-AUTOMATIC SWITCH
HP HORSEPOWER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR CONDITIONING
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LPS LIGHTNING PROTECTION SYSTEM
LTG LIGHTING
LV LOW VOLTAGE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MG MOTOR GENERATOR
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MSBD MAIN SWITCHBOARD
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NIC NOT IN CONTRACT
NTS NOT TO SCALE
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PF POWER FACTOR
PH PHASE
PNL PANEL
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
QTY QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
SBJ SYSTEM BONDING JUMPER
SCH SCHEDULE
SEC SECONDARY
SHT SHEET
SPKR SPEAKER
SSBJ SUPPLY-SIDE BONDING JUMPER
STD STANDARD
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UH UNIT HEATER
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VA VOLT-AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WATT
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
ABBREVIATIONS
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
S U
BM
IT
TA
L
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
C :\U se rs
\H 2E
D D
LF
A\
D oc um en ts \5
6_ v2
2_
E_ H
2E D
D
LF
A.
rv t 2/
/2
1:
:3
PM
E-001
G
EN
ER
AL
E
LE
C
TR
IC
AL
N O
TE
S
AN
D
L
EG
EN
D
N O
LI
N
D
AM
R O
AD
M
AM
M
O
TH
C
AV
E, K
Y
L.
A
LE
XA
N D
ER
L.
A
LE
XA
N D
ER
J.
T
IM
BA
S
-2
4-
N
O
LI
N R
IV
ER
L
AK
E H
O
IS
T R
EP
LA
C
EM
EN
T
P2
ARIMS: 1200 Disposition: Permanent
W
2Q R
BA
4_
Pl an s-
MCC
ELEVATOR
J
MCC
ELEVATOR
SHEET NOTES
KEY NOTES
1. HALFTONE INDICATES ITEMS ARE EXISTING.
2. HATCHED AREA INDICATES ITEMS FOR DEMOLITION.
3. VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION. EXISTING CONDITIONS
SHOWN IN THESE DRAWINGS ARE BASED ON AS-BUILT RECORDS AND CURSORY
SITE INSPECTION.
4. SEE SPECIFICATION SECTION 26 20 00 FOR ELECTRICAL SYSTEMS TECHNICAL
REQUIREMENTS.
5. SEE SPECIFICATION SECTION 41 22 13.14 FOR OVERHEAD HOIST TECHNICAL
REQUIREMENTS.
6. THE PREMISES ELECTRICAL SYSTEM IS 240 VOLTS, 3-PHASE/4-WIRE, DELTA-
CONNECTED. (I.E. "HIGH-LEG DELTA")
7. THE EXISTING MCC IS A SQUARE D MODEL 6.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
S U
BM
IT
TA
L
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
C :\U se rs
\H 2E
D D
LF
A\
D oc um en ts \5
6_ v2
2_
E_ H
2E D
D
LF
A.
rv t 2/
/2
1:
:3
PM
E-101
EL
EC
TR
IC
AL
P
LA
N
S
N O
LI
N
D
AM
R O
AD
M
AM
M
O
TH
C
AV
E, K
Y
L.
A
LE
XA
N D
ER
L.
A
LE
XA
N D
ER
J.
T
IM
BA
S
-2
4-
N
O
LI
N R
IV
ER
L
AK
E H
O
IS
T R
EP
LA
C
EM
EN
T
P2
1/4" = 1'-0"A9 REFLECTED CEILING PLAN - ELECTRICAL
1/4" = 1'-0"A1 REFLECTED CEILING PLAN - ELECTRICAL DEMOLITION
1 EXISTING HOIST. DEMOLISH ELECTRICAL EQUIPMENT, CONDUCTORS AND RACEWAY
BACK TO MOTOR CONTROL CENTER.
2 #2 AWG CONDUCTORS IN 1 1/4" RMC. SIZES ARE PROVIDED FOR BIDDING PURPOSES
ONLY. PROVIDE ACTUAL SIZE AND ROUTING PER HOIST MANUFACTURER'S
REQUIREMENTS. FINAL CONNECTION TO CRANE TO BE PER SUBMITTED/APPROVED
CRANE MANUFACTURER RECOMMENDATIONS.
3 INSTALL CIRCUIT BREAKER TO SERVE AS MOTOR AND MOTOR CONTROLLER
DISCONNECTING MEANS IN ACCORDANCE WITH NFPA 70. SIZE SHOWN IS FOR
BIDDING PURPOSES ONLY. PROVIDE SIZE PER HOIST MANUFACTURER'S
REQUIREMENTS. FINAL CONNECTION TO CRANE TO BE PER SUBMITTED/APPROVED
CRANE MANUFACTURER RECOMMENDATIONS.
4 LOCATE JUNCTION BOX AND PROVIDE FINAL CONNECTION TO HOIST EQUIPMENT
PER MANUFACTURER REQUIREMENTS.
5 EXISTING SERVICE CONDUCTORS - #1/0 AWG, VERIFY PRIOR TO CONSTRUCTION.
6 PROVIDE ADDITIONAL SET OF #1/0 AWG CONDUCTORS TO SUPPLEMENT EXISTING
SERVICE CONDUCTORS. ROUTE CONDUCTORS IN SAME RACEWAY AS EXISTING AND
CONNECT IN PARALLEL.
