McEntire JNGB Fire Suppression Discrepancies 2018
Bldg. 1057 Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
Deluge system is due for 5yr internal inspection
Status: Open
1. A.5
5. Has there been an air leakage test of the system(s) within the last 3 years?
System is due for 3yr air leakage test
Bldg. 210
Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
Wet system due for 5yr internal inspection
Bldg. 212
Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
Wet system is due for 5yr internal inspection
Status: Open
2. B
b. Are all control valves sealed, secured, or supervised in the open position?
OS&Y 6" control valve is not secured or tampered
Status: Open
7. C
c. Do sprinkler heads generally appear to be free of damage, corrosion, paint, loading and visible obstruction, escutcheon plate in place, and appear to be installed in the correct orientation?
Riser room has 3 brass upright heads SR 212 degree that are painted Loading dock has 2 chrome dry sidewall heads that are corroded (155 degree SR @ 12" in length)
Status: Open
7. G
g. Have all dry heads known to be more than 10 years old been replaced or a sample tested?
2 dry sidewalls on loading dock appears to be older than 10 yrs
Bldg. 216
Status: Open
6. D
d. Did the supervisory alarms operate during testing?
Shutoff #1 tamper didn't operate during inspection
Bldg. 251
Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
Bldg. 257
Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
System is due for 5yr internal inspection (no lift needed)
Status: Open
6. B
b. Did the electric alarms operate during testing?
Panel didn't read any troubles, supervisory, or alarm during inspection
Status: Open
6. C
c. Did alarms activate within appropriate time?
Water flowed for 2minutes no alarm sounded.
Bldg. 258
Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
Wet system is due for 5yr internal inspection
Bldg. 260
Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
Wet system is due for 5yr internal inspection
Status: Open
6. B
b. Did the electric alarms operate during testing?
No alarms sounded during inspection
Status: Open
6. C
c. Did alarms activate within appropriate time?
No alarms during flow inspection
Status: Open
6. D
d. Did the supervisory alarms operate during testing?
No supervisory during inspection Status: Open
Bldg. 878
Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
(10)- Wet systems is due for 5yr internal inspection (no lift needed)
Bldg. 979
Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
Wet system is due for 5yr internal inspection
Status: Open
6. A
a. Did the water motor gong operate during testing?
Water motor gong didn't operate during inspection (globe model H-3)
Bldg. 984
Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
1 wet system is due for 5yr internal inspection
Status: Open Bldg. 1070 Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?
Wet system is due for 5yr internal inspection
Bldg. 1080 Status: Open
1. A.4
4. Has there been an internal inspection of the piping within the last 5 years?