ARIMS: 1200 Disposition: Permanent
W
2Q R
BA
4_
Pl an s-
MAIN
PUMP
60A PLUGS PANEL
PUMP
JIB CRANE
JIB CRANE
ELEVATOR
OVERHEAD HOIST
SHEET NOTES
KEY NOTES
1. HALFTONE INDICATES ITEMS ARE EXISTING.
2. HATCHED AREA INDICATES ITEMS FOR DEMOLITION.
3. VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION. EXISTING CONDITIONS
SHOWN IN THESE DRAWINGS ARE BASED ON AS-BUILT RECORDS AND CURSORY
SITE INSPECTION.
4. SEE SPECIFICATION SECTION 26 20 00 FOR ELECTRICAL SYSTEMS TECHNICAL
REQUIREMENTS.
5. SEE SPECIFICATION SECTION 41 22 13.14 FOR OVERHEAD HOIST TECHNICAL
REQUIREMENTS.
6. THE PREMISES ELECTRICAL SYSTEM IS 240 VOLTS, 3-PHASE/4-WIRE, DELTA-
CONNECTED. (I.E. "HIGH-LEG DELTA")
7. THE EXISTING MCC IS A SQUARE D MODEL 6.
MAIN
PUMP
60A PLUGS PANEL
PUMP
JIB CRANE
JIB CRANE
ELEVATOR
OVERHEAD HOIST 1
MAIN
150AT/3P
100% RATED
AT
MCC
PANEL
SERVICE CONDUCTORS
FROM POLE-MOUNTED
SERVICE DISCONNECT
(240 V, APPROX. 250 FT)
PUMP
AT
PUMP
GENERATOR
MANUAL TRANSFER
SWITCH
AT
60 A PLUGS
AT
JIB CRANE
AT
JIB CRANE
1.5
AT
ELEVATOR
0A
T
OVERHEAD
HOIST
MAIN
200AT/3P
100% RATED
AT
MCC
SERVICE CONDUCTORS
FROM POLE-MOUNTED
SERVICE DISCONNECT
(240 V, APPROX. 250 FT)
PUMP
AT
PUMP
GENERATOR
TRANSFER
SWITCH
AT
60 A PLUGS
AT
JIB CRANE
AT
JIB CRANE
1.5
AT
ELEVATOR
0A
T
OVERHEAD
HOIST
PANEL
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
S U
BM
IT
TA
L
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
C :\U se rs
\H 2E
D D
LF
A\
D oc um en ts \5
6_ v2
2_
E_ H
2E D
D
LF
A.
rv t 2/
/2
1:
:3
PM
E-601
EL
EC
TR
IC
AL
D
ET
AI
LS
N O
LI
N
D
AM
R O
AD
M
AM
M
O
TH
C
AV
E, K
Y
L.
A
LE
XA
N D
ER
L.
A
LE
XA
N D
ER
J.
T
IM
BA
S
-2
4-
N
O
LI
N R
IV
ER
L
AK
E H
O
IS
T R
EP
LA
C
EM
EN
T
P2
NTSA1 MCC ELEVATION
NTSH1 MCC ELEVATION (DEMOLITION)
NTSH6 ELECTRICAL ONE-LINE DIAGRAM (DEMOLITION)
NTSA6 ELECTRICAL ONE-LINE DIAGRAM
1 DEMOLISH CIRCUIT BREAKER, SUPPORTING EQUIPMENT, BRANCH CIRCUIT
CONDUCTORS AND RACEWAY SERVING THE OVERHEAD HOIST. PRESERVE MCC
ENCLOSURE FOR RE-USE.
2 PROVIDE CIRCUIT BREAKER, SUPPORTING EQUIPMENT, BRANCH CIRCUIT
CONDUCTORS AND RACEWAY TO SERVE THE UPGRADED OVERHEAD HOIST.
3 PROVIDE A 4"X6" STICKER ON THE MCC BUCKET THAT READS "DO NOT OPERATE
SIMULTANEOUSLY WITH OTHER CRANES"
4 INSTALL CIRCUIT BREAKER TO SERVE AS MOTOR AND MOTOR CONTROLLER
DISCONNECTING MEANS IN ACCORDANCE WITH NFPA 70. SIZE SHOWN IS FOR
BIDDING PURPOSES ONLY. PROVIDE SIZE PER HOIST MANUFACTURER'S
REQUIREMENTS. FINAL CONNECTION TO CRANE TO BE PER SUBMITTED/APPROVED
CRANE MANUFACTURER RECOMMENDATIONS.
5 #2 AWG CONDUCTORS IN 1 1/4" RMC. SIZES ARE PROVIDED FOR BIDDING PURPOSES
ONLY. PROVIDE ACTUAL SIZE AND ROUTING PER HOIST MANUFACTURER'S
REQUIREMENTS. FINAL CONNECTION TO CRANE TO BE PER SUBMITTED/APPROVED
CRANE MANUFACTURER RECOMMENDATIONS.
6 REPLACE EXISTING MCC MAIN CIRCUIT BREAKER.
7 PROVIDE ADDITIONAL SET OF #1/0 AWG CONDUCTORS TO SUPPLEMENT EXISTING
SERVICE CONDUCTORS. ROUTE CONDUCTORS IN SAME RACEWAY AS EXISTING AND
CONNECT IN PARALLEL.
8 DEMOLISH EXISTING MCC MAIN CIRCUIT BREAKER.
9 EXISTING SERVICE CONDUCTORS - #1/0 AWG, VERIFY PRIOR TO CONSTRUCTION.
ARIMS: 1200 Disposition: Permanent
W
2Q R
BA
4_
Pl an s-